ML16343A210

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 14, Table 14.A.4-2
ML16343A210
Person / Time
Site: Cook  
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A210 (1)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

23 Table: 14.A.4-2 Page:

1 of 1 REVISED TRITIUM PRODUCTION IN THE REACTOR COOLANT 1 Tritium Source Total Produced (curies/yr)

Expected Release to Reactor Coolant (curies/yr)

Ternary Fission 10,000 1000 Burnable Poison Rods (Initial Cycle) 1420 142 Soluble Boron (Initial Cycle)

(Equilibrium Cycle) 206 294 206 294 Lithium and Deuterium Reactions 105 105 Total Initial Cycle 11,730 1453 Total Equilibrium Cycle 10,400 1400 Basis:

Release Fraction from Fuel 10%

Release Fraction from Burnable Poison Rods 10%

Burnable Poison Rod B-10 Mass 6160 gpm 1 This table was included in the Original FSAR in May, 1976.