ML17228B261

From kanterella
Jump to navigation Jump to search
Amend 79 to License NPF-16,changing Table 3.3-3 & 3.3-4 to Accommodate Improved Coincidence Logic & Relay Replacement for 4.16 Kv Loss of Voltage Relays
ML17228B261
Person / Time
Site: Saint Lucie 
Issue date: 09/01/1995
From: Matthews D
NRC (Affiliation Not Assigned)
To:
Shared Package
ML17228B262 List:
References
NUDOCS 9509080329
Download: ML17228B261 (8)


Text

gA'0 REGS

+4 po Cy O

I C

Vl Pi ~

0 Op gO

++*++

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 0 ID GH 0

ANDO U OMM S 0

THE CITY OF OR ANDO F

OR D

F ORIDA MUNICIPA POWER AGENCY

~ODC N.5-39 ST.

UC A T UNIT AMENDMENT TO FACILITY OPERAT NG C

NS Amendment No.

License No. NPF-16 The Nuclear Regulatory Commission (the Commission) has found that:

A.

B.

C.

D.

The application for amendment by Florida Power

& Light Company, et al. (the licensee),

dated February 27,

1995, complies with the standards and requirements of the 'Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

9509080329 '-'-95090 l

'PDR " ADQCK 05000389 F

PDR 2.

Accordingly, Facility Operating License No. NPF-16 is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and by amending paragraph 2.C.2 to read as follows:

2.

echnical S ec'cations 3.

The Technical Specifications contained in Appendices A and 8, as revised through Amendment No.

79

, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

This license amendment is effective as of its date of issuance and shall be implemented within 60 days.

FOR THE NUCLEAR REGULATORY COMMISSION David B. Matthews, Director Project Directorate II-1 Division of Reactor Projects I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

SePtember 1,

1995

N TO N

N

. 79 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages.

The revised pages are identified by amendment number and contain vertical lines indicating the area of change.

The corresponding overleaf pages are also provided to maintain document completeness.

e ove se t es 3/4 3-14 3/4 3-18 3/4 3-14 3/4 3-18

TABLE 3.3-3 Continued NGINEEREO SAF TY F ATURES ACT ATION SYSTEM INSTRUMENTATION FUNCTI NAL UNIT 4.

MAIN STEAM LINE ISOLATION (MSIS) a.

Manual (Trip Buttons) b.

Steam Generator Pressure - Low c.

Containment Pressure-High d.

Automatic Actuation Logic 5.

CONTAINMENT SUHP RECIRCULATION (RAS) a.

Manual RAS (Trip Buttons) b.

Refueling Mater Storage Tank Low c.

Automatic Actuation Logic TOTAL NO.

OF CHANN 4/steam generator 1

2 1, 2, 3

2/steam generator 3/steam 1, 2, 3(c) generator 2

3 1, 2, 3

1, 2, 3

1, 2, 3, 4

1, 2, 3

1, 2, 3

HINIHUM CHANNELS CHANNELS APPLICABLE

~TO TR P

~OP RAB

~NODE

~CT~IN 16 13*,

14 ~

13*,

14 12 12 17 12

M I

0ill z

=I lO R

z0 FUNCTIONALUNIT 6.

LOSS OF POWER (LOV) a.

(1) 4.16kV Emergency Bus Undervoltage (Loss of Voltage)

(2) 480 V Emergency Bus Undervoltage (Loss of Voltage) b.

(1) 4.16kV Emergency Bus Undervoltage (Degraded Voltage)

(2) 480 V Emergency Bus Undervoltage (Degraded Voltage) 7.

AUXILIARYFEEDWATER (AFAS) a.

Manual (Trip Buttons) b.

Automatic Actuation Logic c..

SG Level (2A/2B) - Low 8.

AUXILIARYFEEDWATER ISOLATION a.

SG 2A - SG 2B Differential Pressure b.

Feedwater Header SG 2A - SG 2B Differential Pressure TOTALNO.

OF CHANNELS 2/Bus 3/Bus 3/Bus 3/Bus 4/SG 4/SG 4/SG 4/SG 4/SG CHANNELS TO TRIP 2/Bus 2/Bus 2/Bus 2/Bus 2/SG 2/SG 2/SG 2/SG 2/SG MINIMUM CHANNELS OPERABLE 1/Bus 2/Bus 2/Bus 2/Bus 4/SG 3/SG 3/SG 3/SG 3/SG APPLICABLE MODES 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 ACTION 17 17 17 17 15 12 13', 14 13', 14 13', 14

TABLE 3.3-4 ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP VALUES FUNCTIONAL UNIT 1.

SAFETY INJECTION (SIAS) a.

Hanual (Trip Buttons) b.

Containment Pressure

- High c.

Pressurizer Pressure

- Low d.

Automatic Actuation Logic 2.

CONTAINMENT SPRAY (CSAS) a.

Manual (Trip Buttons) b.

Containment Pressure High-High c.

Automatic Actuation Logic 3.

CONTAINMENT ISOLATION (CIAS) a.

Manual CIAS (Trip Buttons) b.

Safety Injection (SIAS) c.

Containment Pressure

- High d.

Containment Radiation - High e.

Automatic Actuation Logic 4.

HAIN STEAN LINE ISOLATION a.

Hanual (Trip Buttons) b.

Steam Generator Pressure -

Low c.

Containment Pressure

- High d.

Automatic Actuation Logic TRIP SETPOINT Not Applicable

< 3.5 psig

> 1736 psia Not Applicable Not Appl icable

< 5-40 psig Not Applicable Not Applicable Not Applicable

< 3.5 psig

< 10 R/hr Not Applicable Not Applicable

> 600 psia

< 3.5 psig Not Applicable ALLOWABLE VALUES Not Applicable

< 3-6 psig

> 1728 psia Not Applicable Not Appl icable

< 5.5p psig Not Applicable Not Applicable Not Applicable

< 3 '

psig

< 10 R/hr Not Applicable Not Applicable

> 567 psia

< 3.6 psig Not Applicable

Co I

O m

CK

=I tO Z

O

.FUNCTIONALUNIT 5.

CONTAINMENTSUMP RECIRCULATION(RAS) a.

Manual RAS (Trip Buttons) b.

Refueling Water Storage Tank - Low c.

Automatic Actuation Logic LOSS OF POWER (1) 4.16 kV Emergency Bus Undervoltage (Loss of Voltage)

(2) 480 V Emergency Bus Undervoltage (Loss of Voltage)

(1) 4.16 kV Emergency Bus Undervoltage (Degraded Voltage)

(2) 480 V Emergency Bus Undervoltage (Degraded Voltage) 7.

AUXILIARYFEEDWATER (AFAS) a.

Manual (Trip Buttons) b.

Automatic Actuation Logic c.

SG 2A &2B Level Low 8.

AUXIUARYFEEDWATER ISOLATION a.

Steam Generator hP - High b.

Feedwater Header hP - Hi h TRIP VALUE Not Applicable 5.67 feet above tank bottom Not Applicable a 3120 volts z 360 volts z 3848 volts with < 10-second time delay

~ 432 volts Not Applicable.

Not Applicable w 19.0%

s 275 psid s 150.0 sid ALLOWABLEVALUES Not Applicable 4.62 feet to 6.24 feet above tank bottom Not Applicable

> 3120 volts w 360 volts a 3848 volts with < 10-second time delay a 432 volts Not Applicable Not Applicable z 18.0%

89.2 to 281 psid 56.0 to 157.5 sid