8 ACCELERATED D1%1BUTION DEMONSTJOllO!i SYS1'EM gl ~
REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:8909210122 DOC.DATE: 89/09/08 NOTARIZED: NO DOCKET FACIL:50-315 Donald C.
Cook Nuclear Power Plant, Unit 1, Indiana a
05000315 50-316 Donald C.
Cook Nuclear Power Plant, Unit 2, Indiana 6
05000316 AUTH.NAME AUTHOR AFFILIATION SMZTHPW ~ G ~
RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)
SUBJECT:
Special rept:on 890717-18,preventive maint conducted by maint personnel resulting in seven inoperable fire dampers.
DZSTRZBDTZON CODE:
ZE22D COPIES RECEZVED:LTR X ENCL J SZZE'TITLE:
50.73/50.9 Licensee Event Report (LER), Incident Rpt, etc.
NOTES:
RECIPIENT ID CODE/NAME PD3-1 LA GIITTERPJ.
INTERNAL: ACRS MICHELSON ACRS WYLIE AEOD/DSP/TPAB DEDRO NRR/DEST/CEB, SH NRR/DEST/ICSB 7
NRR/DEST/MTB 9H NRR/DEST/RSB SE NRR/DLPQ/HFB 10 NRR/DOEA/EAB 11 NUDOCS-ABSTRACT RES/DSIR/EIB EXTERNAL EG&G WILLIAMSI S LPDR NSIC MAYSI G
~
NUDOCS FULL TXT COPIES LTTR ENCL 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 4
4 1
1 1
1 1
RECIPIENT ID CODE/NAME PD3-1 PD ACRS MOELLER AEOD/DOA AEOD/ROAB/DSP IRM/DCTS/DAB NRR/DEST/ESB SD NRR/DEST/MEB 9H NRR/DEST/PSB 8D NRR/DEST/SGB 8D NRR/DLPQ/PEB 10 NRR D EP/RPB 10 EG ILE 02 FILE 01 L ST LOBBY WARD NRC PDR NSIC MURPHYPG.A COPIES LTTR ENCL 1
1 2
2 1
1 2
2 1
1 1
1 1
1 1
1 1
1 1
1 2
2 1
1 1
1 1
1 1
1 1
1 NCTE 'IO ALL RIDS" RECIE2ÃIS PLFASE HELP US 'IO RECCE %ASTE!
CON'ZACT 'IHE DOCUMEÃI'ONIC)LDESK, RDCN Pl-37 (EXT. 20079)
KO ELDGMXH YOUR ÃQ93 PKH DISTRXBUZICH LISTS MR IXXX1MERZS YOU DEPT NEEDt TOTAL NUMBER OF COPIES REQUIRED: ITTR 40 ENCL 40
Indiana Michigan Power Company Cook Nuclear Plant P.O. Box 458 Bridgman. Ml 49106 616 465 5901 INDIANA NICHIGAItI POWER September 8,
1989 Donald C.
Cook Nuclear Plant Unit Nos.
1 and 2
Docket Nos.
50-315 and 50-316 License Nos.
DPR-58 and.DPR-74 U.S. Nuclear Regulatory Commission Document Control One White Flint North 11555 Rockville Pike Rockvilie, Maryland 20852 Attn: A.B. Davis
Dear Mr. Davis:
This special report is being submitted in accordance with Technical Specification 3.7.10 Action a, to inform you that 1) seven fire dampers were inoperable for longer than seven days permitted under Technical Specification 3.7.10 Action a,
and that the special report required by Technical Specification 3.7.10 Action a was not submitted within thirty days as specified; and
- 2) that one fire barrier has been inoperable longer than the seven days allowed by Technical Specification 3.7.10 Action a.
On July 17 and 18,
- 1989, Maintenance department personnel conducted a preventive maintenance activity which had been developed in March, 1989.
The intent of this activity was to have Maintenance inspect the plant fire dampers which were not covered by Technical Specifications.
