ML17263A399
| ML17263A399 | |
| Person / Time | |
|---|---|
| Site: | Ginna |
| Issue date: | 09/08/1993 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML17263A398 | List: |
| References | |
| NUDOCS 9309150267 | |
| Download: ML17263A399 (6) | |
Text
gP,R RE00 c<
~o
+>>*<<~
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Enclosure SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION OF THE THIRD 10-YEAR INTERVAL INSERVICE INSPECTION PROGRAH RE UES S
FOR RELIEF ROCHESTER GAS AND ELECTRIC CORPORATION R.
E.
GINNA NUCLEAR POWER PLANT DOCKET NUMBER 50-244
1.0 INTRODUCTION
Technical Specification 4.2. 1.5 for the R.
E. Ginna Nuclear Power Plant states that the inservice inspection and testing of the American Society of Hechanical Engineers (ASHE) Code Class 1, 2, and 3 components shall be performed in accordance with Section XI of the ASHE Boiler and Pressure Vessel Code and applicable Addenda as required by 10 CFR 50.55a(g),
except where specific written relief has been granted by the Commission pursuant to 10 CFR 50.55a(g)(6)(i).
The Code of Federal Regulations of 10 CFR 50.55a(a)(3) states that alternatives to the requirements of paragraph (g) may be used, when authorized by the NRC, if (i) the proposed alternatives would provide an acceptable level of quality and safety, or (ii) compliance with the specified requirements would result in hardship or unusual difficulty without a compensating increase in the level of quality and safety.
Pursuant to 10 CFR 50.55a(g)(4),
ASHE Code Class 1, 2, and 3 components (including supports) shall meet the requirements, except the design and access provisions and the preservice examination requirements, set forth in the ASHE
- Code,Section XI, "Rules for Inservice Inspection of Nuclear Power Plant Components,"
to the extent practical within the limitations of design,
- geometry, and materials of construction of the components.
The regulations require that inservice examination of components and system pressure tests conducted during each 10-year interval comply with the requirements in the latest edition and addenda of Section XI of the ASHE Code incorporated by reference in 10 CFR 50.55a(b) on the date 12 months prior to the start of the 120-month inspection interval, subject to the limitations and modifications listed therein.
The applicable Edition of Section XI of the ASHE Code for the R.
E. Ginna Nuclear Power Plant Third 10-Year Interval is the 1986 Edition, no addenda.
The components (including supports) may meet the requirements set forth in subsequent editions and addenda of the ASHE Code incorporated by reference in 10 CFR 50.55a(b) subject to the limitations and modifications listed therein.
9309150267 930908 PDR ADOCK 05000244 P
By letter dated July 21,
- 1989, Rochester Gas and Electric Corporation (the licensee) submitted the R.
E. Ginna Nuclear Power Plant Third 10-Year Interval Inservice Inspection Program Plan.
In a Safety Evaluation Report (SER) dated August 6, 1990, the staff found the Program Plan, with the exception of Requests for Relief Nos.
10 and 13, acceptable and in compliance with the regulations.
Revision 1 of the R.
E. Ginna Nuclear Power Plant Third 10-Year Interval Inservice Inspection Program Plan was submitted in a letter dated August 10,
- 1992, and a subsequent revision was submitted by letter dated January 25, 1993.
The January 25, 1993, submittal of the Program Plan was reported to have been reformatted for ease of use, and supersedes the previous submittals in their entirety.
The reformatted Program consists of eleven (11) independent
- sections, each of which carries its own revision number and may be revised separately.
In a letter dated January 5,
1993, the licensee submitted Relief Request (RR)
No.
19 and notified the NRC of the intent to incorporate Code Cases N-460 and N-498 into the Program Plan.
These items are also addressed in the following section.
The staff, with technical assistance from its Contractor, the Idaho National Engineering Laboratory (INEL), has evaluated the R.
E. Ginna Nuclear Power Plant Third 10-Year Interval Inservice Inspection Program Plan, as submitted January 25,
- 1993, and the January 5,
1993, submittal which includes RR No. 19.
The results are reported below.
- 2. 0 EVALUATION The following are the major changes that have been incorporated into the January 25, 1993, revision of the R.
E. Ginna Nuclear Power Plant Third 10-Year Interval Inservice Inspection Program Plan:
(a)
Relief Re uest No.
4 Reactor Coolant Pum Casin Welds and Internals Based on the Licensee's use of ASHE Code Case N-481, "Alternative Examination Requirements for Cast Austenitic Pump Casings,Section XI, Division 1,"
RR No. 4 is no longer required and was withdrawn in Section 2 of the revised Program Plan.
