DESIGNING OFFSHORE INTAKES FOR FISH PROTECTION Yusuf G. Mussalli Edward P. Taft, III Stone

& Webster Engineering Corp.

Boston, Massachusetts and Johannes Larsen widen Research Laboratories Holden, Massachusetts American Society of Civil Engineers National Convention Atlanta, Georgia - October, 1979 830h080303 830bOb PDR ADOCK 050004i0 A

PDR

0

DESIGNING OFFSHORE INTAKES FOR FISH PROTECTION BY YUSUF G

MUSSALLIz~ M ASCE~

EDWARD P TAFT~ III2~ AND JOHANNES LARSENs INTRODUCTION Cooling water intake structures are often located offshore to avoid problems with shoreline pack ice, severe wave action, heavy debris accumulations, siltation, and fouling organisms.

In addition, offshore locations are sometimes selected due to the availability of deeper, cooler water or the low level of biological activity.

Numerous offshore intakes exist on the Atlantic and Pacific coasts and on the Great Lakes which are utilized for both once-through and closed-loop cooling purposes.

Since

1972, the impingement and entrainment of fishes at cooling water intakes has become a major concern due to the potential impacts which fish losses may have on the fisheries resources of an area.

As a result, extensive research has been directed toward developing methods for diverting or collecting fish within intakes or preventing their passage into structures altogether.

This research has led to the development of several intake design concepts which have shown varying degrees of success in achieving the goal of fish protection.

This paper addresses five concepts which have been, or are being, pursued actively:

velocity

caps, wide-spaced louvers, behavioral barriers, wedge-wire screens, and infiltration intakes.

Several of these designs have not been shown to yield a high degree of biolo'gical effectiveness or have limited applic-ability due to design, operational and maintenance problems.

However, they are presented below to afford the designer with the information necessary to select an intake which best suits the site-specific require-ments of the power plant under consideration.

VELOCITY CAP INTAKES The velocity cap was evolved from preliminary research carried out in 1956 by F.

R.

H. Jones.

It was found that fish cannot sense a vertical displacement of flow to any substantial degree.

Up to this time, water intakes were open pipes usually built up from the ocean or lake bottom with possibly a large-spaced trashrack placed over the opening.

When it was found that fish do not respond to vertical flow components, the velocity cap was designed (15) and was applied to the El Segundo Steam Electric Station.

In essence, the cap changes vertical flow components to horizontal components which allow fish to sense their movement toward the structure and escape the intake system.

Preliminary 1Consultant, Hydraulic Division, Stone 6 Webster Engineering Corporation,

2Boston, Massachusetts 02107 Senior Ecologist, Environmental Engineering Division, Stone 6 Webster 3Engineering Corporation,
Boston, Massachusetts 02107 Lead Research
Engineer, Hydraulic Structures, Alden Research Laboratory, Worcester Polytechnic Institute, Holden, Massachusetts SToNE R WeesTeR

decreases in fish entrapment averaging 80 to 90 percent were recorded at El Segundo and later at Huntington Beach using intakes which incorporated velocity caps.

Further research by Schuler and Larson (8) has theoretic-ally lowered the entrapment factor even more.

By extending the top of the cap and the sill of the intake, eddies which concentrated the flow, and thus created higher velocities in lower parts of the intake opening, were eliminated and a more uniform approach velocity was maintained.

Lower average velocities and a longer approach to the vertical intake shaft allowed fish to sense the drawing influence of the intake and avoid entrapment.

Velocity caps have since become standard features on many power plant offshore intake structures.

Although the velocity cap apparently acts to reduce fish entrapment, it has two inherent biological drawbacks.

First, experience on the Great Lakes has shown that some operating plants utilizing a cap still entrap large quantities of fish each year, sometimes numbering in the millions (9)

~

Without an additional system onshore to safely collect or divert those fish which are not excluded, all entrapped fish will ultimately die within the inake system.

