1985 Docket Nos.:

50-529 and 50-530 Mr. E.

E.

Van Brunt Executive Vice President Arizona Nuclear Power Project Post Office Box 52034 Phoenix, Arizona 85072-2034 DISTRIBUTION:

NRC PDR NSIC MLey JPartlow (ACRS (16)

EJordan

,Docke-t Fi.l.e~

Local PDR LB83 Reading JLee OELD, Attorney BGrimes

Dear Mr. Van Brunt:

SUBJECT:

LARGE BREAK LOCA EVALUATION MODEL -

PALO VERDE UNITS 2 AND 3 This letter is to confirm our telephone conversation on August 7, 1985 concern-ing a non-conservatism in the Combustion Engineering (CE) large break LOCA evaluation model and the action required to resolve the matter prior to issuance of a license for Palo Verde Units 2 and 3.

Because of the non-conservatism identified in the previously approved CE ECCS evaluation

model, as discussed in your letters of July 12 and 19, 1985, you state that the peak clad temperature for Palo Verde would exceed 2200'F by a small amount if the large break LOCA analysis is corrected for the non-conservatism.

In order to satisfy the requirements of 10 CFR 50.46, a new

analysis, performed with an acceptable ECCS model which demonstrates that limits will not be exceeded, is required.

Compliance with Commission regulations, including 10 CFR 50.46, is required prior to licensing of Palo Verde Units 2 and 3. If such compliance cannot be demonstrated before your projected fuel load dates, the necessary findings for licensing cannot be made and a license cannot be issued unless a schedular exemption is requested and granted.

Such a request would require a

justification for interim operation which included the actions to be taken for providing an adequate level of safety until compliance is demonstrated, and a

timely schedule for submitting the reanalysis described above.

The information needed to resolve this issue, i.e., the reanalysis or a request for a schedular exemption, should be submitted at least 45 days prior to your projected fuel load date.

Should you require further discussion concerning this matter, please contact Marilyn Ley, Licensing Project Manager, on (301) 492-7792.

Sincerely, e)g.try) l pg ~g~S >1p 8509090203 850830 PDR

. ADOCK,05000529 A

PDR' gB 8/ZV/8 DL:LBg3*

EALicitra 8/09/85 cc:

See next page

  • Previous concurred on by:

DL:LBj/3*

DSI:RSB*

GWKnighton BSheron 8/09/85 8/12/85 ELD J

o 8/

/85 George W. Knighton, Chief'icensing Branch No.

3 Division of Licensing

I F4 IH)

II H

~ I

Hr.

E.

E.

Van Brunt, Jr.

Arizona Nuclear Power Project

~I Palo Verde CC:

Arthur C. Gehr, Esq.

Snell

& Wilmer 3100 Valley Center Phoenix, Arizona 85073 Mr. James M. Flenner, Chief Counsel Arizona Corporation Comnission 1200 West Washington Phoenix, Arizona 85007 Charles R. Kocher, Esq. Assistant Council James A. Boeletto, Esq.

Southern California Edison Company P. 0.

Box 800

Rosemead, California 91770 Kenneth Berlin, Esq.

Winston

& Strawn Suite 500 2550 M Street, NW Washington, DC 20037 Hs.

Lynne Bernabei Government Accountability Project of the Institute for Policy Studies 1901 gue Street, NW Washington, DC 20009 Ms. Jill Morrison 522 E. Colgate Tempi, Arizona 85238 Mr. Charles B. Brinkman, Manager

. Washington Nuclear Operations Combustion Engineering, Inc.

7910 Woodmont Avenue Suite 1310

Bethesda, Maryland 20814 Hr. Hark Ginsberg Energy Director Office of Economic Planning and Development 1700 West Washington - 5th Floor Phoenix, Arizona 85007 Mr. Wayne Shirley Mr. Ron Rayner Assistant Attorney General P. 0.

Box 1509 Bataan Memorial Building

Goodyear, AZ 85338 Santa Fe, New Mexico 87503 Hr. Roy Zimmerman U.S. Nuclear Regulatory Commission P. 0.

Box 239

'Arlington, Arizona 85322 Ms. Patricia Lee Hourihan 6413 S. 26th Street

.; Phoenix, Arizona "85040

',,=

Regional Administrator, Region V

U. S. Nuclear Regulatory Commission 1450 Maria Lane Suite 210 Walnut Creek, California 94596,'