6 to the Updated Final Safety Analysis Report, Reference Drawings 03201-0102 Through 33013-1353
ML16180A214
Person / Time
Site: Ginna 
Issue date: 05/05/2016
From:
Exelon Generation Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16180A174 List:
References
Download: ML16180A214 (77)


Text

{{#Wiki_filter:BATTERY A MAIN 125 voe ----JDISCONNECT. *----~ VITAL - BATTERY A CLASS 1 E <DCPDPCBD1A> 'SWT 14 I E49 I I E2 I I BATTERY A MAIN FUSE CABINET <DCPOPCB02A> ~2 MAIN DC DIST PNL A <DCPDPCB03.A> SWT 15 ~I -E5~o~I I 52/MCC1C ) BUS 14 POS 22C I CLASS 1E I MCC C CLASS 1E MCC I ) 52/INVTCVTA POS 16D I I c2499 I 52/MCC1A I BUS 13 ) POS 88 I NON CLASS 1 E MCC A NON CLASS 1 E MCC I ) 52/CVTAUX POS I 4K ~


r - INvrcvri\\l

) B800 I 1-1~ MCB DC DIST PNL A <DCPDPCBfJ4A> I I INVERTER I 120 VAC 7.5 KVA <INVTA> INVERTER A I ~CVTA


480/120 VAC

~7.5KVA ' ' ! ' - '1¢ I I l-~----1 ~ _s_TA_T_1c_s_w_ITC_H_~~-~--~ I I I I L B4 I I MANUAL BYPASS SWITCH f __,,-........ I I I I i ~CVTAUX


480/120 VAC

~7.5KVA I ' 1¢ MAINTENANCE SUPPLY J l ' I ) 52/CVTA1 POS 4H C640 1 J. CVTA1


480/120 VAC r-..r-..r--,r-, 7.5 !<:VA

{ y '1¢ 12s voe BA~~~Y B VITAL ---;DISCONNECT f------, BATTERY B CLASS 1 E I 52/MCC10 <DCPDPCBD1B> I E71 I BATTERY B MAIN FUSE CABINET ) BUS 16 POS 16C MCC D I CLASS 1 E CLASS 1 E MCC <DCPDPCB028> SWT 2 I E76 I MAIN DC DIST PNL B <DCPDPCB03B> I SWT 15 I E123 I I I ) 52/INVTCVTB POS i 40 I I lc2Ls I 1-1)81- - - - - - I I t- ') 8800 I INVERTER I 120 VAC 7*5 KVA INVERTER 8 I I <INVTB> i ~CVTB 480/120 VAC ~7.5KVA I

  • 1¢ I

I B2 B3 I _,,-... ___ ~I _s_TA_T_1c~sw_1_Tc_H __ 1--,,--..._~ i ~ - -~MA-N-UAL-_-BY-~~ 1 AS-~-S-W-ITC-~~ ---~- 4 I I I I I I J i SWT 14 I E217 I


1 -------

. _____ __j El/INVTCVTA NORMAL i f MAINTENANCE NORMAL NORMAL El/MQ483 I 52/MCC1B ! ) BUS 15 POS 4A I NON CLASS 1 E MCC B NON CLASS 1 E MCC MAINTENANCE i ) 52/CVTA2 POS i 7K I I I i I I cs;oo I ~CVTA2 --~- 480/120 VAC rv-v-v\\ 7.5 KVA I 1¢ I I

NORMAL I c2507 I UVD-1

@) I@ 1-CJ!-~2~00 I.1 C2f ~~------*------------~ C2510 11-----------------------*----------l~t~3 I - M~l~,T.cE._N_A_,N_cCcE_.*, ** _______________ 11 C2511 f---*--.--***-----*-**-**-**----***-* ----*-*****--------------*---=C=2~50-4-, SEE NOTE 5 '-' )- - -.'.j UVB-1 / )- - ~ SEE NOTE 5 El/INVTCVTB / )- - - ~ I r---(Dj MCB


*---------------------------------IC2512f--------*-*---.---***----------*-------------*-**-~--i--'---+'7"'

ANN E30 El/CVTAUX / )- __ -j MAINTENANCE ~ INVERTER <MQ483> 10904-0458 LOCATED AT BOTTOM OF MQ-4000 INST BUS A MCB o=:=n--*-/ INST BUS B IQl-1~1~fl--.-/ INST BUS c PWR DIST ANN E14 PWR DIST \\!:y PWR DIST PANEL PANEL PANEL CB-AR CB-BW CB-CB <IBPDPCBAR> <IBPDPCBBW> <IBPOPCBCB> 17,Sl ___ _/ INST BUS D ~ PWR DIST SEE NOTE 5 PANEL SEE NOTE 5 CB-DY <IBPDPCBOY> I C3593 j 1 B CET DISPLAY INCORE #4 <IC4> 33013-1569 1A CET DISPLAY I BKR 2 I C2517 INST RACK R1 (RED) <R1> PW-2 BKR 3 IC2518I INST RACK R2 (RED) <R2> !Fl PW-3 BKR 4 I C2519 I INST RACK SD <SD> PW-11 BKR 6 I C2521 I /\\ 00 BKR 4 BKR 5 -~-, C2566 I IC2520 INST RACK PLP <PLP> !Fl PW-13 v BKR 21 I C2536 f I 1*---*-**-----***-*---*------- -----r--_-:_-::_*:::=~====~----=~~:::::::::::::::::::::::: *---------------------1 I BKR 4 BKR 2 I BKR 3 BKR 8 I BKR 5 BKR 21 I I El/MQ400B ~ I N/A I C2542 C2540 C2541 I r--N~/A-. -,I I C2543 I C2559 I INST RACK RIL <RIL> ([)PW-10 INST RACK W1 (WHITE). <W1> PW-4 INST RACK W2 (WHITE) <W2> CD PW-5 I INST RACK RCS2 <RCS2> PW-16 I SPARE I c3~92 I I c2~13 j I I I I L0870 I lc2633l C2631 C2630 I I C2~32 I 0 I ~3 I C2617 j I C2651 DIST i BKR 6 I BKR 4 Pl),~~L I l BKR 10 I BKR 9

BKR 2

- - -,----J__ -r* .......1........ -** -**--****** -* - -,,. I BKR 1 I I <IBPDPCBA> I 1 ,--*---_J BKR 11 [ BKR 5 I L0869 I D ~ El/MQ400A MAIN CONTROL BOARD AOV 836A 62AST <MCB> 11300-0174 C2513 I BKR 1 ~ MAIN CONTROL BOARD RK-12A <MCB> 11300-0606 i ...,'.... l ' I BKR 4 I C2615 j INST RACK CVCS2 <CVCS2> PW-19 C2522 I BKR 7 INST RACK RSC <RSC> PW-12 I C2524 I BKR 9 BKR 18 -~-, I C2589 I INST RACK RCS1 RACK RVLMS-1 <RCS1> !Fl PW-17 SPARE BKR 14 FOX 1 RACK RECEPT CNMT ISOLATION PB RESET PANEL ~ <CIRP> 21489-0670 C3502 j BKR 15 BKR 8 C2523 L _______ _J EVAC FLASHERS 10905-0437 C3580 BKR 16 BKR 17 -=-c, BKR 22 .--=-c, C2537 I I C3581 RACK NIS RACK <RMS1>

  1. 1 (RED) 33013--1618,5

<NIS1 > 33013-1843 @1045F71 AND SHEET 2 TOXIC GAS A <RVLMS1> 33013-1583 <FOX 1> 10905-0546,1 I c3~94 I ~ ~ ~I c2~21 I ~5

  • -***,-... ~ ---- __ J --- ----. -. I l i BKR 4 I BKR 3

---isKR 2 I BKR 1 ----- ______ J _____.. -**** L__..... '.,,.. -* L..... ' -- DIST PANEL "E" <IBPDPCBE> I I \\ DIST PANEL "B" I SPARE SPARE ~ 4 BKR 2 I BKR 1 I BKR 3 ! BKR 11 I BKR 9 ! BKR 8 l L 1 c 5 r:~;~--- ~-;-------- --:r~:;- 6 _____ ~-~------ _ <IBPDPCBB> EHC REMOTE FOX 3 CABINET BATT MON RACK IN CNMT <EHCC1> IBKR 18 I C3583 f UV RELAY UVB-2 ISOL RACK <VBRM> I BKR 8 I C2547 I SAFGD RACK SIA1 ~ <SIA1 > 34500-0132 SHEET 5 I BKR 1 I C2514 MAIN CONTROL BOARD RK-45 TC-3040 RLY ZXC I BKR 9 I C2548 I I Rx LOGIC TEST RACK RLJ('.1 00 <RLTR1> 34501-0138 SHEET 9 I BKR 15 I ZC1 FIRE SYS SATELITE STATION "A" \\BKR 10 C2550 I MISC RLY RACK M1 <M1> 33013-1606 SHEET 15 BKR 16 -~-, ZC2 FIRE SYS SATELITE STATION "8" <FOX3> --'-"BK_,R 11 I C2551 RELAY RACK RW1 (WHITE) M <RW1> 34501-0132 SHEET 8 I BKR 17 I ZC3 FIRE SYS SATELITE STATION "c" I BKR 12 I C2552 I I RELAY RACK RW2 (WHITE) M <RW2> 34501-0143 SHEET 7 I BKR 14 SPARE IBKR 19~~1 fzcooo4f fzcoo18I FIRE SYS FIRE SYS ALLISON CTRL PNL CTRL PNL M <ACl-A888> BKR I L0873 j 11 IBKR 10 !BKR 9 SPARE SPARE \\BKR 8 SPARE .BKR7 IBKR6 SPARE SPARE (SPARE) MAIN CONTROL BOARD (TIM.TIN) RELAY RACK RR2 MED) RELAY RACK RR1 ~ED) <MCB> ~11300-0729 <MCB> 11300-0174 <SSA> 10907-0206 <SSB> 10907-0206 <SSC> 10907-0206 I 10907-0051 10907-0055 SFP-7 SPARE <MCB> 11300-0147 G733A <RR2> 34501-0141 SHEET 7 I C2526 <RR1> 34501-0131 SHEET 7 I BKR 24 I BKR 23 SPARE SPARE BKR 20 IBKR SPARE 13 IBKR 7 SPARE I BKR 6 C5600 11 C2544 I I I BKR 2 I C2564 I INST RACK* B1 (BLUE) <B1> PW-6 I I BKR 3 C2565 I INST RACK B2 (BLUE) <B2> PW-7 BKR C3501 I 10 IBKR 9 'BKR 3 I c5J5s I I C3501 I FOX 2 SEE RACK NOTE 4 <FOX2> MAIN CONTROL BOARD RK-12C <MCB> 11300-0606 BKR 5 C2567 I INST RACK ADFCS r--'--.,-..LC.BK~R 7 BKR 8 C5600 11 C2569 I C2570 I I NIS RACK

  1. 3 (BLUE)

I INST RACK SA <ADFCS> /\\ 33013-2521 00 SHEET 2 <NIS3> @ 1045F71 SHEET 6 <SA> PW-15 i i BKR 6 I C3595 I RACK RVLMS2 <RVLMS2> 33013-1583 ' BKR I C3505 RACK <RMS3> 33013-2295 AND TOXIC GAS B 10905-0546,2 11 BKR 7 I LD871 I l El/MQ400C I BKR 21 I C2583 I ' I i l I i DIST PANEL "C" BKR 22 @) El/IBPDPCBCB 0 HZM/IBPDPCBCB El/MQ400D ~ 0 I BKR 3 I C2588 I INST. RACK Y2 (YELLOW) <Y2> pW-9 BKR 2 I C2587 I INST RACK Y1 (YELLOW) <Y1> !Fl PW-8 BKR 6 I C2591 I NIS RACK

  1. 4 (YELLOW)

<NIS4> @ 1 D45F71 SHEET 8 BKR 5 I C2590 I INST RACK CVCS-1 <CVCS1> PW-18 I I R933A I I c2r61 I ~ I C2~66 I M I C2664 I BKR 21 -~~ C2607 I . DIST PANEL "D" SPARE SPARE I I BKR 1 !BKFI R 2 '1' BKR 6 I BKR 4 BKR 11 ~ I BKR 9 i BKR 7 k--- I I 11.. - - - - i BK~l~~~/_B_K_R_3 ____ ~----------~-----~--------* -------'------* <IBPDPCBD> SPARE SPARE I G1499 I I BKR 19 BKR 1 BKR 9 BKR 10 BKR 11 BKR 17 I SPARE I C2516 I I C2595 I [rC-2~5-96-,[ lrC-2~59-7~1 rC-2~60-2~1 I RRMSR01 NOTE 8 SPARE SPARE SPARE SPARE IBKR 24 IBKR 22 IBKR 8 IBKR 4 I BKR 23 I BKR 20 I BKR 7 SPARE SPARE SPARE BKR 18 -~-, I C3586 f MCB RECORDERS & PERMISSIVE LIGHTS ~ <MCB> 11300-0174 BKR 12 lr-c-25~98..,f SAFEGUARD RACK SIB1 ~ <SIB1 > 34500-0138 SHEET 5 BKR 13 -~~ I C2599 f Rx LOGIC TEST RACK <~> 34501-0148 SHEET 9 BKR 16 r-~-, I G273 I MISC RLY RACK M2 <M2> 33013-1606 SHEET 17 BKR 15 -~~ I G272 I TURBINE EH PANEL ~EHCC1> IWl 721J299 I UV RELAY I C2665 I iE3KR "--**-*** __ *--*-* __ ___ ___ *--------******----- ------~ _ _J RELAY RACK RY1 RELAY RACK RY2 FW XMTR PANEL TURBINE GAUGE PANEL I BKR 14 IBKR SPARE 6 BKR I G300B I I 14 I BKR 23 BKR 1 SPARE IC2515 MCB TIC PT-2021 PT-'2014 PT-2023 PT-2024 LT-2006A <MCB> 11300-0147 IBKR 24 M IBKR 18 IC2504CI NOTES: I UV RELAY (ANN E22) uvc <MCB> 11300-0729 MCB AOV 836B & PROT RELAYS <MCB> 11300-0174 I BKR 16 L66B I UV CTRL CABINET BUS 17 10905-0056 SHEET 1 <ARB2CC17> <AR82RC17> I BKR 9 I C2322 I CNMT RECIRC FANS A,B, C,D VIBR SMB 25 24189-0748 SHEET 5 BKR 13 r-~~ I L674 I I UV CTRL CABINET BUS 16 10905-0055 SHEET 1 <AR81CC16> <AR81RC16> I BKR 11 I C2573 I I RELAY RACK RB1 (BLUE) ~ <RB1> 34501-0135 SHEET 7 I BKR 15 I C3584 I I OUTLETS FOR MCB CNTRL'S & RECDR'S <MCB> 11300-0175 I BKR 12 C2574 I I RELAY RACK RB2 (BLUE) ~ <RB2> 34501-0145 SHEET 7 I BKR 17 AHC58 I I ISOL DAMPER CONTROL PNL <IDCP> 33013-1415 BKR 20 ,.---'-"'-C, I MEC4 I I SAFWP-D INST PNL <SAFWPDIP> PW-10 I BKR 19 SPARE UVD-2 11300-0901 (YELLOW) (YELLOW) T @) <RY1> 34501-0137 SHEET 7 <RY2> 34501-0147 SHEET 7 <FWTP> 33013-1627 <TGP> SK60983-W El/IBPDPCBDY THIS DRAWING SUPERSEDES 21946-0269, REV 0, 21489-0270, REV 5, AND 21489-0271, REV 6 AS BUILT DATE RELEASED FOR I. " I ENGINEER REVISED PER ADC 000341-CN-006 & ECP 000198-CN-001 RJM O!ir- {J/.i..,.,, 0 ~ El/MQ400E BKR 19 BKR 13 BKR 11 C2525 f BKR 10 El/MQ400F I NIS RACK

  1. 2 (WHITE)

RACK RMS-2 1)@ - WESTINGHOUSE DRAWING REFERENCE

2) CE) -

FOXBORO DRAWING REFERENCE

8) ALTERNATE POWER SUPPLY. NORMAL POWER SUPPLY IS ACPDPCB09/02.

,__R_EV_~ ___ REV_IS_E_D_F_O_R ___ -< DRAWN CHECKED RESP REVIEWER BKR 28 IC2500C UV RELAY (ANN E6) UVA <MCB> 11300-0729 BKR 27 F I 0 HZM/IBPDPCBAR El/IBPDPCBAR BKR 26 I C2528 SMOKE DET XFER SWITCH (SEE NOTE 3) 33013-0462 I I C2572 I BKR 10 BKR 25 I G300A I MCB TID PT-2020 PT-2027 PT-2028 PT-2031 PT-2032 <MCB> 11300-0147 BKR 24 -~-, MEC3 SAFWP-C INST PNL ~ <SAFWPCIP> PW-1C BKR 23 -~-, L673 I UV CTRL CAB BUS 14 10905-0054 SHEET 1 <ARA1CC14> <ARA1RC14> BKR 20 -~-, L667 UV CTRL CAB BUS 18 10905-0057 SHEET 1 <ARA2CC18> <ARA2RCl8> BKR 1~@1 I C2527 :1-;..:;:.;r ~ r---coF"°IR""E-,1 PZ42 RELAY I LOB74 I PANEL M <FRP> C2527A 33013-2460 M, SHEET 2 ~ 25 El/IBPDPCBBW SPARE /\\ <NIS2> @1045F71 SHEET 4 I <RMS2> 33013-1618 I*

3) PYTRONICS SYSTEM
4) 120VAC POWER TO 1 B CET DISPLAY IS ROUTED THROUGH FOX 2 RACK WHERE CIRCUIT C3501 TIES TO C3593 AT TERMINAL DECK
5) MECHANICALLY INTERLOCKED SO THAT ONLY ONE OF THE TWO BREAKERS CAN BE CLOSED. THE AUXILIARY POWER SUPPLY IS FOR MAINTENANCE PURPOSES ONLY.

USE OF THE MAINTENANCE BACKUP POWER SUPPLY SHALL MAINTAIN CHANNEL SEPARATION INTEGRITY.

6) ENCLOSURE EIN'S ARE PLACED WITHIN CARETS TO FACILITATE RECOGNITION
7) CIRCUITS C5599 AND C5600 SUPPLY INSTRUMENT AND CONTROL POWER TO N-32 DRAWER IN RACK NIS2. POWER IS SUPPLIED FROM INSTRUMENT BUS "C" AND BOTH CIRCUITS ARE FUSED (7 AMP) IN RACK NIS3.

(PCR 2002-0044) FACILITY GINNA BY BY ENGR SCALE NONE R.E, GINNA STATION CAD FILENAME 03201-01 02 ONTARIO, NY ELECTRICAL 120V AC INSTRUMENT BUS ONE-LINE DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 4777 03201-0102 1..... CCD 3 1 Ct~I Rl_ C20PY i

125 WC eATIERY A CLASS 1E <BIRfA> AUX BlDG DC DIST PNL ta <DCPDPABOJA> MCC K MCC B MCC H CNTRl ROD DRIVE MG SET A CN1RL PNl ISOPHASE ClG SYS RLY BOX Af:N 4529 GEN EXCITER EQUIPMENT PNL BUS 11A NORM, BUS 12B EMERG BUS 12A NORM, BUS 11 B EMERG BUS 13 NORM, BUS 15 EMERG MOV 3505A FW PMP A DC OIL PMP PA INVERTER eATT RM VENT CN1RL PNL BR\\/-1 BUS 14 W CNTRL CAB NORM, 16 EMERG, SSAUVLOC MCC E MCC C MCC C AUX CKT BKR CAB BUS 14 NORM BUS 16 EMERG SI PUMPS FAN CNTRl PNL H2 RECOMBINER A CN1RL PNL WASTE DISPOSAL PNL SECT W1 Rx TRIP SWGR UNIT 1 BKR RTA.BYB CNTRL PWR I) eus 14 l'OS 22C llCC c I aASS IE aASS 1E ll:c j)POS 160 8800( ~CVTA --- 480/120 VAC rY'(V'\\ 7.5 KVA INSTR BUS A <llll'!l!'CBAR> 03201-0102 I 111 <INVrCVTA> 5 SPARE 6 5 SPACE 6 SPPCE SEE NOTE 1 125 WC 1SC eATIERY NON CLASS 1E <BIRYlSC> eATTERY A MCB VOLTMETER & INVERT RL)' RL-6 El/PG 00 A CNTRL PNL NORM SUPPLY 00 8 CN1RL PNL EMERG SUPPLY BUS 17 EMERG SUPPLY BUS 18 NORM SUPPLY DFPCP AR-100 RELAY A BUS 18 W CN1RL CAB NORM/17 EMERG PPS SWGR TRAIN A DC POWER MAIN XFMR ANN STATION UNIT XFMR 11 ANN STATION AUX XFMR 12A ANN MCB ALM SYS A TS SG DMP VL\\IS TB-DCDC POWER TRAIN A LOCKOUT & DIFF RLYS BUS 11A IN RLYS H2 MON ISOL VLV 921 H2 MON ISOL VLV 922 MCCN SIA1 DC PWR (SI TRAIN A) RA RACKS DC POWER MQ 483 INVERTER DC PWR Rx TRIP TARGETS RLY BOX CNDST 8STR PMPS RLY PNL AVC-5 CIRC W1R PMP TRIP UlGIC RLYS RCS OVERPRESS HEAD VENT VL\\IS TRAIN A CR EMERG LTG DC FUSED XFER SWT CNMT !SOL RLY RACK RLTRt RACK I:t.i:: ~p ~/RX TRIP 43/11A 43/12A 83/00A 83/13 83/12A 83 E201 <83/J'Sc> AUTb TRANSFER SWfTCH ) ) G=*~ TURBINE EMERG DC LUBE Oil PUMP CIRC W1R PUMP A DISCHARGE MOV 3150 CIRC W1R PUMP 8 DISCHARGE MOV 3151 GEN AIRSIDE DC SEAL OIL BACKUP PUMP 4KV BREAKER TEST CABINET AUTOMAllC THROWOVERS 83/008 83/16 E168 E64 83/128 E200 50 KVA REGULATING TRANSFORMER ~-1---~ <PXCD001> 00 8 AUX BKR 183 CABINET D G 8 CN1RL PNL NORM SUPPLY D G A CN1RL PNL EMERG SUPPLY TRAVELING SCREEN CNTRL PNL MCC G BUS 18 EMERG SUPPLY BUS 17 NORM SUPPLY BUS 17 IN CNTRl CAB NORM/18 EMERG PPS SWGR TRAIN B DC PWR S'IM DUMP VL\\IS TDAFWP GOV IND & TB-DC TURB DRAIN VLVS LOCKOUT & DIFF RLYS MSR VL\\IS RLTR2 SIB1 DC PWR (SI TRAIN B) RA RACKS DC PWR CNMT EVACUATION ALARM H2 MON lSOL VLV 923 H2 MON ISOL VLV 924 CIRC W1R PUMP TRIP LOGIC RLYS MCB ANN AA CNDST DEMIN CTRL PNL (AVC-1) BUS 118 W RLYS RCS OVERPRESS HEAD VENT VALVES TRAIN B CNMT !SOL RLY RACK 81 CNTRl ROOM VENT FAN MCB ALARM SYSTEM 8 83/ANN SPN:E SPACE llCC D eATT 8 MAIN DISC SWT PNL <DCPOPC001B> aASS IE ll:c ')POS 4MM SEE NOTE 1 I )'*JS 1s POS 16C llCC D I aASS IE aASS IE llCC ')W INSTR BUS C <IBl'lll'C8C8> 03201-0102 CN1RL RM EMERG LTG TRANSFER SWITCH CN1RL ROD DRIVE MTR GEN SET B CNTRL PNL MCCJ MCCP MOV 3996 BUS 11B NORM BUS 12A EMERG BUS 128 NORM BUS 11A EMERG BUS 15 NORM BUS 13 EMERG FWP 8 DC Oil PMP BUS 16 lN CN1RL CAB NORM, 14 EMERG AUX BLDG H & V CNTRL PNL MCC D GAS ANALVZER CNTRL PNL BUS 16 NORM SUPPLY BUS 14 EMERG SUPPLY MCC D AUX CKT BKR CAB H2 RECOMBINER B CNTRL PANEL WASTE DISPOSAL PNL SECT W2 CCW PMP SEAL ORN TK PMP HI LVL AlM Rx TRIP SWGR BKR RTB,BYA CNTRL PWR <INVTCVlll> 125 WC eATTERY 8 Cl.ASS 1E <SllMI> CNMT EMERG LTG PNL H2 SEAL OIL UNIT CNTRl PNL MCC A MCC f PRI W1R TREATMENT PNL IBELIP ARE RLY PNL--i_~l!_JHH-<llL_JJp-9' AIR COOLED PENET & EQUIP HATCH lEMP AlM PNL NUCLEAR SAMP PNL 'IDAFW PMP DC WBE OIL PMP NOTES: t) ~~~r~1fl~~= ~JEME.

2) ~

~~~3;tJ83XViGSl-{;Aili~ 2 FOR

3) ~TT A-B MANUAL TTiROWOVER ES ARE KEYLOCKED. A & 8 SIDE SWICHES OPERATE INDEPENDENTLY. TWO KEYS ARE REQUIRED TO CLOSE BOTH swrrcHES SIMULATANEOUSLY.

I xxxx I - NO CIRCUIT SCHEDULE ASSIGNED FOR PRE.V!OUS RE.VISIONS SEE MICROALM AS BUILT RELEASm FOR M RtVISED FER ECP-1~ RIY RtVISED FOR DIWlll CIEKBl RESP IEIDER FACllJIY GINNA 11( 11( ENGR SCILE NONE R.£. CllNNA STA1ION COD F11.ENA11E 03202-0102,1 otrrNl!(), tit 125 voe POWER DISTRIBUTION SYSTEM ONE-LINE DIAGRAM JOB NUMBER DIWllNC NUMBER SllEEI' REV EWR 4777 03202-0102 M CNTRL COPY#

L 4160V BUS NO. 128 I I L __ 1l!!!!. e&/129 33013-1949 33013-1~ 3:!013-1951 33013-@52 THIS DRAWING IS INTENDED FOR USE IS A PURVIEW OF PlANT OPERATION. FOR COMPLETE EJN'S OF COMPONENTS, REFER TO a.EMENTARIES OR CCD DRAWINGS COVERING THE SPECIFIC AREA REQUIRED T~ r+=-t--l I I I r I I '--""" <r:~ I 86"/128 2 1 I ,--~~ I I WI. I I I I I I I I I I l WE I 200/11T-12B I 6,.;;~,~:~ l ' I ' I SS 1----------------------1 4160V BUS NO. 118 I,,---,.'1?- 1 y ae/118 ',.J ! 5(, I 15$$ I I I I o I FlF __t"'JOS T,.,,...,,,_,.., 480V BUS N0.15 TRIP JU. FEEDER BR£AICERS ON BUS 11A. TRIP A1. nED£R 9RFJ.K1'.RS ON BUS t ta IU. FEEDER ~ ON at.IS 121... ALL fEEDER BREN<EJIS ON SUS 129. Kl>-< 1HIS DRAWING INCWOES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES ANO SPECIFICATIONS TO DETERMINE DPECIFIC QA PROGRAM APPLICABILITY. STA. SERY. XfMR.

  1. 15: a..G. FANS 480V BUS N0.17 KDGOtB DIESEL GENERATOR B ro 115KV swm:t<<ARO
  • 11--j/

<I* r----1 l<N-7 ""'-" I 1C I I I I ~~ ""' ) -'i>'°'


1 x

y @ -- """"-.... ~----.----<~ ~>--,,, -----lCJI-----, ____.+/-_~~-------- L ___________ _ ! ~A--T,--+-------~ i i 118 ' *ltit-I 88/118 ~t---9----1------------------------! SS t---- ~ >+-+---' 86/11B I I I I I I I ~- 4160V BUS NO. 11A i 3-CrS nA KV-1 -1 -@t """"'*W<CE """" f.::\\_ __________ ( ~~t~ ~IOC-2151 I I I I I '-I I I I I I I I I I I (61)- ID T ------ I I I I I I I I I I I I I TO STA. AhN..J_ !IOro T87P/PC I -2.&X T.-.P) I I I I I r----Utai:-- __________________ J 1 IS11lU(


~---1 I

I I I I I I I SEE. 33013...Q;U 878/12.1. s i ~'1--t--+--~-~ 4160V BUS NO. 12A 5 ffe.,, I~ I l~

11ii! & i ____ -.---. T ""'

i T1I +~~~,. 3-CTS

  • 1A-1 jf85l(/1G I

l:=t---JC;A.:L_j_... I T-' I

--~'
. ----

I I I I I I I Alll11 I I _________.J I *,__.,,.. I <00-5 I BYZ lB!p oo !!! OCK M}BTA--A 52/12ll'f I 100-5 ~------L-----~~ L ~~ ~ I I I I I I I I I I I I I f-l I 60/74/1G --1----;!f---- I I I I I I L_--lJ _ _____j__.,__ ___ --L ____ __':=====::::'il;__~60>--~-~-J I I I 1-- 87G I I I I I I I I I I I r -.I- :;tf---f-i;<-T~~ I I 152 I I t I ZA i ~*[__ __J __ _ I I I I I I I I I I I I L-1 I I I I I I I I I I I I I I I I ~----,-, I I I I I I I I I I I I I I I I I I ___ 20.000 NIP BUS r-- 1 I I I ,.,, 1 - 1 1 1 a?G ~H~I I coo I I ~-1 ~~ 41/lG I I I I OUT?Ur 'flJf: : I +- ---- -----, I I I t-r- ---- I I l *--r- --i-l--+-1=+- -+---'--- ~- __ LL_ -*-- ~---i-- / I: *--lf-'l°'/I/ ---- _l ___ ~----:__ "" r-... I 1 I ll,"I 'to


--:-.-lf-.--lf-

.l J_ 11 I // I" I "" P9-cr=P9-2T I 1 L - _I f...LI\\_ I 1G1372 1G -t H --, I L-J~.. J I I I I ( I I I ' P1t-1..Lpg_2..L I 1 r- _. l I l ! I L _ _!X".!!72 __ _ L-~ 11 i. j_ I I I' L _____ _ A I t TP&-1 P8-~ I I I ¥t:"* I I I I I I I m r-I....L ...L I ~J:r rH-...., I ii L.='. "~ : ~ - --t' I #-w I I 1 I 1 1.., I..., L... I 11 "--"'I i.10 _l_-;o I 111 '">r1T T w II IL_L - "' I


;lf--

--;ff------ 80/74/tG IUF-* l<P-m l<A--24*


If----


1 TD-1 Wl

--H---.!.-t---- ~ 861'~ 10: ro?f-I ~ ...... \\ #~ ~~!~ ..,. ~ ro / I / I I / I / / I l'Z, TRIPS ( r - _J lO sua SrA.13\\ I I I I --' I ~-------~ I _ _J I I I I


i---w-.

I ro-1 MIN I I I r~/ r~I

  1. =
  2. =

I I +----r-1 : I I I I ..L,,,. J_.,,J_,,,. --¥w T* T* T* 'f"" I I I I .l_B.JX.l..63X_LMX J.t~ T' T' T' ~* I I I I 480V BUS N0.14 480V BUS N0.13 ~ i iH-i _ _J~ 1 r--4-- 1 I I I I ~~tll'.Cl'RCN.. JI I I t I I 11 I 11 I I I c~ STA. SERY. XfMR f14 ClG. FAAS c !!!!;;;! c KH-1 c !ilH KDG01A DIESEL GENERATOR A 480V BUS N0.18 l<<J-4 FROMST<>3' _:J I I I I j 1 I I I I,,..I I ..,...,,..1 I I I FRCN STA. 1JA I I I I


j-'

~"!.".:"1 I I ..,.,._.I I r--. I I DFT..L.§6..l... I I T ex-r I I L-4~! i ,... -1 I I I I I L_t-rl f-t--'""+---' I I I I I I I I I L----:-- 1 I \\11P1/1 L __ _______ J ~ 'f. ~ ~ KCD01 )-"- s s ~,= ,i;,'li 1~ 1,~ I, ~-------~---h] ~

~ : L_~~~

r I I r--+---, 14 ...L ...1!/41-<<B'....L ...L ....L T 11P:1/rnT -, eBP/mT-"T"' BRIJSHt£SS~~~ l SYSlBI 4=11P2/11>#88X/1G 1 I

  • 1[4.141JI I

I ,_ __ l __ _, I I I I I I I I : N /0 It 13 I I I I AS BUILT DATE RELEASED FOR ENGINEER j\\ REVISED PER /J!A ADC--13--01228 RJM 10/16/17 to/1<(13 ,__REV_~ ___ R_EVJ_s_ED_F_o_R __ --1 DRAWN CHECKED RESP FACIUlY GINNA BY BY ENGR SCA1E NONE R.E. GINNA STATION CAD FILENAME 33013--0623, 1 ONTARIO, NY MAIN ONE LINE OPERATING DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-0623 ~ ~C~C~D_3~ ~C_N_T_RL_C_O_P_Y~#--~~

FROM 12A CT's TO BUS 12A TO SYNCH METER TO BUS 12B FROM 128 CT* ~ ~ ~ ~ ~ REMOVABLE UNKS


OPERATE UNE


TRIP LINE


CURRENT OR POTENTIAL LINE TH!S DRAWING SUPERSEDES 33013-480, SK-500-63. N*D SK-500-96 THIS DRAWING IS INTENDED FOR USE AS A PURVIE OF PLANT OPERATION. FOR COMPLETE EIN'S OF COMPONENTS, REFER TO ELEMENTARIES OR CCD DRAWINGS COVERING THE SPECIFIC AREA REQUIRED 3000A BUS DUCT 1/12AX-SYN J0lol0A BUS OUCT BLOCK CLOSING 62/12[1)(

~~~-..~~~~~~--1~~~~~~~~~~-e-~~~f--'~+-~~-t-~---t------- 52/12BY BLOCK CLOSING 52/12AlC 52/12AY


+-~-t-~~--1~~)-~~~~~~~~~~~~~~~~~~~~~~~1-~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~*

OPERATt STA. 13 ANNUN. OPERA.Tt STA. 1 l ANNUN. "'"'"'} 86/12-B ll6T/12A - -- --\\ 86TBU/12A 868/128 c ON asr 86B aemu aerau ee 21x ccx ""'"' ""' - - -II- - -1 I-- -;W-- - -+!'- - -+!'- - -:lf- - -;W-- - -:lf- - -1 I- - - - - - - - - - ~ l SS 12A 128 12A 128 128 12A 128 51fl CiFH-' t2AX 1°2AX AUTO OPEN- - -j t- - -j --~'\\--'-~ 12BX ~ ~~AL - - -J 1- _j 1/12AlC 52/12AX I ,---r-1f.. - - - -WJ. I SS 52/12AX I 12BX L -1 f- _ -~~AL 'l'J"' ~ Bf>T/128 86TBU/128 868/128 86/12B 76702/b 52/12BX CCX 27X B6 s,6, e~u ~o/ 861'BU ON c '- - - - -H- - -+F- - -J,l'- - -;n- - -;11- - _,,r-- -J,l'- - -H- - --1 f- - -~;, 12B 12B 128 128 128 128 12A A 1/128X 128X ~t1. - - - ~k-52/128Y _..§§._ I ~JJAL- - _J 1/12AY .:u,,. }- alITSU/12A BBB/12A 66/12A 7T1352/b \\ I I I 52/12AY 52/12BY --0"'"' 86T8U/128 S68/12A ~/12A 78702/b CCX 2,76 ~~ 86B 8~).I 8eT 8~wi ifN C ---~~--,n---,n---.,fl'---;ff---,if---,rr--~f----1f---~, 12.ll 12B 12A l2A 128 12B 12A SS/128Y 1/128Y OFF' 52a C BSTBU ON SST 8Slffi1U 85 868 27X C~X 1; / "' ---11---:lf---H---;ff---:tt---:lf---Jf---jf---li--------- CLOSE 1/12AY 128 A 12A 12A 12A 12A 12A 12A T ~-I~ - --1 f- - _.,,,,, °'" 1' 11 2.i_ 12AY JJ 128Y ~2J'J'.:120v 1 L - -1 r---- - -MANUAL OPEN I I I I I I I I I I I I I I I I I I I I I

  • R y

x 600A J000A BUS DUCT PXY0012"'. STA. AUX. XFMR. 12A 34,500 - 4160 - 4160V 28/41.S. MVA 3.44% IMP 0 14 INA HV/LV

  • 6S'C RISE 1200-5/SKORT SUPERV!SOIW

!SOL.AUD 12A MWH TO --§J AND STA. 13 CPU REl.AY TONES ,_,,, 1 +2e0-120v T FUTURE l {FUSES f!EUOVED) 1200/Sl30-5 '~--"'>---* I 'iiiV 1-S ~:L_ _ _J-;----L:;.J -*~

g.

