Forwards Final Rept Re Response to IE Bulletin 85-003, Motor-Operated Valve Common Mode Failures & Improper Switch Settings. Procedures for Correct motor-operator Switch Setting Determination & Maint Established
ML17303A733
Person / Time
Site: Palo Verde  
Issue date: 01/15/1988
From: Van Brunt E
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
161-00745-EEVB, 161-745-EEVB, IEB-85-003, IEB-85-3, NUDOCS 8801200042
Download: ML17303A733 (76)


Text

ACCELZMTED DISXRJBUTJON DEMONSTRATION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

DOCKET 05000528 05000529 05000530

SUBJECT:

- Forwards final rept re response to IE Bulletin 85-003, "Motor-Operated Valve Common Mode Failures...."

L/m DISTRIBUTION CODE: IE11D COPIES RECEIVED:LTR ENCL SIZE:

/V/

TITLE: Bulletin Response (50 DKT)

ACCESSION NBR:8801200042 DOC.DATE: 88/01/15 NOTARIZED: YES FACIL:STN-50-528 Palo Verde Nuclear Station, Unit 1, Arizona Publi STN-50-529 Palo Verde Nuclear Station, Unit 2, Arizona Publi STN-50-530 Palo Verde Nuclear Station, Unit 3, Arizona Publi AUTH.NAME AUTHOR AFFILIATION VAN BRUNT,E.E.

Arizona Nuclear Power Project (formerly Arizona Public Serv RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

NOTES:Standardized plant.

Standardized plant.

Standardized plant.

05000528'5000529 05000530 RECIPIENT ID CODE/NAME PD5 LA LICITRA,E INTERNAL: AEOD/DOA AEOD/DSP/TPAB NRR/DES T/ADS NRR/DOEA/EAB EPB REG LE 02 GN LE 01 EXTERNAL'PDR NSIC NOTES:

COPIES LTTR ENCL 1

0 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 RECIPIENT ID CODE/NAME PD5 PD DAVIS,M AEOD/DSP NRR/DEST/ADE NRR/DEST/MEB NRR/DOEA/GCB NRR/PMAS/ILRB RES/DE/EIB NRC PDR COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 A

Sj A

TOTAL NUMBER OF COPIES REQUIRED LTTR 21 ENCL 20

Arizona Nuclear Power Project P.O. BOX 52034

~

PHOENIX, ARIZONA85072-2034 Docket Nos.

STN-528/529/530 January 15, 1988 161-00745-EEVB/JBK U. S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555

Dear Sir:

Subject:

Palo Verde Nuclear Generating Station (PVNGS)

Units 1, 2 and 3

NRC IE Bulletin 85-03:

Motor-Operated Valve Common Mode Failures and Improper Switch Settings File:

87-055-026

References:

(2)

(3)

(4)

(5)

(6)

Letter from ANPP to U.S.

NRC

(

Subject:

Same; ANPP-37192-EEVB/JBK/98.05; dated June 30, 1986).

Letter to ANPP from U.S.

NRC

(

Subject:

Same; dated September 17, 1986).

Letter from ANPP to U.S.

NRC

(

Subject:

Same; ANPP-38862-JGH/JBK/98.05; dated October 27, 1986).

Letter from ANPP to U.S.

NRC

(

Subject:

Same; 161-00213-JGH/JBK; dated May 15, 1987).

Letter to ANPP from U.S.

NRC

(

Subject:

Same; dated June 30, 1987).

Letter from ANPP to U.S.

NRC

(

Subject:

Same; 161-00420-JGH/JBK; dated August 3,

1987).

Reference (1) contained ANPP's-response to Item e

in the subject bulletin.

Reference (2) requested further clarification for two specific areas within Reference (1).

Reference (3) provided clarification regarding the two specific areas.

Reference (4) revised ANPP's schedular commitment's provided in Reference (1).

Reference (5) requested further information for four items within Reference (1) and (3).

Reference (6) provided the information requested by Reference (5)

~

This Letter and Attachments provide ANPP's final report for completion of each 'item in the subject bulletin.

880i200042 880ii5 PDR ADOCK 05000528 0

DCD

+il

U.

S. Nuclear Regulatory Commission Page 2

If you have any questions or require additional information, do not hesitate to call.

Very truly yours, v

cczu)

AU <

E.

E. Van Brunt, Jr.

Executive Vice President Project Director EEVB/JBK/dim Attachments cc:

0.

M.

De Michele A. C. Gehr E. A. Licitra J.

B. Martin J.

R. Ball (all w/a)

L II t

STATE OF ARIZONA

)

)

SS ~

COUNTY OF MARICOPA)

I, Edwin E.

Van Brunt, Jr.,

represent that I am Executive Vice Presideng Project Director of Arizona Nuclear Power

Project, that the foregoing document has been signed by me on behalf of Arizona Public Service Company with full authority to do so, that I have read such document and know its contents, and that to the best of my knowledge and belief, the statements made therein are true.

Edwin E.

Van Brunt, Jr.

Swore to before ee tbfsudsy o

Notary blic My Commission Expires:

t8 Comn'.~si~n Exgi!e! Apr'i 6, 1991

ATTACHMENT A ANPP RESPONSES TO BULLETIN ITEMS 14 61K/0049K

For motor-operated valves in the high pressure coolant injection/core spray and emergency feedwater systems (RCIC for BWRs) that are required to be tested for operational readiness in accordance with 10 CFR 50.55a(g),

develop and implement a

program to ensure that valve operator switches are

selected,

-set and maintained properly.

This should include the following components:

NRC Item a a ~

Review and document the design basis for the operation of each valve.

This documentation should include the maximum differential pressure expected during both opening and closing the valve for both normal and abnormal events to the extent that these valve operations and events are included in the

existing, approved design basis, (i.e.,

the design basis documented in pertinent license submittals such as FSAR analyses and fully-approved operating and emergency procedures, etc.).

When determining the maximum differential

pressure, those single equipment failures and inadvertent equipment operations (such as inadvertent valve closures or openings) that are within the plant design basis should be assumed.

PVNGS Res onse ANPP has completed the design basis review for the operation of each motor-operated valve in the Auxiliary Feedwater (AFW) and High Pressure Safety Injection (HPSI) systems for Palo Verde Units 1, 2, and 3.

The system valve data summary for each unit is presented in Attachment B.

The Differential Pressure values for each'alve listed in Attachment B were determined by a review of the design basis events documented in the PVNGS FSAR/CESSAR, and the normal and emergency operating procedures.

Particular derivations and assumptions are documented in calculations for the AFW system and HPSI system.

For the AFW system, the maximum differential pressure for each valve is determined using the most severe design basis event (i.e., the design basis event which imposes maximum differential pressure at the valve) coupled with sufficient conservatism (e.g.,

frictionless flow).

For the HPSI

system, the maximum differential pressure is also determined using the most severe design basis event coupled with sufficient conservatism.

Water hammer due to valve closure is considered to not be a

concern with respect to developing the differential pressures for each IEB 85-03 motor-operated valve.

Based on flowrates at time of valve closure and slow valve closure

times, any flow induced water hammer pressure waves are believed to be low magnitude and within the design limits of the piping system.

-Al-

I

This position is consistent with the analysis described in NUREG-0582, "Water Hammer in Nuclear Power Plants."

Therefore, water hammer effects were not included in the maximum differential pressure calculations.

-A2-

n

NRC Item b b.

Using the results from item a above, establish the correct switch settings.

This shall include a program to review and revise, as necessary, the methods for selecting'nd setting all switches (i.e.,

torque, torque
bypass, position
limit, overload) for each valve operation (opening and closing).

If the licensee determines that a valve is inoperable, the licensee shall also make an appropriate justification for continued operation in accordance with the applicable technical specification.

PVNGS Res onse Using the results from Item a,

switch settings for each motor-operated valve were determined using a switch setting procedure.

The final switch settings are provided in Attachment B for each motor-operated valve.

-A3-

t I

I

NRC Item c c ~

Individual valve settings shall be

changed, as appropriate, to those established in item b,

above.

Whether the valve setting is changed or not, the valve will be demonstrated to be operable by testing the valve at the maximum differential pressure determined in item a above with the exception that testing motor-operated valves under conditions simulating a

break in the line containing the valve is not required.

Otherwise, justification should include the alternative to maximum differential pressure testing which will be used to verify the correct settings.

Note:

This bulletin is not intended to establish a

requirement for valve testing for the condition simulating a

break in the line containing the valve.

However, to the extent that such valve operation is relied upon in the design

basis, a

break in the line containing the valve should be considered in the analyses prescribed in items a

and b above.

The resulting switch settings for pipe break conditions should be verified, to the extent practical, by the same methods that would be'sed to verify other settings (if any) that are not.

tested at the maximum differential pressure.

Each valve shall be stroke

tested, to the extent practical, to verify that the settings defined in item b

above have been properly implemented even if testing with differential cannot be performed.

