IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 21.2 Table:

11.3-3 Page:

1 of 2 RADIATION MONITORING SYSTEM CHANNELS CHANNEL PURPOSE ASSOCIATED TRIP FUNCTION OVERVIEW ERS-1301, 1401, 2301, 2401 Containment Airborne Particulates - Detection Containment ventilation isolation, prevent further release ERS-1303, 1403, 2303, 2403 Containment Radioiodine - Detection Containment ventilation isolation, prevent further release ERS-1305, 1405, 2305, 2405 Containment Low Range Noble Gas - Detection Containment ventilation isolation, prevent further release ERS-1307, 1407, 2307, 2407 Containment Mid Range Noble Gas - Detection Containment ventilation isolation, prevent further release ERS-1309, 1409, 2309, 2409 Containment High Range Noble Gas - Detection Containment ventilation isolation, prevent further release ERS-7401, 8401 Control Room Area Monitor Isolate Control Room Ventilation SRA-1905, 2905 Steam Jet Air Ejector low Range Noble Gas - Detect primary to secondary leakage None SRA-1907, 2907 Steam Jet Air Ejector Mid Range Noble Gas - Detect primary to secondary leakage None SRA-1909, 2909 Steam Jet Air Ejector High Range Noble Gas - Detect primary to secondary leakage None R-17 A, R-17 B, CRS-3301, 3401, 4301, 4401 Component Cooling Water Loop Liquid Monitor - Detect leaks from RCS or RHR into the CCW system Isolate CCW surge tank vent RRS-1001 Waste Disposal System Liquid Effluent Monitor Automatic valve closure to prevent further release R-5 SFP Area Monitor Place SFP ventilation into service VRS-5006 SFP Area Monitor Place SFP ventilation into service R-19 Steam Generator Blowdown Liquid Monitor - detect primary to secondary leakage via common blowdown header Isolate steam generator blowdown system.

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 21.2 Table:

11.3-3 Page:

2 of 2 RADIATION MONITORING SYSTEM CHANNELS CHANNEL PURPOSE ASSOCIATED TRIP FUNCTION OVERVIEW R-20, R-28 Essential Service Water Liquid Monitor - Detect leakage in the containment spray heat exchangers, (post LOCA)

None R-24 Steam Generator Blowdown Treatment System Liquid Monitor - measure activity in the blowdown liquid after it passes the treatment demineralizer Isolate steam generator blowdown system VRA-1501, 2501 Unit Vent Airborne Particulates - Detection None VRA-1503, 2503 Unit Vent Radioiodines - Detection None VRS-1505, 2505 Unit Vent Low Range Noble Gas - Detection Gas decay tank isolation valves 1 VRS-1507, 2507 Unit Vent Mid Range Noble Gas - Detection None VRS-1509, 2509 Unit Vent High Range Noble Gas - Detection of accidental release Sample pathway bypass of channels 1, 3, 5, 7 to sample pallet SRA-1805, 2805 Gland Seal Condenser Exhaust - Low range detection None SRA 1807, 2807 Gland Seal Condenser Exhaust - Mid range detection None SRA 1809, 2809 Gland Seal Condenser Exhaust - High range detection None Unit Vent Continuous air flow sampler Tritium sampling None 1 Available setpoint is used to accommodate: 1) normal operation, and 2) gas decay tank release.