Ro:On 810501,fire Announced on Operating Floor of Containment Vessel.Caused by Spark from Work on Seismic Support Entering Storage Box Igniting Webbing.Open Flame Welding & Grinding Permits Cancelled During Investigation
ML17258B066
Person / Time
Site: Ginna 
Issue date: 05/01/1981
From: Noon J
ROCHESTER GAS & ELECTRIC CORP.
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
NUDOCS 8106010155
Download: ML17258B066 (3)


Text

RCCHESTcR GAS AN3 ELECTRIC CGRPClAAT,'CPi' 85'AST AVEt'iVE, ROCHES ER,

~I.'c'.

Ost I &A Ginna Station May 1, 1981 a6~,

g gy SB~

lt S Qg%s ggggQH Mr. Boyce H. Grier, Director U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King of Pr

SUBJECT:

ussia, Pennsylvania 19406 q~O Q

Smoldering Fire in Ginna Station Containment Vessel (NUREG 0654,,

Appendix I, Unusual Event, Fire Lasting More Than 10 Minutes)

'ear Mr. Grier:

This is to follow up on the one-hour notification made by our Shift Supervisor at approximately 0225 hours0.0026 days <br />0.0625 hours <br />3.720238e-4 weeks <br />8.56125e-5 months <br /> on the morning of May 1,

1981, and to close out the above referenced NUREG 0654 Unusual Event.

At 0144 hours0.00167 days <br />0.04 hours <br />2.380952e-4 weeks <br />5.4792e-5 months <br />, a fire was announced on the operating floor of the containment vessel.

The fire watch assigned

-to monitor modifications to a

main steam line seismic support in the containment made the announcement.

At 0157 hours0.00182 days <br />0.0436 hours <br />2.595899e-4 weeks <br />5.97385e-5 months <br /> the Ginna Control Room was notified by the Fire Brigade Captain that the f i re was out.

Smoke had been observed coming from a

storage box for the reactor vessel head "0" rings located below and adjacent to the modification work area.

The box was opened and the fire put out by use of portable extinguishers.

It appears that a grinding spark from the work on the seismic support entered the storage box through an opening in the side and ignited some four inch webbing that holds the "0"-rings in place in the box.

The inside of the wooden box was in turn ignited.

The outside of the storage box had been protected with a fire-retardant

paint, however, the inside of the box had not been protected.

ROCHESTER CAS AND ELECTRIC CORP.

DATE 5-1-81 TO Boyce H. Grier, NRC SHEET NO 2

Open

Flame, Melding and Grinding Permits were cancelled until an investigation of the event had been completed by the Sta-tion Fire Protection and Safety Coordinator.

8.. gu John C.

Noon Assistant Superintendent JCN:kac xc: