IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.4 Table: 14.4.6-18 Page:
1 of 4 UNIT 2 EFFECTS OF PRESSURES AND CIRCUMFERENTIAL BREAK IMPINGEMENT LOADS ON WALLS AND SLABS (1) PANELS AT MAIN STEAM LINES ENCLOSURE EAST OF CONTAINMENT Panel Identification Governing Pipe Break Peak Applied Impingement Force (Kips)
Peak Applied Pressure (Psi)
Required Ductility Factor Allowable Ductility Factor Adequacy of Panel Remarks E-SL2 4F (MSB) 0 12.0 2.33 3.0 O.K.
E-SL3 4F (MSB) 0 12.0 1.00 3.0 O.K.
W-WN1 4G (MSB) 0 12.0 1.42 3.00 O.K.
Assuming 4G has same pressure build up as 4F E-WN2 4F (MSB) 0 12.0 1.00 3.00 O.K.
E-WN1 1C (MSB) 0 12.0 1.42 2.00 O.K.
Assuming 1C has same pressure build up as 1F E-WS2 1F (MSB) 0 12.0 1.00 3.00 O.K.
E-W1 1F or 4F (MSB) 0 12.0 2.13 3.00 O.K.
E-W2 1F or 4F (MSB) 0 12.0 1.00 3.00 O.K.
E-W3 1F or 4F (MSB) 0 12.0 1.51 3.00 O.K.
E-W4 1F or 4F 0
12.0 1.00 3.00 O.K.
Assuming central portion of panel is allowed to fail, but the larger side portions are adequate
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.4 Table: 14.4.6-18 Page:
2 of 4 UNIT 2 EFFECTS OF PRESSURES AND CIRCUMFERENTIAL BREAK IMPINGEMENT LOADS ON WALLS AND SLABS (2) PANELS AT MAIN STEAM LINES ENCLOSURE WEST OF CONTAINMENT Panel Identification Governing Pipe Break Peak Applied Impingement Force (Kips)
Peak Applied Pressure (Psi)
Required Ductility Factor Allowable Ductility Factor Adequacy of Panel Remarks W-SL1 2E or 3E (MSB) 0 11.7 60.44 10.0 N.G Slab modified and determined to be acceptable (see 14.4.9.1)
W-SL2 2E or 3E (MSB) 0 6.2 1.00 3.00 O.K.
W-WN1 3D (MSB) 0 11.9 2.56 10.00 O.K.
Assuming 3D has same pressure build up as 3E W-WN2 2E or 3E (MSB) 0 6.2 1.00 3.00 O.K.
W-WS1 2E (MSB) 0 11.9 1.00 10.00 O.K.
W-WS2 2D (MSB) 0 11.9 1.00 10.00 O.K.
Assuming 2D has same pressure build up as 2E W-WS3 2E (MSB) 0
- 11. 7 1.00 10.00 O.K.
W-WS4 Not affected by any pipe break within the west enclosure W-WS5 2E or 3E (MSB) 0 6.2 1.00 3.00 O.K.
W-WS6 2E or 3E (MSB) 0 6.2 1.00 3.00 O.K.
W-W1 2E or 3E (MSB) 0 6.2 1.00 10.0 O.K.
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.4 Table: 14.4.6-18 Page:
3 of 4 UNIT 2 EFFECTS OF PRESSURES AND CIRCUMFERENTIAL BREAK IMPINGEMENT LOADS ON WALLS AND SLABS (2) PANELS AT MAIN STEAM LINES ENCLOSURE WEST OF CONTAINMENT Panel Identification Governing Pipe Break Peak Applied Impingement Force (Kips)
Peak Applied Pressure (Psi)
Required Ductility Factor Allowable Ductility Factor Adequacy of Panel Remarks W-W2 2E or 3E (MSB) 0 6.2 1.00 3.00 O.K.
W-W3 2E or 3F (MSB) 0 11.9 1.00 10.00 O.K.
W-W4 2E or 3E (MSB) 0 11.9 1.00 3.00 O.K.
W-W5 2E or 3E (MSB) 0 11.9 1.00 10.00 O.K.
W-W6 2E or 3E (MSB) 0 11.9 1.00 10.00 O.K.
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.4 Table: 14.4.6-18 Page:
4 of 4 UNIT 2 EFFECTS OF PRESSURES AND CIRCUMFERENTIAL BREAK IMPINGEMENT LOADS ON WALLS AND SLABS (3) AUXILIARY BUILDING PANELS ADJACENT TO MAIN STEAM LINES ACCESSWAY Panel Identification Governing Pipe Break Peak Applied Impingement Force (Kips)
Peak Applied Pressure (Psi)
Required Ductility Factor Allowable Ductility Factor Adequacy of Panel Remarks W-SL3 F8 (FWB) 355 5.8 1.00 3.00 O.K.
W-SL4 F8 (FWB) 0 5.8 1.00 3.00 O.K.
W-SL5 F8 (FWB) 0 5.3 1.00 3.00 O.K.
W-WN3 F8 (FWB) 0 5.8 1.00 3.00 O.K.
W-WN4 F8 (FWB) 0 1.0 1.00 3.00 O.K.
W-WS7 F8 (FWB) 0 5.8 1.17 10.00 O.K.
W-WS8 F8 (FWB) 0 5.8 1.05 10.00 O.K.
W-WS9 F8 (FWB) 0 5.8 1.00 3.00 O.K.
W-W7 F8 (FWB) 0 5.8 1.00 3.00 O.K.
W-W8 F8 (FWB) 0 1.0 1.00 10.00 O.K.
W-W9 F8 (FWB) 0 1.0 1.00 10.00 O.K.
W-W9A F8 (FWB) 0 1.0 1.00 10.00 O.K.
W-W10 F10 (FWB) 355 5.1 1.00 10.00 O.K.
Assuming F10 has same pressure build up as F8 (3) MSB = main steam line break FWB = feedwater line break N.G. = no good