PVNGS Res onse Individual valve settings were

changed, as appropriate, to those established in Item b

and in accordance with switch setting policies established in ANFP procedures.

A MOVATS static test was performed on all motor-operated valves within the scope of Bulletin 85-03.

A differential pressure test was performed on a representative sample for each valve group listed in Attachment D.

Each valve group consists of valves of the same type, size, motor actuator size and actuator motor voltage.

Attachment B

indicates the specific valves which were differential pressure tested and other

-pertinent information for each motor-operated valve.

Attachment C

provides a summary of the abnormalities which were corrected as a result of the Bulletin.

-A4-

NRC Item d Prepare or revise procedures to ensure that correct switch settings are determined and maintained throughout, the life of the plant.*

Ensure that applicable industry recommendations are considered in the preparation of these procedures.

PVNGS Res onse Procedures for correct motor-operator switch setting determination, and maintenance of this information throughout the life of the plant, have been established as part of ANPP's

<<Valve Motor Operator Monitoring and Test Program."

  • This item is intended to be completely consistent with action item 3.2, "Post-Maintenance Testing (All Other Safety-Related Components),"

of Generic Letter 83-28, "Required Action Based on Generic Implications of Salem ATWS Events."

These procedures should include provisions to monitor valve performance to ensure the switch settings are correct.

This is particularly important if the torque or torque bypass switch setting has been significantly raised above that required.

-A5-

[1

'f I

NRC Item e e.

Within 180 days of the date of this bulletin, submit a

written report to the NRC that:

(1) reports the results of item a and (2) contains the program to accomplish items b through d above including a schedule for completion of these items.

For plants with an OL, the schedule shall ensure that these items are completed as soon as practical and within two years from the date of this bulletin.

2 ~

For plants with a

CP, this schedule shall ensure that these items are completed before the scheduled date for OL issuance or within two years from the date of this bulletin, whichever is later.

PVNGS Res onse (1)

ANPP has completed the design basis review for the operation of each motor-operated valve in the AFW and HPSI systems.

(2)

Items a through d have been completed and are summarized in this report.

-A6-

NRC Item f Provide a

written report on completion of the above program.

This report should provide (1) a verification of completion of the request

program, (2) a summary of the findings as to valve operability prior to any adjustments as a result of this bulletin, and (3) a summary of data in accordance with Table 2,

Suggested Data Summary Format.

The NRC staff intends to use this data to assist in the resolution of Generic Issue II.E.6.l.

This report shall be submitted to the NRC within 60 days of completion of the program.

Table 2 should be expanded, if appropriate, to include a summary of all data required to evaluate the response to this bulletin.

~

PVNGS Res onse ANPP submits this letter as a final report for completion of Items a

through d.

Summaries of findings and data are contained in Attachments B and C.

-A7-

t) 1 I

NRC uestion Although no specific request.

or requirement is intended, the time required to complete each action item above would be helpful to the NRC in evaluating the cost of this bulletin.

PVNGS Res onse As of May 23,

1986, the estimated time expenditure on each action item is summarized below:

Item a:

ANPP Over 1500 man-hours Vendors Over 1500 man-hours Item b:

ANPP Over 1500 man-hours*

Vendors Over 1200 man-hours Item c:

ANPP Over 1500 man-hours Vendors Over 1100 man-hours Item d:

ANPP

. 800 man-hours Vendors 400 man-hours Item e:

ANPP 400 man-hours Vendors 200 man-hours

  • Includes time expenditure for NRC IE Module 35743 Motor-Operated Valve Maintenance Program begun in Fall of l983.

-A8-

M i

l I

I l

I

ATTACHMENT B VALVE DATA

SUMMARY

FOR AFW AND HPSI FOR PALO VERDE UNITS lg 2

AND 3

1 1

I

Hotes:

H.AD = The designation H.A. under the heading of maximum differential pressure indicates there is no safety impact in the specified mode of operation.

2.

2, and 3 JAFAHV 0054 (which is spring closed) has been determined to be outside the scope of IEB 85-03 since the safety related function is to close and this is accomplished with the stored energy of a spring and not the electric motor actuator.

3.

Ho differential pressure test required due to system configuration.

This HOV is required to close for system isolation during zero differential pressure conditions.

Proper operation was verified during static testing.

The rating of the Limitorque SNC-04-7.5 is based on motor torque capability not valve operator thrust.

5.

Due to conservative construction Limitorque allows actuator output thrust values to exceed published rated value by 10X.

6.

During the performance of torque switch adjustment (TSA) a change in philosophy was adapted.

At first specific thrust values were targeted requiring multiple tests.

The later guideline was changed to adjust for required thrust plus margin up to actuator rating.

7.

Abbreviations Defined Aux F.M. Reg Aux F.M. Isol PPA to SG1 PPB to SG2 AFPP Auxiliary Auxiliary Pump A to Pump B to Auxiliary Feed Mater Regulator Valve Feed Mater Isolation Valve Humber 1 Steam Generator Humber 2 Steam Generator Feed Mater Pump RMT HPSI Refueling Mater Storage Tank High pressure Safety Injection 8.

Torque switches are not actuated during the first 20 to 25K of valve stroke or rotation when the valve is moving in the open direction.

This provides opening forces as high as those associated with the actuator motor stall torque.

After initial opening, valve stroking force drops rapidly and lower torque switch settings are appropriate.

9.

The closing forces for torque seating of the auxiliary feedwater isolation valves (1, 2, S 3 [[::JAF-UV-0034|JAF-UV-0034]], 0035,

0036, and 0037) as determined by test on 1JAFCUV-0036 and 3JAFBUV-0035 have been reduced by position stopping rather than torque seating ensuring these. valves open (which is the safety-related function) during worst case accident conditions.

1461K/0049K

PVNGS AUXILIARY FEEDIIATER SYSTEM VALVE DATA SUHHARY UNIT ¹ 1

I I

(Valve Number(

(Hanufacturer(

Model

( Type/Size (Bod Ratin I

I (1JAFBHV-0030(

(CCI I

(EXG9-X3-X6P6(

( Globe/4" (900 lb I

I (1JAFBHV-0031(

(CCI I

(EXG9-X3-X6P6(

(Globe/4" I

(900 lb.

I I

(1JAFAHV-00321 (CCI I

(EXG9-X3-X6P6(

(Globe/4" 1900 lb.

I I

(1JAFCNV-0033(

(CCI I

IEXG9-X3-X6P6(

(Globe/4~~

(900 lb I

I (1JAFBUV-0034(

(Anch/Dar (5746 (Gate/6" (900 lb.

Valve Operator:

Hanufacturer Hodel Hotor RPH Ratin s LBS Limitorque SHB-00-15 3600 RPM 14,000 Limitorque SHB-00-15 3600 RPH 14,000 Limitorque SHB-00-15 1900 RPH 14,000 Limitorque SMB-00-15 1900 RPM 14,000 Limitorque SMB-00-25 1700 RPH 14,000 Valve Function I

I (Aux FIJ Reg (Valve:

PPB to(

ISG1 I

I I

I (Aux FH Reg (Valve:

PPB Ito SG2 I

I (Aux. Fll Reg (Valve:

PPA (to SG1 I

I (Aux Fll Reg (Valve:

PPA (to SG2 I

I (Aux FM Isol (Valve:

PPB (to SG1 I

Haximum Design Differential Pressure (PSID)t 0 enin Closin 1, 740/1, 740 1, 740/1, 740 1,810/1,810 1, 810/1, 810 1, 740/1, 740 As-Found Torque Sw. Trip Thurst Equiv't.

Opening/Closing LBS LBS 4,350/3,850 I

5,600/4,560 8,800/8,800 8,680/15,340 8, 730/9, 131 As-Left Torque SM ~ Trip Thrust Equiv't.

Opening/Closing LBS LBS 5,220/6,700 6,120/6,680 10,600/10,460 12,810/11,680 11,820/11,340 See Note 9 Test Diff. Pres.(

Heasured Thrust Required For Opening/Closing LBS LBS See Valve No.

1JAFAHV-0032 See Valve Ho.

1 JAFAHV-0032 I

I 18OO I SIO I

I (4846 lbs/4846 lbs(

I I

See Valve No.

1JAFAHV-0032 See Valve No.

3JAFBUV-0035 Satis-factory Test Results Yes No Yes Yes Yes Yes Yes

UNIT ¹ 1

PVNGS AUXILIARY FEEDWATER SYSTEH VALVE DATA SUHMARY I

I (Valve Number]

)Manufacturer)

Model

[ Type/Size

)Bod Ratin Valve Operator:

Hanufacturer Hodel Hotor RPM Ratin s

LBS I

II-I Valve Function Maximum Design Differential Pressure (PSID)i 0 enin Closin As-Found Torque SN. Trip Thurst Equiv't.

Opening/Closing LBS LBS As-Left Torque Su. Trip Thrust Equiv't ~

Opening/Closing LBS LBS Test Diff. Pres.)