1 GEN. NET MW I TO P.C. "" >------; s f----- ,,, L--1,---Y COMPUTER 1200-5/SHORT SHORT 2-Prs i 4200-1Z0V T FUTURE l (FUsgs REMOVED) 7651\\ 0 30KV j__ !RIP ANO BLOCK "'=" s2(7T13s2 -m OPERATE --- -- --#---------1 STA 13 ANNUN 7T 4JOTT I NoFm" I TRIP ANO BLOCK 34KV B 52/7T!J52 ---*~---------- OPERATE ~ 85TT/)T/1J'I---------- STA.13 l\\NNUN, """'Jn } Mo, 86L(7r52 66TSU/12A

  • ---*----- 52/7T1J52 66T/12A

~ MAN. OPEN II s2/1v.x I 52/12AY 62/7Tl::352 II s~/TI~x -- - - - - ~---s~r~--+')!!l'-J.--- s2112BY ~! I STl\\.~UN. / AC!".L_ I 50T-, L-----------------------------------------------------------~' ~' 3 12A ;osc I TRIP AND BLOCK 52/12A)( 52/12AY 52/711352 OPERATE STA. 13.>J-INUN. ALL ITEMS SHOWN ARE PREFERRED POWER SUPPLY, NON-CLASS 1 E. '/.......,, 12A TRANS -~--------<t----\\1-----<~ MTRS K1J1B "'" ~ <~-c:J-7, SP~~O~gES ~ v ' *+/-o ~ OISC/7T1 J5J SI 1275 0 40"C 34.6 KV 1200 CONT 25KA 1C 6-1KA MOM 1500A 0.WC "Y"'" ~ SHORT 2E K1323 1/12BY PXYC012B TRIP AllD BLOCK

m~}

52/BTB-B 52~5 J.3013-623,1 62/17SS - STA. 13 ANNUN. j /LJL_'-_"f1J;'/.......,, '\\."\\-"""L ~ ~}-~>-~~--t~~~~~~~~~~12B TRANS MTRS. SPARE FUSES K1J19 REMOVED +/- " "+/- 34 KV, BUS 2 POTS v 115\\111-¢ STA. AJJX. XFMR. 128 34,500 - 4160 - 4160V 28/41.8* Ill/A 3.541C IMP 0 14 MVA HV/LV

  • 65'C RISE y

20,1211 - 115/81 - 11s/e1V 3-4KVA )(PT/167CA XPT/767CB XPT/767CC 127SA 0 40'C 34KV 1200 61M MOM 1200 CONT s I 25KA IC 61KA MOM 1500A 0 40"C J4 KV BUS 2 76701 1 1200-5/SHORT $7[ -------1 INSUl SKORTS-<1> PW TERM t 87LX/767 67LX 16102 PILOT WIFlE ~--<>-~-TO STI\\. 1JA HOUSE SERVlCE ~/87l/767 ,,,,,,, T.~

  • --+".,=,_--;

115VAC BllLC 1 sfc I 4 2X/87L/787 -{" 94/6T 94/BU/6T 52/76702 ---------- 86T/12B BfiltU/12B MAN. OPEN 34 KV BUS 2 POTS 1200/600-5 12~0-5/SHORT 128 MWH TO -- SUPER\\4SOIW ANO STA. 13 CPU 1 GEN. NET MW TO P.C. COMPU1ER x 600/:>00-5 R I I I I I I 8STEU 86T/ { I 76703 2-25~KCM 12s 1129 I '- - - -:;if- - -;t1- - ~~f I 50T..L ' ~

  • ~

I I I TRIP ANO BLOCK I I I 52/76702 ~ I 52/12AY I '\\. STA. 0f5R1TiNuN. I ~--------------------------------------------------------------~ 128 A9C l-------------------------------------------------------------~:~& I TRIP AllD BLOCK 52/128)( 52/12BY 1>2/16702 OPE~ATE STA. 13 l\\NNUN. AS BUILT DATE RELEASED FOR REVISED PER AJV3 OCR 2006--0202 & PCR 2005--0029 9/26/'6 REV FACILITY SCALE CAD FILENAME JOB NUMBER CCD REVISED FOR GINNA NONE 3G62302 DRAWN CHECKED RESP REVIEWER BY BY ENGR R.E. GINNA STATION ONTARIO, NY MAIN ONE LINE OPERATING DIAGRAM DRAWING NUMBER SHEET REV 33013-0623 3 CNTRL COPY#

~-----A-----~ I 3A u~5-1 i 12-PT'S 480-120V 2 480V-3¢-60Hz BUS 15 3 4 5 6 7 480V-3¢-60Hz BUS 13 8 9 B CAB CD ABC DAB CD ABC D A 8 C D ABC DAB CD A 8 C D

  • 1 1 k 1

/1' 1 ~l i----i-r--1 --1~i~J -~~J-~ ~ -l 1111' J*~~~"';:*====~4Jr--iJ~-----TJ-~1 1 k 1 k 1 1 1 ~ ~ 1 I I I I I I 1' I I I I I I 1' i I l I I I I I I I I I I I. I ) 52/ ')521 )52/ )521 ')521 )521 1.)52; ')52; ')52; )521 ') )521 ')521 ')52; 1.)52/ I )52/ )52/ ')52; 1)52/ ')521 ')521 ')521

  • )52;

)521 ')52; l)52/ ')521 ')521 1)52/ 1)521 )521 ')52/ I)~ I. ~WI"'" ~""~II MCClF~rnO ~~ I'"" ~~'"~ ~~ ""~. "'" ~ [,~'"{' -~I "~~H 1~~ 0~*::~ f~"-' I ~=,,-~,,,_, .,._,,, -~-1 ~*"~"' i '~"I'"'"~'" I~ I""~"'~" i "" I I .L J, 5 J, I I), ! f ! r f. f ~ ! < Y ~y )/ ~ Y ~ ~ Y Y ~ WY'J)/ ~ wy 1wy ~

  • Tw Y,*

Y,

WT~~ Y y

~ Y 10 B K15-2 6A Busl 15 II @I I I TSIC LT.G i I I

~ !

I I I @H'~ ~ IMCCA,"C21 I I I i I 0JSEP-11P I ~ ~ MAJN jMcC el (1(;0\\ SPACE PWR !Mee El (60\\ LTG I WELDING/ MAIN ~ jMcc Al ~ LTG (1(;0\\ (1(;0\\ ~

~b~~~,

P <MCCF> !~fg3 <f[~:of5> ~ E1.i~R~ <MCCB> ~ - 01068 PNL <MCCE> ~ <~~~ogg> -0502 I ~~s Wo~~ <MCCA> ~ <f[~:Oa~> ~ ~ ~ CRD IA -0097F I -0088 A/C PWR -00978 IA SEP-4G -0097E CTRL -0553 CTRL <MCCAVC2> -0106A !rt~ A/C -0097A AB SPLY -0087 SERV IA CRD BUS 13 SUPPLY -0064A STA SERV XFMR 15 COOLING FANS 10905-0566 11 UNOERVOLTAGE SCHEME BUS 15 -0053 3 © 5 CV-8 GROUND DETECTION SCHEME -0050C i MTR CMPRSR WA'rER SPLY CMPRSR <SEP-4G> ROD ROD I oogJA WA'rER AHU AIR CMPRSR MTR GEN GEN B CHLR -00938 C -05638 SHROUD SHROUD 1 CHLR <AAF09> CMPRSR A SET A 'I SET e <CIA02B> gt:J,B B!fG B <CIA02C> I FAN B FAN A A -0086 <CSA02> <CIA02A> <CRDMGA> <CRDMG8> -00838 sJ:i~cH FR ----i CMPRSR -0D83C <ACF058> <ACF05A> CMPRSR -0084 -0083A -007QA -0070B I <SCI038> GE BETZ WATER TREATMENT SYSTEM -00968 -0096A GE BETZ WATER TREATMENT SYSTEM <SCI03A> <43/COHTB01 > I -0085B ~ B TRAIN TRANSFER SWITCH A TRAIN TRANSFER SWITCH -0085A SECURITY I I <43/GEBETZ-B> <43/GEBETZ-A> FEED I I 10905-0563A TURB <ACPDPWW36/04> I I l BLOG I CRANES (OFFSITE POWER) I . I I I I . I <COHTBQ1 > <ACPDPWW36 02> <ACPOPWW36 01>1 <COH~B02> (OFFSITE POWER) GE BETZ WATE: {i\\ii~TMENT SYSTEM (OFFSITE POWER) GE BETZ WA'1R fR~JMENT SYSTEM -0092 <GEBETZ-B> <GEBETZ-A> 480V-3¢-60Hz BUS 16 -0107 -0105 480V-3¢-60Hz BUS 14 I STA SERV XFMR 13 COOLING FANS 10905-0566 15 16 13 14 17 23 22 21 20 I ---i---\\2~---- __l_ ____ _,1_i,:i~----- UNDERVOLTAGE SCHEME BUS 13 -0051 3 I L I L@. 4 13 CV-8 GROUND DETECTION SCHEME -0050A 18 ~-----A-----~

  • ~----- A-----~

B c rA I B c 1 A B c A B c A B c A B c A B c ~ i c B A c B A c B A c B A re I - B A' c B -!-K-16~---6K16-1 K16~-- k k +-1 + -+ ---+ -~-+ ** --*i~1---+ ----1 ~--~+ ~ + -I J k + + + k i -~+~-~~~~1 -~+ + -~ + --~"'°;-.....:J~- i k 1 1 ,!~-'kF---~--i ..... 1 __ _,k,_----,6-~-,4---3 -- 1 ,-! -~-4--,-- 1 ---~4-5 2A ' 2A 2A ~ 1)£1 )~I I ')~/ )£1 )~I l)~I ')~/ I)~/ I) )~/ )~/ )~/ )~I I)~/ I)~/ l)~/ !)~/ )~/ )~I I)~/ I)~/ )~/ ')~I !)~/ )~I )~I

)~I

)~I i) !)~/ !)~/ I)~/ I)~/ l)g/ I I)~/ l)~/ 1)£/ , __ T ~~""'I= ~l;;="'l'w ~l~I- \\W ?oo'"~"" I $",_,,I ITT,._,.. ""' ~"'" I ~'" ~"' ' ~ -*~m~m I '""". '"~~oo ~ ~~~'?"'" 11~ """' ~ '"""~:r,1, ("' ? '"'" I ~'" (~'\\- ' -"~mo f '"~'" + ~ I I ITT"-'~"~j,~"' :)lj; ~f= ' ~"7,w ~"7,w I " I~

h.

I I I ? l ? I ~ I I I + + + :i + r r '1 ~ { ~ . J, I ~*-* 0~1 6 6 ~1 6 2 0~1;_ 4 ~ i I I i1 I I I 1-cT r-_ ~~ 6 b~f (d I I I lcVJf (Aj I ~! ii 1-cT 11 1 I I I I I I T I 1 I K16-7 i I I ( 1' I /\\- I I I i I ILJ' 1' II ~~~p~~ i CVL @ L.J i I I I @ I PPCS l sPkE ~@215 510 Mee c i~! @oo cs@o'o sP!cE i @) ' I I I -oos5 0-JG. 11

  • _:1 I

15 A I 350 ~us 16 TO I_ @~o\\ I @ @~o @oo S0P1A1C0EB 300 @~o 125 @25 ~- @' !Mee Dl SPARE 0110A @ 300 @~o @so I BUS 14 TO 11 ,1* CPT HP BUS 15 TIE 1 HP I P HP HP HP HP HP HP P <MCCD> P _gfJ"98 P P _gfJ"9A HP HP <MCCC> HP HP HP HP HP I BUS 13 TIE 1 I 1.5 v:./A -0061 I -0098B 0098A l -0060 l I T 480-SI SI cs CNMT CNMT AUX RHR CHG CHG PRZR ccw SFP SAFW SAFW CNMT CHG ccw PRZR RHR AUX AB CNMT cs SI I I' II* MCB BUS 16 240/120V PMP B PMP c ' PMP B RECIRC RECIRC FW PMP B PMP B PMP c BU PMP B RECIRC PMP D PMP c RECIRC PMP A PMP A PROP PMP A FW EXH RECIRC PMP A PMP A I METERING j SUPPLY <PSI018> SPLY C1 ! <PSIQ28> FAN B FAN C PMP B <PAC01B> <PCH01B> <PCH01C> HTRS <PAC02B> PMP B <PSF01B> <PSF01A> FAN A <PCH01A> <PAC02A> HTRS <PAC01A> PMP A FAN G FAN 0 <PSl02A> <PSI01A> BUS 16 -oo56 -00738 i <PSl01C> I -0079B <ACF08B> <ACF08C> <PAF01B> -00788 -0071B -0071C -0090 -0072B <PAC07B> -0446 -0445 <ACFOBA> -0071A -0072A -OD89 -0078A <PAF01A> <AAF04> <ACF08D> -0079A -0073A -0055 3 I -0074 -0095A -0094B -0077 -0108 -0094A -0076 -0112 -0095B I I 1 *{0 x/J!v16 I 1 1 1,.,-. CPT 1.5 KVA T 48Q-240/120V Lcv-8 cJ:i5G I

  • -----------------~--~*~---------~-1---

GROUND I I D~~~iN ~~~------~---~-~-- ~~~L~ <KOG018> ! I ! ! I l /!' TO BUS 16 -0102 I AKR-50 )52/EG1B3 I (MANUAL) ~ BUS 16 TO BUS 14 TIE -0062 OG A <KDG01A> BUS 14 TO BUS 16 TIE -0554 S! SPLY C2 PMP C -0075 STA SERV XFMR 14 COOLING FANS -0054 DG A SPLY TO BUS 14 -0101 GROUND DETECTION SCHEME -0050B UNDERVOLTAGE SCHEME BUS 16 -0055 (NOTE 3) ~NMARKEO - ? TYPE 08-25 ACB

  • - ? TYPE OB-50 ACS 25 480V-3¢-60Hz BUS 17 26 27 28 480V-3¢-60Hz BUS 18 Q -

? TYPE OB-75 ACB ? TYPE OB-50 DUMMY ACB UNDERVOLTAGE SCHEME BUS 14 -0054 (NOTE 3) r------A------.. l ~!~it I ~ ~ Ii~ ~ ~ B ~

  • ----'Cr-~-

D B A

2) DRAWING NUMBERS LISTED BELCW BUS UNITS REFER TO CONTROL SCHEMATICS (21946 SERIES) UNLESS OTHERWISE SPECIFIED. SEE REFERENCED CONTROL SCHEMATICS FOR PT, CT, RElAY ANO METERING EIN'S.

5

  • ~--r-
3) OPERATION OF ANY (ONE) 27 RElAY Will CAUSE ANNUNCIATION. OPERATION OF TWO OR MORE 27 RELAYS Will INITIATE A DIESEL START AND GENERATE A BUS TRIP.

MCB METERING BUS 14 -0054 /~ I)~/ I I) 1)52/ 1)52/ 1)52,.; ~c\\'~'i'2ov 1 ~/ (G1B21 \\ (CC1G{2' FP I IH 8 ~~21o i l i 1,.** l l.)s21 i)s21 I)~/ l)52/ ~~m ~ ~rn ~ mM* ~""

4) UNITS 24C, 26A, 28C, JOA AND 300 HAVE EMPTY CUBICLES.

2 PT'S 2-PT'S ~-120V h0-120V I = =

0.

K17-6 6A ~ MCB METERING BUS 17 -0056 K17-2 6A UNDERVOLTAGE SCHEME BUS 17 -0056 (NOTE 3) 1)17~ ! ~~ ~ ~

W I
w :-].,

~ YJ., r r 1 '!' r 1 I l I 3-Cr'S~ 200-5 3 BUS 17 I I s_ubb6~ l, ) I A ! SP~CE I @) I Lf64\\ l! -0111A <J I XFMR T1 ~ j I ~48'1(48DV-3¢-60Hz CV-8 II p <1115 KVA <PXSH007> GROUND I I MO DETECTION l FIRE SCHEME DG B PMP I XFMR T2 -OOSOE SPLY <PFP02> <] ~ 480/240V-3¢-60Hz TO -0080 <] rvy'I\\ 45 KVA BUS 17 1 1 <PXSH001> -0104 I ~~3~~v MCC G SPLY G2 <MCCG> -0100 cw INTAKE HTR B <EHTRCW01 B> -00918 ~ ~og~~EJ=(b3 I <l.. I.. XFMR Tl ~48'1(480V-3¢-60Hz <l I ~~xs\\roi9> <l I XFMR T2 ~480/240V-3¢-60Hz <] r'fYY', 45 KVA I <PXSH004> I s.33 KW 5~ 240V cw INTAKE HTR D <EHTRCW01D> -00910 r r, r 1'

  • x. 1 3-CTStt (j) l

@I L __, __ J 200-5 I A 3 350 BUS 17 TO I XFMR T1 HP Bu:0)ii3nE <I VJJJ 48'1(480V-3¢-60Hz s~~ ~~ <I~ ~~xs~~i6> PMPB PMPD I <PSW01 B> <PSW01 D> I XFMR TZ -0D82A -00826 <J VJJJ 480/240V-3¢-60Hz <lT~x~i11> ~33 KW 5~ 240V cw INTAKE HTR A <EHTRCW01A> -0091A MCC G SPLY G1 <MCCG> -0099 UNOERVOLTAGE SCHEME BUS 18 -0057 (NOTE 3) ITE-J13

REFERENCES:

