Notice of Violation from Insp on 890907-1018.Violation Noted:Emergency Diesel Generator Control Room Unit Cooler Declared Operable & No post-maint Test Performed
ML17056A618
Person / Time
Site: Nine Mile Point  
Issue date: 02/06/1990
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML17056A617 List:
References
50-410-89-08, 50-410-89-8, NUDOCS 9002230108
Download: ML17056A618 (2)


Text

APPENDIX A Notice of Vipl ati on Niagara Mohawk Power Corporation Nine Mile Point Unit 2 Docket No.:

50-410 License No.:

NPF-69 As a

result of the inspection conducte'd on September 7,

1989 through October 18,

1989, and in accordance with NRC Enforcement Policy (10 CFR Part 2,

Appendix C) the following violation was identified:

10 CFR 50, Appendix B, Criterion XI requires, in part, that operational proof tests be'performed on nuclear power plant systems and components to ensure they perform satisfactorily in service.

NMPC Quality Assurance Topical Report, Section 11, Test Control, requires post-maintenance test-ing be performed to demonstrate that components will perform satisfac-torilyy in service.

Contrary to the

above, on September 8,
1989, the Division III Emergency Diesel Generator control room unit cooler (2HVC*U2C) was declared operable following electrical preventive maintenance, and no post-maintenance test was performed.

Twelve hours later, on September 9,

1989, the unit cooler was found to be inoperable.

This is a Severity Level IV Violation.

(Supplement I).

\\

Pursuant to the provisions of 10 CFR 2.201, Niagara Mohawk Power Company is hereby required to submit to this office within thirty days of the date of the letter which transmitted this

Notice, a written statement or explanation in
reply, including:

(1) the corrective steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved.

Where good cause is shown,'onsideration will be given to extending this response time.