Measured Thrust Required For Opening/Closing LBS LBS Satis-factory Test Results Yes No I

l l 1JAFBUV-0035I (Anch-Dar i5746

]Gate/6" I900 lb.

I I

/ 1JAFCUV-0036/

/Anch/Dar (5746 IGate/6<<

I I900 lb.

I I

I 1 J AFAUV-0037 I

[Anch/Dar

]5746

[Gate/6" 1900 lb.

I I

i 1JAFANV-0054'Gimpei IGS-N I

[Globe/4" I900 lb.

I I

I 1JSGAUV-0134I JAnch/Dar I

I iGate/6" I900 lb.

Limitorque SHB-00-25 1700 RPH 14,000 Limitorque SMB-00-25 1900 RPH 14,000 Limitorque SHB-00-25 1900 RPH 14,000 Limitorque SHB-000 1900 RPH 8,000 Limitorque SB-0-40 1900 RPM 24,000 I

)Aux FN Isol

/Valve:

PPB ito SG2 I

I

/Aux Fll Iso1

[Velvet PPA ito SG1 I

I iAux FN Iso'I

[Valvei PPA Ito SG2 I

I I

/Aux Fll

/Turbine Trip

/

/ Valve I

I I

SG2 Steam i

To AF PP f Turbine I

'1,740/1,740 1,810./1,810 1, 810/1, 810 NA/1,355 Note 1

1,355/NA Note 1

8,670/5,730 Spring Pk/5,605 Shift I

)11,380/'l3,880 I

I I

7,040/7,400 10,900/9,260 9,200/9,320 See Note 8&9 9,500/9,840 See Note 9 9,680/11,240 I

I 7i020/7i360 I

I I

I I 21 980/16 200 I

I I

See Valve No.

3JAFBUV-0035 1800 PSID 8,620/10,160 See Valve No.

1JAFCUV-0036 See Note 2 See Valve No.

2JSGAUV-0138 N.A.

Yes Yes Yes Yes

b

UNIT ¹ 1

PVNGS AUXILIARY FEEDNATER SYSTEH VALVE DATA SUHHARY I

I

]Valve Number)

)Manufacturer)

Model

) Type/Site

)Bod Retin Valve Operator:

Hanufacturer Model Motor RPH Ratin s

LBS Valve Function I

I Maximum Design Differential Pressure (PSID):

0 enin Closin As-Found Torque SN. Trip Thurst Equiv't.

Opening/Closing LBS LBS I

I I

I As-Left

/ Test Diff. Pres.f Satis-

/ Torque Su. Trip f Heasured Thrust

( factory

/

/ Thrust Equiv't ~

/

Required For

/

Test

/ Opening/Closing

) Opening/Closing

) Results LBS LBS LBS LBS Yes No I

I (1JSGAUV-0138) Limitorque (Anch/Dar

) SB-0-40 I

I 1900 RPH

)Gate/6"

) 24,000 1900 lb.

I SG2 Steam To AF PP

) Turbine I

I I

I 1,355/NA

/

11,060/22,300

/

23,900/21,980 Note 1

l I

I I

I I

I

[ See Valve No.

I 2JSGAUV-0138 I

I I

I I

I Yes I

I I

I I

UNIT ¹ 2 PVNGS AUXILIARY FEEDMATER SYSTEH VALVE DATA SUHHARY I

I

[Valve Number(

)Hanufacturer)

Model

) Type/Size

[Bod Ratin Valve Operator:

Hanufacturer Hodel Hotor RPH Ratin s

LBS Valve Function Haximum Design Differential Pressure (PSID):

0 enin Closin As-Found Torque Su. Trip Thurst Equiv't.

Opening/Closing LBS LBS As-Left Torque Su. Trip Thrust Equiv't.

Opening/Closing LBS LBS Test Diff. Pres.(

Heasured Thrust Required For Opening/Closing LBS LBS Satis-factory Test Results Yes No I

I l2JAFBHV 030I COCCI I

IEXG9-X3 X6P6I

/Globe/4" I900 lb.

I I

I2JAFBNV 00311 COCCI I

IEXG9-X3-X6P6I

]Globe/4" I900 lb.

I I

I2JAFANV-0032I COCCI I

IEXG9-X3 X6P6I J G Iobe/4a I900 lb.

I I

i2JAFCHV-0033/

COCCI I

IEXG9-X3-X6P61

[Globe/4" I900 lb.

I I

I2JAFBUV-0034I

)Anch/Dar i5746

)Gate/6" 1900 lb.

Limitorque SHB-00-15 3600 RPH 14,000 Limitorque SHB-00-15 3600 RPH 14,000 Limitorque SHB-00-15 1900 RPH 14,000 Limitorque SHB-00-15 1900 RPH 14,000 Limitorque SHB-00-25 1700 RPH 14,000 I

I

]Aux FM Reg

/Valve:

PPB to/

I SG1 I

I I

I lAux FM Reg

[Valve:

PPB ito SG2 I

I

]Aux.

FM Reg

[Valve:

PPA

)to SG1 I

I

/Aux FM Reg

)Valve:

PPA ito SG2 I

I iAux FM Iso1

]Valve:

PPB ito SG1 I

1, 740/1, 740 1, 740/1, 740 1,810/1,810 1, 810/1, 810 1,740/1,740 4,655/5,540 3,920/3, 140 7,200/8,000 9,093/11,045 9,740/8,652 8,060/6,200 9,520/8,200 11,740/13,000 12,500/12,820 8,820/10,640 See Note 849 See Valve No.

1JAFAHV-0032 See Valve No.

1JAFAHV-0032 See Valve No.

1JAFANV-0032 See Valve No.

1JAFANV-0032 See Valve No.

3JAFBUV-0035 Yes Yes Yes I

I Yes Yes I

I I

I I

I

H

'I

UNIT ¹ 2 PVNGS AUXILIARY FEEDNATER SYSTEH VALVE DATA SUHMARY I

I

)Valve Number(

(Hanufacturer)

Model

/ Type/Size

]Bod Ratin I

I i2JAFBUV-0035'Anch-Dar I5746 I

)Gate/6" I900 lb.

I I

i2JAFCUV-0036'Anch/Dar i5746

]Gate/6" 1900 lb I

I l2JAFAUV 037I

)Anch/Dar i5746 IGate/6" I

1900 lb.

I I

I2JAFAMV-0054I

)Gimpel IGS-N I

)Globe/4>>

I900 lb.

I I

I2JSGAUV-0134I

)Anch/Dar (5746 (Gate/6" 1900 lb Valve Operator:

Hanufacturer Hodel Hotor RPH Ratin s LBS Limitorque SHB-00-25 1700 RPH 14,000 Limitorque SHB-00-25 1900 RPH 14,000 Limitorque SHB-00-25 1900 RPH 14,000 Limitorque SHB-000 1900 RPH 8,000 Limitorque SB-0-40 1900 RPH 24,000 Valve Function I

iAux FM Iso1

) Valve:

PPB ito SG2 I

I

)Aux Fll Isoi

)Valve:

PPA ito SG1 I

I iAux FM Iso1

)Valve:

PPA Ito SG2 I

I iAux Fll

)Turbine Trip iValve I

I

[SG1 Steam ito AF PP

]Turbine I

Haximum Design Differential Pressure (PSID):

0 enin Closin 1, 740/1, 740 1,810/1,810 1,810/1,810 NA/1,355 Note 1

1,355/NA Note 1

As-Found Torque SM. Trip Thurst Equiv't.

Opening/Closing LBS LBS 14,651/12,351 I

11 855/12 '20 I

I I

I I

10 ~ 830/15 038 I

I

=I I

4, 792/6, 518 I

16,553/12,457 I

I I

I As-Left Torque SM. Trip Thrust Equiv't.

Opening/Closing LBS LBS 10,660/10,500 See Note 9 8,360/9,940 See Note 8&9 11,640/15,038 See Note 5

3, 840/3, 130 21,600/15,750 Test Diff. Pres.)

Heasured Thrust Required For Opening/Closing LBS LBS See Valve No.

3JAFBUV-0035 See Valve No.

1 JAFCUV-0036 See Valve No.

1JAFCUV-0036 See Mote 2 See Valve No.

2JSGAUV-0138 Satis-factory Test Results Yes Mo Yes Yes Yes Yes Yes

l

UNIT fI 2 PVNGS AUXILIARY FEEDNATER SYSTEH VALVE DATA SUNHARY I

Valve (Valve Number)

Operator:

(Hanufacturer(

Hanufacturer Hodel

(

Hodel

) Type/Size

(

Hotor RPH (Bod Ratin Ratin s LBS Valve Function I

I Haximum Design Differential Pressure (PSID):

0 enin Closin As-Found Torque SM ~ Trip Thurst Equiv't.