Code Case N-481 is acceptable for general usage as it is referenced in NRC Regulatory Guide 1.147, Revision 9, "Inservice Inspection Code Case Acceptability ASHE Section XI, Division l."
(b)
'ce see's use o
a uthorized uclear Inservice Ins ecto NII In a letter, A. Johnson (NRC) to Dr.
R.
C. Hecredy (RG&E), dated June 16, 1992, the NRC requested that the licensee confirm that all duties were being performed by an ANII as required by the Code.
In the response dated August 17,
- 1992,
[Dr. R.
C. Mecredy (RG&E) to Document Control Desk (NRC)], the licensee committed to contract with the Hartford Steam Boiler Inspection and Insurance Company for services of an ANII for the Third 10-Year Inspection Interval.
The licensee stated that the ANII will perform all required Code duties in accordance with IWA-2110.
Consequently, the licensee withdrew RR No. 3 (Use of an Authorized Inspection Agency to Provide Inspection Services) in Section 2 of the revised Program Plan.
(c)
NIS-1 and NIS-2 Forms:
The NRC's June 16, 1992, letter to the licensee also addressed the use of NIS-1 (Owner's Report fo} Inservice Inspections) and NIS-2 (Owner's Report for Repairs or Replacements) forms.
These forms are specified in Handatory Appendix II of ASHE Code Section XI.
IWA-6220(d)(10) states that the NIS-1 and NIS-2 forms shall be included in the required Inservice Inspection Summary Report and that they include the signature of the ANII. Therefore, Section 1.6. 1 of the Program Plan, in the latest revision, has been revised to include use of the NIS-1 and NIS-2 forms.
Section 1.6.1 now states:
"An Inservice Inspection Report shall be generated to document applicable inservice inspection and associated
- repair, replacement and modification activities.
ASME NIS-1 and NIS-2 forms shall be generated and included within the Inservice Inspection Report."
(d)
Remova of 'nsulation at bo ted 'pints stems for co tro lin boration durin ressure testin In the June 16, 1992, letter to the
- licensee, the staff did not agree with the licensee's basis for limiting the extent of removal of insulation to inspections at bolted connections with ferrous steel fasteners.
A non-isolatable leak could occur anywhere in the piping systems used for controlling boration regardless of fastener material types.
Therefore, the licensee was requested to satisfy the Code requirements regarding VT-2 visual examinations at bolted connections.
In the response dated August 17, 1992, the licensee agreed with the staff's evaluation and stated that paragraph
- 1. 10.3.2 would be revised to require the removal of insulation for inspection of both ferritic and austenitic bolting.
Section
- 1. 10.3.2 of the January 25,
- 1993, Program Plan submittal was revised to state, in part, that:
"Insulation removal during the VT-2 examination is not required, however, in accordance with IWA-5242(a), systems borated for the purpose of controlling reactivity shall have insulation removed at bolted connections during conduct of the VT-2 examination.
This requirement is only applicable to those VT-2 examinations performed during a
h drostatic test, since
- Leakage, Functional and Inservice tests are intended to be non-intrusive type tests.
At Ginna, this requirement is considered to be applicable to borated lines only in the primary flow path of piping from the boric acid supply and CVCS Charging to the Reactor Vessel and return through CVCS Letdown, and
is not applicable to branch lines connected to the primary flow path."
The staff considers this response unacceptable.
The licensee is not intending to perform any hydrostatic testing based on the use of ASME Code Case N-498, Alternative Rules for 10-Year Hydrostatic Pressure Testing for Class 1 and 2 Systems,Section XI, Division 1.
Additionally,Section XI of the Code requires the removal of insulation at bolted connections on all systems that contain borated water during the conduct of a VT-2 visual examination.
This does not exclude VT-2 visual examinations during functional or inservice tests.
ASHE Code Interpretation XI-1-89-38 supports this conclusion and should be referenced if further clarification of this requirement is necessary.
For the January 25, 1993, revision of the Program Plan to be considered acceptable, the licensee must meet the Code requirements regarding bolted connections on systems containing borated water.
As stated in Section 1.0 of this report, the staff denied Requests for Relief Nos.
10 and 13 in the SER dated August 5, 1990.
It is noted in the January 25, 1993, revision of the Program Plan that Request for Relief No.
10 has been withdrawn.
- However, Request for Relief No.
13 has not been withdrawn and appears to be applicable for the current 10-year inspection interval.
Request for Relief No.
13 should either be withdrawn, or acknowledged in the Program Plan as being NRC unacceptable.
The following evaluations address the January 5,
1993, letter notifying the staff of the licensee's intent to incorporate Code Cases N-460 and N-498 and the submittal of RR No. 19.
ASME Code Cases N-460 and N-498 have both been approved for use by reference in Regulatory Guide l. 147, Revision 9, "Inservice Inspection Code Case Acceptability ASNE Section XI Division 1", dated April 1992.
