ML17138B865

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 81-06, Failure of Ite Model K-600 Circuit Breaker. No Response Required
ML17138B865
Person / Time
Site: Susquehanna  
Issue date: 03/11/1981
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Curtis N
PENNSYLVANIA POWER & LIGHT CO.
References
NUDOCS 8103200170
Download: ML17138B865 (4)


Text

~R RK0II P0

+a*++

Docket Nos.

50-387 50-388 NUCLEAR REGULATORY COMMISSION REGION I 631 PARK AVENUE KING OF PRUSSIA PENNSYlVANIA19406 r~ X MAR 11 1981 Pennsylvania Power and Light Company ATTN:

Mr. Norman M. Curtis Vice President Engineering and Construction Nuclear 2 North Ninth Street Allentown, Pennsylvania 18101 Gentlemen:

The enclosed IE Information Notice No. 81-06, "Failure of ITE Model K-600 Circuit Breaker," is forwarded to you for information.

No written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, Boy e H. Grier Director

Enclosure:

1.

IE Information Notice No. 81-06 with 1 attachment CONTACT:

S.

D. Ebneter (215-337-5283) cc w/encl:

A.

R. Sabol,

Manager, Nuclear guality Assurance M.

E.. Barberich, Licensing Engineer H.

M. Kei'ser, Superintendent of Plant 810880

( lo

~

~ I <I+

,j')),i(b

-,'4

,.g]@)A J. "

~gL$4 lb<~

gfOff'@)(~g(~

~

SSINS No.:

6835 Accession No.:

8011040269 IN 81-06 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 March 11, 1981 IE Information Notice NO, 81-06:

FAILURE OF ITE MODEL K-600 CIRCUIT BREAKER

~Pur use:

The purpose of this information notice is to provide early notification of a matter that could adversely affect the safety of nuclear power plants.

Toward this end, this information notice alerts holders of operating licenses and construction permits of a possibly generic deficiency involving Model K-600 circuit breakers manufactured by ITE.

De seri tion of Circumstance:

By letter dated February 20, 1981, the Sacramento Municipal Uti'lity District informed us that, while performing preventive maintenance on electrical circuit breakers at its Rancho Seco facility, an ITE Model K-600 breaker was observed not to trip.

An investigation revealed that a tripping coil wire had slipped out of its terminal.

Further examinations revealed that the coil wire size was AWG 20, whereas the mating lug was si'zed for AWG 16-14 wire.

A check of other ITE electrical breakers indicated that the problem may be generic.

Subsequent to the letter, the Sacramento Municipal Utility District informed us orally that ITE Model K-1600 breakers have the same deficiency and that Model K-3000 breakers may be similarly affected.

The information provided by the Sacramento Municipal Utility District is pre-liminary and will be followed by a complete report.

Consequently, we have not yet evaluated the safety significance of this event.

Nevertheless, the information herein is being provided as an early notification of a possibly significant event.

Although no specific action or response is requested at this time, recipients should review the information for possible applicability to their facilities. If NRC evaluations so indicate, further licensee actions may be requested.

If you have any question regarding the information contained herein, please contact the Director o'f the appropriate NRC Regional Office.

Attachment:

Recently issued IE Information Notices

, RECENTLY ISSUED IE INFORMATION NOTICES Attachment 1

IN 81-06 March ll, 1981 81-05 Degraded DC System at Palisades Information Subject Notice No.

Date Issued 3/10/81 Issued to All holders of a power reactor OL or CP 81-04 81-03 81 "02 81-01 80-45 80-44 80-43 80-29 Supplement No.

1 Cracking in Main Steam Lines Checklist 'for Licensees Making Notifications of Significant Events in Accordance with 10 CFR 50.72 Transportation of Radiography Devices Possible Failures of General Electric Type HFA Relays Potential Failure of BMR Backup Manual Scram Capability Actuation of ECCS in the Recirculation Mode While in Hot Shutdown Failures of the Continuous Mater Level Monitor for the Scram Discharge Volume at Dresden Unit No.

2 Br oken Studs on Terry Turbine Steam Inlet F,l ange 2/27/81 2/2/81 1/23/81 1/16/81 12/17/80 12/14/80 12/5/80 11/26/80 All holders of a power reactor OL or CP All holders of a power reactor OL or NTOL All holders of a '

radiography license All holders of a power reactor OL or CP All holders of a power reactor OL or CP All holders of a PMR power reactor OL or CP All holders of a BWR power reactor OL or CP All holders of a power reactor OL or CP