N.R.C.
OPE NG DATA REPORT DOCKET NO.
DATE COMPLETED BY TELEPHONE OPERATING STATUS
- l. Unit Name D.
C.- Cook Unit 1
- 2. Reporting Period April-90
- 3. Licensed Thermal, Power (MWt) 3250 4.
Name Plate Rating (Gross MWe) 1152
- 5. Design Electrical Rating (Net MWe) 1030 6.
Maximum Dependable Capacity (GROSS MWe) 1056 7.
Maximum Dependable Capacity (Net MWe) 1020 01-May-90 WT Gillett 616-465-5901 notes
- 8. If Changes Occur in Capacity Ratings (Items no.
3 through
- 7) Since Last Report Give Reasons 9.
Power Level To Which Restricted. If Any (Net MWe)
- 10. Reasons For Restrictions. If Any:
This Mo.
Yr. to Date Cumm.
- 11. Hours in Reporting Period 719
~ 0 2879
~ 0 134375. 0 12.
No. of Hrs. Reactor Was Critical 719
~ 0 2816.2 99258.4
- 13. Reactor Reserve Shutdown Hours 0.0 0.0 463.0
- 14. Hours Generator on Line 719 '
2811.3 97500.3
- 15. Unit Reserve Shutdown Hours 0.0 0.0 321.0
- 16. Gross Therm.
Energy Gen.
(MWH) 2267944 8972418 283860437
- 17. Gross Elect.
Energy Gen.
(MWH) 735480 2917400 92489630
- 18. Net Elect.
Energy Gen.
(MWH) 708769 2813637 88945465
- 19. Unit Service Factor 100.0 97.6 73.7
- 20. Unit Availability Factor 100.0 97.6 73.7
- 21. Unit Capacity Factor (MDC Net) 96.6 95.8 65.9
- 22. Unit Capacity Factor (DER Net) 95.7 94.9 64.0
- 23. Unit Forced Outage Rate 0.0 0.0 7.4 24.
Shutdowns Scheduled over Next Six Months (Type, Date,and Duration):
Refuelin
'outa e to be in October 12
.1990 for an estimated duration of 75 da s.
- 25. If Shut Down At End of Report Period, Estimated Date of Startup:
- 26. Units in Test Status, (Prior to Commercial Operation):
Forcast INITIALCRITICALITY INITIALELECTRICITY COMMERCIAL OPERATION Achieved 90051SOi01 900507'DR ADOCK 0 000315 R
\\
AVERAGE DA POWER LEVEL (MWe-Net)
DOCKET NO.
50-315 UNIT ONE DATE 01-May-90 COMPLETED BY WT Gillett TELEPHONE 616-465-5901 DAY MONTH AVERAGE DAILY POWER LEVEL April-90 DAY AVERAGE DAILY POWER LEVEL 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 1019 1021 1020 857 815 1018 1018 1019 1019 1020 1021 1019 1018 1019 1020 1020 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 1020 1019 1019 1020 1019 1019 1021 1018 1018 1019 1019 1006 688 684 0
UNIT SHVZDOWNS AND PONIES REDUCTIONS REPORT MRS: April 1990 DOCKI'.T NO:
UNIT NAME:
IRTE:
CGMPXZZED BY:
TEXZXKQNE:
50-315 D.C.
COOK UNIT 1 May 7, 1990 E.C. Schirmoel (616) 465-5901 MEZHOD OF SEiUZIXNG LICENSEE IX3BATION DONN EVEFZ SYSTEH CGMEGMÃZ CAUSE AND OOEKEICTIVE ACTION KO NO.
IRTE TYPE HCUEB REASON RFACIOR REPOEK NO.
CODE CODE5 PHIVENT REXXJRHENCE 284 04/04/90 F 285 03/29/90 S
N/A N/A zzzzzz Unit power was reduced to 56% startir 1500 hours0.0174 days <br />0.417 hours <br />0.00248 weeks <br />5.7075e-4 months <br /> on 900404 for cleaning of the east and west main feed pump turbine condensers.
Unit pcarer was then increased starting 0310 hours0.00359 days <br />0.0861 hours <br />5.125661e-4 weeks <br />1.17955e-4 months <br /> on 900405 and was held at 874 for main turbine control valve testing.
Unit power was restored to 100% at 2120 hours0.0245 days <br />0.589 hours <br />0.00351 weeks <br />8.0666e-4 months <br /> on 900505.
Unit power was reduced to 70% at 2240 hours0.0259 days <br />0.622 hours <br />0.0037 weeks <br />8.5232e-4 months <br /> on 900428 for fuel cycle extension until the beginning of the scheduled refueling outage.
1 2
F:
Forced Reason:
S:
Scheduled A:
Equipment Failure (Explain)
C:
Refueling D:
Regulatory Restriction E:
Operator Training and Li~Examination F:
Adrainistrative G:
.Operational Error (Explain)
H:
Other (Explain) 3 Method 1:
Manual 2:
Manual Scram 3:
Other (Explain) 4 5
Exhibit G - Instructions Exhibit I:
Same Source for preparation of data entxy sheets for Licensee Event Report (LER) File (NUREG 0161)
\\
A
~
"~
~
DOCfKT ?
UNIT NAME:
CCMPLEXKD BY:
TELEPHONE:
DATE:
PAGEOS 50-315 D.C. Cook Unit 1 E.C. Schiaael (616) 465-5901 May 4, 1990 1 of 1 MONTHLY OPERATING ACTIVITIES ril 1990 HIGHLIGHTS The unit entered the reporting period at 100% Rated Thermal Power.
A power reduction was required fram 1500 hours0.0174 days <br />0.417 hours <br />0.00248 weeks <br />5.7075e-4 months <br /> April 4, 1990, to 2120 hours0.0245 days <br />0.589 hours <br />0.00351 weeks <br />8.0666e-4 months <br /> April 5, 1990, to allow cleaning of the east and west main feedpump turbine condensers.
On April 29, 1990, at 2240 hours0.0259 days <br />0.622 hours <br />0.0037 weeks <br />8.5232e-4 months <br />, a power reduction to 70% Rated Thermal Power was initiated for fuel cycle extension to the scheduled beginning of the refueling outage.
The unit exited the reporting period at 708 Rated Thermal Power.
Gross electrical generation for the month of April was 735480 MNH.
DETAILS 04/04/90 1500 Cormenced unit power reduction to 56% RTP.
1923 Unit is at 568 RTP to allow for cleaning of the east and west main feedpump turbine condensers.
04/05/90 0310 Conmenced unit power increase to 87% RTP.
1315 Unit is at 87% for testing of main turbine control valves.
1615 Conxnenced unit power increase to 100% RTP.
2120 Unit is at 100% RTP.
04/28/90 2240 Gonmenced unit power reduction to 70% RTP.
04/29/90 0206 Unit is at 70% RIP to extend core life to the scheduled beginning of the refueling outage.
I' t.
t)
CJ
~
1 0
t, C
n 4
~
~
DOCKS'0-315 UNIT NAME:
D.C. Cook Unit 1 COMPLEX') BY:
E.C. Schiaael TELEPHONE:
(616) 465-5901 DATE:
May 4, 1990 PAGE:
1 of 1 MAJOR SAH".TY-RELATED ril 1990 1-M-1 Replaced Snubber 1-GRC-C-519, pressurizer spray line support.
~
~
tlPI g