Technical Specification 3.4.18, Amendment Nos. 284/263, Steam Generator (SG) Tube Integrity
ML16243A352
Person / Time
Site: Mcguire, McGuire  Duke Energy icon.png
Issue date: 08/17/2016
From:
Duke Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML16243A352 (3)


Text

'

Distribution:

Duke Energy Date: 8l17l2Q1§ Document Transmittal #: TR-NUC-MC-003871

1. Boyer, Robert P DOCUMENT TRANSMITTAL FORM

Purpose:

Issue

2. Carroll, Michael E
3. Gardner, Troy R Released By:
4. Gibby, Lori C Facility: MCGUIRE NUCLEAR STATION Duke Energy
5. Helton, Daniel E SUBJECT 13225 Hi!g~rs Feri:y RQi!d
6. Mc Ginnis, Vickie L Issue MNS-TS-3.4.l8 Rev.1 Document Management
7.

MCG DOC CNTRL MISC MAN MG02DM

8.

MCG OPS PROCEDURE GP Huntersville, NC 28078

9.

MCG PLANT ENG. UBR.

MNSDCRM@duke-energy.com

10. MCG RAD PROT
11. Morton, Jill C
12. OPS HUMAN PERFORMANCE -
13. OPS TRNG MGR.
14. QATS-
15. RESIDENT NRC INSPECT
16. SERV BLDG FILE ROOM -
17. U S NUC REG WASHINGTON, DC
18. USNRC
19. WESTINGHOUSE ELECTRIC CO LLC Page 1of1 x:,,ix },:;,~'* ':*1ilfF"' t< ~,,

__,,.---~.. '~. ~~::*t..; ;"',._., ~---:.;

~~~~-'~,~~:~fJ,~'.t c'.*'\\6.+~"'i:. '*'

l*:li:A:

1 2

3 4

5 6

7 8

9 10 11 12 13 14 15 16 17 18 19 t.,Icl'J,<r{c:~~Mr\\JS;q*~~~l~~i~'mP!it:~'.'JS$.U~I) (~ :X,~':<';;}!~:\\;;*~-; FYIIE FYIIE FYIIE FYIIE FYIIE FYIIE FYIIE R&AIE FYIIE FYIIE FYIIE FYIIE R&All FYIIE PRINl lllllE R&AIE R&All R&AIE Remarks: MNS Tech Sgec. - Amendment 284£263

3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.18 Steam Generator (SG) Tube Integrity LCO 3.4.18 SG tube integrity shall be maintained.

SG Tube Integrity 3.4.18 All SG tubes satisfying the tube plugging criteria shall be plugged in accordance with the Steam Generator Program.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS


NOTE-----------------------------------------------------------

Separate Condition entry is allowed for each SG tube.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more SG tubes A.1 Verify tube integrity of the 7 days satisfying the tube affected tube(s) is plugging criteria and not maintained until the next plugged in accordance refueling outage or SG with the Steam tube inspection.

Generator Program.

AND A.2 Plug the affected tube(s) in Prior to entering accordance with the Steam MODE 4 following the Generator Program.

next refueling outage or SG tube inspection B. Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A not AND met.

B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> OR SG tube integrity not maintained.

McGuire Units 1 and 2 3.4.18-1 Amendment Nos. 284/263

SURVEILLANCE REQUIREMENTS SR 3.4.18.1 SR 3.4.18.2 SURVEILLANCE Verify SG tube integrity in accordance with the Steam Generator Program.

Verify that each inspected SG tube that satisfies the tube plugging criteria is plugged in accordance with the Steam Generator Program.

SG Tube Integrity 3.4.18 FREQUENCY In accordance with the Steam Generator Program Prior to entering MODE 4 following a SG tube inspection McGuire Units 1 and 2 3.4.18-2 Amendment Nos. 284/263