Limerick/NRC Pre-Submittal Meeting Risk Informed Completion Times TSTF-505 License Amendment Request August 30, 2016
Agenda
- Introduction
- License Amendment Request
- Implementation
- Closing Remarks 2
Introduction
- Desired Meeting Outcomes
- Discuss license amendment content
- Identify variances from TSTF-505
- Provide overview of Configuration Risk and PRA models
- Provide overview of implementation activities
- Validate timeline for September 2016 submittal 3
License Amendment Request
- 24 LCOs (Modes 1 and 2 only)
- New TS Section 6.0 Program
- Variances from TSTF-505
-LGS TS are old BWR STS; not ITS
-Subtle differences in Condition/RA wording
-TSTF-505 LCOs/Conditions not in LGS TS
-RICT added to plant-specific LCOs not in TSTF-505
-Typed TS pages not included 4
LGS TS 3.1.5 - Standby Liquid Control (SLC)
System
- Condition not in TSTF-505 or NUREG-1433 (BWR ITS)
-TS 3.1.5.b - Standby Liquid Control System otherwise inoperable (vs. two subsystems inoperable)
- Administrative deviation
- RICT added to each respective Required Action
-Consistent with similar TSTF-505 changes 5
LGS TS 3.3.1 - Reactor Protection System (RPS)
Instrumentation
- Condition not in TSTF-505 or NUREG-1433
-TS 3.3.1.a - Number of inoperable channels in either trip system for one or more Functional Units less than the minimum required operable channels per trip system
- Includes a 1-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 6
LGS TS 3.3.3 - Emergency Core Cooling System (ECCS) Instrumentation
- Conditions not in TSTF-505 or NUREG-1433
-TS 3.3.3.c.1 - Either ADS trip system inoperable (with HPCI and RCIC systems operable)
- Restoration action with 7-day AOT
-TS 3.3.3.c.2 - Either ADS trip system inoperable (with HPCI or RCIC systems inoperable)
- Restoration action with 72-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 7
LGS TS 3.3.4.2 - End-of-Cycle Recirculation Pump Trip (EOC-RPT) Instrumentation
- Condition not in TSTF-505 or NUREG-1433
-TS 3.3.4.2.c.1 - Number of OPERABLE channels two or more less than required consisting of one turbine control valve channel and one turbine stop valve channel
- Restoration action with 12-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 8
LGS TS 3.3.4.1 - Anticipated Trip Without Scram Recirculation Pump Trip (ATWS-RPT)
Instrumentation
- Condition not in TSTF-505 or NUREG-1433
-TS 3.3.4.1.c.1 - Number of OPERABLE channels two or more less than required consisting of one reactor vessel water level channel and one reactor vessel pressure channel
- Restoration action with 12-hour AOT
- ATWS-RPT is modeled in PRA
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 9
LGS TS 3.3.2 - Primary Containment Isolation Instrumentation
- Conditions not in TSTF-505 or NUREG-1433
-TS 3.3.2.b.1 - OPERABLE channels less than the Minimum OPERABLE Channels per Trip System (tripped condition would cause an isolation)
- Restoration action with 6-hour AOT
-TS 3.3.2.c - OPERABLE channels less than the Minimum OPERABLE Channels per Trip System for both trip systems
- Restoration action with 1-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 10
LGS TS 3.5.1 - ECCS - Operating
- Condition not in TSTF-505 or NUREG-1433
-TS 3.5.1.b.5 - Three LPCI subsystems inoperable with both Core Spray subsystems operable
- Restoration action with 72-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 11
LGS TS 3.6.1.3 - Primary Containment Air Lock
- Condition not in TSTF-505 or NUREG-1433
-TS 3.6.1.3.a.1 - One air lock door inoperable
- Restoration action with 24-hour AOT
- Air lock is not currently modeled in PRA
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 12
LGS TS 3.7.1.1 - Residual Heat Removal Service Water (RHRSW) System
- Conditions not in TSTF-505 or NUREG-1433
-TS 3.7.1.1.a.3.a) and a.3.b) - Allows the 72-hour allowed outage time (AOT) for the RHRSW system to be extended up to 7 days during repairs of the RHRSW subsystem piping
-Also affects TS 3.6.2.3 - Suppression Pool Cooling mode of RHR, TS 3.7.1.2 - Emergency Service Water and TS 3.8.1.1 - A.C. Sources -Operating [Emergency Diesel Generators]
