ML17312A687
| ML17312A687 | |
| Person / Time | |
|---|---|
| Site: | Palo Verde |
| Issue date: | 04/05/1996 |
| From: | James M. Levine ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| 192-00963-JML-B, 192-963-JML-B, 2-SR-96-001, 2-SR-96-1, NUDOCS 9604160423 | |
| Download: ML17312A687 (8) | |
Text
CATEGORY 1 REGULATORY INFORMATION DISTRIBUTiON SYSTEM (RIDS)
ACCESSION NBR:9604160423 DOC.DATE: 96/04/05 NOTARIZED:
NO DOCKET I FACIL:STN-50-529 Palo Verde Nuc'ear S"ation, Unit 2, Arizona Publi 05000529 AUTH. NAME AUTHOR AFFILIATION LEVINE,J.M.
Arizona Public Service Co.
(formerly Arizona Nuclear Power RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)
SUBJECT; Rev 1 to Special Rept 2-SR-96-001,on 960404,alert declared due to fire in voltage regulator for CR 6 remote shutdown pane'ssential lighting,clar'fy.'ng status of power to UPS 2EQDNN02.Further investiga='ons
.'nto e rent being performed.
DISTRIBUTION CODE:
IE22D COPIES RECEIVED:LTR I
ENCL I
SIZE:
TITLE: 50.73/50.9 Licens~~ Event Report (LER), Incident Rpt, etc.
NOTES:Standardized plant.
E 05000529 G
REC.PIENT D CODE/NAME PD4-2 PD INTERNAI: ACRS AEOD/SPD/RRAB NRR/DE/ECGB NRR/DE/EMEB NRR/DRCH/HICB NRR/DRCH/HQMB NRR/DSSA/SPLB RES/DSIR/EIB EXTERNAL: L ST LOBBY WARD NOAC MURPHY,G.A NRC PDR COPIES LTTR ENCL 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 RECIPIENT ID CODE/NAME THOMASPC AEOD SPD RAB CE TE E EELB NRR/DRCH/HHFB NRR/DRCH/HOLB NRR/DRPM/PECB NRR/DSSA/SRXB RGN4 FILE 01 LITCO BRYCEPJ H
NOAC POORE,W.
NUDOCS FULL TXT COPIES
'TTR ENCL 1
1 2
2 1
1 1
1 1
1 1
1 1
1 1
1 1
1 2
2 1
1 1
1 0
D NOTE TO ALL "RIDSN RECIPIENTS:
PLEASE HELP US TO REDUCE WASTE!
CONTACT THE DOCUMENT CONTROL DESK, ROOM OWFN SD-5(EXT. 415-2083)
TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!
TOTAL NUMBER OF COPIES REQUIRED:
LTTR 26 ENCL 26
JAMES M. LEVINE VICE RREEIDER NUCI,EAR RRODUC iON Arizona Public Service Company PALO VERDE NUCLEAR GENERATING STATiON P 0 BOX 52034
~
PHOENIX, ARIZONA85072-2034 192-00963-JML/BAG/DRL April 5, 1996 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Mail Station P1-37 Washington, DC 20555-0001
Dear Sirs:
Subject:
Palo Verde Nuclear Generating Station (PVNGS)
Unit 2 Docket No. STN 50-529 (License No. NPF-51)
Special Report 2-SR-96-001, Revision 1
Enclosed please find Special Report 2-SR-96-001, Revision 1 prepared and submitted pursuant to PVNGS Emergency Plan Implementing Procedure (EPIP-03),
"Emergency Classification Implementing Actions". This report discusses a condition requiring the declaration of an Alert due to a fire in a voltage regulator for Control Room and Remote Shutdown Panel essential lighting and clarification for the status of power to 2EQDNN02.
Ifyou have any questions, please contact Burton A. Grabo, Section Leader, Nuclear Regulatory Affairs, at (602) 393-6492.
Sincerely, GRO/BAG/DRL Attachment cc:
L. J. Callan K. E. Perkins K. E. Johnston (all with attachment) 9604i60423 960405 PDR ADOCK 05000539 S
>zP~
ENCLOSURE PALO VERDE NUCLEAR GENERATING STATION UNIT 2 ALERT DOCKET NO. 50-529, LICENSE NO. NPF-51 SPECIAL REPORT 2-SR-96-001, Revision 1
PALO VERDE NUCLEAR GENERATING STATION UNIT 2 ALERT DOCKET NO. 50-529, LICENSE NO. NPF-51 SPECIAL REPORT 2-SR-96-001, Revision 1 This Special Report is being provided pursuant to PVNGS Emergency Plan Implementing Procedure (EPIP-03), "Emergency Classification Implementing Actions" to report a condition requiring the declaration ofan Alert for Palo Verde Unit 2 at approximately 1714 MST on April 4, 1996. The Alert was terminated at approximately 1807 MST on April4, 1996.
On April4, 1996, at approximately 1700 MST, Palo Verde Unit 2 was in Mode 6 (REFUELING) when a fault occurred in the voltage regulator for Control Room and Remote Shutdown Panel Essential Lighting (2EQBBV02) resulting in a fire in the 100 foot elevation ofthe Control building "B"Battery Equipment Room and smoke in the 140 foot elevation ofthe Control building Unintermptable Power Supply (2EQDNN02). Fire teams responded and both fires were considered out by 1735.
At approximately 1700 MST, a smoke condition was discovered on the 140 foot elevation ofthe Control Room area immediately behind the main control panel. This fire was identified at 2EQDNN02 which operators then down-powered. Light smoke was present in the local area.
Main Control Room access was not lost and evacuation ofControl Room staF was not required.
HVACequipment was switched to smoke removal mode and the smoke was quickly removed from the area. In addition, a second related fire was noted in the Control building "B"Battery Equipment Room and the event was classified as an Alert in accordance with EPIP-02. The Nuclear Regulatory Commission (NRC) Operations Center was notified at approximately 1810 MST.
At approximately 1807 MST on April4, 1996, the Alert was terminated in accordance with EPIP-03. The fires caused a briefdelay to work on the stuck fuel assembly. The assembly is now scheduled to be liAed and moved early Saturday morning. Further investigation into the circumstances surrounding this event is being performed in accordance with the APS Incident Investigation Program.
The results ofthe investigation willbe reported pursuant to 10CFR50.73.