Second, since the cap acts on a behavioral basis requiring an active avoidance
response, this system is ineffective in preventing the passage of nonmotile organisms, such as fish eggs and larvae.

Therefore, unless the intake is located in an area of low fish abundance at a distance from spawning areas, this design will afford little protection for the early life stages of fish.

In conclusion, while the velocity cap intake acts to reduce fish impinge-

ment, the level of reduction at a specific site may require implementation of additional fish protection measures.

Further, it is difficult to

quantify, a priori, the reductions which might be achieved, since similar designs at different sites often yield conflicting results.
Finally, a

velocity cap design will not protect the early life stages of fish, except by virtue of the fact that it may be located in a nonproductive area.

~

'IDE-SPACED LOUVERED INTAKES One possible solution to fish entrapment could be to prevent the presence of fish in the screenwell area by diverting them to a bypass within the offshore intake.

Such an intake design, as shown in Figure 1, was tested hydraulically and with live fish in a full-scale model (11)

~

This intake design, representing a self-contained

module, could be used for closed-loop cooling system or incorporated into a once-through cooling system by connecting several segment modules to an intake shaft.

Conceptually, the intake module would incorporate a wide-spaced louver array through which the cooling water would pass while directing fish to a bypass.

The louvers would be spaced 10 in. (0.25 m) apart to minimize clogging, angled at 11.5 deg to the flow in the horizontal, and leading to a bypass 2 ft (0.61 m) wide by 2.5 ft (0.76 mg) high.

A center wall would be incorporated between the louver arrays to enhance fish guidance.

The bypass flow would be induced by an offshore submerged jet pump.

The driving flow for this jet pump would be supplied from the blowdown or discharge system onshore.

STONE & WEBSTER

Prior to biological testing of this concept in a full-scale (1:1) model, hydrodynamic studies were conducted in a 1:9 scale model.

The objectives were to study the flow distribution along the louvers for various louver geometries, louver array angles, and locations of the backwall of the structure.

The 1;9 scale model is shown in Figure 2.

Nine different louver configurations were tested.

A louver configuration which has progressively longer louvers toward the downstream end (as shown in Figure 3) was selected for testing with live fish in the full-scale model.

The selection of this configuration was based on the resultant velocity gradient along the face of the louver (Figure 3), which was judged desirable for fish diversion, and on the small region of high velocity that was located at a greater distance from the leading edge of the louver than the other louver configurations.

Moving the backwall further away from the louvers resulted in a slightly improved velocity distribution along the louver face, as shown in Figure 3 (Configuration B).

This additional feature was not, however, tested in the full-scale model with fish.

The objectives of the full-scale model testing were to evaluate the effectiveness of the wide-spaced louvers in guiding fish to a bypass and to verify the 1:9 scale hydraulic model results on a larger scale.

The full-scale (1:1) model was constructed in a large basin, as shown on Figure 4.

Since the intake was symmetric around the center wall, only half of the structure was modeled.

The velocity distribution achieved along the face of the louver is shown in Figure 5.

Unfortunately, it was found that the velocities increased gradually and then suddenly decreased in the vicinity of the bypass.

This could have resulted in the poor fish guidance which was observed.

The biological testing strategy was straightforward and involved placing fish in the upstream end of the model basin and allowing them to react naturally to the established hydraulic conditions.

Test species included rainbow smelt and alewife.

Louver section entrance velocities of 2, 3, and 4 fps (0.5, 0.9, and 1.2 m/sec) and bypass velocities ranging from 2.25 to 4.8 fps (0.69 to 1.5 m/sec) were tested.

Water temperatures ranged from 39 to 85 F (3.9 to 29.4 C).

Tests were conducted in three distinct periods between the fall of 1974 and the fall of 1975:

fall of 1974 (eight alewife tests);

spring and summer 1975 (23 alewife tests, 4 smelt tests);

and fall 1975 (10 alewife tests).

The results of the wide-spaced louver studies were statistically analyzed.

The number of smelt tests was too small to include in the analysis;

however, the mean diversion efficiency for 4 tests was 22 percent, with a

95 percent confidence interval of +7.9 percent.

The mean diversion efficiency for alewives under all conditions tested was 48 percent with a

95 percent confidence interval of +14.5 percent.

A predictive least-squares model was developed from the data and was applied to actual conditions at a power plant located on Lake Ontario.

Because of the large variability in the laboratory test results, it was predicted that a wide-spaced louver system installed in the offshore intake at this plant could be from 27.8 to 86.3 percent effective in diverting fish to a bypass.

Seoul & Weasvaa

On the basis of results obtained during the offshore intake diversion system study, it did not appear that such a concept, as presently designed, offered a practical solution to the problem of fish entrapment at offshore intakes due to the wide variability in the data and lack of confidence in the predicted efficiencies which might result.

The installation of wide-spaced louvers at the offshore intake would result in a large and costly structure.

Further, the operation of such a system would necessi-tate the withdrawal of approximately 20 percent additional flow, as required for the bypass and jet pump.

Assuming that flow is positively related to entrapment, this could result in additional entrapment, thus reducing the effectiveness of the system relative to the total number of fish saved.

For the specific power plant under consideration during these studies, this concept was eliminated from consideration.

Instead, a highly effective screenwell fish diversion and transportation system will be used to minimize impingement at the plant (12).

WEDGE"WIRE SCREEN INTAKES Wedge-wire screens are in use today in many applications.

The recent concern for the protection of small organisms at power plant intakes has resulted in biological and engineering evaluations of these screens for such a purpose (1, 2, 14).

Biological research on cyclindrical wedge-wire screens indicates that they could be relatively effective in prevent-ing the entrainment of fish eggs and most larvae at power plants provided that the screen slot size is small (approximately 0.5 to 1 mm), that the through-slot velocity is low (approximately 0.5 fps; 0.15 m/sec),

and that a relatively high velocity cross flow exists to carry organisms around and away from the screen (1).

In laboratory studies, Hanson et al (4) found that entrainment of fish eggs (striped bass),

ranging in diameter from 1.8 to 3.2 mm, could be eliminated with a wedge-wire screen incorporating 0.5 mm slot openings.

However, striped bass larvae, measuring 5.2 to 9.2 mm (4 to 20 days old), were generally entrained through a

1 mm slot at a level exceeding 75 percent within one minute of release in the test flume.

Larval tests were conducted in a static mode with no cross flow passing the screen.

It was concluded that, since positive rheotaxis was observed among these early larvae, a cross flow would act to reduce entrainment to some extent.

However, where current velocities are very low (less than 0.5 fps; 0.15 m/sec), it could be expected that the early larvae of many species would be susceptible to entrainment.

Further, with 0.5 to 1.0 mm slot openings, eggs of some species would also be subject to entrainment depending on egg diameters.

0'espite encouraging biological results with wedge-wire screens under experimental conditions, certain design, operational and maintenance problems exists which may limit the applicability of this screening concept at some power plant sites.

General engineering criteria that

should be considered in evaluating wedge-wire screens for possible power plant application are given below:

1.

Clogging -'o minimize clogging, the screen should be located in an ambient current of at least 1 fps (30 cm/sec) to establish suitable hydraulic conditions for self-cleaning and the dispersal of backflushed debris.

An adequate backwash system is also required for periodic cleaning of the screen.

Compressed air or water can be utilized.

2.

Velocity distribution - A uniform velocity distribution along the screen face is required to minimize the probability of entrapment of motile organisms and to minimize the need for debris backflushing (2).

3.

Navigation - The screens must be located such that they do not interfere with navigation.

4.

Large debris - In many areas, large debris (trees, etc) and pack ice could damage or block the screens.

1 5.

Frazil ice - In northern latitudes, provisions for the preven-tion of frazil ice formation on the screens must be considered.

6.

Siltation - Allowance should be provided below the screens for silt accumulation to avoid blockage of the water flow.