- Affected systems are modeled in PRA
- RICT added to Required Actions and footnotes
- Only change is a calculated RICT 13
LGS TS 3.7.1.1 - Residual Heat Removal Service Water (RHRSW) System
- Conditions not in TSTF-505 or NUREG-1433
-TS 3.7.1.1.a.6 - Three RHRSW pump/diesel generator pairs inoperable
- Restoration action with 7-day AOT
-TS 3.7.1.1.a.7 - Four RHRSW pump/diesel generator pairs inoperable
- Restoration action with 8-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 14
LGS TS 3.7.1.2 - Emergency Service Water (ESW) System
- Conditions not in TSTF-505 or NUREG-1433
-TS 3.7.1.2.a.4 - Three ESW pump/diesel generator pairs inoperable
- Restoration action with 72-hour AOT
-TS 3.7.1.2.a.5 - Four ESW pump/diesel generator pairs inoperable
- Restoration action with 8-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 15
LGS TS 3.8.1.1 - AC Sources - Operating
- Condition not in TSTF-505 or NUREG-1433
-TS 3.8.1.1.e.1 - Two train systems, with one or more diesel generators inoperable
- Restoration action with 72-hour AOT
- RICT added to Required Action
-Consistent with similar TSTF-505 changes 16
PRA Models and Configuration Risk Management Program (CRMP)
- PRA models updated/upgraded and peer-reviewed
- F&O closure independently validated
- Updated screening for RG 1.200, Rev. 2 hazards
- Total CDF/LERF meet RG 1.174, Rev. 2 criteria 17
Internal Events PRA
- Focused scope BWROG review for internal flooding May 2008; PRA Standard Part 3
- Gap Assessment performed relative to RG 1.200, Rev. 2
- Most Supporting Requirements (SRs) assessed as PRA Standard Capability Category II
-Majority of unresolved peer review findings related to documentation
-Most Findings addressed in latest internal events PRA model update
-SRs met at Capability Category II after resolution of findings
-No significant impact on CDF or LERF 18
Internal Fire PRA
2 following NEI 07-09 peer process
- Most Supporting Requirements judged to meet Capability Category II
-Majority of findings addressed in latest Fire PRA model update 19
Peer Review Findings Closure Review
- Formal process by Independent review team
-Assessed disposition of Findings for Internal Events and Internal Fire PRAs
-Observed by NRC
-Confirmed resolution of most Findings, resulting in SRs Met/Capability Category II
-Identified several areas for additional assessment relative to specific applications
- Will be addressed in the LAR assessment of Technical Adequacy 20
Other Hazards
- Seismic
-No Current Limerick Seismic PRA
- Limerick is a relatively low seismic hazard site
- NRC Staff Assessment of Limerick (ML15296A492):
-Re-evaluated hazard bounded by SSE in frequency range of 1 to 10 Hz
-Therefore, seismic risk evaluation not merited
-Seismic penalty will be applied to all RICTs based on
- Current seismic hazard (EPRI 2013)
- Other
-Updated IPEEE screening evaluation performed
-No other external hazards required to be included in the RICT calculations 21
- Real-time risk model as currently used for existing Maintenance Rule a4 CRM
- Uses PARAGON software
- Incorporates RICT/RMAT calculation features
- Handles multiple overlapping configurations
- Developed with operator input 22
Implementation
- Operations owns implementation
- Cross-functional team supporting implementation
- RICT implemented in Modes 1 and 2 only
- Procedure changes and training
- Site-wide Communications 23
Procedures and Training
- Procedures
-Revised to address risk management action times, PRA functionality, and incremental risk tracking
-New RICT Program Procedure
- Level 1 Training
-Hands-on (detailed) training for Operators and Work Management
-Classroom training to address how RICT impacts Station Operations
-Integrated with current online processes
- Level 2 Training
-Support training for managers on process, expectations, limitations
- Level 3 Training
-Awareness training for all others 24
Closing Remarks
- Next Steps
-Submit the LAR in September 2016
-Refine implementing procedures
-Conduct training in 2016/2017
-Ready to implement in 2017
-Submit 50.69 using generic template
- Questions 25