SAFETY EVALUATION SUPPORTING ANENOt~ENT WO.

4 TO CONSTRUCTION PERMIT HO. CPPR-144 ST.

LUCIE PLANT UNIT 2 ST LUCIE 2 IHTRODUCTIOH Florida Power 5 Light Company (FPBL) is a holder of HRC Construction Permit No.

CPPR-144 for Unit 2 of the St. Lucie Plant.

On September 18, 1980, the HRC issued Amendment Ho.

1 to the permit to include conditions to alleviate effects of the loss of AC power in the event of a station blackout.

Amendment Ho.

2 was issued on November 14, 1980 to provide for the transfer of an ownership interest in St. Lucie 2 to the Orlando Utilities Commission of the City of Orlando (Orlando.

Amendment No.

3 was issued on Hay 26, 1981 to add certain antitrust conditions based on a settlement agreement and an April 24, 1981 Atomic Safety and Licensing Board memorandum and Order in the then ongoing construction permit antitrust proceeding.

By application dated June 14,

1982, the Florida Power and Light Company FPBL, as Project Manager and Operating Agent of the St. Lucie 2, submitted a request for an amendment to Construction Permit Ho. CPPR-144 to add Florida Hunicfpal Power Agency (Ft1PA) as a co-owner and co-applicant and to secure approva'l of a transfer of the current ownership percentage to Ff1PA.

FHPA ownership share amounts to 8.806 percent of the facility.

Also FPSL filed antitrust information on June 14, 1982, regarding FtiPA.

At our request, the Attorney General reviewed the antitrust information submitted by FPSL with regard to ownership by Ft1PA.

The Attorney General determined that an antitrust hearing was not required.

ANALYSIS The transfer of partial ownership to FHPA does not involve any change in the exclusive responsibility and control to be exercised by FP&L over the physical construction, operation and maintenance of St. Lucie 2.

Therefore, the proposed amendment to the Unit 2 construction permit does not involve either an unreviewed safety question or a significant hazards consideration.

FHPA was organized in February 1978 by twenty-six Florida municipalities and was created to plan, finance, acquire, construct, own, lease,

operate, main-tain, repair, fmprove, extend or otherwise participate joint'ly in one or more electric projects for the benefit of its members.

8302240005 830203 PDR ADDCK 05000389 A

PDR OFFICEI SURNAME/

OATE Q i NRC FORM 318 (10-80) NRCM 0240 I

OFFlCIAL RECORD COPY USGPOl 1981-335.960

g l 4a 1

I, J

>>'n'>>,

The HRC regulations relating to the determination of an applicant's financial qualifications are fn Section 50.33(f) of 10 CFR Part 50.

These regulations, as amended on Harch 31,- 1982, state that a financial review of an applicant to construct a production or utilization facility (commerfcal nuclear power plant) shall not be conducted if the applicant is an electric utility.

Since St. Lucie 2 is a utilization faci lfty and since FHPA is an electric utility within the meaning of Section 50.33 (f) of 10 CFR Part 50, a financial review of the proposed transfer of ownership shares is not required.

COHCLUSIOH On the basis of the above evaluation, the staff finds that the issuance of the requested amendment transferring ownership of 8.806 percent of St. Lucie 2 will not be inimical to the common defense and security or to the health and safety of the public.

The staff finds that the requested amendment does not involve a sfgniffcant-hazards consideration because this action will not involve any signiffcant increase fn the probability or consequences of any accident, and this action will not involve any significant decrease in safety margin.

Date Issued:

FE8 g lg@

OFFICEI SURNAME IN OAVEP e~

s: ph 1/g Q

/83 DL:LB83 GKiiighton "i/"j'$"783" NRC FORM 318 (10-80) NRCM 0240 i

OFFICIAL RECORD COPY USOPOl 1991~5 9t>>0

0

January 25, 1983

c~

SUBJECT:

ST.

LUCIE 2 -

ISSUANCE OF AMDT 4 to C.P.

(ELD 8 830 226)

The amendment and the F.R. Notice are okay but the SER has a legal error which must be corrected.

On the second page of -the SER, 50;33f is dis-cussed in terms of "production" facilities and St. Lucie 2 is called a

"production" facility.

That is incorrect.

50.33f relates to "production and utilization" facilities and St. Lucie 2 is a, "utilization" facility, not a production facility.

That should be corrected before this is dispatched.

cc:

B.Vogler oseph F. Scinto

~

~

'r I

UNITED STATES NUCLEAR REGULATORY COMMISSION DOCKET NO. 50-389, FLORIDA POllER AND LIGHT COMPANY ET AL ST.

LUCIE PLANT UNIT 2 NOTICE OF ISSUANCE OF AMENDMENT TO CONSTRUCTION PERHITS Notice is hereby given that the U. S. Nuclear Regulatory CoRmfssfon (the Commission) has issued Amendment No.

