Discusses 880201 Telcon Re Authorization for Startup of Facility,Per 880121 Confirmatory Action Ltr CAL-88-02. Understands Listed Actions Completed.Reminds That Reporting Requirements of CAL-88-02 Remain in Effect
ML17055D548
Person / Time
Site: Nine Mile Point 
Issue date: 02/01/1988
From: Kane W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Lempges T
NIAGARA MOHAWK POWER CORP.
References
CAL-88-02, CAL-88-2, EA-88-036, EA-88-36, NUDOCS 8802090039
Download: ML17055D548 (6)


Text

REGULATORY INFQR,ATION DISTRIBUTION SYSTEi1 (RIDS)

ACCESS1QN NBR:,88020~00'"

DQC. DATF. 88/02/01 NG,x I ZED:

NQ FACIL. 50-410 Nine Nile Point Nuclear Station, Unct 2>

Niagara aloha AUTH. NANE AUTHOR AFF ILIATION WANE> M. F.

Region 1>

Qfc of the Director REC IP. NAYiE REC IP IENT AFFILIATION LENPGES> T. E.

Niagara Nohaek Poeer Corp.

DQ'E 0"00~'41;

SUBJECT:

Discusses 880201 telcon re authori zation for startvp of facility per 880121 Conf irmatorg Action Ltr CAL-88-02.

Understands listed actions completed. Reminds that reporting requirements of CAL-88-02 remain in ef fec t.

DISTRIBUTION CODE:

IE36D COPIES RECEIVED: LTR J ENCL 0 SIZE:

TITLE: Immediate/Conf irmatorg Action Ltr <50 Dkt-Other Than Emergency Prepar NOTES: 21 05000410 REC IP IENT ID CODE/N*NE PD1-1 LA HAUGHEY> N INTERNAL: NRR/DOEA/EAB RES/DE/EIB RGM2/DRSS/EPRPB COPIES LTTR ENCL REC IP IENT ID CODE/NANE PD1-1 PD l3ENEDICT> 9

~ZZa 02 RGNi FILE 01 COPIES LTTR ENCL EXTERNAL:

LPDR NSIC NRC PDR TOTAL NUMBER OF COPIES REQUIRED:

LTTR 12 ENCL.

Docket No. 50-410 CAL No. 88-02 EA No.88-36'i FEB,.U8 Niagara Mohawk Power Corporation ATTN:

Mr. Thomas E.

Lempges Vice President 301 Plainfield Road

Syracuse, New York 13212 Gentlemen:

Subject:

Restart Authorization Pursuant to Confirmatory Action Letter 88-02 This refers to our telephone conversation on February 1,

1988 leading to the authorization for startup of Nine Mile Point Unit 2 in accordance with Confirmatory Action Letter (CAL) 88-02 dated January 21, 1988.

During the NRC Region I Augmented Inspection Team (AIT) effort at the site January 21-24,

1988, you committed to completing the following actions prior to restart; 1.

Modify the feedwater lockup circuit or setpoint calibration procedure as needed.

2.

Correct the setpoints of the lo lo and lo lo lo trip function for containment isolation on low vessel water level.

3.

Revise the setpoint procedure for setting the lo lo and lo lo lo trip function for containment isolation on low vessel water level.

4.

Review operating procedures and EOPs for coping with:

a.

Low vessel level b.

Hi vessel level c.

Loss of instrument air (full or partial) and revise those procedures as required 5.

6.

Provide operator training on the revised procedures.

Provide a written analysis of the stresses experienced by the vessel, steam line nozzles and steam lines as a result of the overfill transient on 1/20/88.

It is my understanding, based on information that you provided during our telecon of February 1,

1988 that you have completed the above actions.

You are reminded that the reporting requirements of CAL 88-02 remain in effect.

Your report, as well as the NRC AIT report will be reviewed, as they become available, to determine whether further NRC action in this matter is warranted.

8802090039 880201 PDR ADOCK 05000410 G

PDR

Niagara Mohawk Power Corporation Thank you for your cooperation.

WFE8 l'incerely, William F.

Kane, Director Division of Reactor Projects cc:

C.

V. Mangan, Senior Vice President Connor

& Wetterhahn John W. Keib, Esquire J.

A. Perry, Vice President, Quality Assurance W. Hansen,

Manager, Corporate Quality Assurance J. Aldrich, Unit 1 Superintendent, Operations R.

G. Smith, Unit 2 Superintendent, Operations C.

Beckham, Manager, Nuclear Quality Assurance Operations T. J. Perkins, General Superintendent R.

B. Abbott, Unit 2 Station Superintendent Department of Public Service, State of New York Public Document Room (PDR)

Local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

NRC Resident Inspector State of New York bcc:

Region I Docket Room (with concurrences)

Management Assistant, DRMA (w/o encl)

DRP Section Chief Region I SLO Robert J.

Bores, DRSS J.

Lieberman, OE W.

F.

Kane, RI W. Johnston, RI R. Gallo, RI

~

E. Wenzinger, RI R. Capra, NRR PDI-1 RI:DRP Johnson/meo W n inger 2/1/88 4i+

g

E lo
D