However, the preventive maintenance task sheet author incorrectly developed the task sheet from a data base of non-safety related
This caused the Maintenance personnel to deal with the subject dampers in a manner which is non-conservative to Technical Specification 3.7.10.
The maintenance procedure has been revised to delete the Technical Specification related dampers.
The following dampers were affected:
Fire damper 1-HV-ET-FD-2, located in the unit one reactor cable tunnel quadrant N4, failed its preventive 8909220122 890908 PDR ADOCK 05000315 S
PNU
maintenance operability test on July 17, 1989. It was restored to operability on August 2, 1989.
A Fire
- Watch, as required by Technical Specification 3.7.10 Action a, was not posted due to an error in the preventive maintenance procedure.
Fire damper 1-HV-ET-FD-4, located in the unit one reactor tunnel quadrant 44 failed its preventive maintenance operability test on July 17, 1989. It was restored to operability on August 2, 1989.
A Fire
- Watch, as required by Technical Specification 3.7.10 Action a, was not posted due to an error in the preventive maintenance procedure.
Fire damper 1-HV-TS-FD-l, located in the pressurizer heater transformer room failed its preventive maintenance operability test on July 17, 1989.
Due to an error in the preventive maintenance procedure, a
Fire Watch, as required by Technical Specification'.7.10 Action a, was not posted until the error was detected on August 24, 1989.
The Fire Watch remained in effect until the damper was restored to operability on September 1,
1989.
Fire damper 1-HV-AS-D4, located in the auxiliary cable vault, failed its preventive maintenance operability test on July 17, 1989.
Due to an error in the preventive maintenance procedure, a Fire Watch, as required by Technical Specification 3.7.10 Action a was not posted until the error was detected on August 21, 1989.
The Fire Watch remained in effect until the damper was restored to operability on August 31, 1989.
Fire damper 1-HV-AS-DlA, located in the normal blowdown flash tank room, failed its preventive maintenance operability test on July 17, 1989.
Due to an error in the preventive maintenance procedure, a Fire Watch, as required by Technical Specification 3.7.10 Action a, was not posted until the error was detected on August 21, 1989.
The Fire Watch remained in effect until the damper was restored to operability on August 23, 1989.
Fire damper 2-HV-ET-FD-3, located in the unit two reactor cable tunnel quadrant g4, failed its preventive maintenance operability test on July 18, 1989.
Due to an error in the preventive maintenance procedure, a
Fire Watch, as required by Technical Specification 3.7.10 Action a was not posted until the error was detected on August 21, 1989.
The Fire Watch remained in effect until the damper was restored to operability on August 21, 1989.
0 Fire Damper 1-HV-AS-D2A, located in the hallway of the 633'evel of the auxiliary building, failed its preventive maintenance operability test on July 17, 1989.
Due to an error in the preventive maintenance procedure, a Fire Watch, as required by Technical Specification 3.7.10 Action a, was not posted until the error was detected on August 21, 1989.
The Fire Watch remained in effect until the damper was restored to-operability on September 7,
1989.
A seismic gap fire seal in the unit one 4KV cable spreading area was declared inoperable on August 2, 1989 due to a tear in the gap fire seal material.
It is anticipated that the seal will be repaired by September 21, 1989.
A Fire Watch, as required by Technical Specification 3.7.10 Action a, was posted and will remain in effect until the gap seal is declared operable.
Respectfully, W.
G. Smith, Jr.
Plant Manager WGS:clw CC:
D.H. Williams, Jr.
A.B. Davis, Region III M.P. Alexich P.A. Barrett J.E.
Borggren R.F.
Kroeger NRC Resident Inspector J.G. Giitter, NRC R.C. Callen G.
Cha-. noff, Esq.
Dottie Sherman, ANI Library D.
Hahn INPO PNSRC A. A. Blind S.J.
Brewer/B.P.
Lauzau
S