Relief Re uest No.
19 Examination Cate or C-B Items C2.21 and C2.22 Char i S ste sat'o Dam e
e No zle Welds and I side d'us Sections~di: I ti XI, T bl MC-2500-1, E
i tl Category C-B, Item C2.21 requires a 100X surface and volumetric examination of nozzle-to-shell welds on nozzles in vessels with nominal wall thickness >I/2 inch.
Item C2.22 requires a 100X volumetric examination of the inside radius sections of the nozzles.
These examinations are to be performed as defined by Figures IWC-2500-4(a) or (b) as applicable.
Licensee's Code R:
Relief is requested from performing the surface and volumetric examinations to the extent required by the Code for the following charging system pulsation dampener nozzle welds and inside radius sections:
Nozzle NDE Method Covera<ae CF-Nl PT 66X UT 65X
~ozz e
CF-N2 CF-N3 DE Method PT UT PT UT
~Cove a
e 66X 65X
>90X 80X Licensee's Basis for Re uestin Relief:
The pulsation dampener contains three (3) nozzles, in line, located at the bottom of the unit.
The outboard nozzle is identified as CF-Nl.
Between this nozzle and the middle nozzle (CF-N2) is a support that covers from the edge of one nozzle's weld heat affected zone to the edge of the other nozzle's weld heat affected zone.
There is only 7/8 inch between CF-N2 and the third nozzle (CF-N3) heat affected zone.
Licensee's Pro osed Alte ative Examinat'o None.
The Code-required surface and/or volumetric examinations will be performed to the maximum extent practical.
Evaluation:
The R.
E. Ginna Nuclear Power Plant was constructed to the 1955 Edition of ANSI B31. 1.
This Code did not contain requirements to ensure that items be accessible for future examinations.
The pulsation dampener was constructed and installed in the early 1970s, and the construction code did not require provisions for accessibility for inservice inspections.
Due to the close proximity of the nozzles and/or the vessel
- support, the associated surface and volumetric examinations are impractical to perform to the extent require by the Code.
The identified surface and volumetric examination coverage of 66X to >90X should be considered acceptable for these nozzles at R.
E. Ginna Nuclear Power Plant.
==
Conclusion:==
Based on the above evaluation, it is concluded that since the original construction code did not specify accessibility requirements for future ISI NDE, compliance with the Code for these nozzle examinations is impractical.
Imposition of the surface and volumetric examinations, to the extent required by the Code, would necessitate redesign or replacement of the charging system pulsation dampener and result in hardship or unusual difficulty without a compensating increase in the level of quality and safety.
Therefore, pursuant to 10 CFR 50.55a(g)(6)(i), relief is granted as requested.
Paragraph 10 CFR 50.55a(g)(4) requires that components (including supports) that are classified as ASNE Code Class 1, 2, and 3 meet the requirements, except design and access provisions and preservice requirements, set forth in applicable Editions of ASHE Section XI to the extent practical within the limitations of design,
- geometry, and materials of construction of the components.
Pursuant to 10 CFR 50.55a(g)(5)(iii), the licensee determined that conformance with certain Code requirements is impractical for their facility and submitted supporting technical justification.
The staff has reviewed the licensee's submittal, dated January 5,
- 1993, and has concluded that pursuant to 10 CFR 55.55a(g)(6)(i) relief can be granted as requested for RR No. 19.
Such relief is authorized by law and will not endanger life, property, or the common defense and security, and is otherwise in public interest.
This relief is being granted giving due consideration to the burden upon the licensee that could result if the requirements were imposed on the facility.
Regarding Revision 2 and the January 25, 1993, submittal of the Program
- Plan, the staff has concluded that the licensee has adequately addressed the deficiencies cited in the June 16, 1992, letter from the NRC regarding the licensee's use of an ANII and the NIS-1 and NIS-2 forms.
- However, as addressed
- above, the licensee's response regarding the removal of insulation, during pressure
- testing, at bolted connections in piping systems used for controlling boration is still considered unacceptable.
In addition, the licensee should either withdraw Request for Relief No.
13 or acknowledge it as being unacceptable to the NRC in the Program Plan.
Based on inadequate VT-2 visual examinations of bolted connections in borated
- systems, and Request for Relief No.
13 not having been withdrawn, the staff concludes that the R.
E. Ginna Nuclear Power Plant Third 10-Year Interval Inservice Inspection Program Plan, Revision 2, as submitted January 25,
- 1993, is not in compliance with 10 CFR 50.55a(g) and Technical Specification 4.2.1.5 and is therefore unacceptable.
Principal Contributors:
T. McLellan H. Khanna Date: