IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

18.1 Table: 14.1.8-1 Page:

1 of 1 UNIT 2 TIME SEQUENCE OF EVENTS (FULL VANTAGE 5 CORE)

Accident Event Time (sec)

Loss of External Electric Load or Turbine Trip

1. With pressurizer control (min fdbk)

Loss of electrical load 0.0 Overtemperature T reactor trip point reached 12.2 Peak pressurizer pressure occurs 14.2 Rods begin to drop 12.5 Minimum DNBR occurs 16.0

2. With pressurizer control (max fdbk)

Loss of electrical load 0.0 Peak pressurizer pressure occurs 8.5 Low-low steam generator water level reactor trip point reached 53.7 Rods begin to drop 55.7 Minimum DNBR occurs 1

3. Without pressurizer control (min fdbk)

Loss of electrical load 0.0 High pressurizer pressure reactor trip point reached 7.3 Peak pressurizer pressure occurs 9.3 Rods begin to drop 9.0 Minimum DNBR occurs (1)

4. Without pressurizer control (max fdbk)

Loss of electrical load 0.0 High pressurizer pressure reactor trip point reached 7.4 Rods begin to drop 9.4 Peak pressurizer pressure occurs 9.5 Minimum DNBR occurs (1) 1 DNBR never decreases below its initial value.