7.

Biofouling - Screen materials should be used which will minimize the degree of biofouling and its resulting effect on hydraulic efficiency.

8.

Access - The screens should be readily accessible for mainten-ance and performance monitoring.

To date, proven methods for preventing frazil ice formation have not been developed.

Limited field testing has been conducted to develop methods for backflushing the screens with water or compressed air.

Testing of various materials is also ongoing to determine their biofouling characteristics (7).

Since the above-mentioned clogging and icing problems have not been

resolved, wedge-wire screens are presently more suitable for closed-'oop makeup flow intakes than for once<<through systems.

Wedge-wire screen and perforated-pipe submerged intakes (which are similar in concept to the wedge-wire screens) are operating satisfactorily on a

number of make-up systems on the Ohio, Mississippi, Susquehanna, and Big Sandy Rivers.

A conceptual wedge-wire screen intake arrangement for a once-through cooling system on the Great Lakes (800 cfs; 22.7 ms/sec) that incorporates many back-up systems for backwashing and deicing is shown on Figure 6.

STONE & WessYCR

The screens would be placed parallel to the predominant current direction and would be sized for a through-slot velocity of 0.5 fps (0.15 m/sec).

The system would incorporate a warm water backflushing capability to melt ice which could accumulate around the screens and a warm water diffuser to minimize frazil ice formation on the screen.

Compressed air would also be provided within the screens to air-burst debris away from the screens.

An emergency onshore intake would also be provided to supply water in case of severe clogging of the wedge-wire screens.

Hydraulic model studies would be required to optimize the header pipe design to achieve equal flow withdrawal from the screens.

Also, in situ long-term (more than 1 yr), pumping tests would be required to determine the effect of frazil ice formation, clogging characteristics, potential damage by pack ice, and biofouling effects on the hydraulic efficiency of the screen.

BEHAVIORAL BARRIERS Extensive research has been conducted to determine the effectiveness of behavioral barriers in guiding fish or preventing their upstream or downstream passage.

Behavioral devices which have been evaluated for possible power plant application include air bubble curtains, electrical barriers, lights, sound, hanging chains, visual keys, water jet curtains, and velocity barriers.

In general, behavioral barriers have not proven effective in deterring the passage of fish, either in laboratory studies and in actual applcation.

To date, sound, lights, and air bubble curtains are the only devices which have been evaluated at actual power plant intakes.

The U.S. Environmental Protection Agency (13) states

that, "as far. as could be determined, there are no existing intakes where a light barrier is functioning successfully.

Light also has the adverse effect of attracting fish under certain circumstances and has resulted in a complete shutdown of plants."

Studies with sound-generating devices have yielded similar results.

The feasibility of using sound to guide or deter fish passage is complicated by species-specificity.

For example, not all fish possess the ability to perceive sound or localize acoustical sources.

Many fish species possess a limited ability to perceive or distinguish sounds (poor auditory capacity).

These fishes rely primarily on their lateral line system to distinguish near-field disturbances (5).

Thus, sound may attract some species, repel
some, or have no effect at all.

In addition, some fish have demonstrated rapid habituation to sound, negating the effectiveness of continuously operated underwater sound generation.

For these

reasons, sound has not been shown to be an effective means of preventing fish entrapment at power plant intakes.

~

)

Air bubble curtains have been used at many locations in an attempt to divert-fish.

The success of this device has been variable and appears to be affected by such factors as species, temperature, light intensity, water velocity, and orientation within a water body.

Power plant air bubble curtain applications have not been highly successful.

For example, an air curtain was not effective at the Indian Point Generating Station SvoNa & WaosveR

on the Hudson River (13).

After several years of operation, the air curtain was removed.

Similarly, at the Commonwealth Edison Company Quad-Cities Generating Station, located on the Mississippi River, an air bubble curtain was not found to be effective in reducing the entry of fish into the intake canal (6).

