Designation 1. ACCUM 2. RHR 3. l?SL SGS-UFSAR TABLE 3.6-1 POSTULATED REACTOR COOLANT SYSTEM PIPE RUPTURES 1 DEC( ) in accumulator line at RCL nozzle DEC in RHR line at RCL nozzle DEC in pressurizer surge line at RCL nozzle double-ended circumferential rupture 1 of 1 Revision 22 May 5, 2006 I foint 121 1 2 3 4 s 13 14 21 22 23 27 28 32 39 40 41 45 (Anchor) TABLE 3.6-2 MAIN STEAM PIPE STRESS

SUMMARY

No. 13 Main Steam Line (1) 0.8(1.8 Sh + Sa) St£@§!,3J AlJ,owabJ,e 6657 46200 14604 46200 13403 46200 15244 46200 17436 46200 14826 46200 14626 46200 15017 46200 13807 46200 11035 46200 11678 46200 18513 46200 11683 46200 12866 46200 12419 46200 9295 46200 3384 46200 (3) RATIO 0.14 0.32 0.29 0.33 0.38 0.32 0.32 0.33 0.30 0.24 0.25 0.40 0.25 0.28 0.27 0.20 0.07 Notes: (1) Stresses tabulated for Nos. 11, 12 and 14 steam lines at geometrically similar locations are of similar magnitude. (2) Stress point locations are shown on Figure 3.6-10. (3) Stresses and allowables from calculation 1SC-110. Minor changes in pipe stresses due to revisions of associated pipe stress calculations will be documented within 1SC-110 and will not require update of this OFSAR table. SGS-OFSAR 1 of 1 Revision 16 January 31, 1998

  • Point (2) 1 2 3 5 6 11 13 15 21 23 26
  • Notes:

SUMMARY

No. 12 Feedwater Line (1) Stress Stress, psi (3) s a + sh (Sa + Sh) 1,187 43,750 0.027 2,567 43,750 0.058 5,951 43,750 0.136 6,201 43,750 0.141 6,365 43,750 0.145 6,669 43,750 0.152 8,199 43,750 0.187 7,938 43,750 0.181 7,857 43,750 0.179 8,140 43,750 0.186 6,220 43,750 0.142 (1) Stresses tabulated for Nos. 11, 12, and 14 steam lines at geometrically similar locations are of similar magnitude. (2) Stress point locations are shown on Figure 3.6-11. (3) Stresses tabulated longitudinal pressure, OBE (1/2 SSE) . 1 of 1 are the swnmation of thermal, dead weight, and Revision 6 February 15, 1987