ML17046A427
Text
- 1.
- 2.
- 3.
Rod.Stop Nuclear Overpower High AT Low Power TABLE 7.7-l ROD STOPS Actuation Signal 1/4 high power range nuclear flux or 1/2 high intermediate range nuclear flux 2/4 overpower AT or 2/4 overtetnperature AT Low turbine steamline inlet pressure Rod Motion Automatic and Manual Withdrawal Automatic and Manual Withdrawal Automatic Withdrawal Actuation of rod stop No. 2 above is accompanied by the initiation of turbine load reference reduction.
1 of 1 SGS-UFSAR Revision 21 December 6, 2004
TABLE 7. 7-2 OVERHEAD ANNUNCIATOR GROUPINGS The alarm groupings are as follows:
DISPLAY A ANNUNCIATOR TEST/TROUBLE ALARMS MISCELLANEOUS FIRE PROTECTION DISPLAY B MISCELLANEOUS WATER SYSTEMS VITAL DC VITAL INVERTERS MISCELLANEOUS ELECTRICAL SERVICE WATER DISPLAY C WASTE DISPOSAL LEAK DETECTION AUXILIARY COOLING CONTAINMENT DISPLAY D ECCS REACTOR COOLANT SYSTEM DISPLAY E CHEMICAL AND VOLUME CONTROL SYSTEM PRESSURIZER NUCLEAR INSTRUMENTATION SYSTEM ROO CONTROL DISPLAY F REACTOR TRIP SAFETY INJECTION TURBINE TRIP DISPLAY G MAIN STEAM TURBINE AND CONDENSER FEEDWATER TURBINE AUXILIARY COOLING SGS-UFSAR 1 of 2 Revision 17 october 16, 1998
DISPLAY H MAIN GENERATOR 25KV TRANSFORMERS DISPLAY J VITAL AC DIESEL GENERATORS GROUP BUSES DISPLAY K CIRCULATING WATER 13KV SYSTEM SOOKV SYSTEM SGS-UFSAR TABLE 7.7-2 (Cont.)
2 of 2 Revision 17 October 16, 1998
TABLE 7.7-3 SEISMIC MONITORING INSTRUMENTATION INSTRUMENTS AND SENSOR LOCATIONS
- 1.
Triaxial Time-History Accelographs
- a.
Reactor containment, Elev. 81'
- b.
Reactor Containment, Elev. 130'
- c.
Auxiliary Building, Elev. 122'
- 2.
Triaxial Peak Accelographs
- a.
Reactor Containment, Elev. 86'5"
- b.
Reactor Containment, Elev. 136'3"
- c.
Auxiliary Building, Elev. 122'5"
- d.
Fuel Handling Building, Elev. 130' 1 of 1 SGS-UFSAR MEASUREMENT RANGE 0 -
0 -
0 -
0 -
0 -
0 -
0 -
lg lg lg lg lg lg 1g Revision 14 December 29, 1995
TABLE 7.7-4 SEISMIC MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS INSTRUMENTS AND SENSOR LOCATIONS
- 1.
- a.
- b.
- c.
- 2.
- a.
- b.
- c.
- d.
M
=
SA R
=
NA Triaxial Time-History Accelographs Reactor containment, Elev. 81' Reactor Containment, Elev. 130' Auxiliary Building, Elev. 122' Triaxial Peak Accelographs Reactor Containment, Elev. 86'5" Reactor Containment, Elev. 136'3" Auxiliary Building, Elev. 122'5" Fuel Handling Building, Elev. 130' every 31 days every 6 months every 18 months not applicable Except seismic trigger 1 of 1 SGS-UFSAR CHANNEL CHECK M*
M*
M*
NA NA NA NA CHANNEL CHANNEL FUNCTIONAL CALIBRATION TEST R
R R
R R
R R
SA SA SA NA NA NA NA Revision 14 December 29, 1995
TABLE 7.7-5 METEOROLOGICAL MONITORING INSTRUMENTATION INSTRUMENT
- 1.
Wind Speed
- a.
Meteorological Tower
- b.
Meteorological Tower
- c.
Meteorological Tower
- 2.
Wind Direction
- a.
Meteorological Tower
- b.
Meteorological Tower
- c.
Meteorological Tower
- 3.
Air Temperature - Delta T
- a.
Meteorological Tower
- b.
Meteorological Tower SGS-UFSAR LOCATION Nominal Elev.
Nominal Elev.
Nominal Elev.
Nominal Elev.
Nominal Elev.
Nominal Elev.
Nominal Elev.
Nominal Elev.
1 Of 1 33' 150' 300' 33' 150' 300' 150' - 33' 300' - 33' Revision 14 December 29, 1995
TABLE 7.7-6 METEOROLOGICAL MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS INSTRUMENT
- 1.
Wind Speed
- a.
Nominal Elev. 33'
- b.
Nominal Elev. 150'
- c.
Nominal Elev. 300'
- 2.
Wind Direction
- a.
Nominal Elev. 33'
- b.
Nominal Elev. 150'
- c.
Nominal Elev. 300'
\\
- 3.
Air Temperature -
Delta T
- a.
- b.
D =
SA=
Nominal Elev.
Nominal Elev.
daily every 6 months SGS-UFSAR 150' - 33' 300' - 33' CHANNEL CHECK D
D D
D D
D D
D 1 of 1 CHANNEL CALIBRATION SA SA SA SA SA SA SA SA Revision 14 December 29, 1995