At the Prairie Island Nuclear Generat-ing Plant on the Mississippi River, small decreases in impingement were achieved for several species when an air curtain was placed across the intake canal.

However, the number of individuals of other species entering the canal actually increased (3).

The air curtain was therefore removed.

At Detroit Edison's Monroe Power Plant, an air bubble curtain was installed across the main intake canal in 1972.

On the bais of daily fish counts made with the system either on or off, it was concluded that the curtain was ineffective in preventing fish from entering the canal.

Considering these failures, it is not believed that an air bubble curtain represents a highly effective means for reducing fish losses at intakes.

This conclusion is further substantiated by laboratory studies that were conducted with behavioral barriers specifically for application to

offshore, submerged intake structures.

In 1976, a model facility was constructed to test the effectiveness of three behavioral barriers (air

bubbles, hanging chain, and water jets) in deterring the passage of alewives and smelt into an offshore, velocity cap intake (10).

Tests 0

were conducted over a range of water temperatures from 44 to 79 F (7 to 26 C).

The model (Figure 7) consisted of two identical intake segments located in a large test basin.

The segments were separated by a screen thus allowing two tests to be run simultaneously.

The air bubble test device was constructed of 2 in.

(5 cm) ID pipe with 1/32 in. (0.8 mm) holes spaced on 2 in.

(5 cm) centers over a distance of about 5 ft (1.5 m).

The diffuser was located 3.5 ft (1.0 m) in front of the 2 ft (0.6 m) high,

5. ft (1.5 m) wide intake opening to avoid air entrainment.

The hanging chain test device consisted of an array of 3/16 in. (4.8 mm) chain lengths each 3 ft (1.5 m) long and spaced on 2 in.

(5 cm) centers.

The actual clear opening between chain lengths was 1.25 in. (3.2 cm).

The water jet curtain test device consisted of 3/4 in. (1.9 cm) diameter vertical tubes spaced 1 ft (0.3 m) apart.

Each tube had a line of 1/32 in. (0.8 mm) diameter nozzles spaced on 1/2 in. (1.25 cm) centers.

Each barrier was tested in each segment at intake entrance velocities of 0.5, 1.2, and 2.0 fps (0.15, 0.37, and 0.6 m/sec).

Control tests were also conducted in which no device was installed.

Smelt tests were conducted with 200 fish per test, with a total of 40 tests.

Alewives were tested in individual groups of 400,

600, 800, or 1,000 fish (48 tests).

Test results showed that the three behavioral barriers significantly reduced the number of fish entrained into the intakes relative to the control; however, the barriers were not in themselves significantly different in efficiency.

The predicted mean number of fish entrained per test was 151 for controls, 66 for the air bubble curtain, 77 for the hanging chains, and 41 for the water jet curtain.

Thus, although the Svove & WcesvaR

devices reduced entrainment, they would not be expected to eliminate fish losses completely.

When considering the use of behavioral barriers at an intake structure, the effect of such devices on intake operation should be carefully evaluated.

For example, an air bubble curtain at an offshore intake should be placed away from the face of the intake to avoid.air entrapment into the tunnels which would result in air blow-backs.

Similarly, in designing a water jet curtain, as shown in Figure 8, the vertical bars should be placed about 1 ft (30 cm) apart in order to prevent potential blocking of the intake due to debris accumulation.

Warm water could be used to operate the water jet curtain to reduce the potential of frazil ice formation.

Filtration of the supply water would also be required to minimize clogging of the small jet nozzle openings.

Operational problems of hanging chains due to wave action, debris, and icing should be consid-ered.

The chains should be placed far enough from the intake face (as shown in Figure 9) to eliminate the potential for entanglement and to allow cooling water to flow through the open area between the chains and the intake should the chains clog with debris or ice.

In conclusion, the decision to install a behavioral barrier at a power plant intake should be made on the basis of cost-effectiveness.

Further, in selecting a specific barrier for application, consideration must be given to the installation, maintenance and operational criteria that exist at a specific site.

