Notice of Violation from Insp on 880222-26.Violation Noted: Personnel Qualification Records of QA Personnel Certified by Licensee to Level II VT-2,VT-3 & VT-4 Visual Insp Did Not Contain Records of Past Performance History
ML17251B058
Person / Time
Site: Ginna 
Issue date: 04/18/1988
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML17251B056 List:
References
50-244-88-04, 50-244-88-4, NUDOCS 8804270197
Download: ML17251B058 (2)


Text

APPENDIX A Notice of Violation Rochester Gas and Electric Company R.

E. Ginna Nuclear Power Plant Docket No.

50-244 License No.

DPR-18 As a result of the inspection conducted on February 22-26,

1988, and in accordance with the "General Statement of Policy for NRC'nforcement Actions",

10 CFR 2, Appendix C, the following violation was identified.

10 CFR 50.55a(g) states that ASME Code Class 1, Class 2,

and Class 3

components'hall meet the requirements set forth in Section XI of the ASME Boiler and Pressure Vessel Code and Addenda.

The facility inservice inspection program states that the facility will meet the requirements of Section XI, 1974 Edition through the Summer 1975 Addenda with guidance from Section XI, 1977 Edition, through Summer 1978 Addenda.

ASME Section XI, 1977 Edition, Summer 1978 Addenda invokes ANSI N45.2.6, 1973 for the qualification of personnel performing the visual examination VT-2., VT-3,

'and VT-4, and states that the practical examination shall be performed using parts representative of the Owner's plant.

ANSI N45.2.6, 1973 states that a file of records of personnel qualifications shall be maintained, and shall contain records of past performance history.

Contrary to the above:

During the period from February 22, 1988 to February 26,

1988, personnel qualification records of gC Personnel certified by the licensee to Level II VT-2, VT-3, and VT-4 visual inspection did not contain records of past performance history, and the practical examination was not performed using parts representative of the Owner's plant.

This is a severity level V violation (Supplement 1).

Pursuant to the provisions of 10 CFR 2.201, Rochester Gas and Electric Corporation, is hereby required to submit to this office within thirty days of the date of the letter which transmitted this Not'ice, a written statement or, explanation in reply including: (1) the corrective'steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved.

Mhere good cause is shown, consideration will be given to extending this response time.

"FFICIAL RECORD COPY IR GINNA 88 0003.0.0 04/15/88 C<