Opening/Closing LBS LBS I

I I

I As-Left

( Test Diff. Pres.(

Satis-

) Torque SM. Trip

) Heasured Thrust

) factory

(

) Thrust Equiv't.

(

Required For

(

Test

( Opening/Closing

( Opening/Closing

) Results

)

LBS LBS LBS LBS Yes No I

I

)2JSGAUV-01381

)Anch/Dar

)5746

)Gate/6" (900 lb.

I I

Limitorque SB-0-40 1900 RPH 24,000 I

)SG2 Steam (To AF PP

)Turbine I

I I

16, 680/18, 220 I

I I

I I

I 1,355/NA 22,060/17,020 Note 1

I I

I I

I I

I I

I 1050 PSID Test Data

( Extrapolated to 1355 PSID I

I 11 086 6 020 I

I Yes I

I I

I

UNIT ¹ 3 PVNGS AUXILIARY FEEDNATER SYSTEH VALVE DATA SUHNARY I

I (Valve Number[

(Manufacturer]

Hodel

/ Type/Size (Bod Ratin I

I

]3JAFBNV-0030]

COCCI I

IEXG9-X3-X6P6I (Globe/4" 1900 lb-I l

(3JAFBNV-0031(

COCCI IEXG9-X3-X6P6I

/ 0 lobe/4" 1900 lb.

I I

I3JAFAMV-0032I COCCI I

iEXG9-X3-X6P6i

/Globe/4" I900 lb.

I I

I3JAFCNV-0033I

/CCI I

iEXG9-X3-X6P6i

/Globe/4" 1900 lb.

I I

13JAFBUV-0034I

)Anch/Dar

!5746 I

[Gate/6" 1900 lb Valve Operator:

Manufacturer Hodel Hotor RPH Ratin s

LBS Limitorque SMB-00-15 3600 RPH 14,000 Limitorque SHB-00-15 3600 RPH 14,000 Limitorque SMB-00-15 1900 RPH 14,000 Limitorque SNB-00-15 1900 RPH 14,000 Limitorque SHB-00-25 1700 RPH 14,000 Valve Function I

I iAux FM Reg

/Valve:

PPB to(

)SG1 I

I I

]Aux FM Reg (Valve:

PPB

)to SG2 I

I

/Aux.

FM Reg

]Valve:

Pl A ito SG1 I

I

]Aux FN Reg

[Valve:

PPA ito SG2 I

I iAux Fll Iso1

[Valve:

PPB ito SG1 I

Haximum Design Differential Pressure (PSID):

0 enin Closin 1,740/1,740 1, 740/1, 740 1,810/1,8'l0 1, 810/1, 810 1, 740/1, 740 I

I I

I I

As-Found Torque Su. Trip Thurst Equiv't ~

Opening/Closing LBS LBS 4, 210/5, 130 5,640/5,480 12,260/10,320 9,340/14,140 9,200/14,140 As-Left Torque Su. Trip Thrust Equiv't.

Opening/Closing LBS LBS 4,732/5,250 5,640/5,780 12,260/10,320 16,720/17,560 See Note 5

12,340/12,000 See Note 9 I

Test Diff. Pres.)

Heasured Thrust Required For Opening/Closing LBS LBS See Valve No.

1JAFAMV-0032 1,800 PSID 4940/5420 See Valve No.

1 JAFANV-0032 See Valve No.

1JAFANV-0032 See Valve No.

3JAFBUV-0035 Satis-factory Test Results Yes No

'Yes Yes Yes Yes Yes

PVNGS AUXILIARY FEEDMATER SYSTEH VALVE DATA SUHHARY UNIT ¹ 3 I

I

)Valve Number)

[Manufacturer(

Hodel

) Type/Size

)Bod Ratin I

I i3JAFBUV-0035'Anch-Dar I5746 I

[Gate/6" i900 lb.

I I

/3JAFCUV-0036/

]Anch/Dar

)5746

]Gate/6" I900 lb.

I I

i3JAFAUV-0037'Anch/Dar I 5746 I

IGate/6" I

1900 lb.

I I

]3JAFANV-0054)

[Gimpei IGS-N I

/ G lobe/4~~

I900 lb.

I I

I3JSGAUV-0134I

/Anch/Dar i5746 (Gate/6" I900 lb.

Valve Operator:

Hanufacturer Model Motor RPH Ratin s LBS Limitorque SKB-00-25 1700 RPH 14,000 Limitorque SMB-00-25 1900 RPH 14,000 Limitorque SMB-00-25 1900 RPH 14,000 Limitorque SHB-000 1900 RPH 8,000 Limitorque SB-0-40 1900 RPH 24,000 I

I I

I Valve Function I

iAux FM Iso1

[Valve:

PPB

]to SG2 I

I iAux FN Iso1

)Valve:

PPA ito SG1 I

I

)Aux Fll Iso1

)Valve:

PPA ito SG2 I

I

)Aux FM

]Turbine Trip

)Valve I

I

[SGI Steam Ito AF PP

[Turbine I

Haximum Design Differential Pressure (PSID):

0 enin Closin 1, 740/1,740 1,810/1,810 1,810/1,810 NA/1,355 Note 1

1,355/NA Note 1

As-Found Torque Su. Trip Thurst Equiv't.

Opening/Closing LBS LBS I

12,320/15,120 I

I I

I 8, 603/10, 157 9,480/8,200 6,560/6,400 I

10,550/13,390 I

I I

I As-Left Torque Su. Trip Thrust Equiv't.

Opening/Closing LBS LBS 10,260/10,540 See Note 9

'11,820/12,520 See Note 9 12, 240/12, 100 See Note 9 4, 100/3, 760 20,685/17,560 Test Diff. Pres.(

Measured Thrust Required For Opening/Closing LBS LBS 1,800 PSID 9,375/13,350 See Valve No.

1JAFCUV-0036 See Valve No.

1JAFCUV-0036 See Note 2 See Valve No.

2JSGAUV-0138 Satis-factory Test Results Yes No Yes Yes Yes Yes Yes

PVNGS AUXILIARY FEEDWATEB SYSTEH VALVE DATA SUHHARY UNIT ff 3 I

I

)Valve Number)

)Hanufacturer)

Model Type/Size

)Bod Ratin Valve Operator:

Hanufacturer Model Motor RPH Ratin s

LBS I

I I

I Valve Function I

I Maximum Design Differential Pressure

<PSID):

0 enin Closin As-Found Torque Su. Trip Thurst Equiv't.

Opening/Closing LBS LBS I

I I

I As-Left

) Test Diff. Pres.]

Satis-

) Torque Su. Trip

) Heasured Thrust

) factory

)

) Thrust Equiv't.

)

Required For

)

Test

) Opening/Closing

) Opening/Closing

) Results

)

LBS LBS LBS LBS Yes No I

I

) 3JSGAUV-0138)

)Anch/Der

)

) 5746

)Gate/6" I

)900 lb.

Limitorque SB-0-40 1900 RPH 24,000 I

)SG2 Steam ITo AF PP

)Turbine I

I 19,150/10,390 I

I I

I I

I I

Ii355/NA I

20,840/18,600 Note 1

I I

I I

I I

)

See Valve No.

I 2JSGAUV-0138 I

I I

I I

I Yes I

I I

I I

(

h l

f

UNIT ¹ 1

PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEM VALVE DATA SUHMARY I

I

)Valve Number)

(Manufacturer[

Hodel

] Type/Size (Bod Ratin Valve Operator:

Hanufacturer Model Hotor RPH Ratin s LBS Valve Function Maximum Design Differential Pressure (PSID):

0 enin Closin As-Found Torque Sw. Trip Thurst Equiv't.

Opening/Closing LBS LBS As-Left Torque Su. Trip Thrust Equiv't.

Opening/Closing LBS LBS Test Diff'res.(

Measured Thrust

[

Required For Opening/Closing LBS LBS Sa't ls factory Test Results Yes No I

I IIJCNBHV-0530 I

]Borg-Ilarner i77890-I

[Gate/20" 1300 lb.

I 11JCHAHV-0531

)Borg-Marner

)77890-1 (Gate/20" 1300 lb.

I I

llJSIAUV-0673

[Pos1-Seal I 14336-3 I

)Butterf ly/244 ]

I150 lb.

I I

I1JSIAUV-0674 I

(Posi-Seal I 14336-4 I

[Butterfly/24")

1150 lb.

I I

l1JSIBUV-0675 I

)Posi-Seal I 14336 I

[Butterfly/24")

I150 lb.

Limitorque SB-1-60 3455 RPH 45,000 Limito'rque SB-1-60 3455 RPH 45,000 Limitorque SHB-00-10 1700 RPH 14,000 Limitorque SHB-00-10 1700 RPM 14,000 Limitorque SMB-00-10 1700 RPM 14,000 I

(RUT Suction

[Isolation I

I RHT Suction Isolation Containment Sump Suction Isolation Containment Sump Suction Isolation Containment Sump Suction Isolation NA/44 See Note 1

HA/44 See Note 1

57/NA See Note 1

100/NA See Note 1

57/NA See Note 1

55,656/49,750 56,300/50,340 I

i1,296 ft-lbs/

1,468 ft-lbs I

I I

[1,196 ft-lbs/

999 ft-lbs I

I I

i1,236 ft-lbs/

1,181 ft-lbs I

I 9,580/10,680 25,574/24,140 See Note ¹6 I

i1,468 ft-lbs/

1,511 ft/lbs See Note 8 I

I i1,463 ft-lbs/

1,451 ft-lbs See Note 8 I

I i1,422 ft-lbs/

1,453 ft-lbs See Note 8 I

See Note 3 Stroke Test Performed See Note 3 Stroke Test Performed See Valve No.

3JSIAUV-0673 See Valve No.

3JSIAUV-0673 I

)

See Valve No.

3 JS IAUV-0673 Yes Yes Yes Yes Yes

UNIT ¹ 1

PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEM VALVE DATA

SUMMARY

Valve Operator:

Manufacturer Model Motor RPH Ratin s

LBS Limitorque SMB-00-10 1700 RPM 14,000 I

I (1JSIAUV-0666 (Borg-Narner (77620-2 I

iT-Globe/2" I

i1500 lb.

Limitorque SMC-04-7.5 1800 RPM See Note 4 I

I (Valve Number)

(Manufacturer(

~odel

( Type/Size (Bod Ratin I

I i1JSIBUV-0676 i

(Posi-Seal i14336-4 (Butterfly/24"i (150 lb.

Valve Function (Containment (Sump (Suction

( Isolation (HPSI Pump (MinifIou (Recirc Line i Isolation Maximum Design Differential Pressure (PSID):

0 enin Closin 100/NA See Note 1

HA/1,966 See Note 1

As-Found Torque Su. Trip Thurst Equiv't.

Opening/Closing LBS LBS I

i1,278 ft-lbs/

1,447 ft-lbs I

I I

9 700/10 260 As-Left Torque Su. Trip Thrust Equiv't.

Opening/Closing LBS LBS I

(1,479 ft-lbs/

1,545 ft-lbs See.Note 8

I 9,700/10,260 I

Test Diff. Pres.)

Measured Thrust Required For Opening/Closing LBS LBS I

(See Valve No.

I 3JSIAUV 0673 I

I See Valve Ho.

3JSIBUV-0616 Satis-factory Test Results Yes No Yes I

I (1JSIBUV-0667 I

(Borg-llarner (77620-2 I

(Y-Globe/2" 11500 lb.

I I

i 1 JS I CHV-0321 (Borg-Marner (79530 (Y-Globe/3" (1500 lb.

I (1JSIDHV-0331 (Borg-Marner 179530 (Y-Globe/3" (1500 lb Limitorque SMC-04-7.5 1800 RPM See Note 4 Limitorque SMB-0-25 1900 RPM 24,000 Limitorque SMB-0-25 1900 RPM 24,000 I

iHPSI Pump (Miniflou (Recirc Line (Isolation I

(Hot Leg (Injection (Floe Contro1 I

I (Hot Leg (Injection (Floe Contro1 I

NA/1,966 See Note 1

1, 924/1,924 1,925/1,924 14,860/13,420 42,232/19,580 30,060/44,826 11,380/11,860 22, 580/18, 400 9,000/13,960 See Valve No.

3 JSI BUY-06'I6 I

( See Valve Ho.

I 3JSIDHV-0331 I

I See Valve No.

3JSIDHV-0331 Yes Yes Yes

UHIT ¹ 1

PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEH VALVE DATA SUHMARY I

I iValve Number) iHanufactureri Model

) Type/Size iBod Ratin I

I IIJSIAHV-0604I igorg-llarner i77910 iGate/3<<

I1500 lb-I I

I IJS I8HV-0609 I igorg-Marner i

I77910 I

IGate/3<<

I 11500 lb.

Valve Operator:

Manufacturer Hodel Hotor RPM Ratin s LBS Limitorque SNB-00-10 1800 RPN 14,000 Limitorque SMB-00-10 1800 RPN 14,000 Valve Function I

lHot Leg

) Injection

)Flow Control I

I iHot Leg iinjection iFlou Control I

Maximum Design Differential Pressure (PSID):

0 enin Closin 1,945/1,400 1,945/1,400 As-Found Torque Sw. Trip Thurst Equiv't.

Opening/Closing LBS LBS 5,880/6,400 5,640/5,700 As-Left Torque SM. Trip Thrust Equiv't.

Opening/Closing LBS LBS I

I 9e000/13e960 I

I I

12,660/13,900 I

Test Diff. Pres.i Measured Thrust Required For Opening/Closing LBS LBS See Valve No.

3JSIAHV-0604 See Valve No.

3JSIAHV-0604 Satis-factory Test Results Yes No Yes Yes I

I i 1 J S I AH V-0698 )

)Borg-Marner

)77740 iGate/4<<

I1500 lb.

I I

I 1 JSI BHV-0699 I igorg-Narner i

i77740

/Gate/4<<

I1500 lb.

I I

I 1 JS IBUY-0616 I

)Borg-Marner i

i77620-2 IY-Globe/2<<

I I1500 lb.

Limitorque SHB-0-10 1700 RPH 24,000 Limitorque SNB-0-10 1700 RPH 24,000 Limitorque SNC-04-7.5 1800 RPH See Note 4 I

iHPSI Train i Isolation I

I I

(HPSI Train i I so let ion I

I I

I iHPSI Header I Isolation andI iThrottling I

I 1, 100/1, 100 1, 100/1, 100 1,924/1,924 15,940/16,380 17, 900/18, 020 11,280/10,320 I

I I

I'I 14,360/13,080 18,520/17,720 11,280/10,320 See Valve No:

3JSIAHV-0698 I

i See Valve No.

I 3JSIAHV-0698 I

I I.

See Valve No.

I 3JSIBUV-0616 I

I Yes I

Yes Yes I

I I

I I

I I

I I

I I

UNIT ¹ 1

PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEM VALVE DATA SUHMARY I

I (Valve Number)

IHanufacturer(

Hodel

( Type/Size (Bod Ratin I

I 11 JS IAUV-06171 (Borg-llarner

(

177620-2 I

( Y-G lobe/2" 11500 lb I

I 11 JS IBUV-06261 (Borg-'Marner 177620-2 I

(Y-Globe/2" 11500 lb.

I I

11JSIAUV-06271 (Borg-llarner (77620-2 IY-Globe/2" 11500 lb-I I

(1JSIBUV-0636(

(Borg-Marner 177620-2 I

IY-Globe/2" 11500 lb.

I I

11 JS IAUV-06371 (Borg-Narner (77620 2

IY-Globe/2" 11500 lb.

Valve Operator:

Manufacturer Hodel Hotor RPM Ratin s

LBS Limitorque SHC-04-7.5 1800 RPM See Note 4 Limitorque SHC-04-7.5 1800 RPM See Note 4 Limitorque SHC-04-7.5 1800 RPH See Note 4 Limitorque SHC-04-7.5 1800 RPH See Note 4 Limitorque SMC-04-7.5 1800 RPH See Note 4 I

I I

Valve Function I

I IHPSI Header (Isolation and(

(Throttling I

I I

I IHPSI Header (Isolation and(

(Throttling I

I I

I IHPSI Header (Isolation and(

(Throttling I

I I

I (NPSI Header (Isolation and(

(Throttling I

I I

I (NPSI Header

( Isolation and(

(Throttling

(

I I

Maximum Design Differential Pressure (PSID):

0 enin Closin 1,924/1,924 1,924/1,924 1,924/1,924 1, 924/1, 924 1,924/1,924 As-Found Torque SM ~ Trip Thurst Equiv't.

I"Opening/Closing LBS LBS 8,815/8,4'l6 8,420/7,340 9,740/7,340 10,980/10, 200 9,700/10,860 As-Left Torque Su. Trip Thrust Equiv't.

Opening/Closing LBS LBS 8,815/8,416 8,815/8,620 9,740/8,620 10,980/10,200 9,700/10,860 Test Diff. Pres.i Heasured Thrust Required For Opening/Closing LBS LBS See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 Satis-factory

(

Test Results

(

Yes No I

I Yes I

I I

I I

Yes I

I I

I I

Yes I

I I

I I

Yes I

I I

I I

YES I

I I

I

UNIT ¹ 1

PVHGS HIGH PRESSURE SAFETY INJECTION SYSTEH VALVE DATA SUMNARY I

I (Valve Number(

(Hanufacturer(

I Nodal I

( Type/Size (Bod Ratin Valve Operator:

Nanufacturer Nodal Notor RPN Ratin s LBS Valve Function Naximum

(

Design Differential Pressure (PSID):

0 enin Closin As-Found Torque SM. Trip Thurst Equiv't.

Opening/Closing LBS LBS I

I I

I As-Left

( Test Diff. Pres.[

Satis-( Torque SM. Trip

( Neasured Thrust

( factory

(

( Thrust Equiv't.

(

Required For

(

Test

( Opening/Closing

( Opening/Closing

( Results

(

LBS LBS LBS LBS Yes No I

I (1 JS IBUV-0646 (

mimi torque (Borg-llarner

(

SNC-04-7.5 (77620 2 I

1800 RPN (Y-Globe/2>>

(

See Note 4 (1500 lb.

I I

(HPSI Header (Isolation and(

(Throttling I

I 1,924/1,924 I

I 11,900/12,329

(

11,900/12,329 I

I I

I I

I I

(

See Valve No.

3JSIBUV-0616 I

I I

I I

I I

YES I

I I

I I

I I

I (1JSIAUV-0647(

(Borg.uarner

(

177620-2 I

(Y-Globe/2>>

(1500 lb.

Limitorque SMC-04-7.5 1800 RPH See Note 4 I

I (HPSI Header

(

(Isolation and(

(Throttling I

I I

1,924/1,924 I

I I

I 9 120/11 320 I

9 120/11 320 I

I I

I

( See Valve No.

I 3JSIBUV-0616 I

I I

I I

I YES I

I I

I I

I

UNIT ¹ 2 PVHGS HIGH PRESSURE SAFETY INJECTION S'STEM VALVE DATA

SUMMARY

I I

IValve'umberI IManufacturerI Model Type/Size IBod Ratin Valve Operator:

Manufacturer Model Motor RPM Ratin s LBS I

I I

Valve Function Maximum Design Differential Pressure (PSID):

0 enin Closin As-Found I Torque SM ~ Trip I Thurst Equiv't.

Opening/Closing LBS LBS As-Left Torque SM ~ Trip Thrust Equiv't.

Opening/Closing LBS LBS I

Test Diff. Pres.(

Measured Thrust Required For Opening/Closing LBS LBS Satis-factory Test Results Yes No I

I 12JCHBHV-0530I Igor g-Marner I

I77890-1 I

IGate/20>>

I300 lb.

I I

12JCHAHV 0531I IBorg-llarner I

I77890-1 I

IGate/20>>

I I300 lb.

I I

l2JSIAUV-0673I IPosi-Seal I14336-3 Igutterfly/24I I150 lb.

I I

I2JSIAUV-0674I IPosi-Seal I14336-4 Igutterfly/24I I150 lb.

I I

I2JSIBUV-0675I IPosi-Seal I14336 IButterfly/24I I150 lb.

Limitorque SB-1-60 3455 RPM 45,000 Limitorque SB-1-60 3455 RPM 45,000 Limitorque SMB-00-10 1700 RPM 14,000 Limitorque SMB-00-10 1700 RPM 14,000

'Limitorque SMB-00-'10 1700 RPM I

IRllT Suction Ilsolation I

I I

IR'llT Suction I Isolation I

I IContainment Isump ISuction I Isolation IContainment Isump Isuction I Isolat Ion IContainment ISump ISuction I isolation HA/44 See Note 1

NA/44 See Note 1

57/NA See Note 1

100/NA See Note 1

57/NA See Note 1

50,000/50,000 20,492/28,685 I

I1,185 ft-lbs/

1,214 ft-lbs I

I I

I964 ft-lbs/

877 ft-lbs I

I I

I1,410 ft-lbs/

1,245 ft-lbs I

I 10,620/8,200 10, 140/7,380 I

I1,532 ft-lbs/

1,587 ft-lbs I See Note 8 I

I I1,500 ft-lbs/

1,569 ft-lbs I See Note 8 I

I I1,418 ft-lbs/

'1,557 ft-lbs See Note 8 I

See Note 3 Stroke Test Performed See Note 3 Stroke Test Performed See Valve No.

3JSIAUV-0673 See Valve Ho.

3JSIAUV-0673 See Valve No.

3JSIAUV-0673 I

I I'I I

II.

I I

I Yes Yes Yes Yes Yes

  • I I

I I

I I

I i

1

UNIT ¹ 2 PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEM VALVE DATA

SUMMARY

I I

[Valve Number(

)Manufacturer]

Model

) Type/Size

)Bod Ratin Valve Operator:

Manufacturer Model Motor RPK Ratin s LBS Valve Function Maximum Design Differential Pressure (PSID):

0 enin Closin As-Found Torque Su. Trip Thurst Equiv't ~

Opening/Closing LBS LBS As-Left Torque SM. Trip Thrust Equiv't.

Opening/Closing LBS LBS I

Test Diff. Pres.)

Measured Thrust Required For Opening/Closing LBS LBS Satis-factory Test Results Yes No I

I I2JSIBUV-0676I

)Posi-Seal 114336-4 I

)Butterfly/24)

I I50 lb I

I 12JSIAUV-0666I

[Borg-llarner I77620-2 I

]Y-Globe/2" i1500 lb.

I I

12JSIBUV-06671 (Borg-Marner

]

[77620-2 IY Globe/2" I

I1500 lb.

I I

12JSI CHV-0321 I

/Borg-llarner 179530 I

/Y-Globe/3" I1500 lb.

I I

/2JSIDMV-0331)

]Borg-Marner

/79530 JY-Globe/3" I1500 lb.

Limitorque SHB-00-10 1700 RPK 14,000 Limitorque SHC-04-7.5 1800 RPK See Hote 4 Limitorque SMC-04-7.5 1800 RPK See Note 4 Limitorque SMB-0-25 1900 RPK 24,000 Limitorque SMB-0-25 1900 RPK 24,000

[Containment (Sump

]Suction

)Isolation iHPSI Pump

[MinifIou

)Recirc Line

]Isolation I

[HPSI Pump

)Miniflou (Recirc Line

[Isolation l

(Hot Leg

)Injection (Flow Contro1 I

I

/Mot Leg

/Injection

)Floe Contro1 I

100/NA See Note 1

NA/1,966 See Hote 1

HA/1,966 See Note 1

1,924/1,924 1,924/1,924 769 ft-lbs/

1,296 ft-lbs 8,540/8,973 8,447/8,660 19,200/19,300 29,930/24,293 I

I1,870 ft-lbs/

I 1 ~ 708 ft-lbs

[ See Note 8 I

8,540/8,973 8,447/8,660 16,460/15,020 25,080/25,940 See Note 5

See Valve No.

3JSIAUV-0673 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve Ho.

3JSIDHV-0331 See Valve Ho.

3JSIDHV-0331 I

I I

I I

Yes Yes Yes Yes Yes I

I I

I I

~

I

UNIT ¹ 2 PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEH VALVE DATA SUHHARY I

I

)Valve Number)

)Hanufacturer)

Hodel

(

) Type/Size

)Bod Ratin I

I

)2JSIAHV-0604)

(Borg-llarner

) 77910

)Gate/3"

)1500 lb.

I I

)2JSIBHV-0609)

)Borg-garner

)

177910 I

)Gate/3"

) 1500 lb.

I I

)2JSIAHV 0698(

)Borg-Harner

(

)77740

)Gate/4" 11500 lb.

I I

)2JSIBHV-0699)

)Borg-Narner (77740 I

)Gate/4" I

(1500 lb.

I I

) 2JSI BUY-0616)

(Borg-Marner

)

)77620-2

)Y-Globe/2"

)1500 lb.

Valve Operator:

Hanufacturer Model Motor RPH Ratin s LBS Limitorque SHB-00-10 1800 RPM 14,000 Limitorque SHB-00-10 1800 RPH 14,000 Limitorque SHB-0-10 1700 RPH 24,000 Limitorque SHB-0-10 1700 RPH 24,000 Limitorque SHC-04-7.5 1800 RPH See Note 4 Valve Function I

)Hot Leg

( Injection

)Flow Control I

I

)Hot Leg (Injection

)Floe Contro1 I

I (HPSI Train

) Isolation I

I I

)HPSI Train

( Isolation I

I I

I

)HPSI Header (Isolation and(

(Throttling I

I Haximum Design Differential Pressure (PSID):

0 enin Closin 1,945/1,400 1,945/1,400 1,100/1,100 1,100/1,100 1,924/1,924 As-Found Torque Su. Trip Thurst Equiv't.

Opening/Closing LBS LBS 1,685/1,665 6,640/9,002 27,500/27,500 34,000/18,809 9,140/8,980 As-Left Torque Su. Trip Thrust Equiv't.

Opening/Clos>ng LBS LBS 9,460/14, 120 See Note 5

12,760/14,320 See Note 5

12,920/13,200 11,380/10,980 9,140/8,980 Test Diff. Pres.[

Measured Thrust Required For Opening/Closing LBS LBS See Valve No.

3JSIAHV-0604 See Valve No.

3JSIAHV-0604 See Valve Xo.

3JSIAHV-0698 See Valve No.

3JSIAHV-0698 See Valve No.

3JSIBUV-0616 Satis-factory Test Results Yes No Yes Yes Yes Yes Yes

0

UNIT ¹ 2 PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEM VALVE DATA SUHMARY I

I

)Valve Number)

]Manufacturer[

Model

) Type/Size

[Bod Ratin I

I I2JSIAUV-0617I (Borg-Marner i77620-2 I

IT Globe/2" I

I1500 lb.

I I

I2JSIBUV-0626I

/Borg-llarner I77620-2 I

/Y-Globe/2" I1500 lb.

I l

)2JSIAUV-0627)

[Borg-Marner

]

I77620 2

I

]Y-Globe/2" i1500 lb.

I I

I2JSI BUY-06361

/Borg-uarner,/

/77620-2

]Y-Globe/2" I1500 lb.

I I

I2JSIAUV-0637I (Borg-Narner

[

I77620-2 I

] Y-G Iobe/2" 11500 lb.

Valve Operator:

Manufacturer Hodel Motor RPH Ratin s

LBS Limitorque SMC-04-7.5 1800 RPH See Note 4

Limitorque SHC-04-7.5 1800 RPM See Note 4 Limitorque SHC-04-7.5 1800 RPM See Note 4 Limitorque SMC-04-7.5 1800 RPH See Note 4'imitorque SMC-04-7.5 1800 RPH See Note 4 I

I I

I Valve Function I

I

[HPSI Header

[isolation and(

]Throttling I

I I

I

)HPSI Header

[Isolation and)

]Throttling I

I I

I

/HPSI Header

)Isolation and]

(Throttling I

I I

I

/HPSI Header

/Isolation and/

/ Thrott I ing I

I I

I

)NPSI Header

)Isolation and)

(Throttling I

I Haximum Design Differential Pressure (PSID):

0 enin Closin 1,924/1,924 1, 924/1,924 1,924/1,924 1,924/1,924 1,924/1,924 As-Found Torque Sw. Trip Thurst Equiv't.

Opening/Closing LBS LBS 9,900/9,743 10,934/10,589 11,460/10,740 8,560/8,740 10, 143/9820 As-Left Torque Su. Trip Thrust Equiv't.

Opening/Closing LBS LBS 9,900/9,743 10,934/'10,589 11,460/10,740 8,560/8,740 10,013/9,805 Test Diff. Pres.)

Measured Thrust Required For Opening/Closing LBS LBS See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 I

( See Valve No.

I 3JSIBUV-0616 I

I See Valve No.

3JSIBUV-0616 Satis-factory Test Results Tes No Yes Yes Yes Yes Yes

UNIT S 2

PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEH VALVE DATA SUHMARY I

I IValve Number)

INanufacturerI Hodei I Type/Size IBod Ratin Va lve Operator:

Manufacturer Hodel Hotor RPH Ratin s LBS Valve Function I

I Haximum Design Differential Pressure (PSID):

0 enin Closin As-Found Torque SM. Trip Thurst Equiv't.

Opening/CLosing LBS LBS I

I I

I As-Left I Test Diff. Pres.]

Satis-I I Torque Su. Trip I Heasured Thrust I factory I

I Thrust Equiv't.

I Required For I

Test I Opening/Closing I Opening/Closing I Results I

LBS LBS LBS LBS Yes No I

I 12JSIBUV-06461 IBorg-llarner Irr620-2 IY-Globe/2>>

11500 lb-I I

12JSIAUV-06471 IBorg-Marner I

Irr620-2 IY-Globe/2>>

11500 lb.

Limitorque SHC-04-7.5 1800 RPH See Note 4 Limitorque sHG-04-7.5 1800 RPH See Note 4 I

I IHPSI Header Iisolation andI IThrottling I

I I

I IHPSI Header IIsolation andI IThrottling I

I 1,924/1, 924 1,924/1,924 I

I re 821/rt 163 I

I I

I I

9i765/9r 009 I

I I

I I

8,443/9,030 I

I I

I 9, 100/10, 120 I

I I

I I

See Valve Ho.

3 J S IBUV-0616 I

I I

I I

I Yes I

I I

I I

I I

Yes I

I I

I I

I See Valve No.

I 3JSIBUV-0616 I

I I

I I

f

UNIT ¹ 3 PVHGS HIGH PRESSURE SAFETY INJECTIOH SYSTEH VALVE DATA SUNNARY I

I

)Valve Number]

)Nanufacturer)

Nodel

) Type/Size

)Bod Ratin I

I 13JCHBNV-0530I

)Borg-Marner

[

I77890-1 I

)Gate/20"

)300 lb.

I I

(3JCHAHV-0531)

[Borg-Marner J

i77890-1

)Gate/20" 1300 lb I

I

)3JSIAUV-0673'Posi-Seal II4336 3 I

]Butterfly/24]

I150 lb.

I I

I3JSIAUV-0674I

)Posi-Seal i14336-4 (Butterfly/24)

I150 lb.

I I

I3JSIBUV-0675I

)Posi-Seal

)14336 (Butterfly/24]

1150 lb.

Valve Operator:

Nanufacturer Nodel Hotor RPN Ratin s LBS Limitorque SB-1-60 3455 RPN 45,000 Limitorque SB-1-60 3455 RPH 45,000 Limitorque SNB-00-10 1700 RPH 14,000 Limitorque SHB-00-10 1700 RPN 14,000 Limitorque SHB-00-10 1700 RPH 14,000 Valve Function

)RMT Suction

[ Isolation I

/RMT Suction

)Isolation I

I

]Containment iSump

)Suction

[ Isolation

[Containment

)Sump

)Suction

) Isolation

)Containment iSump

[Suction

[Isolation Naximum Design Differential Pressure (PSID):

0 enin Closin NA/44 See Note 1

HA/44 See Note 1

57/HA See Note 1

100/HA See Note 1

57/NA See Note 1

As-Found Torque Sw. Trip Thurst Equiv't.

Opening/Closing LBS LBS 70,400/77,450 41,450/35,350 I

i1,319 ft-lbs/

1,208 ft-lbs I

I I

i504 ft-lbs/

672 ft-lbs I

I I

i1,256 ft-lbs/

'l,013 ft-lbs I

I As-Left Torque Sw. Trip Thrust Equiv't.

Opening/Closing LBS LBS 8,958/9,720 10, 784/10, 784 I

i1,820 ft-lbs/

1,803 ft-lbs See Note 8 I

I i1,688 ft-lbs/

1,616 ft-lbs See Note 8 I

i1,688 ft-lbs/

1,567 ft-lbs See Note 8 I

Test Diff. Pres.]

Neasured Thrust

)

Required For Opening/Closing LBS LBS See Note 3 Stroke Test Performed See Note 3 Stroke Test Performed 95 PSID 2,016 ft-lbs/

333 ft-lbs See Valve Ho.

3JSIAUV-0673 See Valve Ho.

3JSIAUV-0673 Satis-factory Test Results Yes Ho Yes Yes Yes Yes Yes

UNIT A' PVNGS NIGH PRESSURE SAFETY INJECTION SYSTEH VALVE DATA SUHHARY I

I

)Valve Number(

[Manufacturer)

Hodel

) Type/Size

)

[Bod Ratin I

I

)3JSIBUV-0676'Posi-Seal i14336-4

[Butterfly/24)

I150 lb.

I I

I3JSIAUV-06661

/Borg-Marner

)77620-2

)Y-Globe/2" I1500 lb.

I I

I3JSIBUV-0667I

[Borg-warner f

I77620-2 I

]Y-Globe/2"

)

I1500 lb.

I I

I3JSICHV-0321I

[Borg-Warner f

/79530

[Y-Globe/3" I1500 lb.

I I

]3JSIDHV-0331 (

[Borg-warner J

I79530 I

) Y-Globe/3" i1500 lb.

Valve Operator:

Hanufacturer Model Hotor RPH Ratin s LBS Limitorque SHB-00-10 1700 RPM 14,000 Limitorque SHC-04-7.5 1800 RPH See Note 4 Limitorque SHC-04-7.5 1800 RPH See Note 4 Limitorque SHB-0-25 1900 RPH 24,000 Limitorque SHB-0-25 1900 RPH 24,000 Valve Function

)Containment igump

[Suction

[ Isolation

[NPSI Pump (Miniflow JRecirc Line

] Iso iat ion (NPSI Pump (Miniflow

]Recirc Line

[Isolation I

)Hot Leg

[Injection

]Flow Contro1 I

I

/Not Leg

)Injection

[Flow Contro1 I

Maximum Design Differential Pressure (PSID):

0 enin Closin 100/NA See Note 1

NA/1,966 See Note 1

NA/1,966 See Note 1

1,924/1,924 1,924/1,924 As-Found Torque Sw. Trip Thurst Equiv't.

Opening/Closing LBS LBS I

i1,056 ft-lbs/

1,233 ft-lbs I

I 8,440/7,040 6,050/5,680 25, 175/20,860 18,991/38,305 As-Left Torque Sw. Trip Thrust Equiv't.

Opening/Closing LBS LBS I

i1,515 ft-lbs/

)

1,466 ft-lbs See Note 8 I

8,960/8,780 6, 476/7, 164 20,860/7580 17,220/4,900 I

Test Diff. Pres.)

Heasured Thrust Required For Opening/Closing LBS I.BS See Valve No.

3JSIAUV-0673 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIDNV-0331 1,920 PSID 10,320/2,500 Satis-factory Test Results Yes No Yes Yes Yes Yes Yes

rf II Jl

UNIT ¹ 3 PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEH VALVE DATA SUMHARY I

I (Valve Number(

IHanufacturer(

Hodel I Type/Size (Bod Ratin I

I I3JSIAHV-0604I (Borg-Marner I

I77910 I

(Gate/3" I1500 Lb.

I I

I I

I I

I3JSIBHV-06091 (Borg-Marner I

(77910 IGate/3" I

(1500 lb.

I I

!3JSIAHV-0698I (Borg-Marner

(

(77740 (Gate/4" I1500 Lb.

I I

(3JSIBHV-0699(

(Borg-Marner (77740 (Gate/4"

(

I1500 Lb.

I I

I3JSI BUY.0616I (Borg-Marner I77620-2 I

(Y-Globe/2" I1500 lb.

I I

Valve Operator:

Hanufacturer Hodel Hotor RPH Ratin s LBS Limitorque SHB-00-10 1800 RPH 14,000 Limitorque SHB-00-10

'1800 RPH 14,000 Limitorque SHB-0-10 1700 RPH 24,000 Limitorque SMB-0-10 1700 RPH 24,000 I.imitorque SHC-04-7.5 1800 RPH See Note 4 Valve Function I

(Not Leg (Injection (FloM Control I

I I

I (Hot Leg (Injection (Floe contro1 I

I (NPSI Train

( Isolation I

I I

(HPSI Train

( Isolation I

I I

I (NPSI Header (Isolation and(

(Throttling I

I I

I Haximum Design Differential Pressure (PSID):

0 enin Closin 1,945/1,400 1,945/1,400 1, 100/1, 100 1, 100/1, 100 1,924/1,924 As-Found Torque SM. Trip Thurst Equiv't.

Opening/Closing LBS LBS 9, 150/10,345 9,345/11,465 23,320/18,880 26,991/19,478 8,300/7,240 As-Left Torque SM. Trip Thrust Equiv't.

Opening/Closing LBS LBS 8,000/13,780 9,980/13,980 13, 410/10, 701 12,220/11,800 8,520/8,760 Test Diff. Pres.i Heasured Thrust Required For Opening/Closing LBS LBS 1,920 PSID Open 1,745 PSID Closed Test Data Extrapolated to 1,945 PSID Opens 7 800 12 580 See Valve No.

3JSIAHV-0604 1,500 PSID 3,620/8,240 See Valve No.

3JSIANV-0698 1835 PSID Test Data Extrapolated to 1,924 PSID 905 6 450 Satis-factory Test Results Yes No Yes Yes Yes Yes Yes I-I I

I I

I I

UNIT ¹ 3 PVNGS HIGH PRESSURE SAFETY INJECTION SYSTEH VALVE DATA

SUMMARY

I I

(Valve Number(

(Manufacturer(

Hodel

( Type/Size (Bod Ratin I

I 13JSIAUV 06171 (Borg-Warner (77620-2 (Y-Globe/2<<

(1500 lb.

I I

13JSIBUV-06261 (Borg-Warner I

177620-2 I

(Y-Globe/2<<

(

11500 lb.

I I

(3JSIAUV-06271 (Borg-Warner I

177620-2 I

IY-Globe/2<<

(1500 lb.

I I

(3 JS IBUV-0636(

(Borg-Warner 177620-2 I

(Y-Globe/2<<

11500 lb I

I (3JSIAUV-0637(

(Borg-Warner I

177620-2 I

IY-Globe/2<<

(1500 lb.

Valve Operator:

Manufacturer Model Motor RPM Ratin s LBS Limitorque SMC-04-7.5 1800 RPM See Note 4 Limitorque SHC-04-7.5 1800 RPM See Hote 4 Limitorque SMC-04-7.5 1800 RPM See Note 4 Limitorque SMC-04-7.5 1800 RPM See Note 4 Limitorque SHC-04-7.5 1800 RPM See Note 4 Valve Function I

I IHPSI Header

( Isolation and(

(Throttling I

I I

I (HPSI Header (Isolation and(

(Throttling I

I I

I IHPSI Header (Isolation and(

(Throttling I

I I

I IHPSI Header (Isolation and(

(Throttling I

I I

I IHPSI Header (isolation and(

(Throttling I

I Maximum Design Differential Pressure (PSID):

0 enin Closin 1,924/1,924 1,924/1,924 1,924/1,924 1,924/1,924 1,924/1,924 As-Found Torque SM. Trip Thurst Equiv't.

Opening/Closing LBS LBS 11,720/11,220 8,692/7,922 10,660/11,580 7,940/8,730 7,220/7,740 As-Left Torque SM. Trip Thrust Equiv't.

Opening/Closing LBS LBS 9,240/9,180 8,961/8,942 10,660/11,580 6,800/9,830 9,080/8,920 Test Diff. Pres.)

Measured Thrust Required For Opening/Closing LBS LBS See Valve Ho.

3 JSI BUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 See Valve No.

3JSIBUV-0616 Satis-factory Test Results Yes No Yes Yes Yes Yes Yes

I 1

UNIT ¹ 3 PVHGS HIGH PRESSURE SAFETY INJECTION SYSTEM VALVE DATA

SUMMARY

I I

/Valve Number)

(Manufacturer)

Model

] Type/Size

[Bod Ratin Valve Operator:

Manufacturer Model Motor RPM Ratin s LBS Valve Function I

I Maximum Design Differential Pressure (PSID):

0 enin Closin As-Found Torque Sw. Trip Thurst Equiv't ~

Opening/Closing LBS LBS I

I I

I As-Left

/ Test Diff~ Pres./

Satis-f Torque Su. Trip

) Measured Thrust f factory

)

J Thrust Equiv't.

/

Required For

/

Test

/ Opening/Closing f Opening/Closing

( Results f

LBS LBS LBS LBS Yes No I

I I3JSIBUV-0646I

/Borg-llarner

)

I77620-2 I

)Y-Globe/2" I1500 lb.

Limitorque SMC-04-7.5 1800 RPM See Note 4 I

I JHPSI Header

)Isolation and[

)Throttling I

I 1,924/1,924 I

I 8,500/10,780 I

I I

I I

9,040/8,640 I

I I

I

] See Valve No.

I 3JSIBUV-0616 I

I I

I I

I Yes I

I I

I I

I I

I3JSIAUV-0647I

]Borg-Warner I77620-2 I

I Y Globe/2" I

I1500 lb.

Limitorque SMC-04-7.5 1800 RPM See Note 4 I

I

/HPSI Header

) Isolation and)

/Throttling I

I 1,924/1,924 I

I 9,800/9,200 I

I I

I 8,560/8,560 I

I I

I I

/

See Value Ho.

I 3JSIBUV-0616 I

I I

I I

I I

Yes I

I I

T tl

ATTACHMENT C

SUMMARY

TABLE OF ABNORMALITIES Deficiency Bypass Switch Improperly Set Incorrect Thrust Unbalanced Torque Switch Valve Backseated High Motor Current Torque Switch Abnormalities Excessive Grease in Spring Pack Loose Stem Nut Lock Nut Number of Occurrences 19 23 28 Spring Pack Abnormalities Limit Switch Abnormalities 14 NOTE:

The data above is based on 99 MOVs in the 3

PVNGS Units.

ATTACHMENT D PVNGS IEB 85-03 VALVE GROUPS Bor -Warner Globe Bor -Warner Gate 2 II SIBUV-616*

SIBUV-617 SIBUV-626 SIAUV-627 SIBUV-636 SIAUV-637 SIBUV-646 SIAUV-647 SIAUV-666 SIBUV-667 3 II SICHV-32 1 SIDHV-331*

3 II SIAHV-604*

SIBHV-609 4 II SIABV-698*

SIBHV-699 20 CHBHV-530 CHAHV-531 See Note 3

On Attach-ment B

ANCH-DAR 6"

GIMPEL 4 II CCI 4 lt POSI-SEAL Butterfl 24" AFAUV-034 AFBUV-035*

AFCUV-036*

AFAUV-037 SGAUV-134 SGAUV-138*

AFAHV-054 See Note 2 on Attachment B

AFBHV-030 AFBHV-031*

AFAHV-032*

AFCHV-033 SIAUV-673*

SIAUV-674 SIBUV-675 SIBUV-676

  • Each tag number indicated has been differential pressure tested.

-D2-

'