In general, it does not appear that behavioral barriers alone offer a high potential for reducing fish entrapment at power plant intakes.

INFILTRATIONINTAKES There are presently two types of infiltration intakes:

the radial well and the artificial filter bed.

Since these intakes function essentially in the same fashion as a natural aquifer, resulting in very low velocities, little or no biological impact is expected to occur as a result of operation.

However, experience indicates that the maximum capacity of a single radial well is limited to about 10,000 to 20,000 gpm (0.6 to 1.25 m /sec).

For a once"through application, given a suitable aquifer, about 20 to 30 miles (30 to 45 km) of shoreline could be required to supply 500,000 to 1,000,000 gpm (30 to 60 m /sec) of cooling water.

This consideration and the associated costs of pumps and a large piping network would rule out this principal as a practical solution for once-through application.

CONCLUSION Infiltration and wedge-wire screen intakes offer an effective and practical solution for fish and larval protection for closed-loop cooling systems when adequate hydraulic conditions exist.

However, for once-through cooling systems, further developmental work is required for wedge-wire screen intakes

~

Over the range of hydraulic and environmental parameters evaluated to date, behavioral barriers appear to offer only limited

efficiency in deterring fish from entering an intake structure.

The wide-spaced louver concept will require further development if it is to become a practical and effective method of bypassing fish within offshore, velocity cap intakes.

SvoNE & WeesvER

REFERENCES

Bason, W.H., "Practicality of Profile Wire Screen in Reducing Entrain-

""'"e

'or Power Plant ~Coolie Water Intakes, Argonne National Laboratory, ANL/ES-66, August 19 78, pp 1 95-233.

of the W~orksho on Larval Exclusion ~gstems for Power Plant ~Coolie Water Intakes, Argonne National Laboratory, ANL/ES-66, August 1978, pp 149-157.

Grotbeck, L.May "Evaluation of an Air Curtain as a Fish Deterrent Device at the Prairie Island Nuclear Generating Plant Cooling Water Intake," In: Northern States
Power, "1975 Annual Report, Environmental Monitoring and Ecological Studies Program, Prairie Island Nuclear Generating Plant, Vol. II," 1975, pp 2.8-1 to 2.8-25.
Hanson, B.N., Bason, W.Hag Beitzp B.E.,

and Charles, K.E., "A Intake Screen which Substantially Reduces the Entrainment and December

1977, pp 393-407.

Practical Impinge-National Incog Latvaitis, B., Bernhard, H.F.,

and McDonald, D.B., "Impingement Studies Ines

, February

1976, pp 269-289.

Harris, G.G.,

and Van Bergeijk, W.A., "Evidence that the Lateral-line Organ Responds to Near-field Displacement of Sound Sources in Water,"

Journal of the Acoustical ~Societ of America, Vol. 34,

1962, pp 1831-1841..

0'ichards, R.T., "Improved Cylindrical Pipe Intakes," presented at October

1979, ASCE National Convention, held at Atlanta, Georgia.

Schuler, V.J.,

and Larson, L.E., "Improved Fish Protection at Intake Systems,"

ASCE, Journal of the Environmetnal Engineering Division, Vol ~

101, No. EE6, December
1975, pp 897-910.
Sharma, R.K., and Freeman, R.F., III, "Survey of Fish Impingement at Power Plants in the United States, Volume I, the Great Lakes,"

Argonne National Laboratory, ANL/ES-56, March 1977.

Stone 6 Webster Engineering Corporation, "Studies to Alleviate Fish Entrapment at Power Plant Cooling Water Intakes - Final Report" Repor't Prepared by Niagara Mohawk Power Corporation and Rochester Gas 6 Electric Corporation, November 1976.

10

11.

Stone 6 Webster Engineering Corporation, "Studies to Alleviate Potential 7ish Entrapment Problems - Final Report," Report Prepared for Niagara Mohawk Power Corporation, May 1977

'2.

