TABLE 3.3-2 REACTOR TRIP SYSTEM INSTRUMENTATION RESPONSE TIMES FUNCTIONAL UNIT

RESPONSE

TIME

1. Manual Reactor Trip 2.

Power Range, Neutron Flux (High and Low Setpoint)

NOT APPLICABLE Less than or equal to 0 '

seconds 3.

Power Range, Neutron Flux, High Positive Rate NOT APPLICABLE 4.

Power Range, Neutron Flux, High Negative Rate Less than or equal to 0.5 seconds*

5. Intermediate
Range, Neutron Flux 6.

Source

Range, Neutron Flux
7. Overtemperature delta T NOT APPLICABLE NOT APPLICABLE Less than or equal to 6.0 seconds
8. Overpower delta T
9. Pressurizer Pressure--Low NOT APPLICABLE Less than or equal to 1.0 seconds 10 'ressurizer Pressure--High Less than or equal to 1.0 seconds 11.Pressurizer Water Level--High NOT APPLICABLE
  • Neutron detectors are exempt from response time testing.

Response

time of the neutron flux signal portion of the channel shall be measured from detector output or input of first electronic component in channel.