IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

16.1 Table:

6.3-1 Page:

1 of 1 CONTAINMENT SPRAY PUMP DESIGN PARAMETERS Quantity 2 (per unit)

Type Vertical, centrifugal Design Pressure 600 psig Design Temperature 400 o

F Design flow rate 3200 gpm Design head 490 ft.

Motor horsepower 600 hp.

Motor speed 1780 rpm