Thank you for your letter of March 22, 1982, informing us of steps
you have
taken to correct the violation concerning activities under
NRC Operating
Licensee
Nos.
DPR-67 and CPPR-144,
brought to your attention in our letter
of February 18, 1982.
We will,e(hmine your corrective actions
and plans
during subsequent
inspections.
We appreciate your cooperation with us.
Sincerely,
>~i
F. J.
Long, Acting Chief
Reactor
Projects
Branch
2
Division of Project and
Resident. Programs
C.
t<. llethy. Plant Manager
B. J.
Escue,
Plant flanager
Nat Weems,
gA Construction
Manager
bcc:
US
NRC Resident
Inspector
Document
Management
Branch
State of Florida
('i04&olm s2033o
DR ADOCK, 05000335
OFFICE
SURNAME
RIt:.
KDL
d s:am
RII:..P.RP........
HCDance
RI I.;P.
FJLon
DATE 3/gP /82
3'/82
NRC FORM 318 t10.80) NRCM 0240
3g I%/82
OFFICIAL RECORD COPY
~
rt',
~a /
l~
I
0
P.O. BOX 529100 MIAMI,F L 33152
>4~lb<
82 gag 8
~10
2~
FLORIDAPOWER 8 LIGHTCOMPANY
March 22,
1982
Mr. James
P. O'Reilly
Regional Administrator, Region II
U.S.
Nuclear Regulatory
Commission
101 flarietta Street,
Suite
3100
Atlanta, Georgia
30303
Dear
Mr. O'Reilly:
Re:
St. Lucie Upits
1
8
2
Docket Nos. 50-335,
50-389
IE Ins ection
Re orts 81-35 and 81-26
Florida Power
and Light Company
has
reviewed the subject
inspection report
and
a response
is attached.
There is no proprietary information in the report.
Very truly yours,
Robert
. Uhrig
Vice President
Advanced, Systems
8 Technology
REU/PLP/mbd
Attachment
cc:
Harold F. Reis,
Esquire
PEOPLE... SERVING PEOPLE
Re:
St. Lucie Units
1
8
2
Docket Nos. 50-335
and 50-389
IE Ins ection
Re orts 81-35
and 81-26
Finding:
Technical Specification 6.8.l.c requires that written procedures
shall
be
established,
implemented
and maintained covering surveillance
and test
activities of safety-related
equipment.
Contrary to the above:
a.
Maintenance
Procedure
M-0017, Revision 2,
was inadequately
established
and
implemented,
in that the procedure failed to direct
the mechanic
to ensure
the nozzle ring set-screw
was installed in
a
notch vice on
a land and the mechanic
turned the nozzle ring the
wrong direction after
checking the relief point.
Improper set
screw
installation is credited
as
a major factor in causing early relief
valve operation
on December
19,
1981.
Response:
1.
FPL concurs with the finding.
2.
The procedure
was not clear
on the set
screw installation.
3.
As corrective action, the replacement relief valve was checked to
assure
correct installation.
4.
As corrective action to prevent future problems,
procedure
M-0017 was
revised to clarify the nozzle ring and set
screw installation
and
this area
was emphasized
by maki ng this procedural
step
a
"gC Hold
Point".- Additionally, the training
program is stressing
the
importance of correct nozzle
and adjusting ring installation.
5.
Full compliance
was achieved
on March 2, 1982.
STATE OF FLORIDA
)
)
COUNTY OF
DADE
)
J.
A. Def1astry
being first duly sworn,
deposes
and says:
Manager,
Nuclear Licensing
Light Company,
the
herein;
of Florida Power
That he has
executed
the foregoing document;
that the state-
ments
made in this said document
are true
and correct to the
best of his knowledge, information,
and belief,
and that he is
authorized to execute
the document,
on behalf of said
J.
A. OeMastry
Subscribed
and sworn to before
me this
Q~ say
oS
NOTARY PUBL C, in and for the County of Dade,
State of Florida
NOTARY PUBLIC, STATE OF FLORIDA AT LARGE
commission expires
MY COMMISSION EXPIRES
MARCH l8, 1984
0
I
t
/
$ A U
F
p 1-~
/
C~
o
'C