4 to Construction Permit I'lo.

CPPR-144, to add Florida Hunfcipal Power Agency as an applicant for the St. Lucie Plant, Unit 2 (the facility), located on f)utchfnson Island in St. Lucie County, Florida.

The amendment is effective as of the date of issuance.

Florida Power and Light Company and Orlando Utilities Commission

'I of the City of Orlando are the present applicants.

The application for the amendment complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations.

The Commission has made appropriate findings as required by the Act and the Commission's regulations in 10 CFR Chapter I, which are set forth in the amendment.

The Commission has also concluded that the amendment involves actions which are insignificant from the stand-point of environmental impact and that, pursuant to 10 CFR Section 51.5(d)(4),

an environmental impact statement or negative declaration and an environmental impact appraisal need not be prepared in connection with the issuance of the amendment.

Prior public notice of the amendments was not required since the amendment does not involve a significant hazards consideration.

OFFICEI SURNAME$

DATE0 NRC FORM 318 (10-80) NRCM 0240 i ~

~ i ~ ~ ~ ~ 0

~

OFFICIAL RECORD COPY USOPO: 1981~i-960 For further details with respect, to this action, see (1) the application for amendment, dated June 14, 1982; (2) Amendment No. 4 to Construction Permit No. CPPR-144 and (3) the Commission's related Safety Evaluation.

All of these items are available for public inspection in the Commission's Public Document

Room, 1717 H Street, H.

W. Washington, D. C., and at the Indian River Community Library, 3900 Virginia Avenue, Ft. Pierce, Florida 33450.

Items 2 and 3 may be requested by writing to the U. S. Nuclear Regulatory Commission, Washington, D. C. 20555, Attention:

Director, Technical Information and Document Control.

Dated at Bethesda, Maryland, this day of February, 1983.

FOR THE NUCLEAR REGULATORY COeIISSIOi'I George W. Knighton, Chief Licensing Branch Wo.

3 Division of Licensing SEE PREVICUS CONCUHHENCES DL:LB¹3 DL':LB¹3 OFFICE/

SURNAME/

GKnighton VNerses:ph 2/

/83 DATEP 2/

/83 NRC FORM 318 (10-80) NRCM 0240 OFFICIAL RECORD COPY USGPO: 1991~5.999

For further details with respect to this action, see (1) the app ication for amendment, dated June 14, 1982; (2) Amendment No.

4 to Constr ction Permit Ro.

CPPR-144 and (3) the Commfssfon's related Safety Evalugat'on.

All of these items are available for public inspection in the Commiss'en's Public Document

Room, 1717 H Street, N.

H. Ilashington, D. C.,

and at he Indian River Community Library, 3900 Virginia Avenue,Ft.

Piegre, Florida 33450.

Items 2 and 3 may be requested by writing to the U

S. Nuclear Regulatory Commission, l<ashington, D. C. 20555, Attention:

Dir ctor, Technical Information and Document Control.

Dated at Bethesda, Maryland, this day of January, 1983.

FOR THE NUCLEAR REGULATORY COththISSION George W. Knighton, Chief Licensing Branch No.

3 Division of Licensing OFFICE 0 SURNAME IP oATE IP

B¹3
ph 1/

q /83 DLL 3

~ ~ ~ ~ ~ ~

~ ~ Ct ~ St ~ 0~0 ~

VN ed ~

DL:LB¹3

~ 0 ~\\ ~ ~ 0

~ 000 ~ 0 ~ 0 ~ 0 1/ I'83 Knighton

~ ~

~

~ 0 ~

~ ~ ~ 0 ~ 0 ~ 0 ~ ~ ~ ~ 0 ~ ~

1/

/83 OfLh

~ 00 ~ 0\\ 0 ~ ~ ~ ~

~ ~ ~

~ ~ ~ 0 ~ 0 ~ 0 ~

~ ~Ottt ~

~ ~ ~ ~

NRC FORM 318 (10-80) NRCM 0240 OFFICIAL RECORD COPY USGPO: 1981~960

DISTRIBUTION FOR AMENDMENT NO. 4 TO CP ST.

LUCIE PLANT UNIT 2 cDocudient Control-(50-389) >

NRC PDR Local PDR PRC System NSIC LBk'3 Reading File V. Nerses J.

Lee G. Knighton B. Paton, ELD D. Easenhut/R.

Purple T. Novak J.

Rutberg, ELD A. Toalston, AIG E. Jordan, DEEDA: IE J. Taylor, DRP:IE L. Harmon, IE File (2)

J.

Sauder W. Miller I. Dinitz W. Jones, OA (1 cy)

T, Barnhart (4 cys)

B. Cotter, ASLBP A. Rosenthal, ASLAP ACRS (16 cys)

F.

Pagano, IE

~ ~

c'

1