APPENDIX A NOTICE OF VIOLATION Niagara Mohawk Power Corporation Nine Mile Point Unit 2 Docket No.

50-410 License No.

NPF-59 As a result of the inspection conducted on April 18-22,

1988, and in accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions,"

10 CFR Part 2, Appendix C (Enforcement Policy), the following violation was identified:

10 CFR 50.49 paragraph (f) requires that each item of electrical equipment important to safety be qualified.

Contr ary to the above on April 22,

1988, the inspector identified that the qualification of the Raychem cable splices associated with Rosemount transmitters CSL"FT126, CSL*PT109, and SFC*LT32A was not demonstrated at the time of the inspection in that the seal length of these splices was less than the qualification requirement (one inch).

This is a Severity Level IV violation (Supplement I)

Pursuant to the provisions of 10 CFR 2.201, Niagara Mohawk Power Corporation is hereby required to submit to this office within thirty days of the date of the letter which transmitted this Notice, a written statement or explanation in reply, including: (1) the corrective steps which have been taken and the results achieved; (2) corrective-steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved.

Where good cause is shown, consideration will be given to extending this response time.

SS07200l49 SS0706 PDR ADOCK 050004i0 9