ML17325A997

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Deleting Overload Test for Diesel Generators Required by Spec 4.8.1.1.2.c.9
ML17325A997
Person / Time
Site: Cook 
Issue date: 10/31/1988
From:
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
Shared Package
ML17325A995 List:
References
NUDOCS 8811040315
Download: ML17325A997 (3)


Text

ATTACHMENT 2 TO AEP:NRC:0896L PROPOSED REVISED TECHNICAL SPECIFICATION PAGES l

8811040315 881031 PDR ADOCK 05000316 P

PDC

(

E.LECmiCai, POWaR SVSTe~S i SURVKII.LAflCE REOUIREHENTS Continue-'f Verifying the diesel starts from ambient condition on the auto-start

signal, energizes the emergency busses with permanently connected
loads, energizes the auto-connected shutdown loads thr ough the load sequencer and operates for

~

5 minutes while its generator is loaded with the shu>down loads.

6.

Verifying that on an KSF actuation test signal (without loss of offsite po. er ) the diesel generator starts on the auto-star t signal and operates on standby for

~

5 minutes.

7.

Verifying that on a simulated loss of the diesel gener-ator (with offsite power not available),

the loads are shed from the emergency busses and that subsequent loading of the diesel generator is in accordance with design requirements.

8.

Simulating a loss of offsite power in conjunction with an ESF actuation test signal, and a)

Verifying de-energization of the emergency busses and load shedding from the emergency busses.

b)

Verifying the diesel starts from ambient condition on the auto-start

signal, ener" zes the emergency busses with permanently connec:

d loads, energizes the auto-connected emergency (accident) loads through the load sequencer and operates for 5 minutes while its generator is loaded with the emergency loads.

c)

Verifying that on diesel generator trip, the loads are shed from the emergency buses and the diesel re-starts on the auto-start signal following manual resetting of the diesel trip lockout relay, the emergency buses are energized with permanently connec.ed

loads, the auto-connected emergency loads are energized through the load sequencer and the diesel operates for

>5 minutes while its generator is loaded wi th emergency loads.

d) Verifying that all diesel generator trips, except engine overspeed and generator differential, are automatically bypassed upon loss of voltage on tne emergency bus and/or sa fety injection ac:uation signal.

9.

Verifying that the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

During this test the diesel generator shall be loaded equal to or greater than 3500 kw.

Within 5 minutes after completing this 24-hour test, perform Surveillance Requirement 4.8.1.1.2.c.5.

0.

C.

COOK - UNIT Z

3/4 8-3a