UNITEDSTATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 NIAGARA MOHAWK POWER CORPORATION DOCKET NO. 50-410 NINE MILE POINT NUCLEAR STATION, UNIT 2
'MENDMENT TO FACILITY OPERATING LICENSE Amendment No.
7 License No. NPF-69 1.
The Nuclear Regulatory Comission (the Comission) has found that:
A.
The application for amendment by Niagara Mohawk Power Corporation (the licensee) dated April 28, 1988, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance IIith the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-69 is hereby amended to read as follows:
PDR 0088 8807RS 88080'DaC]( 05000 PNU
9 4 ~
(2)
Technical S ecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix 8, both of which are attached
- hereto, as revised through Amendment No.
7 are hereby incorporated into this license.
Niagara Mohawk Power Corporation shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendment is effective as of the date of its issuance, and is to be implemented within 30 days.
FOR THE NUCLEAR REGULATORY COMMISSION Robert A. Capra, Director Project Directorate I-1 Division of Reactor Projects, I/II
Attachment:
Changes to the Technical Specifications Date of Issuance:
July 25, 1988
~8 REoy P0 Cy 0O I
Cp
+n gO
++*++
UNITEDSTATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO.
7 TO FACILITY OPERATING LICENSE NO.
NPF-69 DOCKET NO. 50-410 Revise Appendix A as follows:
Remove Pa e
3/4 3-107 Insert Pa e
3/4 3-107
TABLE 3.3.9-2 PLANT SYSTEMS ACTUATION INSTRUMENTATION SETPOINTS TRIP FUNCTION 1.
Feedwater S stem/Main Turbine Tri S stem a.
Reactor Vessel Water Level High Level 8
2.
Service Water S stem ALLOWABLE TRIP SETPOINT VALUE
< 202.3 in.*
< 203.8 in.
a.
Discharge Bay Level b.
Intake Tunnel 1
& 2 Water Temperature c.
Service Water Bay d.
Service Water Pumps Discharge Strainer Differential Pressure-Train "A" e.
Service Water Pumps Discharge Strainer Differential Pressure Train "B" f.
Service Water Supply Header Discharge Water, Temperature g.
Service Water Inlet Pressure for EDG*2 (HPCS, Division III) 1)
Division I Supply Header 2)
Division II Supply Header
< 275'lev.
> 39'F
> 234'lev.
10 psid 10 psid
> 25 psig
> 22 psig
< 275'-3/4" Elev.
> 38'F
> 233'-l/4" Elev.
< 14.5 psid
< 14.5 psid NA
> 17.5 psig
> 17.5 psig
- See Bases Figure B3/4 3-1.
NINE MILE POINT UNIT 2 3/4 3-107 Amendment No.
7