Taft, E.P.,

and Mussalli, Y.G., "Fish Diversion and Transportation System for Power Plant Applications," Fisheries, A Bulletin of the American Fisheries Society, Vol. 3,, No. 3, May-June

1978, pp 2-5.

13'PS.

Environmental Protection Agency, "Development Document for Best Technology Available for the Location, Design, Construction, and Capacity of Cooling Water Intake Structures for Minimizing Adverse Environmental Impacts,"

EPA 440/1-76/015-a, U.ST Environmental Protec-tion Agency, Washington, D ~ C ~

, April 1976

'4

'igander, S

~, "Current TVA Work on the Fluid Mechanics of Screens with Very Small Openings for the Exclusion of Larvae at Power Plant

~g stems for Power Plant ~Coolie Water Intakes, Argonne National Labora-tory, ANL/ES-66, August 1978, pp 91-105

'5.

Weight, R.H.,

"Ocean Cooling Water Systems for 800 MW Power Stations,"

ASCE, Journal of Power Division, Vol. 84, No. P06, December

1958, p 1888.

STONE & WEBSTER

VERTICAL SHAFT 4

~

a

~ ~

a 0 04:

4 0

~

~

V "- 0.5 FPS 0 I-160 CFS 0

~

0 4

4

~

~

~ 4 4.

'a o ~

404

~

~

0

~ 4

~

~ ba 0 ~

4 000

~

0 0 ~ 004 4

~

~

~ 4 ~ ~

4

~

Oo 00

~

0 a

~

0

~

0 A

0 oo Py

~

~3 FPS T 50 1 1.5o 5

2' CENTERWALL 5'2'ET PUMP 4 p 0

PLAN 0

0

~

0

~.00

~

4

~ 0

~

~

goo 0

4 0 Oo Oo o 0o BAR o ~ 4 '

~ o 0

~ ~

0 ~ 0 io

'ACKS 04 ~

4 00 04 0 0

~

0

~ O4

~ 4 4 ~

o 4

~

~

40p0 0 p 0'. ~

O ~

~

0

~

0

~ o 15'0'ISH BYPASS

PIPE, 1.5' 0 ~

q

~

0

~ Dg Dy ~

0 0 O. ~ ~ ~

~ 000,00 5I

~

~

0 0

~

4 ~

2.5' 00 OD SOP

~ 0 4

00 0

0

~

~ 0 00

~ 0

~

0

~

, ~ o

~

aoob0 0

0

~ 0 4 0 0000 DRIVING

FLOW, 1.5'ECTION A-A FIGURE 1

INTAKE STRUCTURE SEGMENT MODULE, CONCEPTUAL DESIGN SToNe & WessTeR

STONE & WKBSTKR

Y t

"k I Jr P 2++

  • ~

kk ~Jgt t M$'<"

k j+L>

f 1

t<

FIGURE 2 1:9 SCALE MODEL OF SEGMENT MODULE STONe & WEBSTER

STONE 6 WEBSTER

0 VELOCITY AT CENTER WALL MID-DEPTH 8

CONFIGURATION A CONFIGURATION 8 DISTANCE CW 11.5o POINT OF MEASUREMENT (TYP.)

CONFIGURATION

&caw ~a~~

aa a~ ~

ee ~ ~ms ca~

~a~

CONFIGURATION B 3.0 CONFIGURATION A 2.0 V

V 1.0 CONFIGURATION B NOTE 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 LOUVER NUMBER 0BYPASS 0 1 5 THROAT FIGURE 3 VELOCITY DISTRIBUTION, 1:9 SECTOR MODULE SvoNe & WeosveR

FLOW STRAIGHTENER TRASH BARS SCREEN

~ ~ ~

~

~

SCREEN FLOW THROAT LOUVERS

/1II Ig I

BYPASS PUMP BAY LOUVER FISH COLLECTION AREA BYPASS FISH COLLECTION AREA FIGURE 4 1:1 SCALE INTAKE SEGMENT MODULE Svove & WessveR

