IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
23 Table: 14.A.3-4 Page:
1 of 1 REACTOR COOLANT EQUILIBRIUM CORROSION PRODUCT ACTIVITIES (Based on Parameters Given in Table 14.A.3-2)
Isotope Activity
µc/cc Isotope Activity
µc/cc Br-84 3.18 x 10-2 Cs-136 2.79 x 10-2 Rb-88 2.54 Cs-137
.819 Rb-89 6.42 x 10-2 Cs-138
.639 Sr-89 3.03 x 10-3 Ba-140 3.09 x 10-3 Sr-90 7.51 x 10-5 La-140 1.21 x 10-3 Sr-91 1.35 x 10-3 Ce-144 3.70 x 10-4 Sr-92 5.69 x 10-4 Pr-144 3.70 x 10-4 Y-90 9.99 x 10-5 Y-91 5.56 x 10-3 Y-92 7.32 x 10-4 Zr-95 6.35 x 10-4 Nb-95 6.26x 10-4 Mo-99 2.25 Mn-54 5.60 x 10-4 Mn-56 2.10 x 10-2 Te-132 0.198 Co-58 1.80 x 10-2 Te-134 1.94 x 10-2 Co-60 5.40 x 10-4 Cs-134
.136 Fe-59 7.50 x 10-4