t TABLE 3.3-12 RADIOACTIVE LI UID EFFLUENT MONITORING INSTRUMENTATION Instrument Minimum Channel's

~0 etable A licabilit Action 1.

Gross Radioactivity Monitors Providing Automatic Release Termination

a. Liquid Radwaste Effluent Line (12-RRS-1001)

(1)

At times of release 23 b.

Steam Generator Blowdown Line (1-R-19)

At times of release 24 c.

Steam Generator Blowdown Treatment Effluent (1-R-24)

At times of release 24

2. Gross Radioactivity Monitors Not Providing Automatic Release Termination
a. Service Water System Effluent Line (1-R-20, 1-R-28)

(1)per At all times train 25

3. Continuous Composite Sampler Flow Monitor
a. Turbine Building Sump Effluent Line At all times 25 4.

Flow Rate Measurement Devices

a. Liquid Radwaste Line(RFI-285)
b. Discharge Pipes*

c.

Steam Generator Blowdown Treatment Effluent

'(1-DFI-352)

At times of release 26 At all times NA At times of release 26

  • Pump curves and valve settings may be utilized to estimate flow; in such
cases, Action Statement 26 is not applicable.

+ Monitor 1-R-18 may be used until monitor 12-RRS-1001 is declared OPERABLE following initial installation.

e D.

C.

COOK - UNIT 1 8612120328 8b1208~!

PDR ADOCK 0500031'5 P

PDP 3/4 3-58 Amendment No.

TABLE 3.3-12 RADIOACTIVE LI UID EFFLUENT MONITORING INSTRUMENTATION Instrument Minimum Channels

~0 arable A licabilit Action

1. Gross Radioactivity Monitors Providing Automatic Release Termination
a. Liquid Radwaste Effluent Line (12-RRS-1001) +

At times of release 23 b.

Steam Generator Blowdown Line (2-R-19)

At times of release 24 c.

Steam Generator Blowdown Treatment Effluent (2-R-24)

At times of release 24

2. Gross Radioactivity Monitors Not Providing Automatic Release Termination
a. Service Water System Effluent Line (2-R-20, 2-R-28)

(1)per At all times train 25

3. Continuous Composite Sampler Flow Monitor
a. Turbine Building Sump Effluent Line At all times
4. Flow Rate Measurement Devices
a. Liquid Radwaste,Line(RFI-285)
b. Discharge Pipes*

c.

Steam Generator Blowdown Treatment Effluent (2-DFI-352)

At times of release 26 At all times NA At times of release 26

  • Pump curves and valve settings may be utilized to estimate flow; in such
cases, Action Statement 26 is not applicable.

+ Monitor 2-R-18 may be used until monitor 12-RRS-1001 is declared OPERABLE following initial installation.

D.

C.

COOK - UNIT 2 3/4 3-54 Amendment No.

1 4I 1

1