STONE & WEBSTER

2.0 APPROACH VELOCITY =

3.17 FPS BYPASS VELOCITY ~

4.83 FPS 1.5 1.0 R>>ARS - O.ta OTHROAT 0.5 0

1 2

3 4

5 6

7 8

9 10 11 12 13 14 15 LOUVER NUMBER OZ KI-z 2.0 APPROACH VELOCITY =

1.99 FPS BYPASS VELOCITY -"

2.73 FPS V

1.5 OBYPRSS

~ 0 17 THROAT 0.5 0

1 2

3 4

5 6

7 8

9 10 11 12 13 14 15 LOUVER NUMBER Q

ALONG CENTERWALL ALONG LOUVERS NOTE:

1) VELOCITY AT MID DEPTH LOUVER 15 2

3 4

5 6

TRANSECT NUMBER

+

+

+

+

+

+

+

FIGURE 5 NORMALIZED VELOCITY GRADIENT, 'I:1 INTAKE SEGMENT MODULE STONE & WEBSTER

STONE & WEBSTER

~

SCREEN ITYP)

P 6'5 REC IRCUALTICN PIPE 0'S INTAKE I )PE~

('Af ~ )

PLAN VIEW 0

10 20 30 SCALE FEET

. WEDGE WIRE SCREEN BASKET ITYP.)

WARM WATER DIFFUSER RECIRCULATION HEADER (TYP.)

~ INTAKE HEADER PIPE SECTION A-A FIGURE 6 OFFSHORE WEDGE WIRE SCREEN INTAKE STONE & WEaSTER

0'

FLOW STRAIGHTENER 27.5' I

~

I I

+s Q I

I If~ SCREENS yl I

I I

FLOW I

I I

I INTAKE STRUCTURES I

I PLAN FI.PW CONTROL AND FISH COLLECTION AREA

~ ~ '

~

~ ~

~ e

~

~ ~

~

~

~

~

PERFORATED BASKET~ ADJUSTABLE HINGE GATE FLOW CONTROL 5 FISH COLLECTION AREA I

I I

PITOT TUBE (FLOW METER 20" DIA.

~,

FALSE FLOOR 10'ECTION A-A FLOW

~

~

~

~

~

~

1

~

~

i ~

INTAKE STRUCTURES10'4" 12"

(

g'I

~

FIGURE 7 MODEL BASIN USED FOR TESTING BEHAVIORAL BARRIERS STONE & WEBSTER

)

Zy r 1/

/

']

/

~..

(0lg FLOW TO o

ooo oooo WATER JET BAR RACK tTYP.)

JET CURTAIN 12" DISTRIBUTION HEADER BAR RACK 5" PIPE 15" CC WATER JET BAR RACK FIGURE 8 OFFSHORE INTAKE WITH WATER JET CURTAIN STONE & WEBSTER

STONe & WEBSTER

SUPPORT FOR CHAIN BARRIER, PLAN ee 0

663 oe Oos' 40 ~ rO

~ 0

~ 4 ~

~

~ ~

~

00 0

040 04 e

0 4

04

~ 063ooe

~ 0 4 ~ 0 4 4

~ '

0

~

63

~

e 4

~

0

~

4 o

~

0 o

FLOW Itl III 3/I6" CHAINS 2" CC

)I)

I

~ll ll.~h~x LFrhiyiv,',.=.. I-'i/

/.)r ~rll,~~"~q~~<zgi4, II-/Il

-.//-~rll,ih" le>g~jy~<ilg<, X> ~ )>

I "zhll4y~ggll ~/g7 "yw )y

< II,+<pl'L II.O'IJ~'O~)))// r'r~~'III

=,IIS~ii'II'0 ~~~)/~;,~xi~<6" SECTION A-A FIGURE 9 OFFSHORE INTAKE WITH HANGING CHAIN BARRIER STONe & WaeSTaR

Svova & WeosveR

~