~P CATEGORY 1 REGULATORY 'INFORMATION DISTRIBUTION

~

TEM (RIDS)

ACCESSION NbR'.9601170205 DOC.DATE: 95/12/31 NOTARIZED: NO DOCKET I FACIL:50-316 Donald C.

Cook Nuclear Power Plant, Unit 2, Indiana M

05000316 AUTH.NAME AUTHOR AFFILIATION JANISSE,J.D.

Indiana Michigan Power Co.

RUSSO,M.E.

Indiana Michigan Power Co.

RECIP.NAME RECIPIENT'AFFILIATION

SUBJECT:

Monthly operating rept for Dec 1995 for DC Cook Nuclear Plant Unib 2.W/960103 ltr.

'DISTRIBUTION CODE:

IE24D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: Monthly Operating Report (per Tech Specs)

NOTES:

RECIPIENT ID CODE/NAME PD3-1 PD INTERNAL: AEOD/SPD/RRAB NRR/DRPM/PECB EXTERNAL: LITCO BRYCE,J H

NRC PDR COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 RECIPIENT ID CODE/NAME HICKMANiJ E C~

1 RGN3 NOAC COPIES LTTR ENCL 1

1 1

1 1

1 1

1 NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE!

CONTACT THE DOCUMENT CONTROL DESKi ROOM OWFN SD-5(EXT. 415-2083)

TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 9

ENCL 9

Indiana Michigan Power Company Cook Nuclear Plant One Cook Place

~ Bridgrnan, Ml 49106 616 465 5901 R

lNMANIL SZECHSSQM POWER January 3,

1996 U.S. Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, D.C.

20555 Gentlemen:

Pursuant to the requirements of Donald C.

Cook Nuclear Plant Unit 2 Technical Specification 6.9.1.10, the attached Monthly Operating Report for the month of December 1995 is submitted.

Respectfully, oQ A.A. Blind Plant Manager Attachment c:

NRC Region III D.R.

Hahn R.C. Callen S.

Hamming INPO Records Center ANI Nuclear Engineering Department E.E. Fitzpatrick W.G. Smith, Jr.

S.J.

Brewer D.W. Paul S.H. Steinhart J.L. Leichner B.L. Bartlett D.G. Turner W.H. Schalk M.E. Russo V~O~i70aoa VS~aSS PDR ADOCK 050003i6l R

PDR

0 I

\\

N.R.C.

OPERATING DATA REPORT DOCKET NO.

50-316 DATE 03/Jan/96 COMPLETED BY JD Janisse TELEPHONE 616-465-5901 OPERATING STATUS

1. Unit Name D.

C.

Cook Unit 2

2. Reporting Period Dec 1995 notes
3. Licensed Thermal Power (MWt) 3411 4.

Name Plate Rating (Gross MWe) 1133

5. Design Electrical Rating (Net MWe) 1090 6.

Maximum Dependable Capacity (GROSS MWe) 1100 7.

Maximum Dependable Capacity (Net MWe) 1060

8. If Changes Occur in Capacity Ratings (Items no.

3 through

7) Since Last Report Give Reasons 9.

Power Level To Which Restricted. If Any (Net MWe) 10.

Reasons For Restrictions. If Any:

This Mo.

Yr. to Date Cumm.

11. Hours in Reporting Period 744.0 8760.0 157776.0 12.

No. of Hrs. Reactor Was Critical 744.0 8307. 8 108324. 3

13. Reactor Reserve Shutdown Hours 0.0 0.0 0.0
14. Hours Generator on Line 744.0 8270.6 104805.7
15. Unit Reserve Shutdown Hours 0.0 0.0 0.0 16.

Gross Therm.

Energy Gen.

(MWH) 2489173 27536283 321634464

, 17.

Gross Elect.

Energy Gen.

(MWH) 819360 8899370 104206360

18. Net Elect. Energy Gen.

(MWH) 792659 8602528 100359963

19. Unit Service Factor 100.0 94.4 67.4
20. Unit Availability Factor 100.0 94.4 67.4
21. Unit Capacity Factor (MDC Net) 100.5 92.6 60.8
22. Unit Capacity Factor (DER Net) 97.7 90.1 59.3
23. Unit Forced Outage Rate 0.0 5.6 15.1 24.

Shutdowns Scheduled over Next Six Months (Type, Date,and Duration):

Refuelin outa e to be in March 23 1996 for an estimated duration of 50 da s.

