ML16343A984

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 14, Table 14.1.10B-4, Time Sequence of Events (Full V-5 Core), Page 1 of 1
ML16343A984
Person / Time
Site: Cook  
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A984 (1)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:14.1.10B-4 Page:

1 of 1 UNIT 2 TIME SEQUENCE OF EVENTS (FULL V-5 CORE)

Accident Event Time (sec)

Feedwater System Malfunctions:

Excessive feedwater flow at full power to all four steam generators (Automatic Rod Control)

All four main feedwater control valves fail fully open 0.0 Hi-hi steam generator water level signal generated 31.8 Turbine trip occurs due to hi-hi steam generator water level 34.3 Minimum DNBR occurs 35.5 Reactor trip occurs due to turbine trip 36.3 Feedwater isolation achieved 42.8