33013 0623, 1 33013-1952,1 33013-2539 34480-0100 & 2 & 2 MAIN ONE LINE OPERATING DIAGRAM THREE LINE DIAGRAM - 4BOV SWGR ONE LINE WIRING DIAGRAM - PLANT LCAD DISTRIBUTION 480V SWGR INDEX SCM.E CAO FILENAME STATION #13 AS BUILT R~ F'OR NONE 33013-0652 480 VOLT R.E. GINNA STATION ONTARIO, NY ONE LINE WIRING DIAGRAM JOB NUMBER DRAWING NUMBER SHEEf REV 4777 33013-0652

~~~@ 52/ 13SS 3-CT'S 200-5 3 2 52/ A\\/P9C 3-CT'S 75-5 3 3 52/ CWP1A 3-CT'S 300-5 3 50 51 C0-8 50 --@ 51 COM-5 SG SG w A 3DAA5 3DAA5 1-cT..+-. BYZ 100-5 1 50G ITH 1 -CT,.+----, BYZ 100-5 ITH <1 4160/480 <1 ~30-60Hz 5H0P0 MO/AVP9C STATIO~ CONDENSATE SERVICE BOOSTER XFMR 13 PUMP C AA/FA <PC001C> Z-5.75% 21946-0038 1000/1333KVA 1 -CT,.+----, BYZ 100-5 ITH 2000 MO/CWP1A HP CIRCULATING WATER PUMP A <PCW01A> 21946-0031A <PXTBSS013> 21946-0028A 1200 KVAR~E-4400 V, Y VAC CAP/CWe1A 17 4160V-30-60Hz BUS 12B 18 3-CT'S 4000-5 1 9 4 . 52/ 1HDP1A 3-CT'S 75-5 1-CT BYZ 100-5 3 3-CT'S 200-5 SG KA-241 1-CT BYZ 100-5 400 MO/HDP1A HP 5 52/ CP1C 3-CT'S 200-5 I SG 3 I 50 _L~ 6 51 COM-5 MG-6 ITH I I I KA-2411 I I I I I I I I 1-CT BYZ ___ J 100-5 1500 MO/CP1 C HP 6 52/ CP1A 41 60V-30-60Hz BUS 11A 7 52/ FWP1A 3-CT'S 800-5 I SG 3 I 3 8 52/ RCP1A 3-CT'S 1200-5 3 3-CT'S 75-5 50 _1_~6 51 COM-5 MG-6 50 - ---04' 51 \\J COM-5 SG 50P __ ---041 51P --v.J SG ITH I A I I KA-2411 I I I I I I I I 1-CT BYZ ___ J 100-5 KA-241 3-CT'S 1200-5 1-CT BYZ 100-5 50G ITH A KA-241 1-CT 3YZ 100-5 1500 MO/CP1 A HP 5500 MO/FP1A HP 6000 MO/RCP1A HP 9 52/ EF1A 3-CT'S 4000-5 3-CT'S 3000-5 r-@ I SG 3 I 1 0 52/

  • 11 A 50

_j_~6 51 COM-5 MG-6 I I A. I KA-2411 I I I I I I I I I ___ J INCOMING SUPPLY FROM UNIT XFMR 11 SEE 33013-062J, SH... 350 MO/EF1 A HP HEATER DRAIN TANK PUMP A <PCD03A> 21946-0035A CONDENSATE CONDENSATE FEEDWATER REACTOR COOLANT PUMP A AUX BUILDING EXHAUST FAN A <AAF08A> 21946-0036A BUS 11A SUPPLY (52/11A) 21946-0023 3-CT'S 3000-5 20 PUMP C <PCD02C> 21946-0034 PUMP A <PCD02A> 21946-0032 PUMP A <PFW01A> 21946-0030A 21 <PRC01 A> 21946-0037A 3-CT'S 400*0-5 22 87 ~ PERIPHERALS 3 {FOR 11T SEE 33013-HU-1 0623, SH.1 l 3-AUX,.,._~ CT'S 5-5 11 A 2E K1305 '-"../ 2-PT'S T4200-120V 6A '--.--{27-1 27X1 11A 11A TO SS BUS 11 A CV-7 62X2 11 A .t: 1303 '-A../ 1-PT If" 4200-120V ~ UNIT 11 MG-6 TO 3-CT'S 2000-5MR 1200-5 TAP X SIDE OF UNIT XFMR 11 SEE 33013-0623. SH.1 TO SS BUS 11 B (NOTE 3) 6A r~ TO I 3 51 11 A C0-8 A ~------ 81-2 B1X2 11A 11A KF TRIP I ANO I TO SS BUS 11A BLOCK I ~;t-- 1 I I 3 L 50S 51S C0-5 51N 11 A C0-B BUS 11A DIFFERENTIAL LOCKOUT RELAY 21946-0044A ~~TO SS BUS 11 A (NOTE 3) 23 UNDERVOLTAGE AND UNDERFREQUENCY SCHEME 21946-0015 ---7X4 11 A KV-1 AGA 4160V-30-60Hz BUS 11 B 24 25 t 3-CT'S 3000-5 12 52/

  • BTA-A 3-CT'S 3000-5 FUSE REIVEO K1309 T

CPT 5KVA 4160-240/120V V' UNIT 12 26 BUS TIE 12A TO 11 A 21946-0020 3-CT'S 4000-5 13 3-AUX CT'S 5-5 TO 87B/12A SEE 33013-0623, Sr.2 DUMMY ~+-~ BREAKER 3-CT'S 3000-5 FUSE REMOVED 12A I K1304 -.J._, 1-PT If" 4200-120V ~ UNIT 14 3 HAND RESET 'Y 51 I 12A FUSE C0-8 REMOVED 86 12A WL I ,_L 1 I TO MOB FOR CONN DIAGRAM SEE 33013-0623, SH.1 INCOMING SUPPLY FROM THE Y SIDE OF AUX XFMR 12A OR 12B FOR CONN DIAGRAM SEE 33013-0623, SH.2 DUMMY BREAKER (DX12A) 21946-0025 51 N __ J 12A C0-8 BUS 12A OVERCURRENT DIFFERENTIAL LOCKOUT RELAY 21946-0045 41 60V-30-60Hz BUS 12A 14 1 5 c-----; 52/ c-----; 52/ K1307 '-".; 2~PT'S If" 4200-120V ~ UNIT 15 3-CT'S 200-5 TO TRIP AND 18SS BLOCK 3 KP-241 3-CT'S 400-5 14SS 3 50 51 C0-8 WI--~ KP-241 27-2 12A 6A I 27-1 12A ITE-27N I ITE-27N 1-CT..+---, BYZ 100-5 1 -CT..+---, BYZ 100-5 ALARM 27-2 VP9 1 6 c-----; 52/ AVP9A 3-CT'S 75-5 3 50 --@ 51 COM-5 TO SS BUS TIE 11 A TO 12A A 3DAA5 25A --8 CVE 1-CT,+---, BYZ 100-5 SG 50G ITH ITE-27N <1 4160/480 <1 ~3i1l-60Hz STATION SERVICE XFMR 18 1000KVA AA-150"C Z-5.753 PXSHSS018 21946-0029A ITH <1 4160/480 <1~3i1l-60Hz STATION BUS 12A. 128 SERVICE UV ALARM XFMR 14 SCHEME 1500/2000KVA 2' 946-0049 AA/FA 150'C Z-5.753 PXABSS014 21946-0027A 500 MO/AVP9A HP CONDENSATE BOOSTER PUMP A <PCD01A> 21946-0039 27 28 29 30 31 TO 87B/12B SEE 33013-0623, SH.2 2E K1308 2-PT'S tf"'-A./ 4200-120V ~ UNIT 21 2E K1306 '-.AJ 2-PT'S T4200-120V 3-CT'S 3000-5 3-CT'S 400-5 1-CT BYZ 100-5 52/ 16SS 3 KP-241 1 50G ITH <1 4160/480 <1 ~3o-60Hz STATION SERVICE XFMR 16 1500/2000KVA AA/FA 150'C Z-5.753 PXA8SS016 21946-0027B 3-CT'S 200-5 1-CT BYZ 100-5 52/ 17SS 3 DUMMY >-+-~ BREAKER 3-CT'S 3000-5 3-AUX CT'S 5-5 12B >---<lf----1--< w 50G ITH INCOMING SUPPLY FROM THE X SIDE OF ALJX XFMR 12A OR 12B FOR CONN DIAGRAM SEE 33013-0623, SH.2 <1 4160/480 <1 ~3o-60Hz STATION SERVICE XFMR 17 1000KVA AA 150'C Z-5.753 PXShSS017 21946-0029B DUMMY BREAKER (DX12B) 21946-0026 52/

  • BTB-B 3-CT'S 3000-5 HAND 3

RESET 51 ~6 128 12B 1 C0-8 WL I I l 1 I TO 51 N J TRIP AND 12B BLOCK C0-8 /!' FUSE REMOVED I K1310 l...A..J CPT tf"5KVA ~ 4160-240/120V V' BUS 12B OVERCURRENT DIFFERENTIAL LOCKOUT RELAY 21946-0045 BUS TIE 12B TO 11B 21946-0021 27-1 12B -1 ITE-27N : ~~ I 27-2 I 12B -j I ITE-27N I ALARM TO SS 1----1 BUS TIE 11 B TO 12B (NOTE 3) 6A BUS 12A, 12B UV ALARM SCHEME 21946-0049 6A 3-CT'S 3000-5 52/

  • 11 B 3-AUX CT'S 5-5 3-CT'S 75-5 52/

EF1B I SG 3 I c-----; 52/ RCP1B 3-CT'S 1200-5 3 c-----; 52/ FWP1B 3-CT'S 800-5 3 c-----; 52/ CP1B 3-CT'S 200-5 I SG 3 I c-----; 52/ HDP1B 3-CT'S 75-5 3 .--~...., 52/ CWP18 3-CT'S 300-5 3 c-----; 52/ AVP9B 3-CT'S 75-5 3 c-----; 52/ 15SS 3-CT'S 200-5 3 50 --f'.74\\ 51 -\\J 50 52/

  • BTA-B 3-CT'S 3000-5 3

50 _j_~6 51 COM-5 MG-6 SG SG 50 _j_~6 51 COM-5 MG-6 SG Sr, COM-5 COM-5 SG 51 00-8 CVE ~ 11 B w INCOMING SUPPLY FROM UNIT XFMR 11 SEE 33013-0623. SH.1 51 ~6 11B 11B --1 C0-8 WL I I TO TRIP 1 I ANO BLOCK 51 I 11B C0-8 I I I 13 ~ 50S ~ 51S HGA C0-5 1-CT,+---, BYZ 100-5 KA-241 50G _J f----127-4 _ ~7X4 11B 11B KV-1 AGA BUS 11 B SUPPLY (52/11 B) 21946-0024 BUS 11 B DIFFERENTIAL LOCKOUT RELAYS 21946-0044B TO SS UNDERVOL~T-AG_E_A_N_D------------------~-1 BUS 118 UNDERFREQUENCY (NOTE 3) SCHEME 21946-0016 ITH 350 MO/EF1 B HP AUX BUILDING EXHAUST FAN B <AAF08B> 21946-0036B 3-CT'S 1200-5 1-CT,.+---, BYZ 100-5 ITH KA-241 1-CT,.+---, BYZ 100-5 50G ITH KA-241 1-CT,.+---, BYZ 100-5 ITH KA-241 ___ _J 6000 MO/RCP 1 B HP 5500 MO/FP 1 B HP 1500 MO/CP 1 B HP REACTOR COOLANT PUMP B FEEDWATER PUMP B CONDENSATE <PRC01 B> 21946-0037B <PFW01 B> 21946-0030B PUMP B <PCD02B> 21946-0033 NOTES:

1)

- @ 50-DH-350 ACB 1200A SOLENOID BREAKER

2) * - @ 50-DH-350 ACB 3000A STORED ENERGY BREAKER
3) SS -

SYNCHRONOUS SWITCH. SEE 33013-2206

4) FOR
5) SEE AND TRIP AND LOCKOUT BREAKER SCHEME SEE 33013-0623.

REFERENCED CONTROL SCHEMATICS FOR PT, CT, RELAY METERING EIN'S.

REFERENCES:

33013-0623.1 33013-1951 33013-2205 33013-2206 33013-2409 33013-2539 34000-0100 & 2 MAIN ONE LINE OPERATING DIAGRAM THREE LINE DIAGRAM - 41 60V SWGR 4160V METERING SCHEMATIC SYNCH CHECK SCHEMATIC ONE LINE WIRING DIAGRAM - AC ELECTRICAL SYSTEM ONE LINE WIRING DIAGRAM - AC SYSTEM DISTRIBUTION 4160V SWGR INDEX KA-241 1-CT,.+---, BYZ 100-5 50G ITH 400 MO/HDP18 HP HEATER DRAIN TANK PUMP B <PCD03B> 21946-0035B 1 -CT,+---, BYZ 100-5 2000 MO/CWP 1 B HP CIRCULATING WATER PUMP 8 <PCW01B> 21946-0031B VAC ! 1200 KVAR 4400 v. y CAP/CWP'B A 3DAA5 1-CT,.+---, BYZ 100-5 50G ITH 500 MO/AVP9B HP CONDENSATE BOOSTER PUMP B <PCD01 B> 21946-0040 1-C:T,.+---, BYZ 100-5 50G ITH w KP-241 BUS TIE 11B TO 11A 21946-0022 <1 4160/480 <1~3i1l-60Hz STATION SERVICE XFMR 15 1000/1333KVA AA/FA Z-5.753 PXTBSS015 21946-0028B 1/bO AS BUILT DATE RELEASED FO.::i ENGINEER ,__R_EV~ ___ R_EVI_S~E~D _F_OR __ __, DRAWN CHECKED RESP FACILITY GINNA BY BY ENGR SCALE NONE CAD FILENAME 3G065301 STATION #13 4160 VOLT R.E. GINNA STATION ONTARIO, NY REVJEWER ONE LINE WIRING DIAGRAM Joa NUMBER DRA1//ING NUMBER SHEET ! REV 4777 33013-0653 CCD 3 CNTRL COPY#

A B c D E F G H J 1 g\\~ z 11"'1 ~ "' I ~I~ ~ NOTE 10 2 3 4

J 8

D I _CALORIMETRIC r71 TEST CONNECTION 5 ~ 3509 6 J ROOF T

il VENT STACK 14-MV-150-4 (TYP.4)

~ 3511 I J 6 ROOF T 0 ~ I VENT STACK 14-MV-150-4 (TYP.4) ~ 3513 6 J ROOF 7 VENT STACK 14-MV-150-4 (TYP.4) ~ ~ i 3515 6 ~ ~- ~~ ROOF T 0 ~ I 8 VENT STACK 14-MV-150-4 (TYP.4) 9 10 11 12 3" 3615 (H-8) FE pi°1 I TUBING 600-1 3455 NOTE 6 30-MS-600-1 I I I I I I -0 T .~ - -0 T~ 6 _6 di -~ T."'_, -~ TT~ TT~ -0 T *' --~'~!----<<'.",_3_3_01_3_-_1_8_9_3~ 30-MS-600-1 NOTE 6 (B-1) 3/4" 3405 SMS03A SMS04A ri1 3 4" 12362B -.:: N ~I~ '" 0

c r r-...-_,

0 '----+---~ E ~ =<! "' 0 0 _,.I ~- ~N =<! "' "U 0 .;':; (J) 12362D 3/4" 3404 SMS03B SMS04B TT1 3/4" L!.l ~+-D 12365B E EMSOlA EMS01B 3401 SMS06A SMS05A 3/4" r71 12359B E 3400 SMS06B SMS05B m 40 3 4" ,)'2--1£ 10 12368B E c <I1 z " CALORIMETRIC TEST CONNECTION £ <I1 0 N

I::

~§ 3 3/4" 0 L!.l 3505D D 11 2" 11 2" .---I I f-(] I I I ~¢¢ ~ I.:: 0 I - ~ I... f D VENT STACK ~~~12-MV-150-4 1* I I 1* ¢¢ 0 ~.---I--'] LOCAL J> 3413C SAMPLE 'j' 0: (A-8) <I1 fc!:;--=i::-_t-J 33013-2711-1 <I1 X1406A ~ : 0 L!.l '-- _J - 3/4" 12361 L 3 I 1--~---. ~ N 0 0 -+~ ~ D 12361H MANIFOLD I 30-MS-600-1 TUBING 600-1 g: 0.... <I1 3 4" I.:: VJ I ~ 0 I - I g: I~ I I I I I I I I I I 3 4" 1--~-'-t--] L ____ _ A-2 33013-1231-2 NOTE 8 1 1 2" 3/4" 3411S IZ/3411 3411A c f.- 1.... 1---11-------ll--C><l-'---l.f------11-----..,1/---(f-------I~ TMS10 3504D TUBING 1150-4 9001A E-8 TMS09 33013-1893 X9003 '------../ 33013-1236-2 FEEDWATER CONTROL FLOW SIGNAL PZ/4269 "' 8 - 0 3/4" TMS08 TMS07 NITROGEN BOTTLES INTER. BLDG._ TURB. BLDG. 0 \\;' Tt.4S06 ROOF VENT STACK 14-MV-150-4 (TYP.4) ROOF VENT STACK 14-MV-150-4 (TYP.4) 11 2" 0 ~ L_ __ TMS05 ROOF ~- 0 - VENT STACK 14-MV-150-4 (TYP.4) ~ L!.l D ~ T

il 3510 6,.

T

il 3512 6,.

~ 1 1 2" t 0 I -"' 'i'... 3508 6 J f D T

il I

-0 T~ _;_:...__'VENT STACK 12-MV-150-4 LOCAL SAMPLE ~ 6 T T ~ ~ I -0 T~ ~ 6 --~ T T:.. 3514 6 T 1-MD-150-4 (B-10) E--1.... 1---~---lL~3~30~1~3~-~2~71~1~-~1...../ 3412C X1406B CT-.--~1,-~M~S~-~60~0c-~1-.-----*"'t--'3v

o.
:

< VJ le "' I g.... 3671 TEMPERATURE COMPENSATED SUPPORTS (TYP.4) N ' INTER. BLDG. --+- TURB. BLDG. N - 33013-1232 351~ IITl lfil 2 3 FOR CREVICE ZMSOB 3 4" 2" CLEANING I ri)ir;J-j I f{j}i I 1-----"N+::M7SO:,.::B __ -C-::l-r2"-",--.--f'--35*2... 1A1---'] ['--I 1---~ 2" g I 3673 (1-1) 33013-1233 MAIN CONDENSER A 1" 1" 3675 (1-1) 33013-1233 MAIN CONDENSER A 11 2" 3605 3674 LMS29 ORIFICE BLOCK r ~ 1" ~525 NOTE g ~ P.> 3523 t.1 ~ ~'i ~<ff ~ ' ill ZMS09 !.{, '? H::-:1-1 I f{j}i 11--=-D,iNi"'M'-"'S0:::.:9'---1::.:::J_J N ' 3607 NOTE 9 " ffi 3603 NOTE If-II..._--' 12 35218 3/4" 3609 1" 1" 3617 ~ 3676 I 3677 3683 1" 1"-600-1 NOTE 9 3604 3/4" 3608 r1' :x:H I f{j}i I NMSl 9 360 ZMS 1 o 3602 1 2" ~ -.\\, 1f D NMS10 3/4" (1-2) _,---~~---. 11 2* 33013-1233 P~~_u_[)f;:<<JJ I ill I 1" 2" 3616 3524 3522 1" MAIN CONDENSER A 3610 N N VENT STACK 14-MV-150-4 (TYP.4) TEMPERATURE COMPENSATED SUPPORTS (TYP.4) 2" r--___,, __ _, 11-J 35208 r 1" ~ ~~3_67_0 _________ ...J 0 TURB. BLDG. INTER. BLOG. N ' 3" 3" 3614 2" (1-1) 3678 ---1, 33013-1277-2 E'-----L,-_..,___, "' "F--'--ft-'-f::<<:J-...J ~ ~--TURB. BLDG. YARD (C-12) ~ 3672 I -0


~~------~~~-----~~.--------<<'."~~3_3_0_13_-_18_9_3_~

T~ 30-MS-600-1 NOTE 6 (C-1) 33013-1232 ---~-:i

  • ~

IITl 3 351~~--+ 35~ [§] 2 3 'if NOTES:

1. FOR GENERAL NOTES, REFER TO DRAWING: 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDES 33013-1231 REV. 44.
3. SAFETY CLASS BREAK POINT FOR EACH VENT, DRAIN, OR TEST CONNECTION SHALL BE AS INDICATED AT EACH CONNECTION POINT.
4. ALL SAFETY CLASS LINES ARE SEISMIC CATEGORY 1.
5. DELETED
6. IN ACCORDANCE WITH EWR 5114, 30" MAIN STEAM LINES FROM PENETRATIONS P401 AND P402 TO THE TURBINE ARE HIGH ENERGY LINES.
7. DELETED
8. THE EIN REFERS TO THE NITROGEN CYLINDER LOCATION THE NYTROGEN CYLINDERS ARE INTERCHANGABLE.
9. LINE SPEC. 600-1 ARE STILL IN EFFECT, PIPE MATERIAL IS CHROME MOLY, P22.
10. RADIOGRAPHY SOURCE ACCESS PORTS ARE 3/4", 3000 LB., SW COUPLINGS.

3410S ...--+-'.:"=+L~- ~"-L-- - _L _ - - - -i

~ I I

N> "'I ;<:; "'1 0 ri; N I~ I !f ~I~ I 12370B ?!I§ I I I I I I I I I I IZ/3410 6-MS-600-1 14915 3410T3 3410A 3/4" l~I 9006 3 - ~

11. DELETED
12. SPOOL PIECE (MID# 5008869) AVAILABLE FOR CONNECTION BETWEEN 3521 B AND 5722G. ~~----~--~--.----~----1

{llJ:s' CAD ALE NAME 33013-1231,1 CONSTRUCTION JTC><P~l~"l1--..-~~-.-~~-3~1r4-*~-,-~.---,~--, 9012 0 0 N LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT F"OR CONSTRIJCTION BIOO!NG PURPOSES ENGR. AS BUILT DATE RELEASED FOR I L---------~ I STEAM GENERATOR B 1 2 (F-5) 1 - - - --l 33013-1236-2 > I I I L------~ ,------~ I ~ I PZ/4270 I ~ L-----------------~ I FEEDWATER CONTROL FLOW SIGNAL 3 4 5 9000A X9002 TUBING *I* 150-4 E-12 [=3~3@0~13~-~18~9~3~:::::>----11--CI-----' 6 7 <DI°' rr oO NOTE 8 8 TMS16 Th!S15 TMS14 TMS13 TMS12 TMS11 NITROGEN BOTTLES 9 10 11 GINNA STA. R.E. GINNA STATION JOB NO. NONE MAIN STEAM (MS) (SAFETY RELATED) P & ID DRAWING NO. EWR 3391E 33013-1231 SHEET 1 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 VENT TO ATMOSPHERE 1 I 2 (E-5) 33013 1231 1 (H-9) I 33013-2285 (CLOSE) (1-9) I 3 I 4 I 6MS6001 I 33013-2285 >~--i-L -~I'" (OPEN) 1/2" PAF03 TURBINE DRIVEN AUXILIARY FEEDWATER PUMP (SEE 33013-1237 FOR PUMP DETAIL) SAF03 TDAFWP GOVERNOR SEE NOTE 5 "'J TURBINE t I f I f OP/9519E NOTE 5 I c___J 9519E SEE NOTE 5 ! l I 1/2" (G-6) I 33013-2285 LEAK OFF Y' \\7 YNOTE 4 3 \\/ 1 HAND .---_,,,,~;,---,--i-----D-~-,1-c-E'l,-------~-L-J1WHEEL L...',3652 TRIP LATCH ~* t (G-6) (G-9) µ I 33013-2285 I 33013-2285 ~ le__ _____ __ TRIP CYLINDER TRIP DRAIN LATCH HOLDING PRESSURE 3-MS-600-1 I en I 0 0 I 5 I 6 7 3570 I 1/4" 600-11150-1 150-2 I 3/4" ZMS16 .---------~-----<'i--t>:::J-l'f---1/<AJ----~T ' 3586 " 3586A I 3/4" '(

\\538 3634 3642 600-1 i150-1 150-2 1/ 2" ZMS15 1 112.. ~

,--------'-----+'1-!><J-fl--~';:-<f-----IT 1--1~1~'2'-'l"~.l---tx.1-'-"-='-l---l " 3585 " 3585A 363l 3633 V 600-1 600-11150-1 1/4" 3641 600-1,150-1 150-2 0 I N ZMS14 ~---------------------------------------1~/_2"_,,f-t;<<::H'l---{':0.:::-l------IT 1-----1*~-~*--i:x*::i-~1/~2~*-l----l ' 3579" 3579A 3636 3632 Pl 2935 c OJ z Gl ~0-1 3640 1/4" I 0 I g I 600-11150-1 150-2 N (J) 0 0 I ~ 1/2" ZMS13 - J 1/2" ~--------------~---------------------------1'1-l><H'l----C:--(l------IT 1----l""'}-'-~-C><}-'-=--l---I 11 3574 11 3574A 3635 3631 8 4" 1/4" INTERMEDIATE BLDG. TURBINE BLDG. (G-10) I L---~: 33013-1277-2 Pl 2512 600-=! 11.50-1 600-,11120-1 1/4" ~ 3639 9 I 3/4-150-2 3570D (J-7) I 33013 1237 LUBE OIL COOLER SW DISCHARGE 4" ___) LOOP SEAL 1" 125-1 1/2" ~---------------~---~-----------<! :1---~-::-:::r----1:><~}--------------------'--------------------------' 3S70B 3570C 4" 2 1/2" 2 I 3 I 4 I 5 I 6 7 I 8 I 9 I 10 TCD04 TURBINE DRIVEN AUXILIARY FEEDWATER PUMP QUENCH TANK 10 4" I 2 1/2" 1" I 1 1 I 12 NOTES:

1. FOR GENERAL NOTES, REFER TO DRAWING:

33013-2241.

2. THIS DRAWING WAS CREATED FROM 33013-1231, R8/. 44.
3. SAFETY CLASS BREAK POINT FOR EACH VENT, DRAIN, OR TEST CONNECTION SHALL BE INDICATED AT EACH CONNECTION POINT.
4. STEAM LEAKOFF IS CHANNELED INTO A COVERED FUNNEL THEN TO THE FLOOR DRAIN.
5. SEE FCMS DESCRIPTION OF EACH EIN FOR FUNCTION.

REF. DWG.: LB112541. 1 1 &ORIGINAL 2;11;13 a1u1r~ '"'".*;-o: a 11/13 CAO FILE NAME 33013~1231,2 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR. '~ GINNA STA. R.E. GINNA STATION SCAt£ NONE JOB NO. EWR 3391E MAIN STEAM (MS) (SAFETY RELATED) P & ID DRAWING NO. 33013-1231 SHEET 2 OF 2 CCD 01 CONTROL COPY # I 12 REV. A B c D E F G H J

A B c D E F G H J 1 (1-1) < 33013-1233 MAIN CONDENSER A 2 3 2943 (F-3) 1" <~_3_30_1_3_-_1_9_0_4~t-----------~ GLAND STM. COND. (G-1) 3/4" <~_33_0_1_3_-_1_2_3_3~r---~-----~~ .. 1-------- MAIN CONDENSER A A-7 --C><f-1 33013-1918-1 X3558B'--------___? D 0 " OJ ~ (/) D 01 (D-1) 3/4" 2911 4 ,,,--~-G--- 7~-,X15352 33013-1894-2 D 01 ED 01 D (!) cu 5 M 3601A SEE NOTES 6 t;l AND 7 0 3869 "' cu <O 6 LMS06 (A-12) 33013-1231-1 MAIN STEAM SYSTEM 30" 36" --{.><J- ~ 33013-1918-2 > ---PA __ N __ E __ L--~ X3830 11000 y X3518 (G-12) 33013-1231-1 MAIN STEAM SYSTEM (G-1) 8 33013-1918-1 HP EXHAUST TO MSR 1B (B-12) 33013-1918-1 X355l MOISTURE SEPARATOR REHEATER 1A (E-12) 36" s INTER. BLDG. TURB. BLDG. 1" 1" TC E----i-r---i---.---j TC 8" 3571A 8-MS-600-1 8-MS-600-1 3571B I (/) 33013-1918-1 X3550 MOISTURE SEPARATOR REHEATER 18 X3552 (E-12) 33013-1918-2 MOISTURE SEPARATOR REHEATER 2B (B-12) 33013-1918-2 H-11 33013-1921 X3249 MAIN CONDENSER B 8-MS-600-1 0 D I H-6 150-4 6"r----' 2* 600-1 600-1 C-1 Ol 0 ~ .j>. I (/) I Ol D D I X3884 150~0-1 01 D u '-.. I .J>. N ~ 600-1 X3885 1-1 33013-2249-2 33013-1904 TUBING 600-1 E--t----t~----l 3856B "' "' ~ 01 f11 4" w D 4"' f---~--------------~----j'-.. C-1 600-1 E---+-.---~--~ (H-1) 33013-1904 (F-1) 3851 "' <D cu D F-1 TURBINE SHELL HEAT FLANGE (TYP.) 11 2" 33013-2249-2 F-1 33013-2249-2 GLAND STM. COND 11/2" TW KMS02 HP TURBINE (G-1) 1" <~_33_0_1_3_-_1_9_0_4~f----"'-- 3870 3545A 1" --j1--1::x:1---~~----11-------'---'--JL GLAND STM. COND SMS19 MAIN CONDENSER PRIMING AIR EJECTOR A 3837A VJ cu "' "' L!J 600-1 D TUBING 600-1 E-+-__,,,...___,""1.;--1 3461 vE--+..._ __ _.,,._. 8534 VE-..4-1 3526 2* 600-1 L---i 6" 150-4 (H-5) (!) 01 L!J TC 3 4" 7 2" NMS17 D <D ~ 3846 "' 4.. w D 2 1/2" 6993 TURBINE SHELL HEAT FLANGE (TYP.) TUBING 600-1 D °'-!-----' 1* L 6" 1" 3658 4* L 8 X15353,--~ 1 -~7~---.... --c><t-t 33013-1894-2 (1-7) 33013-1894-2 D 0 .j>. OJ 9 10 2942 2945 (1-2) 3/4"


~~-------------------;___33_0_1_3_-_1_2_3_3~>

.j>. 600-1 C-1 3/4" 'I ~ (/) 0 .j>. 2940 NOTE 5 C-1 33013-2249-2 (D-1) .-----LL---<<:33013-2249-2

==='==~L========~L~ 3/4" 3/4" MAIN CONDENSER A J-2 33013-1233 MAIN CONDENSER A G-1 33013-1233 (D-5) MAIN CONDENSER A ---;L>--------~L------~L---~<33013-2249-2 (F-1) 2912 11/2"


'-"-=--------..... 0------------ll 33013-1233 11/4" (A-1)

--;L-------tL------tL---~<33013-2249-2 O> ' (A-1) --~L------~L-------<L---~<33013-2249-2 600-1 C-1 600-1 MAIN CONDENSER A (F-3) ~---f><l:- 1------~ X3883 Ol D ~--<"' ~ 8" t 36020 8" f71 D 600-1 C-1 ~ ~I~ '------r--...e----j cu Ol 3857 1 1/2" (C-1) 33013-1918-2 HP EXHAUST TO MSR 2A (J-1) 33013-1904 X3886 1 1/4" (F-1) _J ,-----(--F--_3--)-----'--'-'-'-------11 ... ----------1~3--3 0 __ 13 __ - __ 19 __ 0 __ 4~> GLAND STM. COND. ---LL-~i<:::33013-2249-2 (F-3)


+---~r(:33013-2249-2 L

L I (1-5) ~. tL,.----<< 33013-2249-2 1 1/2" (G-1) _____ ___::::::===========:::_ ___ _'._:.!.;.'.:_ __ -l... ~------------1 33013-1233 (H-1) ~----


tL---<< 33013-2249-2 MAIN CONDENSER A (1-2) 3 4" NOTE 5 D

D cu L!J D D 0 H-1 33013-2249-2 8513 L!.I D 3/4" NOTE 5 3543 MS-150-2 SEE NOTE 9 33013-1903 33013-1922 ATM. VENT HOR. <D 01 3580 g: I ~ 3581 <D 01 33013-1922 ATM. VENT HOR. (H-6) 12* 600-1 1-1--------------------------'-"'--"'""'---'----------------j 33013-1918-2 <D (") FLooi0/ DRAIN. I 0 I 150-2, I.600-1 3 4* 1/2" 3420 600-1 TCE... 4--1"' 3421 1' (/) I D D I <D rn 3-MS-600-1 4* D-10 33013-1896 3-MS-600-1 1/2" 3424A 11014 600-1 TUBING 1/2" 1/2" ,---------~.----:-.-'"--c-1-:---r-----i l-.... 1-j ~ ~ ~ 3424B <D (]1 2" <D 01 cu x 33013-1896 x15437'--------___? F12515 9518U [-----, 3299B 2" NOTE 5 <t~ ~ N '°to '----, "' 0>D 11 ;2* NMS14 01 ~~~ 3582 3584 <SiJ l~n' ~ ':::; 1 1/2" 0> ATMOSPHERE ~0-1 '---9>4-- D A-4 3527A "'.-.-.c 33013-1251-1 L__Jr'j ___ ~ ~ ~ ....._ _____ _.X4798K c--------<~-~ ~ "';. £ ECD07C AIR EJECTOR SAMPLE COOLER 125-8 150-1 2" 3215 .j>. " cu L!J i;; D 150-1 C-1 ~ i ~ 1/4" j

J

~16 TI1M ~t -j[><J 3* ~D _ 3231 9519M v 1/2" £ ZMS03A Tc-------~ 3/4" (F-4) JJ _;...__~~--:-i _ ___,I L!J 33013-1251-1 y \\2Ql><J I...

  • I

~1'71 <D <D <D D N U 3234 3233 3232 3231 1/2" 1 1/2" 1 1/2" 1 1/2" .j>. .j>. .j>. s FLOOR DRAIN LOOP SEAL 4* ~ _,.-- 2 1 /2" ---'--.-----------1----, ~~jj I 3236 ~* ~ 3* X3214 1 (A-12) (G-8) < 33013-1233 MAIN CONDENSER B (D-7) 33013-1252 SS ZMS03 t--'--~----; ECD07B MAIN CONDENSER AIR EJECTOR AFTER COOLER 1--~ 1---~1-~M~D~-~15~0~-~4 ___ __.;l><Hlf-[l};ll-{><r------1~"-_, 3235C 3235 2 3 4 150-1 C-1 Ol D D I -i c ~ z G) 5 0 0 I -i c OJ z G) 3214A 6 L!J 1 /8" L!J 1/8" .j>. 1/4" ECD07A MAIN CONDENSER AIR EJECTOR INNER COOLER 7 4-MV-150-1 4-MV-150-1 4-MV-150-1 4-MV-150-1 1-MD-150-4 8 9 .j>. D -i c rn _J~ S f o N I ~ 0 I STEAM DUMP TO CONDENSER 1B (A-6) 33013-1904 GLAND STEAM SUPPLY (H-11) 33013-1921 MAIN CONDENSER A H-11 33013-1921 MAIN CONDENSER A 1----_.~j TC VJ 11034 j ~ c TC E1-11~011131-5-~-~-I ~ i: N~O I ~ 10 (G-11) 33013-1921 MA,IN~C_O_N_D_E_N_S_ER_B__. X3244 G-11 33013-1921 MAIN CONDENSER B X3246 (G-8) 33013-1233 MAIN CONDENSER B 1 1 12 NOTES:

