Text
gg REG&
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 DUKE POWER COMPANY DOCKET NO. 50-269 OCONEE NUCLEAR STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.210 License No. DPR-38
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Oconee Nuclear Station, Unit 1 (the facility) Facility Operating License No. DPR-38 filed by the Duke Power Company (the licensee) dated February 24, 1994, as supplemented by letters dated April 19, May 25, August 25, 1994, January 4, January 27, February 22, March 15, April 19, and May 31, 1995, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.3 of Facility Operating License No. DPR-38 is hereby amended to read as follows:
9508210182 95615 PDR ADOCK 05000269 F
-2 Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 210, are hereby incorporated in the license.
'The licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days from the date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION Herbert N. Berkow, Director
- Project Directorate 11-2 Division of Reactor Projects -
I/II Office of Nuclear Reactor Regulation
Attachment:
Technical Specification Changes Date of Issuance:
August 15, 1995
C tgREGe& 1 UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-4001 DUKE POWER COMPANY DOCKET NO. 50-270 OCONEE NUCLEAR STATION, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.
210 License No. DPR-47
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Oconee Nuclear Station, Unit 2 (the facility) Facility Operating License No. DPR-47 filed by the Duke Power Company (the licensee) dated February 24, 1994, as supplemented by letters dated April 19, May 25, August 25, 1994, January 4, January 27, February 22, March 15, April 19, and May 31, 1995, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.8 of Facility Operating License No. DPR-47 is hereby amended to read as follows:
-2 Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 210, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days from the date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION H r ert N. Berkow, Director Project Directorate 11-2 Division of Reactor Projects -
I/II Office of Nuclear Reactor Regulation
Attachment:
Technical Specification Changes Date of Issuance:
August 15, 1995
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 DUKE POWER COMPANY DOCKET NO. 50-287 OCONEE NUCLEAR STATION, UNIT 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.
207 License No. DPR-55
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Oconee Nuclear Station, Unit 3 (the facility) Facility Operating License No. DPR-55 filed by the Duke Power Company (the licensee) dated February 24, 1994, as supplemented by letters dated April 19, May 25, August 25, 1994, January 4, January 27, February 22, March 15, April 19, and May 31, 1995, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.3 of Facility Operating License No. DPR-55 is hereby amended to read as follows:
-2 Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.207, are hereby incorporated in the license.
iThe licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days from the date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION H bert N. Berkow, Director Project Directorate 11-2 Division of Reactor Projects -
I/II Office of Nuclear Reactor Regulation
Attachment:
Technical Specification Changes Date of Issuance:
August 15, 1995
ATTACHMENT TO LICENSE AMENDMENT NO. 210 FACILITY OPERATING LICENSE NO. DPR-38 DOCKET NO. 50-269 AND TO LICENSE AMENDMENT NO. 210 FACILITY OPERATING LICENSE NO. DPR-47 DOCKET NO. 50-270 AND TO LICENSE AMENDMENT NO. 207 FACILITY OPERATING LICENSE NO. DPR-55 DOCKET NO. 50-287 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain vertical lines indicating the areas of change.
Remove Pages Insert Pages 4.6-1 4.6-1 4.6-3 4.6-3
4.6 EMERGENCY POWER PERIODIC TESTING Applicability Applies to the periodic testing surveillance of the emergency power sources.
Objective To verify that the emergency power sources and equipment will respond promptly and properly when required.
Specification 4.6.1 Monthly, a test of the Keowee Hydro units shall be performed to verify proper operation of these emergency power sources and associated equipment.
This test shall assure that:
- a. Each hydro unit can be automatically started from the Unit 1 and 2 control room.
- b. Each hydro unit can be synchronized through the 230 Kv overhead circuit to the startup transformers.
- c. Each hydro unit can energize the 13.8 Kv underground feeder.
- d. The 4160 volt startup transformer main feeder bus breakers and standby bus breaker shall be exercised.
4.6.2
- a. Annually, the Keowee Hydro units will be started using the emergency start circuits in each control room to verify that each hydro unit and associated equipment is available to carry load within 25 seconds of a simulated requirement for engineered safety features.
- b. Promptly following the above annual test, each hydro unit will be loaded to at least the combined load of the auxiliaries actuated by ESG signal in one unit and the auxiliaries of the other two units in hot shutdown by synchronizing the hydro unit to the offsite power system and assuming the load at the maximum practical rate.
- c. Also, the ability of the Keowee Unit ACBs to close automatically to the underground path will be tested on an annual frequency.
4.6.3
- Monthly, the Keowee Underground Feeder Breaker Interlock shall be verified to be operable.
4.6.4 During each refueling outage, a simulated emergency transfer of the 4160 volt main feeder buses to the startup Oconee 1, 2, and 3 4.6-1 Amendment No.
210 (Unit 1)
Amendment No.
210 (Unit 2)
Amendment No.
207 (Unit 3)
RI*
>2.12 VDC.
(3)
The electrolyte level of each connected cell is between the minimum and maximum level indication marks.
- c. Annually verify that:
(1) The cells, end-cell plates and battery racks show no visual indication of structural damage or degradation.
(2) The cell to cell and terminal connections are clean, tight and coated with anti-corrosion grease.
4.6.10 Annually, a one hour discharge service test at the required maximum load shall be made on the instrument -and control batteries, the Keowee batteries, and the switching station batteries.
4.6.11 Monthly, the operability of the individual diode monitors in the Instrument and Control Power System shall be verified by imposing a simulated diode failure signal on the monitor.
4.6.12 Semiannually, the peak inverse voltage capability of each auctioneering diode in the 125 VDC Instrument and Control Power System shall be measured and recorded.
Bases The Keowee Hydro units, in addition to serving as the emergency power sources for the Oconee Nuclear Station, are power generating sources for the Duke system requirements.
As power generating units, they are operated frequently, normally on a daily basis at loads equal to or greater than required by Table 8.1-1 of the FSAR for ESF bus loads.
Normal as well as emergency startup and operation of these units will be from the Oconee Unit 1 and 2 Control Room. The frequent starting and loading of these units to meet Duke system power requirements assures the continuous availability for emergency power for the Oconee auxiliaries and engineered safety features equipment.
It will be verified that these units will carry the equipment of the maximum safeguards load within 25 seconds, including instrumentation lag, after a simulated requirement for engineered safety features. To further assure the reliability of these units as emergency power sources, they will be, as specified, tested for automatic start on a monthly basis from the Oconee control room.
These tests will include verification that each unit can be synchronized to the 230 kV bus and that each unit can energize the 13.8 kV underground feeder.
Also, the verification of the ability of the Keowee Unit ACBs to automatically close to the underground power path will be performed by the annual tests.
Amendment No.
210 (Unit 1)
Oconee 1, 2, and 3 4.6-3 Amendment No.
210 (Unit 2)
Amendment No.
207 (Unit 3)