ML16343A034

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 11, Table 11.2-12
ML16343A034
Person / Time
Site: Cook  
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A034 (1)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

23 Table: 11.2-12 Page:

1 of 1 DOSE RATE (REM/HR) RHR OR CONTAINMENT SPRAY Time Pump Room Heat Exchanger Room Safety Injection Pump Room 0

2.8 22.7 37.6 0 - 5 hr 2.3 18.6 32.2 1 hr.

2.0 16.3 27.4 2 hr.

1.6 13.4 22.1 8 hr.

0.83 6.6 10.5 1 day 0.l8 l.5 2.6 1 week 0.02 0.2 0.41 1 month 0.008 0.08 0.18 Under the assumptions of:

(1) increased sump dilution by melted ice, (2) core and halogen releases in accordance with Safety Guide No. 4 (in effect on September 1971), and (3) washdown of 50% of the core halogens to the sump occurs as a result of the action of the containment sprays.