Docket No. 50-237 Mr. Henry Bliss Nuclear Licensing Manager Comirionwealth Edison Company Post Office Box 767 Chicago, Illinois 60690

Dear Mr. Bliss:

~ovember l, 1988

  • DISTRIBUTION.

cQ_oc ket_ttle)

NRC & Local PDR POii I-2 r/f DMuller BSiegel CYCheng LLuther WKoo

SUBJECT:

FALL 1988 OUTAGE IGSCC INSPECTION PROGRAM FOR DRESDEN NUCLEAR POWER STATION UNIT 2 (TAC NO. 69165)

In your letters dated July 29, 1988 and.October 5, 1988, you provided a response to Generic Letter 88-01 and supplemental information on the Fall 1988

°IGSCC Inspection Program for Dresc;ten Unit 2. Based on our preliminary review, l

the staff has determined that the Fall 1988 Inspection Program described in your July 29, 1988 submittal is acceptable with ~he followi.ng exception.

Because of CECo' s inability to provide information to determine the types of inspections and the qualifications of the.inspectors used for those Category G welds that were inspected in 1983 and 1984, no credit can be given for hydrogen water chemistry (HWC) and all those welds should be inspected during the 1988 refueling outage. *For the remaining weld categories where CECo has requested

.,'*credit for HWC, the* staff has determined that this credit can be granted *

. The staff.is evaluating your response to.Generic Letter 88-01 and when the

. review is completed, a Safety Evaluation will be issued which will include an

)_.*

  • evaluation of your HWC Program.

.~..

I I

I

~..

  • , 'f cc:

See next page PDIII-2 ~

. PDIII-2~

LLuther:d~j BSiegel

I I o*~/88

. II Io'; /8 8811100104 8~1)03 PDR ADOCK 05000237 Q

PDC Sincerely, Byron Siegel,* Senior* Project Manager Project Directorate III-2 Division of Reactor Projects ~ III, IV, V and Special Projects

~N!fRAp~*

CY Cheng "

  • o.Mfl e~

\\\\f11 /88 j I 13 !88

~

.~

UNITED STATES

  • NUCLEAR REGULATORY COMMISSION WASHINGTON. D. C. 20555 Docket No. 50-237 Mr. Henry Bliss Nuclear Licensing Manager Commonwealth Edison Company Post Office Box 767 Chicago, Illinois 60690

Dear Mr. Bliss:

November 3, 1988

SUBJECT:

FALL 1988 OUTAGE IGSCC INSPECTION PROGRAM FOR DRESDEN NUCLEAR POWER STATION UNIT 2 (TAC NO. 69165)

In your letters dated July 29, 1988 and October 5, 1988, you provided a response to Generic Letter 88-01 and supplemental information on the Fall 1988 IGSCC Inspection Program for.Dresden Unit 2.

Based on our preliminary review, the staff has determined that the Fall 1988 Inspection Program described in your July 29, 1988 submittal is acceptable with the following exception.

Because of CECo's inability to provide information to determine the types of inspections and the qualifications of the inspectors used for those Category G welds that were inspected in 1983 and 1984, no credit can be given for hydrogen water chemistry (HWC) and all those welds should be inspected during the 1988 refueling outage.

For the remaining weld categories where CECo has requested credit for HWC, the staff has determined that this credit can be granted.

The staff is evaluating your response to Gent!ric Letter 88-01 and when the revi~w is completed, a Safety Evaluation will be issued which will include an evaluation of your HWC Program.

cc: See next page Sincerely, 1:6.~nfor Project Manager Project Directorate III-2 Division of Reactor Projects - III, IV, V and Special Projects

Mr. Henry E. Bliss Co1TU11onwealth Edison Company

~

cc:

Michael I. Miller, Esq.

Sidley and Austin One First National Plaza Chicago, Illinois 60603 Mr. J. Eenigenburg Plant Superintendent Dresden Nuclear Power Station Rural Route #1 Morris, Illinois 60450 U. S. Nuclear Regulatory Co1TU111ss1on Resident Inspectors Office Dresden Station Rural Route #1 Morris, Illinois 60450 Chairman Board of Supervisors of Grundy County Grundy County Courthouse Morris, Illinois 60450 Regional Administrator Nuclear Regulatory Co1TU11ission, Region III 799 Roosevelt Road, Bldg. #4 Glen Ellyn, Illinois 60137 Mr. Michael E. Parker, Chief Division of Engineering Illinois Department of Nuclear Safety 1035 Outer Park Drive, 5th Floor Springfield, Illinois 62704 Dresden Nuclear Power Station Units 2 and 3