1. FOR GENERAL NOTES, REFER TO DWG.: 33D13-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DWG. 33013-534.
3. IN ACCORDANCE WITH EWR 5114, 30" AND 24" MAIN STEAM LINES UP TO AND INCLUDING VALVES 3544 AND 3545 AS WELL AS THE 12" LINES UP TO AND IN-CLUDING VALVES 3532 AND 3533 ARE SAFETY SIGNIFICANT CLASS FOR HIGH ENERGY CONSIDERATIONS ONLY. CLASS BOUNDARY FOR ALL BRANCH LINES IS AT THE CON-NECTION TO THE MAIN PIPING.

ALL OTHER PIPING ON THIS DRAW-ING IS NON-NUCLEAR SAFETY CLASS.

4. PT-485 AND PT-486 ARE CLASSI-FIED SAFETY SIGNIFICANT BECAUSE THEY PROVIDE TRIP SIGNALS TO THE REACTOR PROTECTION SYSTEM (RPS).

PRESSURE BOUNDARY IS NON-NUCLEAR SAFETY.

5. LINE SPEC. 600-1 IS STILL IN EFFECT,EXCEPT PIPE MATERIAL IS CHROME MOLY, P22.
6. THE MOTOR OPERATORS ON VALVES 3601A AND 3602A ARE ELECTRICALLY DISCONNECTED. THE VALVES MUST BE OPERATED USING THE MANUAL HANDWHEEL.
7. VALVES 3601A AND 3602A ARE IN A THROTTLED POSITION.
8. STAINLESS STEEL SPOOL PIECE WITH FLANGES FOR RADIATION MONITOR.
9. LINE SPEC. 150-1 & 150-2 IS STILL IN EFFECT, EXCEPT PIPE MATERIAL IS CHROME-MOLY, P22.
10. PLANT ORIGINAL SCH.40 PIPE DEVIATES FROM LINE SPEC. BETWEEN VALVES 3545 AND 7792 REVISED PER

~ ADC-16-0126 CAD FlLE NAME 33013-1232 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES '1S BUILT DATE RELEASED FOR c ENGR. GINNA STA. R. E. GINNA STATION SCALE NONE JOB NO. EWR 3391E MAIN STEAM NON-SAFETY RELATED (MS) P & ID DRAWING NO. 33013-1232 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 2 I 3 I 4 I 5 I 6 7 I 8 I 9 I 10 1 1 I 12 EXHAUST HOOD SPRAY v ©-~ ~ EXHAUST HOOD v ~ SPRAY ~ (E-7) [~3~30~1~3~1~8~9~6==~>---~,,"'---------i x1543o1 (F-7) " "'I [~3~30~1~3~1~8~9~6==)>----lf-,,_l-l X4Z63H11 I (G-6) I 33013 1236 1 I FW PUMP B RECIRC. LINE (E-7) ~ I 33013-1896 X 15431 L......:...:..:c..(.c:E _-7..:.).:...:..c___,,, I II II 4" ~ D*

  • gA.._

L'.I D ~ 4263 X42B2H11 33013-1896 (E-6) I 33013-1236-1 MAIN FW PUMPS RECIRC. DUMP LINE ~ PT [ill o' 2020 -J TC L'.I 6" v£. ~t;.. ~,_@ '4262' D it;' ' TUBING 300-1 (A-5) 33013-1924 (F-5) 600-2 I x5B11 1 PG &:ii ~ f-'-IXl-**__j__~---+-r*~r-14*--1:iTI] 6402 11253 9523G - [J~~~~==)rJ,10f*~* v I 33013 1924 X5615 {J-2) 600 8" v ~ I 33013-1924 X5619 .---~(~B_-_11~)-,1.:.0-1 7

4429

33013-1922 (B-7) 1 1/2" _j 1r-:ru~:14-....>--...:i1.:..i* x:3863B1 33013 1904 NCD02 KMS01A 600-2 (B-6) 3-BD-600>12 I v ~ I 33013-1277-2 X5767 DRAIN HEADER 1 /2" I 33013-22s3 '-J (F-3) 20" r SEE NOTE 4 (B-3) .J er


~

IDO v ~ I 33013-1923 / '- X4143 ~ "'gl (J-1) ECD01A CONDENSATE HEATER 1A ECD02A CONDENSATE HEATER 2A

...::: : 33013~1277~2 I

X5768 (F-3) ~ ,r-3_3_0i1c..3-~19_2_3-~'>- lO-HD-600-Z x414s 1L.....::..:.:--'--'.:..:::c=----- (1-3) I v I 33013-1923 X1919L.....'-'-'-------..../ (H-10) I 33013-1905 GLAND SEAL LJ'>/1 WATER RETURN 40528 (G-10) -........_ 6-HD-600-2 3-MD-150-1 J---......---1 '4o52 1-FW-900-1 I. - 4361 133013-1236-1 FW DRAIN (1-4) - {J~~~~==)>-------J1_.1_1L/~2=._l:IH~S=.1.c15~0~4~--i v ~ I 33013 1915 X7974 600~-~1c-i_,,6=00-2 TYP. 4 TYP. 4 ECD03A CONDENSATE HEATER 3A (B-11) ~I ~>-_....1__,,1~/2~"---+---------~ Xl7S6 1 33013-1232 / (E-11) 1 1/2" -,r- ,-~-~--....., v ~ I 33013-1232 >--'---'-....'.:.---+---------~ X7792 (B-1) 3/4" - -,.--~~~--..... X2911 I 33013-1232 >-__--'-'-----+---------~ (B-11) -~-~--..... 3/4" ~ I 33013-1232 />-----'-'-----+---------~ X2912 IL__ _____ _/ (E-7) . -,.--~~~------ v ~ I 33013-1894-2 />---/1-,,-------/1-,,--, X15005 (H-1) I 33013 1234 SOV4316S (J-1) v 33013-3124 3/8-C-2 ~v-::: X9500S of::,_tv (C-9) OT ' ---'*' 2 1/2" - ,. ~~ 4-rl-i-!... r---'-'--'-'~-~ I 4.. ~ ~ I 33013 1908 3 L:'.J,....,_7"T"4-l:0>4d2 Hf-~~,~'-,[ 1>40<4'1-3-.l,---j NORMAL MAKE-U:/ t;., 431 TREATMENT ~ ABANDONED 2 1/2-DW-150-5 ~ IN PLACE 0-:;:-L.........=2_....,._ _____ _J ~ 600-1 4044 1 o" 1 1/2" ~ ,600-1 (F-8) ~~<~c-_8~) __ 1 1 /2" \\ ~ ~ I 33013-1231-1 I t..-' -.....i v~ 1 33013 1231 1 X3616 X36051"-600-1(NOTE 5)'.:\\ '\\3/4"-15~2(NOTE 5) (E-11~) - (D-8) 33013-1232 1 v ~ _ 1[~~~~~~),_j_j X3542 v ~ 1 33013 1231 1 \\ 600-1 (A-11) X3684 (A 1) 600-11 3 /4" 33013 1232 1. 1X2909

  • ': 33013-1232 3! 4" r150-2 (A-11) xfo10 c___ ____

L3*i_/+/-'.4':_' _\\l_,/-:;:;;-;-:~~-;--i (E-1) 150-21 33013 1232 5 7 I v ~ I X3601 33013-1232 !3/4" (J-6) k---<~~~;=-;--i1. - \\_ 33013 1918 1 'X4181 (D-10) 3/4"-150-2 (NOTE 5) ,.--~-~--..... 4" ~ ~ I 33013-1919-2 >-:::_-I X2423 (H-10) (D-10) 4" ~-~-~---., * '[~~.:2~~!::::),._+/-4"=---{I--_:.--<,.- 33013-1919-1 v I 33013 1919 1 1)(24()7 X2415 (H-10) SEE NOTE 7 ~l-~ _ ____'.41:'.'."--<~3~3;;;0-;"13~1~9~19;::::2;--i:f--x1-::.2<431 1 0 DRAIN HEADER I 2 I ECD06A MAIN CONDENSER A 3 ~* r -'°a

a

~ <D, r: CJ> co~ l -l y ~ 9519P 1 1/2" (C-2) l---=~"l------::::;i:::::---ll-"--<C~~~=1 - ,, Q " 33013 1896 I v ~ X15427 TC 2621 4066 ) rc-n 8 --~~~, 1" ... : I 4333 X1S423 33013 1896 ] 1 /2" 1-....:2::..:1:.t.,/,::2_" --1 4065 11/2" 4062 1" I ; ;.. ~ I 4334 II TC 2622 4063 KMS018 LP TURBINE B 1 1/2" Tl 2015 TAH TAH 2002 2003 TRAP HEADER 11 /2" > 11/2" 3/4"-150-2 NOTE 5 8"----:1 (J-6) E---~L<_~~~*. (G-1) 33013 1918 2 1 v ~ 1 3/4" X4182 x3'5?5.__3_3_0_13_-_1_2_3_2 _ _,... J 150-2 3/ 4.. (C-12) / (F-12) f-'-'.\\_--<, 33013-1918-11 * - 3/4" X3625 L.:.J I 150-1 1" ' / (F-3) X4403C 4067 11 /2" 11 /2" 4064 150-1 l fB-8) 1 1 /2" [r~~~;~==)>-lli-11---' v ~ I 33013 1922 X4430 ~3~3~0~13~1~9~1~8'=21__,:>-=-'-j-l 150-2 X3534 150_ 2 --~(C_-_1~2)'---- 3/4" I \\_ 33013 1918 21 " ~ (F-12) I *..: CA 33013-1922 I.. - TRAP HEADERf 3/4-300-3 l"\\ 150-1 (F-5) (E-4) ~:..s_;,:::--1~3;3~0~1~3~19;;:2;:2;--i: v / 33013 1904 X4404C ,..-- 150-1 (F-10) ~ A_" ~~--~-'-'.L_~ / 33013-1922 I ::- ...__::..::_:...:..:c......:..::..::::_ilx4447 (G-11) I

  • 13/4-300-3 j

(C-4) I-'--<" 33013-1904 13/4-300-3 t. (F-4) 33013-1904 33013-1922 I...--... X4443 °' I I Xz922 I I v X2930 8" TRAP ZGS03 (J-5) ~r-<::~~~~~==J-' - _J I 33013 1922 'x441'4 1 1/4-300-ll (B-7) 1112" 1" 1----:...:..L-=-----11-----'----<C 33013-1904 6* ,..,~-l,,_.'G:...-...:1co2,,_)_~ 1 LGS02 ~ 33013-1922 I... '-:.:.:~_.:.:..::..:: _ _J X44 73E (A-6) 300-1 8" I .--=-'--"--I, 33013 1252 6 v X3956 6" ,~~(~H-_1~) __ 300-1 >--Cx":J-- i-.:=---'----l, 33013-1234 v ~ 0 ' X4055 CONDENSATE REJECT fH-1\\ 1--3-0-0---1-~2~"__,:[=3~3~0~1~3~1i23~4~==>--;;:~~:t-X4053 18 CD 300 1 v (G-11) 33013 1235 GLAND STEAM CONDENSER (A-3) 150=1., . *c ,~~~~~=>-.Ll ...-11~* x44DlAI 33013 1922 !G-8) 150-1 - r~~~/4!'.'..L"7~ ~ L33013 1922 X4448 (G-8) [~~~~~:::::~2J11/~2* y ~ l 33013 1922 { X4444 (A-6) 150-1 ~ : 33013-1922 >-1'-.. ~-I X4402A ,-----'ri""B_-,,_.9 le____, 1.. I 33013-1904 -->-c1-- , 11/2" LGS03 3/4" X3627 33013 1918 2 j 150-2 150-2 1114.. (B-8) (G-11) ~-.... 33013-1918-21 v ~ 1/2" X3667 33013-1903-2 j 1" 1 "' 150-2 150-1 er-~" (J-3) I 8,, 1 1 /2","' 8,, \\_ 33013 1904 I XJBiJ2 9.

~_

9.:,.,~, 2 1 1/2" 150-2 150-1 (l-l) SEE NOTE 5 c 33013-1918-2 I (A-7) L'.I l.!..J 1 :::. 0"---<_,...~-3~3~0-1~3~--1-92-4--,: I


'xs61o 20" 600-2 v

X3620 X5643 20" -~(~F-_7~) __ 10" I , --"'~-1 v -,.. 'L..:.3..:.3..:.0..:.13:..-_..:.1 9:;:2:..4..:.___,...-.>- X5614 j 600-2 (J-3) 6-HD-600-2 ~-~~~---.,

  • L.....--"===="----<, 33013-1923 I * -..,

X1923 (F-8) (B-6) 11/2" 1" l----:...:..L-=-----11------'--<, 33013-1904 LGS01 ~ (TI\\__ ~ rt;,. ~ 1/2" ~*~ / 14" 14" 18" 14-CD-300-1 Pl 2008 ~ l~'~: 7 _ _,__{SEE NOTE 4 o~ ~'-.... {fl'. l.:6~":__-<:=::~~-;;_~~=1 I 33013 1922 , x.44l4E (J-10 ) ,r--~-~-~, 8" v ~ L~3~3~0~13~1~9~2~4~_,;>-~J----j X5618 600-2 (G-1) 11 /2" I 1----.---'---I 12" v 1/2" * ,} '3960 (C-12) 1-CD-300-1 I ~-----------!, 33013 1909 11072 v ~ 3/4" r:.. v L: 4243A 1/2". 4243 ---© 1/4" Pl 2551 Pl 2011 (F-6) 11 / 2" / 33013-1903 \\.-=:::: x565'3 I

  • l 5D-2 NOTE 6 Pl 6403 v

OXYGEN ANALYlER 14-CD-300-1 3963 't' ~--~=~---~--I FT ~, 7 1104BB

, cL 2003 0

OJI

c f!'

11;2*~~)-~ ~ 33013_ 1903 o--..***---1 TUBING IPIPING 'x564'8 1* *104-9 150 2 ~1 7--" ~ ~--~ q. *[ '2-~~(=11-21~1)~==>----====---~8:'.'.:I.'.-;:,i,_--l ~ ~ v ~ I 33013 1923

I H,

~ 3965A X5065 Pl 2012 300-1 TUBING Pl 2010 300-1 ........ 12" 1/4" - 1/2' ~ 4242 3/4" ~...; :Jv 4242A X4122 ~ (B-6) TE 11/2", f-'-\\'-<::____:3~3~0'!_1 :'._3 ::.1.:19~0~3'._j

  • 6406 3

TW 2013 (J-11) ~rw '~m--'>-,-_j x:322S 1 33013 1232 __ I I \\_ 1X1967 NOTE 6 (A-6) r-:- 1 ~ 1 l\\2~"<::___*_:3~3~0'!_1::_3::_i_:19~0~3'._jr-1><*::i-1 \\_ 'x19n NOTE 6 (C-6) L!-1 _,__, 1 1~2r"<:33:3\\Co~1 ~3 ~19:lCoi33:---i * ,..._ _____ __JI X-196'2 (D-6) C7 11 /2" _,,,~--""---""'--~, - 33013-1903 ~------X':f 959 TRAP HEADER D ' Pl 2056 4249 (H-10) 11 / 2" 33013-1903 \\_1~-2 (H-8) 11 / 2" 33013-1903 \\_1~0-2 (E-8) 11 / 2" 33013-1903 TT 2060 I 'x566'3 I 'X5658 I X5638 11 /2" ,..,~-("'E'---'-11'--'-)-~HD<l-33013-1903 I ~------'x5633 TRAP HEADER I 4 I 1-MD-150-4 _j 12" ~ 3965 I 12" ~ E 1 /2" Pl 2013 I 0 1/4". - 1/2" 1/2" 4247 ~~---:J ECD04A CONDENSATE HEATER 4A E.--1*~-I--{ 9500C ) <}- 1"

J TC o

Pl I 4246 - I A" / (J-10) ~ r 8 300--1-~-~-2-0-1 ~4 1 33013-1252 1f-fX v~:1-- ..._ _____ __JX3502 1 /f." - 3967B Pl 2057 v ~ 4248 v E ~, 9500B 1/2" ECD04B CONDENSATE HEATER 4B 11/2" TT v E-1.IMIH--i 2061 3997B ~..; :Jrc 9500A 11/2" ~,, I-" ~,.. _....... y m->. NJ ffi~ ~ TW 2014 3997A ~* ~~ i>* ~ ' '1---...1.....:.':,--{*)~><'.-1---..:.12~*-*---CJ--.-.L.~1~8-"..LJ~-:r---r*~(}--.--'-~' r-- 13969 ~ '396l ~ 3966 ~ 3968 ~, ~ ~ o;

    • io c.o

-...J.. ()) )>L'.I 3966B \\;: (E-3) D 18-CD-300-1 33013-1236-1 ~ FEEDWATER PUMPS ~~ ~ g I 5 I 6 l.!..J D 7 I 1_1 /_2" . ~ 9500E 8 ECD01 B CONDENSATE HEATER 1 B ECD02B CONDENSATE HEATER 2B 300-11 TUBING ::'.., D

jJ..

.., I 33013 1918 2 X3499B (B-3) 150-2_} I 10" v-... I 33013-1923 J X4144 600_ 2 _..r I i!i 'f--t-'-1-"_t:e:*j--+,---t*::<<:J-r-<~*f-l I 4Z39A I 11078 ~ (D-1) 11/2" -C><':H1 33013-1918-2 ':>-'-.:..!...::,_-j XJ499A I _}

l NCD03 7

0 ()1 ~ -...JJ.. CJ> PG 6405 I I X4146 V}--_...,.........=:J TC 11076 PT 3201A 150-2 (C-3) 33013-1923 _} 10" 7 5oo-2 DRAIN HEADER ~------_,.l-_.'.'.10~C~D_:2:15~0'.:_21~--<::::~~(~G-~l~)~;-:=J

  • 33013 1234 I,

~ X4059 CONDENSATE MAKE-UP ECD03B CONDENSATE HEATER 3B ECD06B MAIN CONDENSER B 9 (B-10) 1" 150 4 33013 1904 I __J LGS04 ~ ~o~,!:!Ql~~_J_J.L+/-::.._~:=+/-_-----<:'°~~(~F-~5~):,g:Ul NOTE 6 1 1/4" 150 4 1 33013 1922 I ~ 1"....... 3 D 9514G X4427 95108 (G-11) f-'6'-"-j~~~~t:=6:-" __ 6~0~0~-3E1~-----<..__23~3~0~1

'._3::.1.:19~1'._11~1'._J 1.

I

  • j_

SP863 'x9515E 150-17 0 ' ... _.1/4", -D-i I.1---tv><1~.'.L.2._J'---< 9591G (F-10) 33013-1905 I v o~ 8" 9507E LCD03 '-D:, ~

1H1h-J1:

~ I LCD01 LCD02 ' 1 ~ 150-~D-1 8-CD-900-1_i -,, (SCH.SO)

1

..J v 9514E (F-10) ' ~-~-~--,. - 33013-1236-1 I v-..,, X9507D NOTES:

1. FOR GENERAL NOTES REFER TO DWG. 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. CONDENSATE HEATERS 1 B AND 2B ARE IN THE SAME SHELL.

CONDENSATE HEATERS 1A AND 2A ARE IN THE SAME SHELL.

5. LINE SPEC. 600-1 ANO 150-2 ARE STILL IN EFFECT PIPE MATERIAL IS Cr-Mo, P22.
6. PART OF THIS PIPING LINE WAS REPLACED WITH CHROME-MOLY PER ECP-10-000528.
7. UNLESS OTHERWISE NOTED, PIPING CONNECTED TO "A" CONDENSER DRAIN HEADER IS CARBON STEEL.

REVISED PER KCL nJ:r-,r ftl';j.ff,.,f:/Y) ECP-10-000528 10 1 1 At>c-1~-000<<>1 11/11/15 11/11/IJ 11fi,{1!" /J*lf*t<' NUM~ CAO FILE NAME 33013-1233 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 11-Jl-f.J AS BUILT DATE RELEASED FOR ENGR. Gl_N_N_A_S_T_A_. _ __, R.E. GINNA ST A TION JOB NO. NONE CONDENSATE LOW PRESSURE FW HEATERS (CDST) P & ID DRAWING NO. EWR 3391E 33013-1233 CCD 01 CONTROL COPY # I 12 REV. A B c 0 E F G H J

A B c D E F G H J 1 2 v r.1 N ' VENT 3 4 5 ~ r4-CD-150-1E 1 2 407 L!J 6 8" 150-1 VENT VENT CD, 7 y <O 0 N

i:

<O g; ~ N CD r NOTE 6 125-uJ "Y' 4" E...,....., __.:....__---, 4076 l.!J N ~-11 4400 2* li:Ql 2-CD-150-1 ~ lLOl 2" 4075 INTER.BLDG. SERV.BLDG. 4074 (G-6) 2* 1 2*

JV 33013-1237 4857A NOTE 6 3/8" 150-1 TUBING lLOI AFW PUMP DISCH.

lLOI 10* 1----11><] t-'1=0_-~CD~--1=5~0-_1'---.-----11><] 1------1 3 4* 9510C 9500G 10-CD-150-1 20* TCD02A CONDENSATE STORAGE TANK A 4071A SERV. BLDG. 4070A (E-10) TUBING ~(-IP_E _~


~--8~*-_,,_,

3 8-CD-A1 11/2" 8282.. INTER. BLDG. 10-CD-150-1 li:Ql ~= 4071 ~ 33013-2252 X8274 ~-------' ~ ~ ~ '-------------~ D 1/4" X4015 H-1 33013-1237 4* 1/2" 11151 <O llJ 4319A <O


~(E_-_1_2~) ------, 11I4" ~

--j)<J--< 33013-1915 7997 X4019 X4018 X9671 B-1 33013-1237 E-1) 33013-1237 4" 4* (D-9)

>~--2~1/_2_-_D_w_-_1_5o_-_5 ________ ~

I 33013-1908-3 9517Y (D-11) INTER. BLDG. [~~2i~~==>~--------------11-~CgD~-~3~0~0~-J1 _______ ~ JT~U~R~B~*lB~L~DG~.'-1 33013-1238 F-12 1/2" 1

  • N 4070 N '

4068A 33013-1905 1 4-CD~ 150-1 V 4058A " [h£] 1--~-1--3 D 4071B (G-8) ---C><:t-1[~33~0~1~3~-~18~9~4~-21:=:>----if--------{f----------ff------i X15506 1/4-CD-150-1 33013-1905 (F-12) TC (F-11) if~ <:::~-3-3~0-13---1~2_3_3_-;... ________ ~----~r------i 1 0-CD-150-1 MAIN CONDENSER B HOTWELL D-1 33013-1252 H-5 1058 4315X,_----------~-t .. *----'6"-"---j 4059 ~ -1:><J-l 33013-1894-2 X15360 (B-10) 4315Z 4315H1 4315S ~ 33013-1896 >~-~,~1-------uu--~ X154341~---~ (C-7) 33013-1233 (G-1) 33013-1233 AOV 4316 (B-3) -C><J-1 33013-1899-2 X4316H1'-------~ (C-7) 6-CD-300-1 2-CD-300-1 4317Z 4055 4316S 1/2" 40571 300-1 -~*~i"'*~-150-1 4317 REJECT 4311X 6" 4056 300-1, j, 150 1 -1 0 I 0 0 I -"' 0 I 0 ' N I 0 I CJ> 0 I - 2" ~~ TCD02B CONDENSATE STORAGE TANK B "' lLC I o ~ 4319C 20* !~ 11/2" .'_. 4318A t, ~"' i m ~ ~NOTE 8 "----------1f---C-c!--l Pl 1--~2"-125-1 11151A 2808 Q 8" 3/8-CO-A1 0 "' I I~ 0 (F-10) 33013-2252 X8275 829~K t, CD 0 (1-10) E. l-j~J;------<::::::~33~0~1~3~-~2~25~2~r-t::><J-8299J X8281 3/8" (J-3) 33013-1912 CNDST. DEMIN. BLDG. TURB. BLDG. <O g N N 2 1 2" 3/4" N I 0 0 I tn 0 I <O 0.,, T AM-6406 AM-6407 v -----i.... 1------i I () 0 I 0 I w TOC SILICA 9513D ~ (A-7) 3/4" ~ 33013-1911 >>-------~~-- x9s38A1~----- 2 1 2" NOTE 12 0:T*

J

/\\ <(, ~ 0 <t 9509D () 1/2"

1.

DE-...., 4050B N I 0 0 I -"' 0 I 8 9 SEE NOTE 11 111-7" 0 -- 4" SS 10 0 VE T N, NOTE 9 0 0 0 ROOF DOOR ~ 1" r.1 0 1 1 12 SAFETY CLASS 2, 3, OR -~**\\ j i~ SAFETY CLASS 1 ~:ilE 'AS MMN I 0 -- 1* "' 1 * "' 1* 0 DETAIL "A" TYPICAL SAfElY CLASS BREAK POINT FOR VENT, DRAIN AND TEST CONNECTIONS 0 00000000000000000000000000000000000 CD, I I 1

  • 0 0

0 0- 1%1 g 9501A I ~. i~ D ~ 4044 04* ~ J.i 1l! 7.-s 10"0 0 0 0 '---'..;;....+41-.....1i-------1 9501B 3 8" 4" PVC v ITT N ' TCD03 OUTSIDE CONDENSATE S10RAGE TANK <O 0 - TC 0 1%1 9501Q 4" 0 0 24" 2" 0 0 0 0 0 0 0 MANWAY 0 0 I ~.. [D 9501D 0 0 0 0 2" 3/4" 11/2" ~~D -"-----------"-----'"-----"-----------"------"-------t--lf--, 9502J EAST DI TRUCK r-----lllk.!Vll MIXED BED INLET + S;MPLE WES1 DI TRUCK '------lllk.fVllMIXED BED INLET 9502K SAMPLE G) ~,...... rri....... G') 0 CDl'.A I <D ~ I .:::. g N ~ 0 f'1 CD o I 0 0 0 0 y

  • ~*1~

2* f-"-.....


1 0 tn 0

0 I r-; I N, 9501L 3/4" F--'--l,.._:J D 9502A 2 1/2" 9529D "'v ~T CD () 9529A 3* 9501S 9501Z 3/8" <D CJ> 0 - ~----10t----1 3" 9501R 9501Y 3" CNDS1. DEMI~ BLDGJ TURB. BLDG. J, SEE NOTE 4 9501X 1* LCD05 2" SCD21 ,...------,3 I 4

  • t--t---)

3 4' y 9528B PCD05 OUTSIDE CST HEATER PUMP 1--_..,t-------j F 1-----.,...____J 9528D FCD01 9528E 9528A 9550V 3/4" I~ y <O CJ> b Iv 3/4" I E9502E 9502C YARD CNDST. DEMIN. BLDG. 9502W 9502Q 0 I 0 0 I 0 0 9513E v ~ 0 G) 0 0 <-; NOTES:

1. FOR GENERAL NOTES, SEE DWG.

0 2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543 33013-2241. 0 r-----r-' 0 3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TES1 CONNECTIONS SHALL 0 w BE AT THE ROOT VALVE IN ACCORD- °' "' ANGE WITH DETAIL "A". ~ ~

4. THIS WALL PENETRATION WAS PREVIOUSLY USED FOR A TEMPORARY CONDENSATE TRANSFER PUMP.

EHTRCD04 L!J D REF. TSR89-07

5. BLIND FLANGE INSTALLED BETWEEN V4051 AND CONDENSER THEREBY ISOLATING FLOW PATH.

11/4" I 9507F 3/4" ~---' TCD14 OUTSIDE CONDENSATE STORAGE TANK HEATER

6. LT 2022A AND LT 2022B PROVIDE REGULATORY GUIDE 1.97 CATE-GORY 1 VARIABLE INFORMATION.

PRESSURE BOUNDARY IS SAFETY SIGNIFICANT CLASS.

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 1 0328.

I I I L D l_J _I_ OUTSIDE CONDENSATE STORAGE TANK HEATER CONTROL PANEL

8. APPENDIX R LOCAL DISPLAY.
9. BLADDER WAS REPLACED UNDER TSR 95-085 WITH POLYPROPYLENE BALLS AND SCREENS.
10. NITROGEN GAS INSERTED INTO "A" & "B" CST'S BETWEEN SIDE WALLS OF TANK AND DIAPHRAGM.

THE NITROGEN GAS TAKES STRESS OFF THE DIAPHRAGM ALLOWING IT TO FLOAT AWAY FROM THE TANK WALLS DURING LEVEL FLUCTUATIONS (THERE IS NO LEVEL/WATER DISPLACEMENT DUE TO ADDmON OF NITROGEN). 33013-1233 405 4311 b "' !j;

11. REFER TO ECP-2008-0101 FOR REMOVAL OF 2" CONDENSATE DRAIN LINE. IT MUS1 BE REPLACED IF A BLADDER IS INSTALLED IN TCD03.

(G-9) 33013-1252 CONDENSATE PUMP SUCTION HEADER 1 3-CD-150-1 2 3 4 b ~* ,. I D 5 ~ (C-11) 2" 4* ,_-j.-:___:!:=;e~~~'---------L--11">-<"f-l."!.-j 33013-1908-2 4-CD-150-1 4"[~~~~~~:::>-;;r~~ 4048 4097 40498 0... <O 150-1 TUBING PCD04 <MO/CTP> CONDtNSATE TRANSFER PUMP 11/2" 6 1" X4833 ~O~ ~ t-'-14~0.49-D -fl;--.. b 4049F ~?~ 1* 9517P 9517R 1* ~----i~i-- 9517U l.!J <O ~t 9517X 9517V 7 8 9 10 /\\ 12. USED WHEN ALIGNING FIRE WATER TO FILL ~ CS1's USING CONDENSATE TRANSFER SYSTEM. 1 1 REFER TO ER-AFW.1. /\\ REVIS£D PER ~ 000849 RJM 8/28/14 CAD FILE NAME 33013-1234.1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. GINNA STA. NONE R.E. GINNA STATION ONTARIO, NEW YORK JOB NO, EWR 3391E CONDENSATE S10RAGE (CDST) P&ID DRAWING NO. 33013-1234 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 (E-1) 33013-1905 X3798 (E-5) ~ 33013-1923 X3359 (1-11) 33013-1911-1 CONDENSATE HEADER (D-12) 33013-1909 X5058B 1 Gi 0 (.}> co 0 0 -1 ~ ~ OJ 5 tD "' 5 " 3 8" 3/8 3 8" ~ 0 I I (() ~ 0 (() (() (J> - "' L!J D (J> 0 (J> (JJ (() (J> 0 1" (() g '1 (() (J> (() co I 0 0 I 8 I - 2 2 I 0 0 I "' v g I r.i 16" co I 0 0 I 0 )> 0 0 I _c--'J 0 "' "' 3/4" 16" <D g ()) OJ OJ Pl 4051 3 4" 16" <O (J> 0 0 v <D (J> -- 0 9506E 0 ~ ~ D rn z (;) }J z v 3/4" 9540A N ' 3 1/2" 3-CD-300-1 v N ' 9514C 9513G FCD04 4 1/2" Pl 4021 3/4" 3/4" ,-------t>Kl-'~,--J'--i><J~F IH/~r~-.____, 9536C ~ Pl L!J ~co TC g Pl 2529 L!J ' D (JJ '1 9513A Pl 2537 95138 3/4" 3/4" .------~-----"'c.c_----1<0 (.}> Pl 2528 (() (J> (JJ )> Pl 2530 14" <D (J> -' 9503A 3/4" N (;) ~-t-Pl 2532 Ci tD z (;) v v <O <D m m 0 0 '1 '1 <O (J> -- r <D (J> 0..

r:

N '<0 m 0 t: <O m 0 14" 'iJ z (;) 5 3923 3/4" 6 (B-10) ~ 33013-1896 >>---11//---#//- x15435 1~----~ AIR LOCKING VALVE \\~ ~-IH!f- ,--'(~C_-_10~)'--~~ co ' --i:><J-1 33013-1896 ~ x 1 5436 L---:..::..:_:_::____:_::..:...::._..-- 1 2-CD-300-1 "' -, SP-863 SP-5291 (J> 3950 NOTE AIR LOCKING o; N 0 LLl D (D-4) VALVE ~.,. .---~-~----- (() --J:><J-133013 -1894-1 )> X15491 15491B 14" 14-CD-300-1 1------+------------N-O_T_E_B-1142301 3/4" 4376 9512B BOOSTER PUMP TRIP 0 SP-863 SP-5291 PS 4027 11063 11065 (3 START 3/4" D


go* ~ ' 1:zc r=::======'.__:3~/~4"~-~~

(;)

J 0

_... D 0 <O ~ (.}> 0 0 co I 0 0 I "' g I 0 3/4" D E--- Tl 4064 ,_3~/_:_._*D--~~ " ---1 (;) Ci

) L!.J

"---A I ti ~ "' PCDO 1 B D 'j2 9504A b I N tD z (;) 0 N 7 3/4" 15436C 3949 15491C 1/2" l/P 2023 X9512K v ~1- -t, co... "; N I 0 0 I 0 0 I 16-CD-300-1 Pl 2054 N 8 1/2" 4375 14" 9 PIPING TUBING TUBING PIPING 4231B 11150 4232B DPT 2036 4231A 4232A ECD05 CONDENSATE COOLER ~ 18'~ (() 1--....:..:::.....__,;. __ __,~ 1 ' 10 1 1 12 18" 14" 12" D 12-CD-300-1 12" r-~~~~~~....:.0:..~~~-11....-1r-~~~~~~~~~---~~~~--=~--1 Tl 2027 SEE NOTE 4 TT 2023 t tD -f c OJ z (;) 3944 ECD01 C H2 co 1/4" COOLER 3940 (() N (JJ 11552B 3928 q SEE NOTE 5 KCD01 GENERATOR SEE NOTE 5 ECD02 ECD03 3/4" D--..--1 H2 COOLER 3939 3/4" D 3947 3946 (JJ }J " z Ci OJ z (;) 16-CD-300-1 16-CD-300-1 Tl Pl 2028 2055 C H2 H2 COOLER co COOLER ~ ~ Zl~.:i---, v ~ 1 /2" TI::c-:'J'=' 1--11>4--v 3941 H.. V 3938 Tl 2033 D 3/4" 3945 (JJ 16-CD-300-1 3937 (() N (() (JJ (D-7} Tl 2029 NOTES:

1. FOR GENERAL NOTES, SEE DWG: 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFElY CLASS.
4. MONITORS HYDROGEN TEMPERATURE AND PROVIDES CONTROL SIGNAL TO POSITION VALVES 4229 AND 4230.