25. If Shut Down At End of Report Period, Estimated Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved INITIALCRITICALITY INITIALELECTRICITY COMMERCIAL OPERATION

AVERAGE DAILY POWER LEVEL (MWe-Net)

MONTH DOCKET NO.

50-316 UNIT TWO DATE 03/Jan/96 COMPLETED BY JD Janisse TELEPHONE 616-465-5901 Dec 1995 DAY 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 AVERAGE DAILY POWER LEVEL 1089 1084 1087 1087 1085 1095 1069 1050 1084 609 925 1072 1091 1090 1086 1091 DAY 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 AVERAGE DAILY POWER LEVEL 1087 1090 1092 1089 1090 1087 1092 1089 1089 1089 1087 1088 1089 1088 1088

DOCKET NO:

UNIT NAME:

COMPLETED BY:

TELEPHONE:

DATE:

PAGE:

50-316 D.C.

Cook Unit 2 M.E. Russo 616-465-5901 January 3,

1996 Page 1 of 2 MONTHLY OPERATING ACTIVITIES DECEMBER 1995 HIGHLIGHTS The unit entered this reporting period in Mode 1 at 100% RTP.

Reactor power was decreased to 94%

RTP December 7,

1995 at 1641 to recover from a Moisture Separator Reheater transient caused by a tube bundle isolation.

Reactor power was stabilized at 100%

RTP December 8,

1995 at 0845 to meet system demands.

Reactor power was decreased to 95%

RTP December 8,

1995 at 2052 to place the Moisture Separator Reheaters in service.

Reactor power was stabilized at 100%

RTP December 9,

1995 at 0400. Reactor power was decreased to 55%

RTP December 10, 1995 at 0518.

Main Feed Pump condenser cleanings were performed following high differential pressures on the traveling screens caused by large amounts of storm intake debris,.

Reactor power was stabilized at 100%

RTP December 11, 1995 at 1445.

The unit exited this reporting period in Mode 1 at 100%

RTP.

There were no challenges to the pressurizer safety valves or power operated relief valves.

Gross electrical generation for the month of December was 819360 MWH.

DETAILS 12-07-95 1641 Reactor power decreased to 94%

RTP due to a Moisture Separator Reheater transient.

12-08-95 0730 0845 Commenced Reactor power ascension to 100% RTP.

Reactor power stabilized at 100%

RTP.

2010 Commenced Reactor power decrease to 95%

RTP to place Moisture Separator Reheaters in service.

12-09-95 12-10-95 2052 0400 0113 Reactor power stabilized at 95% RTP.

Reactor power stabilized at 100%

RTP.

Commenced Reactor power decrease to 55%

RTP to perform Main Feed Pump condenser cleaning.

0518 Reactor power stabilized at 55K RTP.

DOCKET NO:

50-316 UNIT NAME:

D.C.

Cook Unit 2 COMPLETED BY:

M.E. Russo TELEPHONE:

616-465-5901 DATE:

January 3,

1996 PAGE:

Page 2 of 2 MONTHLY OPERATING ACTIVITIES DECEMBER 1995 DETAILS (cont'd) 12-11-95 0000 1445 Commenced Reactor power ascension to 100% RTP.

Reactor power stabilized at 100%

RTP.

UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MONTH: DECEMBER 1995 UNIT NAME:

DATE:

COMPLETED BY:

TELEPHONE:

PAGE:

D.C.

COOK UNIT F

'anuary 3,

1996.

M.E. Russo 616-465-590i Page 1 OF 1 DURATION NO.

DATE TYPE HOURS METHOD OF SHUTTING LICENSEE DOWN EVENT SYSTEM COMPONENT CAUSE AND CORRECTIVE ACTION REASON REACTOR REPORT NO ~

CODE CODE TO PREVENT RECURRENCE 249 951210 F

N/A N/A N/A N/A N/A Reactor power was decreased to 55%

RTP 951210 at 0518.

Main Fee~

Pump condenser cleanings were performed following high differential pressures on the traveling screens caused by large amounts of storm intake debris.

Reactor power was stabilized at 100%

RTP 951211 at 1445.

1 F:

Forced S:

Scheduled 2

Reason:

A:

Equipment Failure (Explain)

B:

Maintenance or Test C:

Refueling D:

Regulatory Restriction E:

Operator Training and License Examination F:

Administrative G:

Operational Error (Explain)

H:

Other (Explain) 3 Method:

1:

Manual 2:

Manual Scram 3:

Automatic Scram 4:

Other (Explain)

Exhibit G Instructions for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 0161) 5Exhibit I: