Orise Analytical Results for SONGS Synchronous Condenser Soil Sample Dated 05/15/17, 5267-LR-07-0
ML17135A420
Person / Time
Site: San Onofre  
Issue date: 05/15/2017
From: Ivey W
Oak Ridge Institute for Science & Education
To: Rachel Browder
NRC Region 4
Browder R
References
DCN: 5267-LR-07-0, DE-SC0014664, IR 2017002, RFTA 17-001, SDG 12678-6
Download: ML17135A420 (3)


Text

May 15, 2017 f\\ Is. Rachel Bro,,*der l1rj OAK RIDGE INSTITUTE FOR

~I SCIENCE AND EDUCATION L1.S. N uclear Regulatory Commission Region TV 1600 ~as r Lamar Boub*ard

.\\ rlingLOn. TX 760 11 ORISE CONTRACT NO. DE-SC0014664

SUBJECT:

LETTER REPORT FOR ANALYTICAL RESULTS FOR THREE SOIL SAMPLES ASSOCIATED WITH THE SAN ONOFRE NUCLEAR GENERATING STATION IN SAN CLEMENTE, CALIFORNIA

[INSPECTION REPORT NO. 05000361/2017-002 & 05000362/2017-002]

[DOCKET NO. 50-361 & 50-362](RFTA NO.17-001)

DCN: 5267-LR-07-0; SDG 12678-6

Dear J\\[s. Browder:

The Oak Ridge Institute for Science and Education (ORISE) is pleased to provide the enclosed data package for three soil samples receiYCd on April 7, 20 17 from the San Onofre Nuclear Generating Star.ion in San Clemente, California. The samples were recci,*ecl in good condition. The samples were analyzed by gamma spectroscopy for Cs-137 and Co-60. The analytical clam, along with the procedure reference, arc presented in the attached report.

Quality Control (QC) requirements were met for this analysis. The QC files arc available for your review upon request.

Please feel free to contact me at 865.576.918..J. or Forrest Smith at 865.57..J..9802 with any questions or comments.

Sincerely, Al4N /.~

Wade Ivey f\\fanager Laboratory ORAC

\\'</ PJ:lw Enclosures Electronic distribution: T. Carter, N RC S. Roberts, ORr\\U E. Bailey, Olv \\ U

0. Hagemeyer, O lv \\U File code: 5267; Lab code: 12678 P.O. Box 11 7 Oak Ridge, T~ 3 7831
  • www.orise.ornu.gov T. Vitkus, ORAU

Gamma Spectrometry Summary Results By Analyte Energy Signature:

201212678-6 SDG # :

201212678 Project # :

CP1 (21)

SOP (Rev. #)

San Onofre Nuclear Generating Station Project Name:

Analyte:

Report Date: May 15, 2017 Co-60 1332.49 (KeV)

Client Sample ID:

Lab Sample ID:

Result TPU (2s)

MDC Units Qualifier Flag Batch pCi/g GS0475 U

A1501 303F1 LA3S1 L04FN CIPWL 00008 12678S0006

-0.014 0.020 0.038 pCi/g GS0475 U

12678S0006Dup 0.003 0.018 0.039 pCi/g GS0475 U

A1501 303F1 LA3S1 L04FN EXCAV 00005 12678S0007

-0.005 0.018 0.034 pCi/g GS0475 U

A1501 303F1 LA3S1 L04FN SOLWL 00007 12678S0008

-0.010 0.018 0.036 Electronically Validated By:

William Smith-5/11/2017 12:19 Electronically Approved By:

Wade Ivey 5/15/2017 10:20 Qualifier Flags:

U = Analyte not detected (< MDC)

TPU =

Total Propagated Uncertainty MDC =

Minimum Detectable Concentration Page 1 of 1

Gamma Spectrometry Summary Results By Analyte Energy Signature:

201212678-6 SDG # :

201212678 Project # :

CP1 (21)

SOP (Rev. #)

San Onofre Nuclear Generating Station Project Name:

Analyte:

Report Date: May 15, 2017 Cs-137 661.66 (KeV)

Client Sample ID:

Lab Sample ID:

Result TPU (2s)

MDC Units Qualifier Flag Batch pCi/g GS0475 U

A1501 303F1 LA3S1 L04FN CIPWL 00008 12678S0006

-0.001 0.019 0.040 pCi/g GS0475 U

12678S0006Dup

-0.001 0.016 0.035 pCi/g GS0475 U

A1501 303F1 LA3S1 L04FN EXCAV 00005 12678S0007

-0.006 0.010 0.028 pCi/g GS0475 U

A1501 303F1 LA3S1 L04FN SOLWL 00007 12678S0008

-0.009 0.015 0.031 Electronically Validated By:

William Smith-5/11/2017 12:19 Electronically Approved By:

Wade Ivey 5/15/2017 10:20 Qualifier Flags:

U = Analyte not detected (< MDC)

TPU =

Total Propagated Uncertainty MDC =

Minimum Detectable Concentration Page 1 of 1