5. THIS IS NOT AN HVAC COOLING COIL BUT REPRESENTS THE TUBE BUNDLE FOR THE HYDROGEN COOLER.
6. ELECTRIC MOTOR EJN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
7. 4229 FAILS TO 50% OPEN ON CONTROLLER FAILURE AND SIGNAL AIR FAILURE. 4229 FAILS AS IS ON SUPPLY AIR FAILURE.
8. 4230 FAILS OPEN ON CONTROLLER FAILURE AND SIGNAL AIR FAILURE. 4230 FAILS AS IS ON SUPPLY AIR FAILURE.

/\\ 9. tJ;t:,. THE GASKETS SPECIFIED IN ME-318 ATTACHMENT C FOR LINE SPEC 300-1 AND ECP-2009-0254. ARE SUITABLE FOR USE WITH ECD06 FLANGES. 1 0. SPACER RING USED BETWEEN ONE OF THE FLANGE FACES AND 3955. SEE ECP-13-000830 & DWG. 03021-1499. 18" 33013-1233 - g CONDENSATE o -:;:. [\\; BOOSTER (J> ~ 0 I u N 14" ECD06 TURBINE GLAND STEAM 14" N 14" l-'-------'--*---irJi--------1 CONDENSATE HEATERS 1A/2A & 1 B/2B Jj z G'l v <D g (.}>., <D (.}> 00 '1 L!J w ' PUMP B TC D <MO/AVP9B> Pl 2535 <O (.}> '1 N Pl 2536 <O <O " N c.o

(0

°' m (.}> 0 0 (J>

r:

~ PCD01 C ..::::. (1: CONDENSATE " "' -, BOOSTER w ' L!.J PUMP C TC D <MO/AVP9C> 18-CD-300-1 3 (() "' g " (.}> 0 Pl 4060 3/4" <D (J> - 14" <D (J> 4 9505A <D (J> 0 0 v Ci OJ z }J " z 5 6 12" 7 [><] 1-'--' ---'--I 3952 SEE NOTE CONDENSER LSEE NOTE 9 3953 12" 12" 1--------------------111111---------------------1 c OJ z (;) ()) I o Tl 0 l 2025 0 0 I 3951.. N N (J> N Pl 2052 10" N N N " N ' 3226 8 3954 1 O" ECD07B AIR ';;;:~' ~t 'l I CONDENSER ECD07A CONDENSER K; AIR ~ EJECTOR INNER COOLER -N N ' 1/2" 3230 1 o" y 9 Tl 2026 12" t---+-~~---1rJ1-----~ N (J> - Pl 2053 3955 g SEE NOTE 10 I Ci OJ z (;) 10 00 I 0 0 I 0 0 I N I 0 0 I 0 0 I 1 1 CMB CJW i1/s/1s Ji IP 1S CAD FllE NAME: 33013-1235,1 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES II ~// AS BUILT DATE RELEASED FOR ENGR. rACUTY GINNA STA. R.E. GJNNA STATION SCALE NONE CONDENSATE (CONDENSATE BOOSTER PUMPS TO HYDROGEN COOLERS & SLOWDOWN RECOVERY SYSTEM) P & ID JOB NO. DRAWING NO. REV. EWR 3391 E 33013-1235 CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H 1 i:=..- 3973C 2 0 I 3 (G-7) 33013-1905 / ~ ( l-D- )>l!J TC ~ X3810D 4 (1-11) r - --iL_3_3_0_13_-_1_25_2:__.> PS 2010 CONDENSATE BYPASS TO SOV 39595 TC lfil PFW01A<MO/FWP1A> 171 FEEDWATER PT 2017 5 ... ~ ~ 17 - rn"


I-_.

4261C 0 I 0 1/2" ? ~

J v 6

~ I 1---P 3973 3973B i" t~~~~Hr ~ PUMP A ~ "- / I 1 o" 14" - 3977 );!* L "'; f--'"---r-E f-..:..;-.,---1.*

  • -,---1 11-.,.-:-,-,-,---1--:))\\.-J M 4260A 1/2"

"--._/ r-.1 /2" ~.;~ 1/2" Cl ~ Y 4H - 1-FW-300-1 J ) b"'; 13975 ~ -; L..-r:- L!J ~1 L!J ~v o El i)1 *E]i)' r 0 D '° 4499E YL{ 1 1/2" 3977A J .... :J -::i 3973D I (.N 5 -1'>- cri.1 l _..j.. L_ = I NPSH ~-- ~-- \\_ 3/4" v E~'-' (H-11) -fLARM TT ~T--, 21--; 7 3977B < 33013-1252 f-2041 I... 8-FW-900-1 CONDENSATE BYPASS 4" ~ TO sov 3959S I ---v ~------------:------ ------== -------~-i '1 1

  • 1 1 /2-FW-900-1 4035 I _________________________ _J

~ ,, l149~~s,,cr:' I L 1/2" t----..... f-'3 v 4499D I '----l - M r:' ~ iTT' -~*L.._, IZ/4147 I I MANIFOLD I r -

  • 1 12" O

v L:.... 0 4099C l 0 A

  • 1 /2" ?

f---+-~-vr><~:1--+-_,_--"v'><'~J-!.l-=---I_ 12167L 4251 ~ -~ 11 rp ~ ~f!'S:\\¥'.,}------/1- ,,---'---f{-,,---','

-ff-Ii I

L FT 2004 I ~... °' I ......i _. ~ m TUBl_N~G-+-~30_0_-1 =~--@ 1 /2" v ~ 12167H 4250 (G-8) -txJ-1 33013-1895 >~----,,,_y-- X14522U '-------------------/ (J-5) 33013 1233 CONDENSATE HEATER 4A & 4B (F-8) ,~------'------'------~ 18" CXl y ~ I 33013-1905 ,>----_J X2900B GLAND SEAL Ii 1" 4373 1 " ~ 4371 1" - : :J D 4374 12-FW-300-1 1/2" 3v 4499C 1" * ~D 4499F OJ I ~ I '" 8 I 12-FW-300-1~ r I I I FT 2005 MANIFOLD I ~' r °' I UJ.i t. OJ ~ 12163H v~ 12163L 1". ~ . 1/2" 4372 4253 TT DE *

  • 1" 4499G N 8"

OJ ' 0 0 OJ'

  • L!J D

I I ------- II 2042

'

IZ/4148-;;J 3 v ~ ~~ f-- 2005


---- -I ---- ---- ---- ---- -


---- ---- ---- ---- ---- :--'T'- I I

I v E.. 1 /2" -~ v LJ ' * /;; I

  • ~

' I 14905S E NPSH 4099D

]

.. ~ I L ____ __ __ __ __ ALARM

r _. ME ,~' 8 I tt*., !fl ~ I o IS ~ .~ f----..,.1-':Jv I ti 4499K H

C:::

(G-8) X 1~ 33013-1895 > PT 2018 it;' 7 °' 00 I rn 4495"" IJ;Q] ~' 0 °' 0 v 171 ~ ' I I I I OJ 3/4"

  • 1-FW-300-1 CXl '

I (H-11) <~_3_30_1_3-_1_25_2__Jf- _J I I 1 1/2" 3976A CONDENSATE BYPASS TO SOV 3959S PT I ~ I "' 8 I I ~ I 0 0 I - 2016 i4*~ PFW01B<MO/FWP1B>

--V r;;-i FEEDWAIER C-_ 1:...J..,;::3:c:.0:0-1 l2J / PUMP B 10*

-=-[:: 12" 14" e_ I .\\7 ' f--.-'-----l M (1-11) 33013-1252 CONDENSATE BYPASS TO SOV 3959S (E-7) .. / I 33013 1905 I X3811D I - - _1/Z" ) '--L-l><f-rl-bo:'.1---1. - 1 42s8 3818 ~1% ~-; PS 2011 C-1 ~ " b ~b'""~b*r 4259 ~- ~.~~AL l.Qj bA L 3820 300-1 )> OA = Y ~--- ~-:_ o __ o-- 0 0 I


JO CJ>

0 I... D 1 1/2-FW-900-1 4034 13974 "' - ~976 ~"' ~.... L!.J D 1" D[ ;.._""" 3979D 8-FW-900-1 14" TT 2063 1" 1" 8-FW-900-1 -1" DE...... 3978D E---'--'---'--'---'-_,_---'----~ I FL 1 2 3 4 5 6 7 8 9 Pl 2D17 0 ' 1.. -i c m z " 0 0 I EFW05A FEEDWATER HEATER 5A 4363 1" ~ t;*, "' "' L!J D 1" \\ 1/2"

  • :J

...... :J v 3979V I ~ I 0 0 (B-5) ~-----------------------I: 33013 2711 3 PT 488 PT 501 ... --'] ~_c1_"_-1.!. NOTE 4 rn CXl - CXl ~... 1" 0 I FEEDWATER LEADING EDGE TRANSDUCER LFW15 <O -1'-.,, a OS, "° ~. ~ ~ !.-'-~--'-' 20-FW-900-1 I I (F-l) q*-71--'-----11 1-----,----'----------11 33013-1236-2 1 /2" ~* r NOTE 3 ~. ~-----+ I r 0 0 I I ~ I 0 0 I OJ L!J v Pl 2540 c1 OJ z -+----1-"' 0 0 I - 1" 4266 FT 488D L@NOTE 4 (H-11) I 33013-1233 FW CLEANUP RECIRC. LINE l" 1.. (E-1) --'--,--,:,--...------_,,,f-----'-----</33013-1236-2 ~ 4362 1" i.0~. ~**~r~*Q ~Al L!.J D 1" 1" L-... t---'------l NOTE 3 39828 14-FW-900-~ 1/2" .... --=i v 3978V t;* °' - (Oj (2J D 4365 (E-1) I 33013 1233 MAIN CONDENSER A L!.J TC EFW05B FEEDWATER HEATER 5B 7 I 8 9 v ~ X1406 PT 502 ... --'] g] ' '" "' °' 0 ~.. / v ~ X9507E v ~ X4361 10 10 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1236,REVISION 10.
3. IN ACCORDANCE WITH EWR 5114, 8", 14", AND 20" MAIN FEED-WATER PIPES ARE SAFETY SIG-NIFICANT CLASS FOR HIGH ENERGY LINE CONSIDEATIONS ONLY. CLASS BOUNDARY FOR ALL BRANCH LINES IS AT THE CONNECTION TO THE MAIN PIPING, 4, ALL 488 SERIES FLOW TRANSMITTERS (FT-488 A,B,C,D,E,F,G,AND H) ARE CLASSIFIED SAFETY SIGNIFICANT SINCE OPERABILITY IS REQUIRED BY TECH.SPEC. PRESSURE BOUNDARY IS NON-NUCLEAR SAFETY CLASS,
5. ELECT. MOTOR EIN'S FOR MECH. EQUIP, ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

DATE f\\ REVISED PER LlB, ADC-15-000876 AS BUILT RELEASED FOR i-;.;:REV::_,___-'R"°EVl'-'S::E::,D,:_F"'OR:.__--l DRAWN CHECKED RESP REVIEWER FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAO F'IL£NAME 3P123601 ONTARIO, NY JOB NUMBER WR 3391 FEEDWATER (FW) P & ID DRAWING NUMBER 33013-1236 SHEET REV 1g 1 1 i___=c=c D::::;__:0::._!1_,I '-"'C'-'-'N'-'-T'-"R L"'--"C,_,,O,_,_P-'-Y....!!..# __ --l A B c D E F G H

2 I 3 4 5 6 I 7 8 9 10 11 12 i A ~

t°..L..1.""iIT~~~
r-1i.,-~~~----_.!!,"-:!"'~-;!900!2;-:.:.'------*

~' *=-1 A 8 c D E F G H P404 11 f--C~N~~.!._ t ~ ~ -.~. J-11) 2 4 5 6 7 8 9 10 ~~~-* ..StLJH£ 'L~~~ a.GS {Q) DETAIL-A. nP.SAFOY CLASS BRE..VC POINT FOR 'iDiT, OfWtl ar TEST CONriCCT10f!S NOTES' !. FCR CE.NO'l'Jtl.. NOTES REfCR 10 ORAWI~ JJ013-1241.

2. PE\\'l".ilUN ~u* Gr nus O!l.r.W!NG SUP£RSEOES POR'llONS Of JJ01J-12J6, REVISK>N 10.

1 ~s~~J:lr E'~~grn1lti~A~ AHL FLOW COHIROL CONS;('V{.(llONS ONLY. 8 c D E F G

8. t8" El.ROWS CONNECTtNG ?l?E 10 S/G'S Wt.RE I H C.~Gf(J TO UAl'Effi""- S\\-2J4-WP11 (CHROME MOU) PtJI CWR 100J4.
9. REFER 10 33013-1236,l FOR INSIRUWEl'H AIR D£TAlLS.

11

1 A B c D E F G H I J 1 NOTE ~.,__ ____ _, 2 ~ ~ OJ NOTE ~ ll--------1 2 '.e ~ 2 ~ I OJ ~ ~ I 2 OP/3995 3 4* OP/3994 3 1 4" ~~ D-7) 33013-1893 INSTRUMENT AIR F-8) 33013-1893 INSTRUMENT AIR 3 1* .... g 1* 4 3995S 3995HH 3995CC "I 3995N 3994S 3994HH 3994N 4 <O <O <O <O 0

r COPPER "l.

"l. 399588 1 Z' <O "l. <O <O <O 5:: U) ~ U) U) <O <O 0

r COPPER "l.

"l. 399488 1/Z' <O <O "l. ~ <O <O 5 3995P 3995U 3994P 3994U 5 AIR AMPUFIER CFW3995A AIR AMPUFIER CFW3995B AIR AMPUFIER CFW3995C AIR AMPUFIER CFW3994A AIR AMPUFIER AIR AMPUFIER F 6 U) <O N <O <O <O <O

'(

<O N 6 L.:.J t.:J 7 1/4" 3/.f' 1> 3995EE "' 3995G [hQl <O <O "' ~ L!.J 1/4" 3994T4 E-_._-r::t:'.l_y_l '..fZ'c-J 39940 ~99400 3994R 3/4" 1> 3994EE "' 3994G [hQl

g
El L!.J 7

1* 1" 8 3995K ~ = r 3994K t.:J 0 D 8 TFW3995 AIR ACCUMULATOR 3 3 TFW3994 AIR ACCUMULATOR 3 3 9 10 11 9 10 11 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REFER TO 33013-1236,2 FOR VALVE PROCESS CONNECTIONS.

LIMrnD CONSIRUCllON: AS NOTED PREllMINAR'f NOT FOR CONSTRUC1ION BIDDING PURPOSES AS-Blm..T GINNA STA. R.E. GINNA STATION SCALE NONE FEEDWATER (FW) P & ID JOB NO. DRAWING NO. SHT. RE.v. EWR 3391E 33013-1236 3 & CCD 01 CONTROL COPY # 12 A B c D E F G H I J

A B c D E F G H J 1 4299H 112" w D 4-SW-125-1 I 301 ~~ (1-1) --1:><1-J 33013-1250..1 X4640 (E-1) 33013-1234 CONDENSATE STORAGE TANKS (F-4) 33013-2681 SUMP PUMP PWT35 4018 s !ill 2" 1/2-CD-300-1 (E-1) 33013-1234 CONDENSATE STORAGE TANKS 4"CS s 301 / 4016 <ill:> 4" 2 m z Q 125-1 --------- (1-1) 4" 1~1 33013-1250-1 4099 !ill 4024A 2 42938 w °' 00 0 (F-2) 33013-2681 3 4 5 J-6 33013-1250-1 X4091A 4" 1~ 4021 6 1----- @) I I I l 00 "' ---+ 2" 7 "' z 4488B Gl 4488A 3/4" (C-5) 33013-1893 !------~-- 3/4 900-1 1/2" C-2 2" 4343 "'30""1o-t-3"'occ1 4343F 301 125-1 3/4" 1/2"

t 1/2" 4343C J HOSE THREADS

+--~--:i 4342F 150-4 C-2 1/2" 1 1/2" 3-CD-150..1 1/2" 9521E 4325 1/2" 4091

~ ~ I 13256 NFW02 <MO/MAFP1A> PAF01A AUXILIARY FEEDWATER X15525 PUMP A NOTE4 2-FW-900-1 !§] 1/2" 1/2" -I c "' z Gl tc-+/- 2 m z Q X15466 3/8" ~ 4300 EAF02A w D (C-5) 33013-1893 AUXILIARY FEEDWATER PUMP A LUBE OIL COOLER 150-4 14371 :..:.s--1>.H~... -1 s ~ v~ 0 ~ 4342 4342C r ____ _,.C-.1--15_0_-4 __ ~~ ~~--~~---...._ v TC 11175 /4305 FLOOR DRAIN BETWEEN A& B PUMPS 4" ~-5) 4" 33013-1915 3" 1/2" SS TUBING r--~~J-~6~-----~ -!:XJ--1 33013-1250-1 X4090A 1-CD-150-1 4083 4" 4014 I( 0 1" (B-5) s 33013-1893 >-/f-C*., <MO/MAFP1 B> PAF01B AUXILIARY FEEDWATER X15523 14372S 2" y 3-CD-150..1 TUBING 150-4 9521G 1/2" ~,---"'----C!------'-.L.'..-1 f--0--, 4326B 112" TC 3/8" 1/2" 4090 NFW04 ~ 9521H -+---C-2 150-4 C-1 3/8" 2-FW-900..1 ~-- L'..J D EAF02B AUXILIARY FEEDWATER PUMPS LUBE OIL ~-~COOLER (l-11) 33013-1909 X5075A (C-4) 43~73 2-CD-150..1 ~ ,--'---{X}-"-'=-=-'---Y 33013-1234 ~ 4080 1I:QJ TO CNDST STORAGE TANKS (G-11) 33013-1238 '--------'X4294A SAFW CONDENSATE 3/4" CASING VENT .. r.i PAF03 til ID 0 TURBINE DRIVEN AUXILIARY FEEDWATER PUMP LFW30 42910 4291H 4291 150..~ING (D-3) MANIFOLD 318" ~~lf-n---11-----J'l---< ____ 33-0~1~3--1~8-93--, __::::-------'X4291S 8~ w 900-1 TUBING 1" Pl 2156 1/2" Pl ~ 1-f<til--- -- -- -- -- -- I TURBINE DRIVEN AUXILIARY FEEDWATER PUMP LUBE OIL COOLER ~-- EAF01 2" 4493 "' z Gl X15456 X15455 3/4" (J-11) 4492 33013-1909 ....___:_:..:_:.:._:.:_:cc_ __ JX507 4A 3-FW-900-1 4494 w 0 ~ 3/4 900..1 4295D TC ? 3 1/2".. c 0-1 ~ ~ 3" ~-~----i"l 1/2" i:~... ---j 4309 C-1 900-1 E 1---t::-:1-'-1 *_* __, I:; g 4308A (B-5) 33013-1893 3" X15524 4495 4295E w D 296D i!J 4295G 5:.,, 4296E 1/2" 1---.,...1-:Jv ~ 42968 3998 (1-11) 33013-1909 (D-3) 33013-1893 (D-3) 33013-1893 0 lo SUMP PUMP PWT36 Dt__.._, 11095 C-2'--o_..,T-"'UBING 11096 TUBIN~G"-f--'C-2 1/2" (D-9) 1" 3 L,,=1:::==:t:::::'.. __ _sc;_-2:2____Jr-----'--rJ-----,-J 33013-1231-2 1 X4087E,-~(_l-9~)----..._ 4087D 1,, 33013-1250-1 2 C-2 4087 3 4087A 4088A 40876 4 NFW03 1" 4085A TURBINE DRIVEN AUXILIARY 3/4" FEEDWATER PUMP 40888 40856 QUENCH TANK 5 6 7 8 4489A 4008 IBLCI ---+ -1 "' z Gl 4483 4351C 350D 4351E 4353E 4350E 9 /\\lo !ID 43530 4353C w 4352D 4352E 6 ~ 43536 '::l ~ OJ w D I ~ -~1 _____ 2_" __ --< I >----------~ 5-FW-900..1 ~ 1" r g X15454 X15453 -I c "' z Gl 4348 44908 (C-3) 33013-1893 (C-3) 33013-1893 3999 !ill C-1 4348A 3-FW-900..1 ~3/4" 4297 NOTE5 J-11 33013-1909 m TC 0 ~ 10 11 12 1" (B-3) 3" r-.. ---'--------'-----1::x:::r:'--I 33013-1236-2 ~ 4011 STEAM GENERATOR A 4000C t !ill m m z 4353F UJ 4352F 4352G w TC L'..J D

Jo 4012

!ill Pl 2794 (J-5) 33013-1235-2 STEAM GENERA TOR B ~ SAFETY CLASS SAME AS MAINLINE SAFETY CLASS 2,3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS v.....-- 43478 i-1 4001 !ill 4347C ~ ~ 3/4" 4003A (A-3) 33013-1236-2 STEAM GENERATOR A (J-5) 33013-1236-2 3"

J v

~ 4349C v r.i NOTES:

1. FOR GENERAL NOTES SEE DWG. 33013-2241
2. EXCEPT WHERE OTHERWISE INDICATED SAFETY CLASS BREAKS FOR ALL VENTS, DRAINS AND TEST CONNECTIONS SHALL BE ATTHE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIRINITROGEN VALVE.

REFER TO INTERFACING AIRINITROGEN DRAWING FOR SAFETY CLASS.

4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
5. VALVES ARE ADMINISTRATIVELY CONTROLLED OPEN.

APF \\.\\(~ 11/12/15 NUMBER CAD FILE NAME 33013-1237,1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIM!NARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR GINNASTA. R.E. GINNA STATION SCALE JOB NO. EWR 3391E NONE AUXILIARY FEEDWATER (FW) P&ID DRAWING NO. 33013-1237 REV. 4004 4006 CCD 01 CONTROL COPY# 8 9 10 11 12 A B c D E F G H J

A B c D E F G H J 1 2 3 4 5 6 7 8 9 10 1 1 12 1----_-.-.. -.---_-_, ~

ANIFOLD

~ 11123B - D-- L!J v ~ -----~ j ~ co U1 f---'V C-11 33013-1250-2 9709A1drlj y 4-SW-152S 9629A IBLCI 4" co 1 /2" FIRE HOSE D CONNECTION <D ~"'----! 0 00 U1 CJ) t * ~ 11124 ';J-1--rl*-.-.[TC D L!J 4-FW-152S f, NOTE 3 ~ co 0 I )> L!.J PSF01A(MO/SAFWP1C) STANDBY AUX. FW PUMP C t

  • co 0

CJ) 1 4" '-1~--<TC '° (B-9) ~

! HH~<

33013-1892 v );' -...__:.::..::..:..::._:.==-_J x 14256S NOTE 5 1/2" <~ wm_. 3 ~ "'- 300-1 152S 0 0 I -"' "' J, icl )>

fl,~

';J-I

fl

)>1~ c,.., x,;u v 9673 (/) (/) 1/2" v i:--1.---i 9674 1/2" vE:..... H 9720D 9720A 9721A ~ 0 CDI CD V 5 r 171 ,g (0 I ~ Ul [DI"' rr co i: ~1--<f-'"-h,-, 1 /2-CD-300-1 ~ O'l 9787A 1" D E-91---1.__'----I 9787 <D 0..... CD 0 00 [I) 33013-1230 (A-6) (G-9) 7 LFW05 3-AFW-151 33013-1908-3 ,__J.---1 I 9781 co 00 9831 r,., <D co 00 0 0 CD 0 ~ I ~ -----~- ~ 0 I 0 0 I '1 L!..J I () f--j~J-::::0--1 v I ' __ 98_3~_E - _J MANIFOLD~ co 00 9832 1 ** >--.!--mi-':J D 9834 ~** 9764 9793 ""'"~** 3"~ }-- 4 .:..." __ _J__:._L~: 0PS~~~ (MO/PS:03) 1 RECIRC. PUMP 9782 9776D ~-----~ I I 1 -CD-150-1 9665 (H-9) 9666 .......... 1-:J 9763G 33013-1908-3 I----~ 9763B'9763D ~~ ! ~ ~ I 9798 "' "' i: L!.J D v 2* 9763A ' 9763C ~L..!.J ~--~MANIFOLD v 00 <D 1/2"" r---- 1 I L r'";-l=::-1 9797 ______ RECIRC JV ~ NITROGEN EQUIPMENT NOTE 10 ~ I - U1 9776E 9776A N17 N10 2" Nl 1 N6 2" I SPARE 3" I SPARE HEATER

1i CONTROL PANEL

~ <D <D I i ~ 9785C i9785A '----'---@ TC TC TCD05 DI WATER STORAGE TANK NOTE 8 2" 1/2" I"' 3-AFW-151 Ol (\\.) Ol (\\.) N7**~S T' :~85D i 97858 CD

s )>
m 2*

'---n-=--11 N 12 j 9774B '-----1%" 9773 9773A 2* E*-+-.,-.--=iF~ 9660 ~ 2" SAFW BLDG. ANN EX


YARD ---

Ml 36" I MANWAY 2" 1 /2" N4 *o * * * *

  • 4" N9 m

~ ~ ~ MANIFOLD g L..!.J ~ 00 (D-9) v 33013-1230 w ~

fl f-N2 3"* *
  • 0 'ii" 2"

--"'---"'--__:1/_'----'-"'-f'-j ~*~llZIS'1~*:......:*:......:*:...i10,_*_*_*_*_,c---~----------~ z 4 0 e

  • N5 P

I NOTE 6 ~ 774 NOTE 6 9790 ~:~ 4" $lb

          • Or.1 N3 0 ~

~ ~ ~ ~co

fl ;fl ffi CD CD 55

)> z z ~ U1 )> L.!J

  • 4

~" 1----..::iv 9760 9780 0 NOTE 6 u D IH*t-:--:"4'-:":-:~N~B _________ ~N'.._'.l_r3'-j** 1*

  • j I *
  • I 0 f-'*:.....;;*e::*--=-*--=-*-'1::---_::3_-.:..:AFW...::...-.:..:1..:5.:..:1 _ _L ___ -1 f--....L---1 j/H--,.J'
  • 9772. *

)> ~ 1 NOTE 6 9770 ,z 9768 ~ ~ m ~ "'~ D J-IM-fJC 8-9 co co I~~ I - 9757 I 0 0 I c gi z L!.J v L.!J 11111A 11109 g ..... 14--':J TC "' Ul --f::><l-i.:3,::3..:,0.;,1 3.:..:-~1.:..:8:.:9..:2~_...- >-\\\\-~H g 'cjl X142575 NOTE 5 "'~ ~ 0 I - 0 v co 0 0 I ~ 0 I

fl I

~ DJ v '71 3* (B-11) "' "' t 33013-1250-2 96298 IBLCI <D CD 1 /2" FIRE HOSE D CONNECTION 0 -D "' t: 0 U1 Ul 11125 -,......,._,-.[TC L.!J L!.J t

  • 4-FW-152S SEE NOTE 3 L.!J 11 1/4" T

~ L!.J PSF018(MO/SAFWP1D) STANDBY AUX. FW PUMP D ~ ~ "'-f -+--+.~ c! ::: CD - -o z 00 <D CD L!.J D t ' 9701B l8LCI 0 "' ' v ID Vl Ill 0 -'---=---'-... D 11106 ~ tll 0 Ul 111D5 D 2"l I ~ ~ I D ~ u~ ~ ~ ~~ ~ L!.J D D 0 9704A ~ "' IBLCI ~. LlJ D ,.lo c::'O X'z . l;g rn z ~1~ Iv ! ~ ~ P1..!ill en 9702A

-:-Tl 9705A ILOlco

~ : I co [§]~ ~1 ~~ LlJ D FW-902S D TC )> ~ (A-5) 33013-1236-2 9706A STEAM GENERATOR A [j;QJ J-----'J D "'~ CD I 0 0 I 0 0 I - I 0 0 I 0 0 I 9746F

J D

~...... 9671 (E-l) 1-CD-300-1 I f-1 -~N'----11>::J---< 33013-1234 > LFW06 9667 ~C-O_N_D_E_N_SA_J_E-~ 9662 LFW42 I

t;

[I) L.!J ~ m 0 9672

t; 0

t

  • 9661 v

Q 1-CD-300-1 m ~... )> L.!J D 1-CD-300-1 t ' ',.lo c'o x'z . I ;g wz "'I z MAKE-UP (J-9) 33013-1252 (F-4) 33013-1915 HOUSE HTG STM (H-4) 33013-1237 MDAFW AND TDAFW PUMPS TC X4084 X7976 X4083 P,123 ! I ~ t (H-5) .:::...u 3"

  • r---'--"'--~-

--t SAFETY CLASS SAME AS MAIN LINE SAFETY CLASS 2, 3, OR SAFETY SIGNIFICANT (0) DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. EXCEPT WHERE OTHERWISE INDICATED.

SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

3. THE ~ SIGNALS TO STANDBY AUX. FW PUMPS C AND D CAUSE THE PUMPS TO BE TRIPPED FOLLOWING RECEIPT OF THE SIGNAL.
4. ELECT. MOTOR EIN"S FOR MECH. EQUIP.

ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

5. VALVE FAILS OPEN ON LOSS OF INSTRUMENT AIR AND FAILS CLOSED ON LOSS OF ELECTRIC POWER TO SOLENOID.
6. STAINLESS STEEL DOUBLE BRAIDED CORRUGATED HOSE.
7. VALVE 9728 SHALL REMAIN IN THE OPEN POSITION TO ISOLATE THE SAFW TEST TANK.
8. REFER TO CBI DWG. 175180-000-SP 000201 FOR DI WATER STORAGE TANK (TCD05)

NOZZLE AND MANWAY NUMBER DETAILS.

9. 3/4" PIPE DOWNSTREAM OF 9774 IS SCH. 80.
10. SEE DRAWING 33013-3167 REVISED PER MLS CA CJW CA AOC-16-000023 1/07/16 1/07/16 1/07/16 1/07/16 3 4*

9738 3 4* 97228 l-~6.J....-l33013-1236-2 ~ --n L 97o5B 9706B STEAM GENERATOR B [bQJ ~ ' i I ILOI ~ ~ LlJ I FW-902S CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES D D 1/07/16 DATE AS BUILT CJW RELE'SED FOR GINNA STA. R.E. GINNA STATION NONE STANDBY AUXILIARY FEEDWATER (FW) P&ID I !:'J 11107B !:'JI l_-=._ f-_-::._-::._*_""_~-=.-_-1~ MANIFOLD 33013-1238 DRAWING NO. JOB NO. REV. EWR 3391E CCD 01 CONTROL COPY # 1 2 3 4 5 6 7 8 9 10 1 1 12 A B c D E F G H J

A B c D E F G H J 1 2 1/2" 5923 ~+/- TC 1181 OB 3 4 TDG02A D/G A COOLING WATER EXPANSION TANK 5 6 r BOLTED ACCESS COVER 3 4" ,------"L:!--r 1" o o o o o 0 d I -i 125 301 o 5935 , I ~ 0 0 0 0 0 7 8 9 10 (C-6) 33013-1250-1 1 1 SAFETY CLASS 2, 3, OR SAFETY SIGNIFICANT (Q) 12 SAFETY CLASS SAME AS MAIN LINE '---11-~TC --i 11802 c J~ 3/4" lill P"-'-J 5939 "-'-o~-,---0---0--L--'o ~ 125-1 I ~ o w"-; 0 0 o o SEE NOTE 10 DETAIL A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN, AND TEST CONNECTIONS FDG02 PRIMARY FILTERS 5 L3/4" PDG04A :J-rv'f 5917 DIG A FUEL OIL PRIMING PUMP PDG05A D/G A FUEL OIL BOOSTER PUMP FDG04 SECONDARY FILTERS 3 8" ESW08A D/G A JACKET WATER HEAT EXCHANGER 5890F 3/8" ~ ...._---l[..,.-1------"L:-"---- 11/2" FUEL OIL BREATHER N 5890G 2 1/2" T~ I 5960A 11/4" 5989iil. I I~ ! ~~t ~ ~ TDG04A DIESEL GENERATOR A FUEL OIL DAY TANK Ci "' OJ 0 z c\\, G) D 12419 O"-rf--3~/_8_-_F0_-_1_5_3 __ ~ ~ 1/4-F0-153 01 1/4-F0-153.,, i:--..lf--1 i:-....11-1 12398N 12398M ~] 11/2-F0-150-6 T 11/2-F0-150-6 TC ~* 1" 5977D I I I I ~ ROOF v I NOTE 7 t b?l 3" TE 6622 ESW09A D/G A LUBE OIL COOLER 5907 lfil 1" 5937 ~ Y 3 I 4" r..l'-----'~ 1--<-><l--f" 90~ ~ ~~ 2" l ? !fol (F-9) ~ 3T t._5947B 2" 1---~--°'__.__._, 33013-1239-2 ~ " 5943A ~ I. ~ ". ~ -:;:-- -ii;QJ ILO I L.:= i 5911 p p ~! ~ )>I w 0 0 G)I G)

u J :u

""I~ ,, OJ A (F-9) 33013-1239-2 12398G X5967 X5975 5941A 5945 N I I <g 0.A.-:;;::_A ~ 150-4 TDG03A Ji. ~ D/G A 150 4 STARTING ~ 1~ ~mt~ REC~~ER ~ D A1 COG01A 5947C <M0/AMS1A> ~ D/G A STARTING ~ AIR ~ COMPRESSOR °' <O... ~ 2"1---' I:: b I -"' 0 I O> 2" 2" 5959i:l SEE 3/8-F0-1t NOTE 3 l I 12398A CJ 1/2" CJ-3/8" <O PIT 2052 TDG03B D/G A STARTING AIR RECEIVER A2 N E 3/8-F0-153 ~ 2 I:: 2" 2" <O O> <O,, D o<t 0 2 12398E <O OJ -t I O> 3" SEE NOTE 10 1 1 /2" <O SEE NOTE 10 ()) 0 L _ -4 '---------t-l ~ 0 ~ 0 r.l 0 0 0 o NDG01 2" 0 0 125-1 0 J 0 0 0 3/8" -D-ITUB-ING 21/2" l___~1815L N ' L!J KDG07A PRELOOP FLOW REG. 0 0 0 0 0 I FILL 0 0 0 ROOF TUBING 125-1 --~ SDG01A D/G EXHAUST MUFFLER 0 N 0 ' 0 0 150-4 f'l .250" ---- ~ WALL eo ~ Ill ~ '11 c-t-'--1-f--- -\\J- (- c _Q_ --+:::i ---" L-.--J 11 /2" Co-o KDG02A D/G A TURBO !--1_,.._~_.__~1-~-f--:-C-)H-A-RG_E_R __ (=-~ ]! 2" KDG03A ) D/G A TURBOCHARGER AFTER COOLER 20" ATM~ATM 150-4

