IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.6 Table: 14.4.6-15 Page:
1 of 1 PRESSURE CAPABILITY OF WALLS & SLABS AROUND MAIN STEAM LINE ENCLOSURE EAST OF CONTAINMENT
- 1.
MATERIAL PROPERTIES
- a. Concrete fc' = 3500 psi;
- b. Reinforcing steel fy= 40000 psi
- 2.
PRESSURE CAPABILITIES TABULATED
- a. Are ultimate values under static conditions;
- b. Do not include any other loading condition Panel ID Thickness (in.)
Pressure Capability (psi)
Remarks E-SL2 12 11.6 Punching Shear Around Col. Governs E-SL3 30 72.5 1 E-WN1 24 16.1 (1)
E-WN2 24 80.0 (1)
E-WS1 24 16.0 (1)
E-WS2 24 83.2 (1)
E-W1 24 13.4 (1)
E-W2 24 78.0 (1)
E-W3 24 11.6 (1)
E-W3 & E-W4, both curved are solved using planar projections E-W4 24 4.5 Critical Value of 4.5 PSI. Results from 1 way action of lightly reinforced portion of panel between the two large openings. The side portions of the panel have capability of 86.1 (1)
See Figure 14.4.6-3 for wall and slab identification.
1 Indicates diagonal tension failure governs.
UNIT 2