5 "---.250" WALL 3

0'" OJ ~ 150-4 <O 0 0 D 0 0 0 ----------- 0 0 0 0 0 0 0 1" ,___ ___ ___,If--) l ~ l~ I "' 11--) L!.J~ ,__,._--j,

+-)

JI I) D ' V TDG06A AFTER COOLER OIL COLLECTION FLASK PDG01A TI 21~rJ -l ) <O 0 -u I D 5" --i c 9l _l 5" ) ~"---+--<f-- 21 /2" I ) D/G A 6 31/2" JACKET !jj '---"'-'----..L..J i-. ... --) 5" TUBING I FDG06 [£] SEE NOTE 6 jj ROOF D/G-BLDG. 3 4" J 3 4" J 3 4" J 3" I,. I I 0 I,. § m 1~ ~ I~ w I ~ I FDG07 [£] Pl 2854 11832 I ;uB1NG '--rlJ-w ) I PDG03A PS 2869 OJ 0 11831 PS 2870 OJ f--...,11-=lTC 11836 NOTES:

1. ANY NEW TUBING OR FITTINGS SHALL MEET LINE SPEC CLASS C-2: EXCEPT THE FUEL DELIVERY TUBES BETWEEN FUEL INJECTION PUMPS AND CYLINDER HEADS, REFER TO ECP-11-000932, FOR GENERAL NOTES, SEE DWG.:

33013-2241.

2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DWG.: 33013-1239, REV.4.
3. FUNNEL UPSTREAM OF VALVE 5915 CONTAINS SCREEN.
4. FOOT VALVE 5919 INSIDE FUEL OIL STORAGE TANK CONTAINS SCREEN.
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL DRAINS, VENTS AND TEST CONNECTIONS SHALL BE AT ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
6. THE EXHAUST MANIFOLD SHROUD VENT EXTENDS FROM THE EXHAUST MANIFOLD THROUGH THE ROOF OF THE DIESEL GENERATOR ROOM. ITS PURPOSE IS TO REMOVE EXCESS MANIFOLD HEAT AND EXHAUST GASES WHICH MAY LEAK FROM THE MANIFOLD JOINTS.
7. VALVE 5979 AT (B-3) HAS INTERNAL THERMOSTATS TO MAINTAIN 170T NOMINAL JACKET WATER TEMPERATURE. VALVE 5987 AT (C-3) HAS INTERNAL THERMOSTATS TO MAINTAIN 180T NOMINAL LUBE OIL TEMPERATURE.
8. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
9. VALVE 5961 INTERNALS REMOVED PER PCR 2001-0047.
10. LOCAL TEMPERATURE INDICATORS Tl-2646, Tl-2658, Tl-2661, AND Tl-2648, ARE LOCATED IN WELLS.
11. LUBE OIL FILTER HOUSING HAS INTERNAL RELIEF, WHICH BYPASSES FILTER ELEMENTS IF FILTER DP IS TOO HIGH.

KDG06A 3" (-~------~~ D/G A WOODWARD GOVERNOR ,Jt~l~{ ~-)----.., EXHAUST PDG03B 3" FAN # 1 .---'-:..:..:.::_~ D/G A CRANKCASE 3.. EXHAUST FAN #2 l--"--r-;r-;--,--,--,--,~J \\J \\J v v \\J v v \\J COOLING WATER DISCHARGE FROM ENGINE n r:-, r:-, r:-, n r,., r,., n 3" PDG08 J D/G A STARTING AIR MOTOR ~us-I L!.J ING KDG05A D/G A STARTING AIR MOTOR LUBRICATOR Ci 9l z G) _j_ (--+t----1~1/~2* ____ .i.__..,..__--I +:] v 5933D 2 CD ---j ) WATER z P_U_M_P _____ "'_ --L!.J-~-w~-:.:_. ___ r.I r.1--'--:;;:-*---~n 3/8" OJ <O 0 '- TS 2882 TS 2878 v n N EOG A ENGINE=KDG01A GENERATOR=EG1A L!.J TUB~ 5905A NDG06 5973 !ill Pl 2852 ()) N "' L!J 3/4" '----'2.3 C-"8_" -( 1 2" j-..rvf 11825 TUBI~ 5995 TUBING 3/8" 11822 E F0-150-6 F0-150-60 0 0 3" 0 5913 1/2" 0 5955 ° 0 NDG04 F0-150-60 OJ 5911AL!.J ~~~~~-1.....-s_. ____.J_..J_...f---J--D<l-2-"_J__, o 0 OPDG02A <MO/DTPlA> 2-F0-150-6 5961 5963 3/4" !:-'---' t 150-4 f\\ REVISED PER ~ ADC-15-000523 DG 7/16/15 0 ;;, OJ r 0 G) c z 0 Cl f'l I ~

u

~ g I z 0 1 <O <O,. <O 3/8-F0-153 Df:--1-----' D/G A FUEL OIL SEE NOTE 9 o 12398C TRANSFER PUMP 3 8-F0-153 o'--- 1-------.~-~o 0 0 3/8-F0-153 _ __,,.__Jo 0 0 'lZI 5919 5951 ROOF MAN WAY SEE NOTE 4 12398D 0 0 0 __j @I 2040

<>lro c

I TDG01A DG.A FUEL OIL STORAGE TANK 2 0 0 0 0 0 12398L 3/8-F0-153 N <O OJ OJ 12398H MANIFOLD (J-9) 5968 33013-1239-2 X5976 (J-9) ~-0--1--0-l 33013-1239-2 X5952 3 L!.J 2" 4 FAL2045/ FALL2046 3" J~ z G) F ~-----<1 NOTE 11 FDG05 5 SEE NOTE 10 3" 3/4" ~ l-<5~98.. 11-----l Ii l I~ JTC I 8 I 11806 3/4" I I OJ 0 °' OJ 11805L I MANIFOJ.Q___J '-l~-1TC 11807 6 TS 2883 7 PDG06A DIESEL GENERATOR A LUBE OIL PUMP 3/4" 1/2" I ,,;;i /,...., 1 3/4"L!:2.i j-..rvf l-5<:9*;9!-"'-?C.:!...--1 ~~ ~ 1 --i PDG07A to

N 65

<MO/LMS1A> ~ ~ z DIESEL GENERATOR A w L§1 ° PRE-LUBE OIL PUMP D 8 9 10 1 1 NUMBER CAD FILE NAME 33013-1239,1 CONSTRUCTION LIMITED CONSTRUCTION; PS NOTED PRELIMINARY NOT FUR CONSTRUCTION BIDDING PURPOSES

  • -1 AS BUILT DATE REl£ASED FOR

~ GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. DIESEL GENERATOR-A (DG) P & ID DRAWING NO. REV. EWR 3391E 33013-1239 SHEET OF 2 & CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 <D N N OJ v~ 59340 59068 2* I 2 KDG06B D/G B WOODWARD GOVERNOR s 5934B I LAS 2719 s 5934A I KDG05B D/G B STARTING AIR MOTOR LUBRICATOR 3 4 5 6 (E-6) BOLTED ACCESS COVER I 133013-1250-1 >>------ 12-5--- 1 -----:-i-----o-~1-o-~l>lbQJ<OJ-o---o-'-\\_0-/ I, 1 ;r 5936 o 0 , 0 "'+-C}-l I f--J 90 125-1 5940 3/4" 3/4" E o 7 0 ')_1" 0 o-TDG02B D/G B COOLING WATER EXPANSION 8 0 0 0 __j ______ r_A~N_K_~j___,,;------:~ 5904 0 0 0 0 MA~ SDG04 SURGE I ~Q~ DAMPENER LC TS 2897 0 0 0 o 0 r;;@E .......__1 1/2" ~ D 6621 0 .---1--------------1~0---------'0=------'-}"vi: 5" ,---------------'---'----J_-------------'--- 0 0 11915L 0 0 9 5924 1191 OB <D 10 ' *~ I~ '0 L MANIFOLD '° ---_:;-FDGos --I ~ E iii F L __ -u~ 5928 1 1 -l c OJ aJ ESWOBB D/G B JACKET SECONDARY FILTER PDG05B D/G B FUEL OIL BOOSTER PUMP PRIMARY FILTER 5891F 171 KDG04C t INLET AIR VALVE LUBRICATOR t---i:~---L.-___J TUBING 125-1 N 0 ATM SDG01B D/G.B EXHAUST MUFFLER 0 M6i'!IF0Ll) __ 1_1_§l15H __ o Ec.L-----i~~----~ --"'-l TUBI~ 0 0 0 0 C' OJ WATER HEAT EXCHANGER N m~ l~G 1~;-*~,J ~~*J___J D 5980A 5890V 5890W C' OJ 5_92.6..... :__l~ 5918 FUEL OIL BREATHER 1 1/2" 5960B 12 ~t SAFETY CLASS SAME PS MAIN UNE t ~SAFETY CLASS 2,3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. ANY NEW TUBING OR FITTINGS SHALL MEET LINE SPEC CLASS C-2; EXCEPT THE FUEL DELIVERY TUBES BETWEEN FUEL INJECTION PUMPS AND CYLINDER HEADS, REFER TO ECP-11-000932. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. EXCEPT WHERE OTHERWISE INDICATED.SAFETY CLASS BREAKS FOR ALL VENTS, DRAINS AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
3. FUNNEL UPSTREAM OF VALVE 5916 CONTAINS SCREEN.
4. FOOT VALVE 5920 INSIDE FUEL OIL STORAGE TANK CONTAINS SCREEN.

"'.(S),---------------------~ FDG13 [£] FDG14 0 ll 2 1/2" ~ '-~4-'-'--14 5990 1 1/4" ,f f 1

5. THE EXHAUST MANIFOLD SHROUD VENT EXTENDS FROM THE EXHAUST MANIFOLD THROUGH THE ROOF OF THE DIESEL GENERATOR ROOM. IT'S PURPOSE IS TO N

<D ~t '-'-' v N JV PS 2886 JV PS 2887 VE--+ 11931 SEE NOTE 5 "' D9 r ~ st%:~I

ij N g z

= ~ ~ M I f 0 I... i::-..---1 11936 1----------------\\.'..I----------------- ( -}..r\\:::r[ 3" PDG03C ~ r---1,-----) ~ ru~ EOG B ENGINE = KDG01 B GENERATOR = EG1 B PDG09 D/G B STARTING AIR MOTOR 1/2" N 3" 3" c +---l\\-) PDG03D D/G.B CRANKCASE EXHAUST FAN #1 3" c --i H---1\\-) DIG B CRANKCASE 3/~"~ 3/4" J J EXHAUST FAN #2 3.. E--~--~-~---.--<"1 COOLING WATER DISCHARGE FROM ENGINE !":),,., (;'\\ "' 17"\\ 17"\\ 17"\\ ""' 3" 150-4 OJ 0 OD KDG07B PRELOOP FLOW REG. FILL N TUBING I


-----t----- :r

'-+-S v v vC, (/),,,__,,_..... 0 Cl ~--~~ OJ c --i 1--I -... - - - -., - -, - - - -, .I.~ l~ ~... N = ~ 3 1/2" 1" '---+--) KDG02B (~'--- 1 1/2" D/G B >-+-~ .--:_-_T_u_;_B_O_-_C_H_A_R_GE_R _ __, ~ ~ (--l>-+-~-l=tJ-KDG03B ( ,2" D/G B TURBO-CHARGER AnER COOLER v (-1---j TDG06B AFTER COOLER OIL COLLECTION FLASK c-:- 1 N ~ LDG05 L--------T--1---) I r 5" D~ (-;.--i)-'--- m 1 ' ' L_ _____________ _ 2-SA-150-4 2 <D ~1 D N OJ <D ~ LDG06 - g; 3 1/2"

( .. I n c_ n n ~---** tt---~~~~*- 11922 PS 2990 TS 2901 11921 PDG01 B c --j -(-:_-:_::*==== D/G B JACKET I WATER C----)---1f-- PUMP n 3" MANIFOLD _ _ __J 3/4" ~-+--:J 5996 3,1' 4" lill3/4" ~ PDG06B DIESEL GENERATOR B LUBE OIL PUMP te' 3/4" r---..--,--t-..--D<J--+--1 Q;! 5982 I H><P-=--CJ-}..rvf 3/4" 1/2" l--=T--JJ*D---1 }.rvf 6000 5891B PDG07B <MO/LMS18> DIESEL GENERATOR B PRE-LUBE OIL PUMP 3 s 1~ z G) 4 Pl 2654 5 ~ ' .~ I i.1"' I ::: '<O ,o 11;; L!.J z Cl 3/4" 11905H : 11905L ' 6 10 FDG12 7 NDG02 1 2" 2 1/2" N I 0 0 _o_ 0 0 N I 0 0 0 N 0 0 <D -..J 3" SEE NOTE 9 1/2" C' 3" 3" N 5988 ~3"

)

TE 1/2 6624 ESW09B D/G.B LUBE OIL COOLER 1" 5938 12399G (F-3) 33013-1239-1 (F-3) 33013-1239-1 5908A [fQ] 12055 TDG04B DIESEL GENERATOR B FUEL OIL DAY TANK ~ D '----------~---~~"' N 12421 N [§] ~ ~ I d I


~3~8~-~F~0-_1~5~3-}.rv(

0 I 5967 1/4-F0-153 J-+.-J 12399M v g I.. ~ 0 I ROOF 2" l:i 5975 N 1/4-F0-153 J-+.-J 12399N 0 I 1 1/2-F0-150-6 T 1" 5978D [QI I 1 1/2-F0-150-6 Pl 2643 5948C~~ E 59428 2" 3~" 1 2"


r><l--i I 5944A UBING 5948 Pl 1bQJ 2542 2"

5944B 1; 4" 1UBll!G ~11/2" 2" 2" ~ ~ 'I' 5921B d J:'-;25"*----[__ _ _j 5946 1/4" 5942A r-.... 1--:J 5942C REMOVE EXCESS MANIFOLD HEAT AND EXHAUST GASES WHICH MAY LEAK FROM THE MANIFOLD JOINTS.

6. VALVE 5980 (B-8) HAS INTERNAL THERMOSTATS TO MAINTAIN APPROX. 170'F NOMINAL JACKET WATER TEMPERATURE.

VALVE 5988 (C-9) HAS INTERNAL THERMOSTATS TO MAINTAIN APPROX. 180'F NOMINAL LUBE OIL TEMPERATURE.

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHAICAL EQUIPMENT PER SFEWR 10328.
8. VALVE 5962 INTERNALS REMOVED PER PCR-2001-0047.
9. LOCAL TEMPERATURE INDICATORS Tl-2659, Tl-2660, Tl-2653, AND Tl-2655 ARE IN WELLS.
10. LUBE OIL FILTER HOUSING HAS INTERNAL RELIEF, WHICH BYPASSES FILTER ELEMENTS IF FILTER DP IS TOO HIGH.

_I.. //150-4 150-4 h 5960 2" ~{SEE NOTE 3/8-F0-153 I 3 12399A 2" "',I): od*~ ~ N 3/8" g TDG03C I D/G B '° ~ "' SYARTING AIR o RECEIVER ~ B1 5948B ~--r CDG01B -[><]--l I 5948A [bQJ 2" E--1 2" ~ <M0/AMS1B> ~ -"; D/G.B STARTING AIR COMPRESSOR {- F0-153 3/8" 12399E TDG05B D/G B 2" E---< TDG03D D/G B STARTING AIR RECEIVER B2 I <O "t" 0 D 2" 0 0 5914 ° 1 2" J FUEL OIL '° TRANSFER g; PUMP PRIMING TANK ~~3 2228 _, T s~D &i 0 0 0 0 z -+--+-G) 3/8-F0-153 1 2" F0-150-6 <D J, 2227 f--l5>9<1J-0---,orl F0-150-6a gLJ Pl ::-1 r2_"__,_2_" -l><J--1.-/'F---'---'-'-"--'-'"'--"--"'-'----I ~.. o o h--H-orll-'-2-"co 1--o -'-~"-L.-/'r-, F0-150-6 0 0 5964 5962 PDG02B NDG08 I 5956 SEE NOTE 8 <MO/DTP1 B> 3/8-F0-153 r.i ~t-!'J_IF_OLp_---i D/G B FUEL OIL .... JD I I TRANSFER PUMP 12399C 3/8-F0-153 12399L 'i 3/8-F0-153 ---<~~*+-=JD 12399D 0 0 0 0 0 0 0 CAD FILE NAME 33013-1239,2 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 5952 2 1/2"-150 ' I 0 ~ FACllll'I' GINNA STA. 0 R.E. GINNA STATION Cl SCALE NONE I------'-'"'-"~--'---------~ 0 0 (J-3) L-<::~3~3~0~13~-~12~3~9~-~1:=J X5968 N c z 0 f'1 DIESEL GENERATOR - B (DG) 0 (J-3) 0 0 0 0 33013-1239-1 24" MANWAY SEE ---i;gy NOTE 4 5920 / / i)l P & ID ~ 1---------~--------------------.----~ 0 JOB NO. DRAWJNG NO. REV. c 1------+-----------+----1 a EWR 3391E 33013-1239 SHEET 2 OF 2 ~ X5951 TDG01 B D/G.B FUE'.L OIL STORAGE TANK CONTROL COPY # CCD 01 8 9 10 1 1 12 A B c D E F G H J

A B c D E F G H I J 1 2 4 5 6 1" 1" 1 1/2" I I ANSUL AUTOMAN Il-C CUTTER HEAD (TYP. 2) SFS20 SFS21 NOZZLE H-1 PI Pl (TYP. 4) ~ N, HALON 1301 TURBINE BLDG. RELAY ROOM STORAGE TANKS 0 360 PSIG AT 70' F 18 LB. - NITROGEN PRESSURE ------- CARTRIDGE ~--- HALON LOCAL CONTROL PANEL S08 HLCP S07 AACR -- 91/i LB. HS PRESSURE SWITCH S08F -CR PUSHBUTTON ACTUATOR ON PANEL CONTROL BLDG. MULTIPLEXOR ROOM AUTOMATIC HALON SYSTEM S08 SEE NOTE 5 & ANSUL AUTOMATIC Il-C CUTTER HEAD ('W. ' '~"' \\ .c 90 LB. HALON 1301 TANKS (360 PSIG AT 70' F) (TYP.8) 1 SFS12 1/4" O.D. 2 . c SFS13 PI,__ _ S08F-RR 1 8 PRESSURE SWITCH ~ / HS 3 RELAY ROOM MULTIPLEXOR ROOM 1 1 /2" PIPE TYPICAL 8 PLACES i ~ SFS14 SFS15 SFS16 PI>--~ PI,__ _ SFS23 ~-~ --- 1/2"0.D. 4 5 REMOTE ACTUATOR N2 CARTRIDGE S08 6 7 NOZZLE H-1 (TYP

4)

~ ~ ~ ~ SFS17 PI r--- 1/2" O.D. CONTROL BLDG. RELAY ROOM AUTOMATIC HALON SYSTEM S08 7 ~ ~ ~ SFS18 PI r---1 8 ~ SFS19 8 9 10 TURBINE BLDG. RELAY ROOM ~ 1 1I4" ~ 340 LB. HALON TANK I'~ I /"' I r--l--i I I+ I

11 I

I t-t-i 1 SFS22 L /"-. /"-

I;
;~;-:;-

/ "-. / "-. /"-. /"-. /"-. /"-. NOZZLE H-4 (TYP. 31) PUSH BUTTON ACTUATOR ON PANEL


NITROGEN PRESSURE CARTRIDGE

~--~ ->---ANSUL AUTOMAN Il-C RELEASE ASSEMBLY 9 HALON LOCAL CONTROL PANEL S©S HLCP S08 10 1 1 12 - I NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. VALVE POSITIONS AT THIS TIME DO NOT REFLECT AUGNMENT FOR ANY MODE OF OPERATION; THEY ARE SHOWN ONLY TO REPRESENT THE SYSTEM AS-BUILT CONFIGURATION.
3. SEE DRAWING 33013-462, 0838 & 0839 FOR DETAILS OF THE ELECTRICAL INTERFACE I &

TO THE FIRE PROTECTION SYSTEMS DEPICTED ON THIS DRAWING. I £4. ALL PIPING IS SCHEDULE 4111, ASTM A-53 OR A-106. NOZZLE V

5.

FIRE SYSTEM S07 AND S08 WERE COMBINED INTO A SINGLE SYSTEM SUCH THAT ANY DETECTOR FROM EITHER OF THE SYSTEMS WOULD PUT THE SYSTEM INTO ALARM. _J REVISED PER OCR 2000-0018 PCR 96-125 AJV3 2/21/00 NUMBER RE\\l'.lS!ON CAD FILE NAME: 3P124201 CONSTRUCTION UMITED CONSTRUCDON: AS NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR.

  • ~

G!NNA STA. SCALE NONE FIRE PROTECTION RELAY AND MULTIPLEXOR ROOMS (FP) JOB NO. DRAWING NO. REV. EWR 10113 33013-1242 CCD 01 CONTROL COPY # 1 1 12 A B c D E F G H I J

A B c D E F G H J X14231S 1 (A-3) 33013-1892 (A-3) 33013-1261 2 1" 152 7321 ccw SURGE f1* I TANK CHEMICAL l ADDITION HOPPER 3 4 5 4-AC-152 2-AC-152 152 ~ .~I~~. ¥i0]~"7I:,------ ~ c:iiEti~~


+~-t---1 I~"'- t MANWAY ril 698A 698

'1. ril 1" 731C TAC02 CCW PUMP SEAL DRAIN TANK (E-6) 33013-1269 RMW (G-9) 33013-1908-3 NAC01 PAC01 CCW PUMP SEAL DRAIN TANK PUMP 2-AC-152 3/4" ~ TAC01 ccw SURGE TANK ~ I L!J D 713 250pl1p2 7300 1/2" 1" 730E 1" L!J L!J D 1" 2" 1" HHXJ---'T-1 J-'--IL><J------rl I 1-730A 730B [§] ~ J 31 J;i Ol T I 1" 2 .. t:9 § 1,s ~ i 2-AC-152 L-------------~ i5 2" ~ (1-11)


~~---+--< 4*

r--~--'---...... L--t-J 33013-1270-1 2* 3/4" 72~!1 152 TUBING S 3 PAC02A <MO/CCPlA> COMPONENT c_ _____ __c4_"-{ 1---"6-" ----, COOLING WATER PUMP A Pl [§] 2669 Tc~----1 12064A 3/8" O.D. v WASTE HOLD-UP TANK 1* 8* 8" 1 o* 6 7 8 v 733B t~ z G) Cll 0 ~ ,--------------------+-~ RM-17 COMPONENT COOLING WATER SYSTEM PROCESS MONITOR SKID R 12517B I A I v ril 12517A Q 10* 733A L--~C>> TE 6874 9 v 734B EAC01B COMPONENT COOLING WATER HEAT EXCHANGER B EAC01A COMPONENT COOLING WATER HEAT EXCHANGER A 10 0 Cll ' 735A ~ ~....__"' ;',, ~23 'tj -~ p 3 ~ ~ L__________________ --------~ L!J w*---~.._ 3-AC-152 s g *.------1 _________ ~""-'=--'-=-------------r><:~------' )> 772A D.I. WATER MAKEUP 14" 1---i,___, --11!~ I LL>::.:..1--,i-i 14" v (J-10) -C><l-J 33013-1246-1 X816 (A-1) ~33013-1246-1 X817 8" (J-10) [~~~~~=:>--~6-~A~C~-~1~5~2--i -l><H 33013-1246-2 X778 8-AC-152 14-AC-152 3/4" Sl-'--~4--------- 779A ~I"' <O 0 ~ )> "' 738A IBLCI 722A PAC02B <MO/CCP1B> COMPONENT COOLING WATER PUMP B [§] 7228 2-AC-152 14.. "\\ I 0 ' PUMP SKID 3/8" v PUMP SKID v t 723A 724A 8" 11~1 7238 7248 3" 772B 14-AC-152 3/4" 3/4" "' " 0 AUXILIARY BLDG. 1*-+---- SERVICE BLDG. £ o 3"'"' -...J -...J G) 0 .p.. 01 01 = 0 ""!(/) c fT1 <<; ;u c~ )> 0 ~!""' OJ CD!' ro OG) SERVICE BLDG. INTERMEDIATE BLDG. (/)I~ r'l r'l

u ;u fT1 Oo fT1 -

I~ l'1 fT1 olrn !" r g (G-5)


J'f--~===-----lf--<~3~3~0~13~-~1~8~9~9-~1]

'-:::=L=:--'l X1471 OS ~__,~ 747F 10048 747J 747G (G-5) 33013-1899-1 X14709S 747K 747D I 11 /2" 10020 I ~~ (F-10) 33013-1259 1 1 12 MANIFOLD 7358 12068L 12068D I ~I ~ OJ 1 2 D ~ 12068H 120691 ~---~ (A-4) 33013-1270-1 > ~5 3/4-AC-152 6-AC-152 3/4-AC-152 6-AC-152 (A-1) 33013-1246-2 B.A. EVAP WASTE EVAP. GAS COMPR. SW HEAT EXCHANGER (A-2) 33013-1270-1 (1-1) 33013-1246-2 CONTAINMENT SPRAY PUMPS & SAFETY INJECTION PUMPS & NON-REGENERATIVE HEAT EXCHANGER & SEAL WATER HEAT EXCHANGER X760A X773 ~I SAFETY CLASS SAME AS MAIN LINE

1' z

L SAFETY CLASS 2,3 OR SAFETY SIGNIFICANT CLASS (Q). DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS INTERMEDIATE BLDG. (E-6) -C><l-l 33013-1246-2 6" X760B 1 2" 2-AC-152 1--*---l'r:f 740A ~---~ v "I"' <O 0 2-AC-152 r:f 7408 ~---~ 10* 7388 IBLCI FIC 651 )>

I z

--+-~ 6 1-----11~-----1 r 0 0 120678 0 O> O> r I of'- °' "' o~ =- "' D 2-AC-152 L-----"'--'-'"'----'-"'"--------{:0-::}----------11 >-------~ 769 © 2 3 4 707A [Q] EAC06A RHR PUMP COOLER A 7078 [Q] EAC06B RHR PUMP COOLER B 7088 [Q] 2" 5 ) ) PAC01A <MO/RHRP1A> RESIDUAL HEAT REMOVAL PUMP A PAC01B <MO/RHRP1B> RESIDUAL HEAT REMOVAL PUMP B 6 7 1" 1* 1" 1" 1" EAC01 FAIL FUEL RAD. MONITOR HEAT EXCHANGER EAC05A PRESSURIZER LIQUID SPACE SAMPLE HEAT EXCHANGER EAC05C 1~ 901 1" 771E PRESSURIZER STEAM 1* SPACE SAMPLE HEAT '-----'-[><:J---j EXCHANGER EAC05B RC LOOP B HOT LEG SAMPLE HEAT EXCHANGER EAC04B S/G SLOWDOWN SAMPLE HEAT EXCHANGER B EAC04A S/G SLOWDOWN SAMPLE HEAT EXCHANGER A 771D 1* 771C 1* 771B 1* 771A 8 10049 9 ESS04B ESS04C SAMPLE COOLER RACK 10 SUMP NOTES: 1. FOR GENERAL NOTES SEE DWG. 33013-2241

2. THIS DRAWING SUPERSEDES PORTIONS OF 33013-435
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. THIS SECTION OF CLASS 3 PIPING ON TOP OF CCW SURGE TANK IS NOT SEISMICALLY SUPPORTED.
5. ELECT. MOTOR EIN'S FOR MECH. EQUIP.

ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328. CAD FILE NAME: 33013-1245,1 CONSTRUCTION LIMITED CONSTRUCTION: PS NOlEO PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES PS BUILT DATE RELEASED FOR ENGR. GINNA STA R.E. GINNA STATION 1 1 SCALE NONE JOB NO. AUXILIARY COOLANT COMPONENT COOLING WATER (AC) P & ID DRAWING NO.

  • SWR 3391E 33013-1245 CCD 01 CONTROL COPY #

12 REV. A B c D E F G H J

A B c D E F G H J 1 (E-1) ~-33_0_1_3_-_1_2_4_5~::::>- ccw HEAT EXCH. OUTLET 33013-1887 X 14138sL..:=c:::__:.::o::_~~ 1 2 3 2-AC-152 817 IBLOI 4 8-AC-152 5 6 6-AC-152 7 8 9 10 (E-3) 33013-1890 ti?:sc X14291S 1 1 12 NOTES:

1.

FOR GENERAL NOTES REFER TO DRAWING 33013-2241

2.

REVISION "O" OF THIS DRAWING SUPERSEDES PORTIONS OF 33013-1246 REV. 5.

3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

3-AC-152 4"

4.

EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING 4* 152 !TUBING 3/4" 1---*~TC 750D VI I /'; I OJ 3" 751B 15 SEE NOTE 152 1 TUBING 3/4" P'-'---.... 1--11-- D 2732 3/4" 152 l~UBING

JTC 2741

--:d b-P1 3" 750B 152 © © 152 4" PRC01B <MO/RCP1B> REACTOR COOLANT PUMP B ECHOBB RCP 8 UPPER BEARING COOLER SEE NOTE 6 N VI <D (:;j i~ D 1" 7 1" 3/4" 1----<f,J\\..n MOTOR 1-JVlr----------.-..-JID 3L8" 3/4" E-U '61... H>---< ~125~i.~1~-~:~~. ::::3 ~ 2738 PUMP ~i1---- 3/4" "' u SEE ~ 2" 761E ~ ~NOTE (:;j ~ "' ' 8rlf---11-~ 1 2 (JI ~ v D 12305H 12305L MANIFOLD ~


jti 758B 765B 1/2"

<Ill D 12307 4" 2" ~-----< 1" 2 VI ~ P125 (}> 4" __(FE\\

  • ~

v 11~2* Fl 615 8" 3 3" 7578 ~ I (}> 4 ~ I (}> 2-AC-152 u ~I 152 l\\UBING 3/4" °' !--'--.... 4--Jif--:J D 1521TUBING 3/4" ~ 2730 <$) ; 152 ITUBING 3/4" TUBIN~2 I 3/4" D Hf--l.... -1 2728 "'27~ ~ <$) ~ ' ~----H-~ (}> -:d 3L8" 3/4" E-l 761G !---'---...-1

J TC 2761 bP127 VI '

AUX. BLDG. CONTAINMENT 01El ~l P124 SEE NOTE 5 2-AC-152 ~ TUBINq 11 ;52 ~ 3/4" TCE ECH03 EXCESS LETDOWN HEAT EXCHANGER 1~BING 3/4"

J TC 750C

~ 751A H""H~---il SEE 2776 2" DI 152 © © 152 4" 3* ".:li~ (}> (}> D PRC01A <MO/RCP1A> REACTOR COOLANT PUMP A ECH08A RCP A UPPER BEARING COOLER v SEE NOTE 6 OM8 2756 NOTE IM B 7 1 * '-r---lk.f'vl H MOTOR f--il----~hJV-1:1-----~-l 152,,.J© .1.152 I- "'*VI 250~ I *~©-~~-©_. I ~so3

J ~

'-t:<<'.1--.---.--1*-l PUMP ,,_,>-----~-~ 761F (}> D D I /'; I (}> ?. 7441Jt--1=- 3/4" (H-10) 33013-1888 152 ITUBING 3/4" t--..... -Jr--:J D 2723 152 ITUBING t--....,-JI D 2724 -:db--- P131 3/4" 2733 15?,:-t-151 3.. 11----- ~ -I 2"--11 -~ ~ 152--1--151 O> 3/4" DI~ 2750 -/ -/ -I -I -I 4" 4" 151---i--- 152 ~ 3" !- ~_.if 2752 £1 ~ 2" /- ~ ~~1-1.-----1 151 152 /- I- /- /- /- /- I-I- I- /- /- I- /- 4" £1 3/4" 1----:J D 2751 SEE NOTE 8 "-------_Jx14132s 1/2" 1--+'4 D 12309 .---1,-.--f><:J---+..L..f 1--{::e:J-,~ 12308H 1765D i--.... t-:J D 12308D 152 2505~ ~I '------+---'----i>Q--+rl 12308L MANIFOLD ~


jti 758A 2"

765C 1/2" <Ill D 12310 3" 2503 1~>----~ 3" 757A I /'; I 4* LAC01 3/4" Dir--. 2748 1" 818 r-- 3/4" -I /- -I I- -I /- -I /- -I /- -I I- -I /- -/ I- -/ I- -/ I- -/ /- REACTOR SUPPORT COOLER B SAGOS 4" 4" 152--j---151 FOR SAFETY clAss.

5.

CHECK VALVE 743A INTERNALS PERMANENTLY REMOVED.

6.

RCP UPPER BEARING COOLERS ARE SUPPLIED WITH MOTORS. SHELL-SIDE PRESSURE BOUNDARY IS NON-CLASS, TUBE SIDE CLASS IS THE SAME AS CONNECTING PIPING.

7.

COMPONENT COOLING WATER FOR MOTORS: CLASS RATING EXTENDS THROUGHOUT CLOSED COOLING COIL.

8.

COMPONENT COOLING WATER FOR PUMPS: COOLING COIL AND THERMAL BARRIER ARE CLASS 1. CLASS BREAK FROM CLASS 1 TO CLASS 2 OCCURS AT CCW PIPE INTERFACE WITH COOLING COIL.

9.

ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328. 1-3"---l I ~l---l~-1~~ -I 151--J-152 13" /- D--4H_.o/ ,___2*-~*1----:__~~~-/ 152--1--151 2771 £1 ~ 2" 1- ::;;; - I 1,.e-,____, 2710 I 151-l-152 4" 3/4" DI----. 2769 4" LAC02 O>... O>..l I- - /- - -/ /- - I- - /- - /- - -/ -/ /- - -/ /- - -/ /- - -I /- - -I -/ /- -/ /- -/ /- -/ /- -I /- -/ /- -I /- -/ I- -/ /- -/ /- -I /- REACTOR SUPPORT COOLER A SAC07 !~ H 4" 3/4 ~. ID .J 2768 4" 1YP. 8 PLCS. 1" 1YP. 96 PLCS. ~-t-----11 D 2767 D VI ~ P126 3/4" v 11---t----I IP130 ~ 5 (}> CONTAINMENT AUX. BLDG. 6 7 1-3/4" O>, 8 816 3/4" D....,1----1 11259D 7368 1/2" DE~4---I 11261 1?~0' ST.STL.PIPE~ MANIFOLD 11259H 1YP. 11259L w 8-AC-152 9 ~~o=*~* AS MAIN LINE r Z tSAfETY CLASS 2 OR 3 DETAIL-A SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS 14" (E-1) 33013-1245 CCW PUMPS 10 1 1 RJM 5/13/1 CAD Fll£ NAME 33013-1246, 1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES I IV PS BUILT DAlE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. AUXILIARY COOLANT COMPONENT COOLING WATER (AC) DRAWING NO. REV. EWR 3391E 33013-1246 SHEET OF 2 L11 CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 (C-12) 33013-1245 ccw HEAT EXCHANGER DISCHARGE TT 2841 <MO/CSP1A> PSl02A CNMT SPRAY PUMP A [I] ) 1/2" EAC11A CNMT SPRAY PUMP A SEAL HEAT EXCHANGER 1 33013-1245 CCW HEAT EXCHANGER DISCHARGE 6" 3" I I fl I - 2 748A [ill 3 2" 3/4" 4 21/2" ~~pwvg-*~1 ~I N ' 3/4" 748D v 0 774C ECH01 BORIC ACID EVAPORATOR DISTILLATE COOLER ECH06 BORIC ACID EVAPORATOR AIR EJECTOR CONDENSER N ' 6" ~-----1!....e-lf-----11-----,----'----, I fl I 3/4" 3/4" 815B 727B 0 OJ

L 1-AC-152 1..

774B ~!--------....----------! 11278L 1.. 5 3/4" f---" '-,.. N ' (FE\\__ 1S2 250S '-----tt:J 77 4A ~I 3/4" I 727C D..... 11--1 11278D 11278H MANIFOLD Fl 642 L!J I fl I -'" N (FE\\__ ~. 11/2" 3/4" 2712 6 11 /2" (FE\\__ ~ 2-AC-1S2 ST.STL.PIPE 1 2505 1 /2" 8 1 D~ 11273 3/4" 727L ~ 152 2505 3/4" 1/2" D~ 112720 727K 11274 I ST.STL.PIP~ ~SOS 0 7 3/4" 11/2" 8 (F-1) 33013-1273 11/2" v 111--... c----; L_ __ __J _ __J 77SB sT.STL.PIP~ I ;sos 1/2" D~ 11276 3/4" 727H 152 3/4" 1/2" D~ 2505 1127SD 11277 I ST.STL.PIP~ ~S05 3/4" 11272L 11272H L!J MANIFOLD 1127SH 1127SL L!J 7740 l:if--~ 1" EWD01A WASTE GAS COMPRESSOR A SEAL WATER HEAT EXCHANGER EWD01B WASTE GAS COMPRESSOR 8 9 3" OJ 10 2-AC-1 S2 v 3/4" (J-1) 3 4" 33013-1273-1 SEAL WATER 1 1 X1032A 12 ~! SAFETY CLASS SAME AS MAIN LINE t SAFETY CLASS 2,3 OR SAFETY SIGNIFICANT (Q) ECH07 BORIC ACID EVAPORATOR HEAT EXCHANGER -~ 1-_ _::2_" -~---------------------------------------------_.__. 2" '::i DETAIL-A 1YP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS A SEE NOTE 6 1/2" 1/2" 3/4" 6" 2 2-AC-1S2 <MO/CSP1B> PSI02B CNMT SPRAY PUMP 8 [I] ) 1/2" EAC11B N 0 ';:) CNMT SPRAY PUMP B SEAL HEAT EXCHANGER 6-AC-1S2 1/2" FE 649 1/2" -.,J ~ ~ ~ Y-4...,,--+ __ 01_ I N 0 0 11263B r 4 7640 ITRL! L'-1 D 6" N 0 ~MANIFOLD I 3/4" EAC08A SI PUMP A SEAL HEAT EXCHANGER 777L !ill (1-1) 33013-1245 CCW PUMP 3/4" 2810A ~ 0 3/4" 777M 2 !ill t::::::::=J i:--H >----"---~------, 3/4" EAC08B 3/4" ) SI PUMP A F~~=l-ror:~.f; *.:(1==::;:=~_:__, SEAL HEAT L EXCHANGER 28108 3/4" 2 3/4" t----;1-- ---{;.(I----( 777F !ill 3/4" EAC10A SI PUMP. C SEAL HEAT EXCHANGER 777N !ill 3/4" 3/4" 2810F N 0 N g; 777E [ill 3/4" 777G [ill t:=:~ r:--.., f--L--__,.,.----, 3/4" ~c~~BMP C 3/ 4"I::::;-~;f;;jj::('f:=:;==::: SEAL HEAT i=::=i t EXCHANGER 28lOE ) 3/4" 2 3/4" 1--1-- --~Cf---{ 777H !ill EAC09A SI PUMP 8 SEAL.HEAT EXCHANGER 3/4" 777S !ill 3/4" 3/4" 2810D I: 2810C N 0 N 0 2 777P !ill 777K !ill ) 3/4" 3/4" 2" 6" ~

1.

N 3/4" N

  • 11-..... Kl~N PSI01A SAFETY INJECTION PUMP A

[fil <MO/SIP1A> 2716 (1-1) 33013-1270-1 PSI01 C SAFETY INJECTION PUMP C [fil <MO/SIP1C> PSl01B SAFETY INJECTION PUMP B [fil MANIFOLD <MO/SIP1B> I:: N I g; I ECH04 SEAL WATER HEAT EXCHANGER 3/4" 12719 ~ FIG 650 11266B N N g; ~oo N 1/2" 1/2" 6-AC-152

  • 3/4-AC-1S2 3/4" 766

~ I fl I N 2-AC-1S2 N (Xl L!J D N g; u 01 7648 NOTE 5 v ~!~152 ECH05 NON-REGENERATIVE HEAT EXCHANGER 3/4" 152 *I ;sos 1/2" 2718 D [C--c-i-- J--- 11270 1/2 D~ 727S 1S2 2505 D~ll--1 11269D 11271 I 1s2.~sos 776 3/4" 3/4" ~f---t-~1--cH D 2721 ~ I N 0 Tl 600 MANIFOLD 11269H 11269L OJ Fl 601 L!J (B-10) [__--f/-----11--~:::::=3~3~0~1~3~-~18~9~1==] (B-lO) X15906 1.* '-----f.__ _ 2-AC-152 2-AC-152 L'J 3/4" 2722 l/P 130 33013-1891 ~X15907 3/4" (F-1) 1-~1-- --t:a:'.1---{~--'------..-------- 11---------Dl(j-----------o--~ 777J [Q] N g; 3/4" 777R !ill 6-AC-152 ~. 764C ~ !TRLI 33013-1245 CCW PUMPS 5 7 8 9 10 1 1 NOTES:

1. FOR GENERAL NOTES SEE 33013-2241 DRAWING
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1246, REV.5
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE !N ACCORDANCE WITH DETAIL "A".
4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
5. THE WASTE EVAPORATOR HAS BEEN ABANDONED IN PLACE. VALVES 764A AND 764B ARE KEPT CLOSED AND LITTLE OR NO MAINTENANCE IS PERFORMED ON THE PIPING OR COMPONENTS WITHIN THE ISOLATED SECTION.
6. THE PIPING FROM THE CONTAINMENT SPRAY PUMP TO THE SEAL WATER HEAT EXCHANGER IS STAINLESS STEEL WITH 405 PIPING AND 150#
FLANGES, CAD FILE NAME 33013-1246,2 CONSTRUCTION LIMITED CONSTRUCTION; AS NOTED PRELIMINARY NOT FOR CONSTRUCTION B!ODING PURPOSES AS BUILT RELEASED FOR ENGR.

'~ GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. AUXILIARY COOLANT COMPONENT COOLING WATER (AC) P&ID DRAWING NO. REV. EWR 3391E 33013-1246 SHEET 2 OF 2 A CCD 01 CONTROL COPY # 12 A B c D E F G H J

N I 0 ID "02d..!.. -!!!!L ~~~~~~~~.-~-+-I ~~~~~~ ..... r I cncu~,.,. I ~, c!""I t& _ff;, I ..-J l( -.0 °:!:a1 l. I~ !111:11ru H1$1 .___1 __ -;-J:~~f-.;;~_!_'.::,.__;:i..:L~ () m N OJ )>

A B c D E F G H J 1 2 3 4 LT-310 3/4" v E---1M--I 799E CPB-AUXILIARY LC 0 y 5 PAC06 <MO/SFPSP> SPENT FUEL POOL SKIMMER PUMP fr z c __, ?< Sti CD CD 'r 00 6 7 (F-11) N -i 33013-1259 > 2-AC-151 "------'Hl-------~-=-='--'"-'-----'-----_J INTER. BLDG. NOTE 3 ( TEMPORARY SKID 8 9 NOTE 5 6-AC-151-SFP SFP FILTER ROOM (F-9) 133013-1908-3 > 2" 788E ~ N 1 0 SFP FILTER ROOM 811 788A [!£] R.R. 4" 6" / SEE NOTE 11 BLDG. 661


"SUMP

---cooc-------~ N 0 C-2 I 2~t# I. 301 ... I-- HOSE 1,, E--+--Nve:--~--- 1" -~ E Nvi::-~-- NAC03 STRAINER LJ z,.. g 2-AC-151 AUX. PUMP SKID (F-11) 33013-1259 ~ "'-"",,__,µ BLDG. CONTAINMENT INTER. BLDG. SACOG SUMP NV[ ~HOSE NORMAL WATER MIN. WATER LEVEL 257'0" LEVEL 276'11 3/4" TAC03 SPENT FUEL POOL ~------1--- SPENT FUEL POOL TRANSFER GATE FUEL TRANSFER CANAL NOTE 4 SAGOS \\_ LEAK DETECTION CHANNEL ~~~-1~~~~__J_~~ LEAKAGE COLLECTION CHANNEL TC °' 650P2 Pl 21 f-"---11-~ Tl 24 650X 3/4' v P~+------' 'T1 °'"" SEE NOTE9\\- r----'~"" "' 0 V ~ C'l ~ Pl 22 °' "' D }.\\ 650P PAC03 SKID MOUNTED SPENT FUEL TC POOL PUMP '] D 8671 1/2" SS TUBING EAC12 SPENT FUEL POOL STANDBY HEAT EXCHANGER Pl 23 1/4" c_~_J 650V 3/4" 6" Tl 26 (F-10) 4" 33013-1272-2 REACTOR COOLANT DRAIN TANK PUMPS (..; V> '0 I :r ~ l"1 ~-------------~"" 0 r f,, I /) I I V>

i J rz N

J (C-7) 33013-1264 NONREGENERATIVE HEAT EXCHANGER (B-7) 33013-1264 NONREGENERATIVE HEAT EXCHANGER v m co I,.. 0 I ~ Q LT-311 N SEE NOTE 6 X1722 Pl 652 501 I 151 2-AC-151 820 601 151 821 y 1/4" (0-1) 33013 1272 2 REACTOR COOLANT DRAIN TANK PUMP 824 0 "' 0,, 0 LAC07 r----.-4--JTC 86728 ~ 783E PAC07A <MO/SFPPA> SPENT FUEL ~ POOL RECIRCULATION PUMP A ~ ~ 0 ~--~ 4" -1'- NOTE 5 co O> N O> NOTE f-'--------,.--_J_--'--i-~ 6" --f:><l----0,-1---1>-"-+-)--=~ 86~4 ~ J 8655 3Q OL'.J 0 NOTE 3 Pl 8665 1/2" SAC01 OTE 3 Pl 8672 1~ 1-----~4--ITC 86666 AC-151-SFP 8658 N N I /) I D 806 8667 vE (C-3) 33013-1261 REFUELING WATER STORAGE TANK X808 PAC05 <MO/RWPP> REFUELING WATER PURIFICATION PUMP 33013-1230 (B-1) X9050 3/4" 7830 Tl 633 Vt-iH----1 783C v [-j!l--i--1 787 7798 11----1 ~ (C-6) 33013-1270-1 WHT g; 0 TUBl1NG 51 °' v Pl ~ 653 co LAC OS 810 3/4" 0 I /) I (J-7) 33013-1264 WHT TO QUICK CONNECT AT RESIN BATCH HOPPER ON DWG. 33013-1264 (H-4) 795 2-AC-151 0 Hll-i'*-r L-j__ce2c:-"'A"-C-=15;_;1<___J 790A TUB$ 4-AC-151 EAC14 SPENT FUEL POOL HEAT EXCHANGER A TAC04 SPENT FUEL POOL DEMINERALIZER Pl 632 786A 785 Pl 665 2-AC-151 8614 OTE 3 6" 1/2" 3/4" D 2" 798B 7968 N I /) I 794 RR ~ 2 RR Q TE 666 4" Pl 637 v DE CON' PIT MAKEUP ~t~ FAC02 0 ~SPENT FUEL 2" / POOL FILTER ,:::.._-._J_ ___ _j F 1--- 2-AC-151 6"

uCO
  • D i"N N

I /) I Pl 638 (B-6) 33013-1270-1 ::.:> WHT

u 0

0 (B-8) 33013-1261 REFUELING WATER STORAGE TANK co O> m O> I /) I I V>

i (J-5) 33013-1264 WHT (E-4) 33013-1269 REACTOR MAKE-UP WATER (1-5) 33013-1264 SPENT RESIN TANK tjO 8635G s

TBG~669A S, c ~~- 3 r----------~~ 1 " tjD 8710 (1-10) 33013-1272-2 AUX. BLDG. SUMP 1 3/4" 2 3 MANIFOLD 4 5 8667E FIT 8667 6 7 Pl 667 TBG~ c-2=1 1 2'" 3/4" o, 8670A 8 EAC13 SPENT FUEL POOL HEAT EXCHANGER B TE 668 6" 9 10 NOTE 3 1 1 +--J v 8635H vO =i tj 0 0 z 12 SAFETY CLASS SAME AS MAIN LINE LSAFETY CLASS 2,3 1 OR SAFETY SIGNIFICANT (Q) DETAIL A TYPICAL SAFETY CL-ASS BREAK POINT FOR VENT, DRAIN AND TEST CONNECTIONS NOTESo

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDES DRAWING 33013-0436.
3. THE PIPING DESIGNATED BY LINE SPECIFICATION 151 -SFP ~VAS INSTALLED UNDER EWR 1594B, WHICH HAD A SEPARATE LINE SPECIFICATION FROM SP5291, 151.
4. SAFETY CLASS CHANGE OCCURS AT PENETRATION 29.
5. THE TUBE SIDE OF THE SKID-MOUNTED SPENT FUEL POOL STANDBY HEAT EXCHANGER (EAC12) AND THE SKID-MOUNTED SPENT FUEL POOL PUMP (PAC03) CONNECTS TO THE SPENT FUEL POOL COOLING SYSTEM, UPSTREAM OF VALVE 8664, GRID COORD. (B-8)

AND DOWNSTREAM OF VALVE 8662, GRID COORO. (F-4) WHEN IN USE.

6. LEAKAGE COLLECTION TANK BODY CONSISTS OF A VERTICAL 10-INCH SCH. 40, 304 S.S. PIPE SECTION, 17 INCHES HIGH.

TOP AND BOTTOM COVERS ARE S.S. 3/8-INCH THICK FLAT PLATES.

7. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES ANO COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
8. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
9. BLIND FLANGE IS REMOVED FROM 8669 ANO 4"¢ HOSE IS CONNECTED TO FLANGE DOWN-STREAM OF 8670 WHEN SKID PUMP IS TO BE ALIGNED TO SFP HEAT EXCHANGER B.
10. THE PIPE IS IN A PENETRATION THAT IS 17' 4" LONG AND 20" IN DIAMETER. THE ENO AT THE OECON PIT HAS A PLATE WELDED AROUND PIPE ANO COMPLETELY COVERS PENETRATION TO PREVENT ANY LEAKAGE IN OECON PIT FROM GOING THROUGH PENETRATION.
11. HOSES ARE REMOVED WHEN NOT IN USE.

f\\ RE.VISED PER f.1..£.. ADC~l&-000051 NIJM8£R POL 1/25/16 CAD FILE NAME 33013~1248 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BU!LT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION 1 1 SCALE NONE JOB NO. AUXILIARY COOLING SPENT FUEL POOL COOLING (AC) P&ID DRAWING NO. EWR 3391E 33013-1248 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 FSW010 C-1 125-1 E-12 N N 0 N o D 2 TRAVELING SCREENS FSW01C FSW01 B C-1 125-1 PS 2664 C-1 125-1 3 N 0 " 2" OJ D C-1 FSW01A 125-1 N 0 N

J> D 4

5 6 7 - ----- ------- --- -- ------ - ---- -- 20:_~~~1* 125-1 I I I I ~ 3 8" TUBING ,,_ ~ s: I ,g I "'-' '-'L t 1~ ESW08A 11504C 11504L I D/G A

J OJ N

0 I (/) I JACKEf WATER ~ I ~ 6626 HEAT EXCHANGER I 2* 1 1/2" g I 11503A 11503C ilJ I I I 16" L ____ l TE 6081 8 9 ltt=~ :--19+---r:----l'f-12-5--1---r--I ,f: ~ h i>< () () N I~ ><W 125-1 152N ~,-- 1.. 4790 [bQ] 125-1 I 1,52N N 01 I .--...... D 12501E 11503H I ! I J~-~~INTER. BLDG. 1.. f----C><:Jl--'---1-. 4789 lLOl I f---D f----l ~ 1 0 3/4" ) 4794 [bQ] w w PSI01 B SAFETY INJECTION PUMP B <MO/SIP1 B> 3/4" 4794A [bQ] 3/4" 1 1 12 1-10 1" ';::,.--~(G_-_1~)--, 1.. 1" 33013-1989 ~ 12501~ f' ~ 2"<t 1/2" ~ NOTE!(/) l.2JN 15 (/) I I N w 4795A [bQ] H-~ ..... t-'-~-1 33013-1250-2 '---.~-H 4739B 4795 [bQ) w PSIO 1 C X5250C 12501C ~ () (/)(/) I D ~"-SW-125 12501 B ESW09A D/G A 11503D I BRASS OJ I LUBE OIL COOLER '--~--'-==-~~~~~~---[;:.::J-}Vv[:-t:::-::J--L----' N I (/) I ~ I SAFETY INJECTION PUMP C <MO/SIP1 C> 1 1/2"-301 125-1 I I:t Pl (F-4)1501D 11501H 1" 3 2102 33013-1896 '"'° i~ N I 47913 4" ) 152N 125-1 125-1 125-12 8" I I 3 4" I __ _, ..._ D 12501A 4667A l-l't/;o2('" 1-----cc__j 4598F ~ SAFETY-DE_.. __ __, ~ E 1/2"SS 4525 3" 2 1/2" OPl4598G RELATED 125-1 [ 150-4 8" ,......----..---~I ~~ t;; I I ~ ~! I r-11--D I 0 4612E I D 12500Z 4667F [Q] f-----l~ ~IH)-H-Gl OP/4598H 01 00 I (A-8) 4501E 4501F )> N ' 4666 Pl 2098 PSW01A SERVICE WATER PUMP A <MO/SWP1A> II] SSW02 NOTE 13 f-------"12._*-1r-1101~114* 4601 4605 NSW20A E=-..i---f-1 4502E Pl 2099 Y450:~ ~x~* I o N i::5 f--'-TC"-{:>>Qf--J../'lf-- 0 - N 45028 4502C ' SSW03 PSW01B SERVICE WATER 1---------'"'12--i" 101~114" NOTE 12 4602 4606 PUMP B <MO/SWP1B> m El~ N 0 ' 2" I 8; 1" I ~ 33013 1239 1 N I

~

LO X5939 o '-"1 L__ 1---~ D/G A COOLING WATER ECD13 SAMPLE COOLER I I I I/NOTE 9 (F-4) EXPANSION TANK II ~21o2**r111125-l DIESEL GEN.RM.A V 45981 33013-1896 1/2" SS SAFETY RELATED DIESEL GEN.RM.B 16" 14" ~ ~ j - 14" M (G-4) I g 4665 C:J<c~1'-'0"i"~--1--1 H 33013-1251-1 > rT1 flr\\l O'l 6" 0 -I I z r ~ :;i:,. -I'-- r;:J rv ~

  • 1:::0 fS1 0

1 -..J ~ )>

01!'.D ~

'---!>Q-'2~"-p2"-J D I c ~ ibQi t~ -;, 4670 ;;5 o c 46~13 150-~ 1 153 I w f'.lw.i.. 0 I £1~ D 1l1 LU~~15 3 J-r-l ' * "'? \\W ' 0 0

  • m 0 4612C I

0 OJ (J-2) 4612A 3/4" SEE NOTE 4 125-1, 1 125-9 'if : 33013-1896 >>--tt//-1 __ 1/2" SS 20" ~ SAFETY RELATED l-*~-,"--.-u--o+1(f) <fl-11,_o(f)--l,~1L:_.J 4668B rJ ~ob ~ .. l 17;. 17;JQP/4599H -":,: i '~EE NOTE ~ i:1 'w',~ : ~Il----jll;i/.. "F' ~l'i 'f ~T Ht---- v1 /2 - >------<[><Jr-I ~----~---- g m 0 E 4599E PT 2027

J G'J 4799A 11 (A-4)

SEE t~~1*~;y;;::_::---------~~~~~~~::>:~:'.8;- 5 0 rn NOTE 14 (\\; 33013-1239-2 °' ~ X594D Fl 0 ~ D/G B COOLING WATER IQ] EXPANSION TANK 301-r--\\Jc-'3L"---~--=2~1/~2~"i Pl .T 1/ 2"\\ 4668F (J-2) 33013-1896 1 /2"SS SAFETY RELATED Pl 20000 4754 4769 0 - z 0 [bQ] w M SS ~-=-+---cs m NOTE iO I (/) 4768 --(:J------1 f 4768A 0 - 4752 301 I 125-1

  • 1

.301 4579 11T1 4579A 45798 4579C 1 (A-1) T 3""'3"'0,..13-=-.,.1=-8=-6_6~1----' ~ ~577 TC 5133 1/2" Pl 2247 w PSI01A SAFETY INJECTION PUMP A <MO/SIP1A> NOTE 5 1" 2 1/2" -~- ~ c ~ AAA01A 2 1" c 2 1/2 ACA05 cw N 2 1/2" AAA01B 2 1/2" N ' ~ 4564 I~ r v.f I 00 1" 1/4" 4770U [bQ] l 1" (/) I 0 - 4770W [bQ] 4" N I 0 N O> I {J~ r-c~="'=-----' NOTES:

1. FOR GENERAL NOTES REFER TO DWG. 33013-2241
2. REV. 0 OF THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1250, REV. 8 Pl 2000 AK
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN

& TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

4. THE ACCEPTABILITY OF VALVES 4611A & 4612A BEING NORMALLY OPEN HAS BEEN EVALUATED BY EWR 5168
5. SERVICE WATER PROVIDES COOLING TO THE OUTBOARD BEARING HOUSING OF THE SAFETY INJECTION PUMPS.
6. CARBON STEEL PLATES HAVE BEEN INSTALLED IN THE INLET AND OUTLET FLANGES OF AAA03A, AAA03B, NSW20B AND AAA03C BY TSR 92-158.

L...j)-*lf--1'-'1.L-"'2_" --1--,..---.......,--4...,7{5]J 5

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS 2104~26 1" :JD 4669A 3 I 3 8" TUBING 1/2" 4503A 4503B 0

3143A = I,, ADJACENT TO MECHANICAL EQUIPMENT 3 4 PER SFEWR 10328. }Vv[-l)<J--,--, 115020 11502H E4503D f503E t () ESW09B D/G B LUBE OIL COOLER 2"~ Ol I (/) I

8. 20"¢ STAINLESS STEEL SPOOL PIECE

~ FOR CONTROLOTRON SITE INSTALLED PER SSW04 t ~. PCR 98-107. PSW01C SERVICE WATER PUMP C <MO/SWP1C> II] 4504E PSW01D SERVICE WATER NSW20C PUMP D <MO/SWP1D> ~ NSW20D 12" I l~I 14" 0 ' XIT-5403 CHLORINE MONITOR OJ 0 ~ NOTE 13 20" w D 125-1 I _,,. j----{)l(}--j/ N 0 0 - 0 _,,.' N ' 4504A 4504B TC SSW05 12" 101~1 NOTE I 4604 12_) 4608 PT 2028 I N 0 -<o II c, (/) ill "' I :< 'Z;o I!, ~)0 N OJ o I '(' 'I"" 8rn ftO 1/ " 11503F I ~RASS 11503G 01 0 N OJ Pl 6081 j '--~~~~~~~~-i;:.:~}Vv[-j,xJ--~~ 11503B rn ESW08B D/G B JACKEf WATER HEAT EXCHANGER 112* I 1/2" ti ' r--- 30l 4718A - 13/4" 00 4llf!B lbQJ 11502C 11502L 3/8" TUBING '-'-~~~-[Xr}Vv[:-i:::-:::i,--, 11505D 11505H 2" 1 1/2" 115~ I eyRASS 01 0 01 OJ 1" f--125-1 DIESEL GENERATOR ROOM A DIESEL GENERATOR ROOM B . I II 10" 6-SW-125-1 5" 4" 1--~~___,Dr~-+~~~~~~~~~~~~~~~~~~~-1-~~~~~~-----"'--1 ~~~~.-'--~~-~-~-~-~~~~ (G-1) 33013-1251-1 I (1-1) II N I USE SPOOL PIECE AT THIS LOCATION FOR SYSTEM BACK FLUSH 16" 301 C-2 1" 125-11150-4 r:______;..-i__ NOTE 6 t.: l._.J I 2" 2 1 I 2 "..---::::::: c SAFETY INJECTION PUMP COOLER B AAA03B NOTE 17 4770E ~.,..=..CW~ NOTE 6 2 1/2" SAFETY lNJECT!ON PUMP COOLER C AAA03C 1-, 125-11150-4 ~NOTE6 NOTE 17 cw 2 1/2" 4770D NOTE 6 2 1 /2"-.--~- SAFETY C INJECTION 1-, PUMP COOLER A "--r:.CW:.:.J ~~ 3 ~ 7 4~70C 2 112.. NOTE 6 2" j 150-41125-1 (J-2) 33013-1237 4087E c__ _____ X4087D (G-1) 4-SW-125-1 4" ,_3~3~0_1~3----12~3~7 _ _J--------------------------------- 1------------------,.._ _____________________ ___,_~c~s-~::_--i..... ------'-~----------------; TURBINE DRIVEN I NOT~S 8 33013-1250-3 47701 [QI 1 4" 1" 477~ 578

\\ 9. CONTROLOTRON TRANSDUCERS, FE-120A i

i'j~ AND FE-1208, MOUNTED ON SS SPOOL PIECE, PROVIDES SIGNAL TO j' CONTROLOTRON FLOW METER, FM-120 ~ "' 10. 3/ 4"¢ STAINLESS STEEL PIPING FOR "C CONTROLOTRON SITE, INSTALLED PER MDCN 2358, TYPICAL FOR ALL SIP'S.

11. TUBING MATERIAL (316SS, 1 1/2" O.D.

X 0.065" WALL) PER PCR 2004-0045.

12. DOWNSTREAM FLANGE OF SWP DISCHARGE REDUCER FLAT FACED PER PCR 96-080.
13. UPSTREAM FLANGE OF SWP DISCHARGE CHECK VALVE FLAT FACED PER TE 2008-0028.
\\ 14. CONTROLOTRON TRANSDUCERS, FE-125A

~ AND FE-125B, MOUNTED ON SS SPOOL PIECE. PROVIDES SIGNAL TO CONTROLOTRON FLOW METER, FM-125

15. VALVE 4623 AND 4624A REPLACED WITH SS EQUIVALENT UNDER ECP-10-000103.
16. THE FOLLOWING LINE SPEC DEVIATIONS ARE JUSTIFIED PER ECP-11-000539.

VALVES 4754A, 4755A, 4769A & ADJACENT PIPE FLANGES ARE 150# CLASS. PIPING LESS THAN 1" DIAMETER IS SCHEDULE 80, NOT SCHEDULE 40. THREADED FITTINGS/CONNECTIONS ARE USED FOR THE RUPTURE DISK ASSEMBLY AND RELIEF VALVES. BUTT WELDED CONNECTIONS SHALL BE USED FOR THE TRANSITION FITTINGS BETWEEN PIPE SIZES GREATER THAN 2" AND PIPE SIZES LESS THAN OR EQUAL TO 2".

17. SAFETY INJECTION PUMP COOLERS AAA03A, AAA03B & AAA03C CUT, CAPPED AND ABANDONED IN PLACE PER ECP-11-000539.

RE.VISED PER j\\ AOC-1-4-000250 ~ CONSTRUCTION UMITED CONSTRUCTION: AS NOTED ~~P~P I SS (D-1) I 4-SW-125-1 4" cs ,_3_3_0_13_-_1_2_3_7__Jf--------------------------------i-----------------...... -'-----------------------="---I 301~--< AUX. FW. PUMP A & B I N 0 ' 1" I ~ I ~~ ~ 1" C~~D~t-t~:"'~ 3" 4738 [Q] ii --t SAFETY CLASS SAME AS MAIN LINE

1----~'--z-S7A-FETY--J!CLASS 2,3,0R SAFETY SIGNIFICANT (Q)

DETAIL-A ? I DATE PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE 1 2 3 33013-1237 u* -(,_L 4090A X4090 -+-------~ D 301 I C-2 J, INTER._JlLDG.m ~ ~ ~ ~ 1., 1/2" (A-3) OJ 3 33013-1237 r Pl 2569 125-9 1 125-1 !"'o ~~ _ I 4091A X4091 I 8 L _______ ~o-sw:..:.25-9 _______ -- _______________________.L _ +-+-----lf-----"----'---- 4 5 6 7 8 9 TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS 20" (A-11) 33013-1250-2 4615 II] X4779 10 1 1 JOB NO. STATION SERVICE COOLING WATER SAFETY RELATED (SW) P&ID DRAWING NO. REV. EWR 3391E 33013-1250 SHEET OF 3 M CCD 01 CONTROL COPY# 12 A B c D E F G H J

2.

3 4 5 7 8 A 3 u~'1rr-~~~~--~~~~~~~~---. 671J c

t.

G

2.

3 4 5 6 7 8 9 g 10 l-A t ~ s..AffTY CLASS S..-.ME I AS UAlf'l LINE ?SAf.CTY CtA~S :::..:!. Off SAFETY SIGN!F1CA.">iT (Q) !:£TJJl.-A TY?. SAf'tT'( ctASinf.;"tN{"""ii°oiNT FOR \\'E.Hi, o~ ct. itST cONN::cnms 10 11 11 12 J. fOP. ClNllilU.. NO'l1.~ HLF[H TO DAAW!HC JJD1J-2241. ~. ~~fl~ 1WSuft.~G SL.i?~SECES Jl013-!.250. REV. 8. Sl'"UON UIMC( t:OOUt.:G Vl!1llR SAFE!YRS.ArrD i2. B E F G H

A B c D E F G H J 1 2 (C-12) 33013-1250-1 (H-9) < 33013-1908-3 1 " I Ill I I ~ 21/2" [_ ,rn rnj'8 oz r r;; 1(g z'F ~!8 f'1 1Ul 10 gi 11'1 (/) Ill f'1 )>

<: IUJ I'.) fl1 1f'T1

'-~ liii N z I I 21/2-S~ O> N (1-10) 33013-1250-1 D-9 33013-1251-2 1 v ~r.i N 0 0 " 16-SW-125-1 4614 ~ 4664 ~ <f 8" 3Ql_\\ .1~ t-91-'---1 "' NOTE 7 47990 1--s-1 4642 [ill 0~~ t;,~ ~ Q § 1* 47~~T l__ U)1z SJ 1' Pi < ;u o* f'1 OJ 'r tll1 0 r\\"'

o.

2 3 NOTE 7 3/4" C----19--Q-j D 12500K 4 D 5 4" l 12540 3" CONTAINMENT 1 RECIRCULATION 153 C 'i FAN D COOLERS TC 4 3 8" ~ D E-'-J~-'4'-"---'j I ~---'4~ I I P312 ...LJ 8" 4" 12542 3" 6" °' ~ lii ' D 4649 T1 Pl 2148 c Ill ~~ 1: \\o/ s ~ t~ co l I I I I I I P--t---------1---. I 2 1/2" SCI03A AIR CONDITIONING WATER CHILLER A 2 1/2" 6 I I ~--~<<i I .-:!;;~_,1, TE 6876 I 4794K I~ ~ 10 q I !)l I 'ii' I I 2*U 2" ---+' Pi09 !,- NOTE! ~ e! 6 ~ {)) 2" Cl ~-=c.J P201 I I E <O w D 2147 4519 2054 TUBING;Jg-1 301 7 4655 TIA 2010 § '1~~ ~ ~ ~ --{ c Ill D ' z " RR Pl 2000C 8" 0 ' 8 301 C-2 v 1/2" 1--=--t----M----::J v 12500R I IJl I I 9 CFRC A B c D SHAFT \\ COOLING COIL ACA10 ACA07 ACA08 ACA09 INBOARD END OF MOTOR " I I MzCJ Xtll '-0 g?Q zo 3141B 10 4580A 4582A 4584A 4586A 1¥p~I DRAIN VALVES 4580B 4580C 4582B 4582C 4584B 4584C 4586B 4586C CRFC MOTOR (TYPICAL) AIR FLOW t [:,_, c A r:*-* B 4580D 4582D 4584D 4586D I 1 1'-2" r:*-* 1 1/2" c [:,_, cw D AIR FLOW.. I.. AIR FLOW DETAIL B CFRC MOTOR COOLING COIL, DRAIN VALVE, AND FLEX JOINT CONFIGURATION (TYPICAL 4) 1 1 INBOARD FLEX JOINT SCS190 SCS192 SCS194 SCS196 OUTBOARD END OF MOTOR I D OUTBOARD FLEX JOINT SCS191 SCS193 SCS195 SCS197 12 fl ~ SAFETY CLASS SAME AS MAIN LINE ZAF~ CLASS 2,3,0R SAFETY SIGNIFICANT (Q) DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS y 2 1/2" 2 1/2" 4592B... c <O CD N z )> 0 0 4659 4659A Pl 2000G 4659B ~ 3 [QI 8" f--~---+-"'---1l....e--J1---~-1 ~ 4643 [@] 5 TIA RR 2012 NOTE 7 4660A 4660B ~ [QI I r-~----+-"'--11....e-- 11-----~ ~ TIA 2013 3/8" y.'--"-,1 i-..+:J D ~ 12502U 4644 [ill RR NOTE 7 4" C-1 0 12516C 3 4" --~ r----:J D 12516F I I I I RM-16

~~ i

,- CONTAINMENT RECIRCULATING TUBING RE 16 H A 1 FAN COOLER PROCESS MONITOR SKID ~301 N ~ <O <O N TURBINE I I 12516J 12516B _J BLDG.BSMT. N ' D f----301 /1/2" 18 CLEAN SIDE BSMT. (G-3) 33013-1893 ~ N... G) '-'-' 4" 15531 D [:'--9"-"1 12516M IB CONTROLLED SIDE BASEMENT II I (G-3) Yf{f----<< 33013-1893 [_,.,__,..,___ ~----~lx'154'6o IB CLEAN SIDE BASEMENT 1" N N I (/) N 0 0

>' D

~ VE-f--'-1 4799X (}) 4624C I N I 4 v E-1 .l.._~ \\."-! 125-1 1 125-9 4 799V '-[;:<<}--! v~ ! 301 125-1 [;~ ! 3" (H-3) 33013-1893 (1-9) 33013-1908-3 (E-12) 33013-1885-1 > 301 12~516H ~4"------trnt-E------~

E C) :;o l 4799W I

Q 3 I (B-3) .-----lf-------11-<:'----:;3~3mo~13~-~18~9~3~1 I (C-6) PC


H----12679 )----------<

.....__3_3_0_13_-_19_2_0 _ _,


Im N

(C-3) X14400 X15451 X5839F N .---j/-------f1---<..._._:3~3~0~13~-~18~9~35___j I X15452 X15461 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1250, REV.8
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTION SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. ALL SAFETY CLASS LINES ARE SEISMIC CATEGORY I.
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASE ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO INTERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
6. 2" AND 2 1 /2" SOCKET WELD FITIINGS WERE INSTALLED ON REACTOR COMPARTMENT COOLER SUPPLY LINES NEAR P201 AND P209 UNDER TE 2008-0037.

7, STAINLESS STEEL BUTIERFLY VALVES AND ASSOCIATED SPACERS INSTALLED UNDER ECP-2008-0064. CAD FILE NAME: 33013-1250,3 A CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE 4652C.---tr-~-- HOSE I C-1 1/4" -*H-:J--,.rV{-~---H~---- (F-3) PC f-----------<::::::~~~~~=:l-:;J;;,;;Q;;; 2680 33013-1920 STATION SERVICE COOLING WATER SAFETY RELATED X5839G 4" 1" 4652B 3" 4" J--"---C}-jf----------+-~--J....--..__, (SW) P&ID 4650 3 4 SCl03B AIR CONDITIONING WATER CHILLER B 5 ,,, 4520 3/ 4" TUBING~-1 6 Tl 2053 4652AI 7 JOB NO. DRAWING NO. REV. EWR 3391E 33013-1250 SHEET 3 OF 3 M CCD 01 CONTROL COPY # 8 9 10 1 1 12 A B c D E F G H J

A B c 0 E F G H J 1 -.~_ 4553 Pl 2200 1/2" PCD02A<MO/CP1A> CONDENSATE PUMP A n I 2 1" I 3 I 4 (H-3) ~------------------;: 33013 1232 ~ Pl 2201 4798K 4798L PCD02B<MO/CP1 B> CONDENSATE PUMP B AIR EJECTOR SAMPLE COOLER v rn °' 3/4" I 4798J Pl 2202 N I ~'t' -s ~ = LC! D PCD02C<MO/CP1 C> CONDENSATE PUMP C I 5 2386A 11/2" I 6 7 I 8 I 9 I 10 I 1 1 I (A 1) 10-SW-125-1 12 v X4693 ~-r::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::;::::::::::::::::::::::::::::::::::;--------t, 33013 1251 2 4682'.J~ I 10" 4675 (A-1) I 33013-1894-2 X14500S Pl 2108 3" 3" 2" 2"., 21/2" ESW04 GENERATOR AIR SIDE SEAL OIL COOLER ESW03 GENERATOR HYDROGEN SIDE SEAL OIL COOLER Pl '----1"~125-1 10" (A-1) ~----------<'1 33013-1251-2 ~ [ill 4682A ' _;;: I _Y'I. ITT DISCHARGE ~14682B 1iJ 3,, HEADER f--.---11---------1 9 2109 1 ~ ~ N 4676 Pl 2110 4677 T '------C><Jf--~----1; l;f------[;x::J---_J 4677A 46778 ATE01A GENERATOR BUS DUCT COOLER A tt A 21/2" 4674A r---125-1 4681B*JJ~ j "' ~ 4681C Pl 2107 )~ 3/4"

JD 4530A 3"

Di:-..r:. 4799K GENERATOR BUS "' ~'.l Tl "' 4674C 'f'~ DUCT COOLER B o o .p.T ~ NOTES:

1.

FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2.

REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1251, REV. 5. I r-i n I r-i ATE01B E0;3 ,,_ 9 V ~I

f---l><!-~2~1~/~2*-1 __

~_,~E~~l@--..-~---"L-';:'.~,--20~4-0-~-'.L[~;:.::}.L,iJ'--~-~_i-'-t~r*;~/_2_"-l

3.

ALL PIPING/COMPONENTS ON THIS DRAWING ARE NON-NUCLEAR SAFElY CLASS. FOR AKP03, AKP04, AKP05, SAFElY CLASS IS SHOWN FOR SERVICE WATER SIDE ONLY. I LJ D (J-11) ~ - 33013-1925 X4785 IL.. _____ _,, 1/2" N 1/2" 1-l I c--'-- Tl '-f--- 2059 1/2" 4555 T Pl 2203 1/2" 2" I LJ D 1/2" Tl '-1---j 2060 1/2"..n 4556 ., = ~ l rnj 1" Pl 2204 8 (1-2) -..rl.-1 33013 1232 X2386B 1 11/2" N LJ x5325 X47BiB 1/2" ~ J 1/2" 1-l I >--'--- )> Tl ';; 1--...J 2061 D 1/2"-"' 3/4" (C-1) 33013 1925 IA COMPRESSOR A (A-1) 33013 1925 IA COMPRESSOR C I "'j N I - Pl 2205 v 11/4" 4" 0 ' T TURB. BLDG. N g~ ~CV? 46748 4674 CONTROL BLDG. AKP05 L'* NSW06 Y 1

  • .I I
  • I i------..,...--1_,* i * - -

>----1,~ v+-,-------~-:..,... T _ __,. ~.,_ _ _, .,,.i T. 4674H (\\; 12502V °' 4674M ~,_1 ~r1 BATIERY ROOM AIR CONDITIONING 1" D UNIT D ~--------------~---~~-1:*~*1--11.1---------------~ 4674G Pl 2111 2 ro z N 125-1+1 ,4: 4684 ,,_V ~J84Aw ~*r~ o Pl 2112 i--:J (';; 7 ~ ~ 2 ro z Tl 2043 11/2" 46741: 1 1 /2" 1 1 /2" 46798 I ~ !""~ CX>ro~ G1 1 ~7 ~lO N~7-~ ~ N I - f--L~-~--------1----~----:f--l il/\\ /\\ /\\ /'J f--J:f----L-----'------~__JL_ _ __l_--1~~--~--'-~---J 4678 v

  • ~

i I v v v I io~; .4679' ~'Ir-;:::_ 4l98G EXg~~~R-gg~LER r1 AEP04 ~g~~u~~~R~61{'J ~ t. r-; Nswq1 12so ... i? _ *c~.,_,,_ L1_2_5_,oo..,sc_A_/_c UNIT 4l98E ~ 479BF ~ 301 ! i4761W 4761T~ 1 /2" 1 /2" 9 3/4" 4fas'A(Pi\\ ~ AKP03 TCV ---v-~~, ... r'_-,-4-;c:6.. :i-1v-'---.---4-1;c:61-:1 P---JN~@~8:1---4-7r..:~.l-1-Q~'---l J-i ::i*---J .._,, 7 RELAY ROOM 4l61E NOTE 6 TC rn ~4761G ~ 7 ~l.J. 9 2 ",9 ~!" ;;i0 DJ §125o2w '-4~-'D\\D T.S.C. BLDG. - I ro TCV 12505 TURB. BLDG. ~ '1 ~ 12504 .;:,*--¥---' 1/2~ N, 7 v ~ 47980 1" ()li.l. 12502x -+-- 1" 476fN '-.l ~,.;. ro ~ 4761 R AIR CONDITIONING '---li761A rr-t:_~ @ P~ U::p:4 I LOI -1>,p I l.CJ 4 6454 ~ I FLUSHING 0, TEE WITH TC rn TCV PLUG I )4761X F301 112* 112* 4---.L_-. _ _L_Y--cf-----J,ftrif---t,__,_1-r)--I~ :: 3/ 4

  • I 1"

4761J NSW09 ~18 "z 12545H 4761M 1/2" 301 £1T f 4761F 4761L 4761K ---... 1"

4. ELECT. MOTOR EIN'S FOR MECH. EQUIP.

ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

5. SPOOL PIECE WITH THREAOOLET FOR FS-2090 INSTALLED UNDER ECP-11-000174.
6.

TCV LOCATED INSIDE THE UNIT HOUSING.

7. GENERATOR EXCITER AIR COOLER SUPPLY AND RETURN PIPING REMOVABLE SPOOL PIECES HAVE VICTAULIC COUPLINGS AT EACH END.
8. TUBING MATERIAL (316 SS SWAGELOK TUBING AND FITIINGS) PER ECP-14-000770.

6" 1/2" Pl 46868 &i' 7 00

?),

,, 'L..--ll.-...J 6 1~*, -, 4686 4686F "' °' "' 0 SS (1-1) 2" h~,---------1: 33013 1251 2 125-1 SS TUBING NOTE 8 X45J7A (1-10) 11/2" - -,r--------.. 33013-1925 >--------.;._----i------, (D-6) 10-SW-125-1 tt A I 33013-1250-1 ~>--------------! ro,-1 "125 "' r 4761S RELAY ROOM NOTE 6 AIR CONDITIONING UNIT B @ JTELEPHONE EQUIPMENT! ~ (til ROOM jcrl ~ ro ATP03 ro 3". - ::J 46B6A x47a6 i._ _____ (1-1) I 33013 1250 1 DIESEL GENERATORS HEAT EXCHANGERS (E-12) I 33013 2286 1 9S37G I 10 SW 125 1 x4s 13 'L.::..::..:.;:__:_: __ x47a7 (F-1) 33013 1925 IA COMPRESSOR B I 21/2" ro ro rr 810 I~ I 12545,TC N ,1 1, (JI 01

  • 10 NSW14

(';;,-' "'I t:;> D 4i:~,+1-25{4}5iG~~"-L--t-112C5k4-15-E-l_ __ ~-:( '-'-'""'~----'-..,'/ D l 12545D 10-SW-125-1 °' 00 0, 11 /2" -SW-125-1 Tl 6450 1 1/2" (J-1) L--r---------------r-----..1.E:~".=.~:=.!.---------~~---------------------------121~0~*------<:::;:~~~~~ 10 SW 125 1 I 33013 1251 2 I. X4693 N, Pl 2208 ~ I I 4781 ~j _1c__1_2*-cf-~-:c.Lt-_s_~_-{ 3/ 4" 1----' I I N 0 - 4707 1/2" ~+--:] v 4799H N I (/) I 0 I N 1/2" ~.- 4799G 1/2" *-* Pl 2209 i--:1 8:' l 0 4-j(js v NSW04 l__J 1/2" 3/4" NSW05 PCD03A<MO/HDP1A> HEATER DRAIN TANK PUMP A C2 125-1 "'-.n I I Tl 6451 125-1 C2 w N 0 N N -,, o-0> 4709 4710 I ~ I 0 I N I I w~ ~ _ 112" ~., ~ PCD03B<M0/HDP1 B>

3 g

l!..l HEATER DRAIN g; N _U ... ~28's-'--=---1

  • ... -:l-C,.1-c ~ -

~*~ "',..,~ 1 1 TANK PUMP B 11 /2" -SW-125-1 '--------------!-------------------------~-------~ 2 I 3 I 4 I 5 I 6 1".... t--1-.c--:J D 12SOOD ~** 0 0'" r'1 D -' 7 I 8 I 9 I 10 I 1 1 /\\ AMID F£R /.ffi AOC-16-CID126 CMB W\\.\\ IL ~./11 P., w H~ 2/17/16 Z/1(\\1i. <.119//t. t}1qf1£. CAD FILE NAME: 33013-1251,1 CONSTRUCTION LIMITED CONSTRUCTION: /JS NOTED PRa.JMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 7 lft/16 /JS-BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE STATION SERVICE COOLING WATER NON-SAFElY RELATED (SW) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1251 SHEET 1 OF 2 CCD 01 CONTROL COPY # I 12 REV. A B c 0 E F G H J

A B c D E F G H J 1 (A-12) 33013-1251-1 (A-11) 33013-1251-1 DISCHARGE HEADER (B-3) 33013-1895 X15303'--.::..::_::.c_:c_:.::..::_=-_,-- (B-3) 33013-1895 X15302 '-------~ 0 I Ul I I 2 3/4" VINYL TUBING 1 /2"15=3'---<-+-_J 4719 3140K TSW03 ~ SW BACKEND BIO-BOX 3/4"PVC 1 2" PSW04 SAMPLE 2.. PUMP 1/4" 0 G) 3140E "' ~ 3140A ~ 4795C 11/2" 4696 1/4" XIT-5400 CHLORINE MONITOR l/P 4538 0 0 'l 3 ~125-1 Tl 2047 10-SW-125-1 4---,:J 4600A 4 (B-1) 2" 33013-2711-1 1/2"-153 TSW02 SW FRONT END f.¥/4" BIO-BOX I PVC 2131D 2131 t 125-1 4721A 1'! ~ N I N ~. 6" n~ ~ Pl 1" '] v <O 2124 ~--------~---- 125-1 301 11/2" 2" 4694B 4723 1" 125-1---l 4723B 4723A lbQJ 1 1 2" 3/4" 1" 4724 125~ 2" I 6" 2" 5 6" v ESW05A TURBINE LUBE OIL COOLER A __/ 3/4" I 1'! L-W--':J D 4692A i ~,3_/_4...

  • -::J v

~ 4690A ESW05B TURBINE LUBE OIL COOLER B --.,-/ 3/4" l ~ c_46*9M-1 A-::J D 3/4" ~-~4597 EEH01A EH CONTROL SYSTEM OIL COOLER A '---_J SEE NOTE 4 '---_J --~ SEE NOTE 4 ~-- EEH01B EH CONTROL SYSTEM OIL COOLER B 3/4" 4698 Pl 2121 8; <O 6 4539A 4539 TUBING 125-1 -I... c )>~ z G) Pl 2125 N * ~-----------------;!rl


<tx::Jr-----11!r---~-=-'---'

4700A N

  • 2" 125-1 SS TUBING NOTE 5 v

v rn... rn 4704 (F-12) o ~ 1t5~: I 4726 Pl 4726A ~ 2" -SS TUBING NOTE 5 zoo ow 0 - '-----!~ 0 - ~ Ol 1" 2" 4703A 11/2" 3/4"

JD

)> L3~3~0~13~-~1~2~5~1-~1~.::r----:---~-.;-1?:;;.--'--"----~:,---'-------11~-----Jf-8--1r---~~ 4537A 4701 NSW12 §1-1 oc "' ;u

u ~

G) '"' gi~ 0 0 6L __ 1 N I 2" v ~ 11" y 4725 125-,.___j 4703 0 ~ (1-10) EH q < 33013-1885-1 ~ - 125-1 SS TUBING NOTE 5 ~ 3,, --14~7~0*6--=----~ (G-3) 125-9 125-1 [~~~~~~~:::::::::____:_1~/~2:.J" v.::::__ 33013-1882 ... 'T' "' X7469 (H-12) ~ 33013-1251-1 X4680 1 2 3 0 'l 1" 4720 Pl 2130 rn... N * "' 1/2" TW '-H--V 2051 ,., 4720A 11/2" 11/2" 10-SW-125-1 4 EFW02B FEEDWATER PUMP B LUBE OIL COOLER EFW02A FEEOWATER PUMP A LUBE OIL COOLER ESW07 CNMT. AIR TEST AFTERCOOLER 5 11/2" 0 N 3" A 1" 3/4" .---*--j

J D 4704A NSW11 8;

<O 4705 6 (C-1) 33013-2711-1 2" Pl 2127 N

  • 4702 7

2" 4687 6" 4690 6" 4689 2" v ~ ' ~ 0 N [!!::,,_ ~ = 7 SS TUBING 125-1 NOTE 5 3" 0 I I N I 0 * ~ ~1 D 8 9

'!! 1"'

CJ r G) CJ . i (H-1) 33013-1250-3 _J X4614 2 1/2-SW-125-1 2" (E-1) 33013 1990 1 1"-125-1 3/4"-301 . I. N

  • X5187 1"

1----t><'.l--'---I 1-----'--W-::J D 4799N 2130 11/2" (A-11) 33013-1921 4799 VACUUM PRIMING PUMPS 8 9 10 10 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1251, REV. 5.
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. EEH01A HAS 503 OF ITS TUBES PLUGGED PER MDCN 3436.

EEHO 1 B HAS 503 OF ITS TUBES PLUGGED PER MDCN 3619. A 5. TUBING MATERIAL (316 SS SWAGELOK TUBING AND FITTINGS) PER ECP-14-000770. 1 1 REVISED PER A -1s-oooa35 [!!::,,_ CAD FlLE NAME GMB 10/30/1 33013-1251,2 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES I 1'S BUILT DATE RELEASED FOR ~ GINNA STA. R.E. GINNA STATION SCALE NONE STATION SERVICE COOLING WATER NON-SAFETY RELATED (SW) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1251 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 I I [~~(A~-~ 3~)~==:>,_21~0~H~D~6~~=; x'41391 33013 1924 10" (G-1) 2 24" MANWAY I 3 KMS01A LP TURBINE A ECD06A MAIN CONDENSER A I x - U>' (]> 'i'.' -~ 0 -~ I (Xl 00 <O ~ I II l/P 4025 4 "' ~ I I co co <D ~ I I NOTE 5 -JVVf ~. 7 U> 0 II II I 0 D t-1.-C--, 9512D II 5 I 12-CD-300-1 SCH.SO 6" 0 ~ G) CA I I 0 <D ~ 0 U> NW~ <O U> 0 ro r'l ' 9591F 6 I I I I I I 8" 4" 7 II 3958 0 ~ 0 u I I 0 <D ~ 0 U> 1 I 300-1 8 0 1'

c 0

I 600-2 g) -~ 0 I m 0 0 I g I (Xl I 0 - );' I I '° - ~ <D -}VVf NOTE 5 0 I 0 0 I m 0 0 I 9 12" 95098 SP-863 20-CD-150-1 I 14" KMS01B LP TURBINE B ECD06B MAIN CONDENSER B 10 I 1 1 f 6-BD-150-2 (H-7) ~-~-~----.,. 1---* ..... 1-~L-<, 33013-1277-2 5744C S/G SLOWDOWN FLASH 24" MANWAY TANK DRAIN 3-CD-150-1 3-CD-150-1 3-CD-150-1 8" 6" X5744B I 12 ~ 6" I I I I ~1T 1-1/-,," -<~CA~-1~0) ~* -:J 6' 33013 1896 I X15433 ~ X6838 l/P 2006A (B-1) I I I I I f-- 1 I 43~. T 3/4" I '-r--f"><l---1 ' I ~. 4'_341A 1" - v ~ 4201 300-! 1 .TUBING 1/2"

J TC 11042 1;2*

1.. .---:J TC f-'--f:x:1'_J 11045 4203 300-1 TUBING 42\\).5 1" \\ *

J D 9512E 3/4"
J v 9534G E-rn (H-1)

~--'---"--~, - - L_ __ -< 33013-1921 '--------'1x321s 1 ~"1;7 U>o (J-1) 6-CD-150-1 __.,t---~1~/4~*---'--f~ I_ I I '-I"" - 33013 1232 '-----------! ------'1"-/_._4" __ _:_1-!C}- ( LI \\ ~~ ~


{jt'--'-1-------------------'-------~

L-cJ-1/4" I ~001 g 6" <O U> 0 00 rn I I ~ I ~ 10" 21 /2"

  • 11 /2" 1

LT 2006 v 4208 4204 4206 LG 2016 ~* T 11 '2"

  • 3/4" I

3/4" g I 15 ~ I s" r-,}---1.t><:t-=2_" -1 ,----v 4336A 1" .,.... :J 11;2* I f 0 I v I 4202 3/4" 1---'="'---=-'--...c+-----J~TC

33013-2711-2 I

I~ ~~ ~ ~, 3/4" 300-1 1-3-'-/_4_-_30_0_-_1 _ __L__:J I 434~ 20.. i.L '----___ _.1H......... ID 14.. 4207 I I I I 4:z1ii 11041 11/2" ~ DC:--..-- 300-1 TUBING ) TC~~ n 2051 4336E r---;--...,---------'~----:-;===I 1 1 1 4336J ____,_, I IL __ 4:2~*=- 1-1-14* __ -- 1_ .. _ -- 1: ""; __ 1:_ 1" 11/4"

    • ,,--"'-'CB:...-_;1..<.) __

1/2" ~-.=:iv 4336L ro I 20-CD-150-1 ...L ...L ~~--1 .. ><~"H1 33013-2711-2 4215 x6s39 1/2" vc-...- q 4336K L 12-CD-300-1 n 2052 ____ U I 20"-CD-150-1 28-CD-150-1 11/4" !:e---------11~/_2_" _________ ~----------------------- ' 1/2" ~ :J D 3900A "' I I 36-CD-150-1 4336C ...., 1/2" '----ti-.---:J D 3901A TUBING 150-1 (A-9) I I 33013 1905 ~ -~ L___ GLAND SEALING WATER 1" 1 /2" D~.--->; 3902A 150- -~1-+--~TU~BING I (J-1) I I I x'6a41 43368 L-,,,-~-~-,.....120" 1.. (B-10 l.!..I ,_;.;;.;;~~_JI IL__!='==l . --r::* ><1*-----11 I - 1 I --~-- .. --i~ ~ 4214 I 33013-2711-2 20" 1 1/ 4" - 4212 (B-10) 33013 2711 2 X6s4o (D-1) 1/2",.--L-.~---.... 33013-2286 -x9s16r SP-5291 SP-863 (.()

.... ~ J v

~ ~ 9512J g !(b-..,-11 --~~I: 3726A~ 1/4"~~.1~1 33013 1234 X4045 I Xl SP-863 (A-1) 18"

  • ~

.--~~~~;-~~~~-,.~~,,_._~___,: 33013-1911-1 0 0 I c rn z G) ~ 1/4" ~ TUBIN~.rr:~-1~~---1cJ 1" U> 0 I (f) §0 ~I 2" -- 4216 112 300 1 DC:--...; ~..; 3914 1/2"

l ----
!

Pl 2037 3903A :JV n I I 2" I,,______, i--..4-" . ~ 3903 L_1 /2" 'T' 1" I 0 0 I (]> 0 I 0 0 I 21/2" 1/2" 4312 U> 0 I (f) 80 '° I 2" Di:* ' 3915 g ~ I <D t -"',. ~ v ~* ~.., 1,/2" 2"

  • '~

3904 1(2" 4218

  • ':iv n 3904A I I

f--,-~J v 14" ~ '....__f--- 1/2" 3918 v 42238 I I 1..:::11, '-r-,,-~J4=>-... N (...I ~~~ ~¢_',~@ I 1" Pl 2948 l!J "'?: ~ PCD02B(MO/CP1 B) D ' Q;l CONDENSATE i5 PUMP B I 0 0 I 0 0 I 1" 0 0 I 21/2" ....__ 1/2" 4313 t* 3721 U> 0 I ~O I 2" 1_/2n 2" 2". ~ DE-1.... ~11----+...---4.i.'41~1---'----1, I' 3916 1/2" 4220 3905 _1--*....:iv n

== 3905A I I Pl '---~J 11H 1116" 14".I. I L---1 I I..::: II L ~LJ.... "' "' 1/2" 3919 ~*"

  • t
  • 1~ " '.;,;, '

ot.1~ D -t>-_.1~ D

  • ., 4=>-

-1 c "' c PCD02C(MO/CP1 C) rn 'o CONDENSATE i\\'5 0 ~I 0.!.L_I <D 0 0 I 0 0 I I I I I I I I I ~ 112" I 12" (Xl ""--N~~ 4314 L . t (f) 0 0 3" I ~~ i~-76.. MIXED RESIN VESSEL (F-7) 300-1 JUBING 1/2" l--'---41:2><2::::61+-----------1, 33013-2251-4 ~ (A-1) X67IB 300-1 I TUBING 1/2" 'I' 4225 4225A 3" -. - 4086 2" 3924 2" .---~--i: 33013-1905 PT 2014 I-I "' 61 I g[ I -r I I 3959S ~~ v GLAND SEALING WATER (B-3) 33013 1236 1 I NPSH (PFW01A) (1-3) 33013 123s 1 I NPSH (PFW01 B) (A-4) 33013-1236-1 I PS 2010 (1-3) 33013-1236-1 I PS 2011 (E-1) ~-~-~--., - 33013-1896 '------__JX76o1o NOTES:

1. FOR GENERAL NOTES SEE DWG. 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543.
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. ELECT. MOTOR EIN'S FOR MECH.

EQUIP. ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

5. FLEXIBLE PIPING CONNECTION CAD FILE NAME 33013-1252,1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATI' RELEASED FOR ENGR.

D (.,.! -- N ~£ 2949 ~ 0,_-_ _J~,. -{8--cJ.-6....,---., 6 PUMP C 0 I I I ll~. I I~I g*.--~(~IH_-~7~)-~ GINNA STA. R.E. GINNA STATION 1 I 2 I Pl 2040 3 SCD18 PS 11036 2055 14" I 4 18-CD-300-1 I 5 Pl 2041 I 6 7 I Pl 2042 NONE CONDENSATE P & ID ..e-f-,--J ..e-33013-1233 & 13501't:: T"', 3959 3502 HEATER DRAIN /;; 4 ~ FO PUMP DISCH. )> t.1 ; D JOB NO. DRAWING NO. REV. EWR 3391E 33013-1252 (E-11) 1" - 1" I L'..--l.,"><_'.l----'---1, 33013 1238 4084 ~. x9661 CCD 01 CONTROL COPY # 8 1 9 I 10 I 1 1 I 12 A B 1--- c D E F G H J

A B c 0 E F G H J 1 (B-3) 33013-1990-2 36" x BIRD _/ J '-----. SCREEN r OUTSIDE AIR 2 3 PROBE LOCATED IN THE TSC MECHANICAL EQUIPMENT ROOM FOR TSC A P. OPEN END FT 5262 4 5 AEP02 TSC TRANE A/C SUPPLY AIR UNIT NOTE 9 AED02 \\ Q !ADI M AEA01 \\ AEA02 6 7 TT 5264 8 SMOKE DETECTOR DSD S33DA F YARD v.,-----,SCS161--1~--1 i SCS161-2------i >-+--) TSC NORTH 1------l p l E N u M ) TSCMR60 36" x 66" EXHAUST TO OUTDOORS 9907V 9906W -i> CD ' x ~ ' WALL Iii g~ <O )> 8 m AEU01 (Tc\\________rfH ~ L!6J AED33 I I@ TC 5266 l00IS L Iii 1' 1' -i> ---~LJ AEP07 SAS/PPCS A/C UNIT A CONDENSING Iii UNIT Tj ~ 28" x 28" RAIN HOOD 9907S 9906R <O 0 " oo AED18 AEF01 AEP01 TECHNICAL SUPPORT CENTER CHARCOAL FILTER SYSTEM MECHANICAL EQUIPMENT ROOM F <O <O 0 " 9907F f"'l 120" x 74" OUTSIDE _ A___ AIR -y~ (C-6) AER01A -i:><t-i 33013-1897-1 X15728 10" x 10" --0--- TSCMR165 o I lcolg Iii 1' 1' "' ~LJ 28" x 28" RAIN HOOD <O <O 0 Ol <O <O 0 9907U 9906L TSCMR90 F ___£ AEP08 {~Qm*, SAS/PPCS A/C UNIT B CONDENSING UNIT COMMON PLENUM RETURN 9907T 9906 0 Tj -i> o- <O zl N Zr~ SCS165 AEZ01 SPARE A~ REFRIGERANT C_J COMPRESSOR AEP03 TSC TRANE A/C CONDENSING UNIT AEF03 36" x 66" TO OUTSIDE l6QI ) SCS167 RECEIVER AET05 <O <O 0 " 0 )> f"'l 0 Ol m m E-~--~-----+-------------~ i8\\ ' ' I l 8"¢ (TYP) ADMINISTRATIVE OFFICE AEP04 ADMINISTRATIVE COMPUTER ROOM A/C UNIT AEA05 AEM03 AEF04 Lr-;;;';;=;;'oo 9906S L---'=4 AEA09

o RECEIVER 9906M AET03

'--'='-l AEA08 ROOF -Hf--- ROOF COMPRESSOR AND CONDENSER AEL07 AEA04 24"X24" :J UNDERFLOOR (TYP.8 PLACES) ADMINISTRATIVE COMPUTER ROOM r+----~R.OOF _ 29"X70" 9906Pl--Y'--- E I r--~~~~~-~~-~-~~---~ 24"X24" l29"X70" [ =i==ll_ (TYP.10 1---Y'--- ) I PLACES) E9906Z I DX DX E I 9906U:J AEL08 AEA 10 AEA 11 AEMO 1 AEF06 AEP06 SAS/PPCS A/C 9906Y 9906T 9906N c___ __ UNIT A --- ROOF INTAKE t~ CD ,,I. ~~Tl ROOF FAN EXHAUST £1~ I I I F CORRIDOR TSCl21 ROOF INTAKE t~ ___ SAS/PPCS COMPUTER ROO_M __ ROOF FAN EXHAUST (1-8) IN 33013-1894-1 I~ X15013S'-------' ROOF INTAKE -i> ' x 0 AEA07 AEA06 AEM02 AEP05 SAS/PPCS A/C UNIT B ) AEF05 16" x 16" I I 16" x 16" l--t--4,..---1 F 16" x 16" F 12" x 12" --0-- TSCl13 116" x 16" 14" X 14" F -- 1-*--l 8 1-----l TSCD24 1-- A --0-- 16.. V.fC. 8 l------l"<'F_-114" X 14" ~: L J TSCl12AE~ A TIER"._ ROOM Q UPS 14"X14" TSC DIESEL GEN. RM. 1 (Tc\\_ ~ 2 f---<t-F ___, !:H/ -..,__,-' TSCl1 AED29 AEF29 3 CORRIDOR HEATING 4 _J A DIESEL GENERATOR -ENGINE COOLING FAN EXHAUST AIR 5 l9907M I 'I 24"X24" (TYP.8 PLACES) 9907L NOTES:

1. FOR GENERAL NOTES, SEE DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DRAWING D-381-432
3. VALVE POSITIONS AT THIS TIME DO NOT REFLECT ALIGNMENT FOR ANY MODE OF OPER-ATION; THEY ARE SHOWN ONLY TO REPRESENT THE SYSTEM AS-BUILT CONFIGURATION.
4. EXCEPT WHERE OTHERWISE INDICATED, COMPONENTS, PIPING, AND DUCTWORK ON THIS DRAWING ARE NON-NUCLEAR SAFETY CLASS.
5. THE TSC HVAC SYSTEM OPERATES ON ONE OF TWO NORMAL MODES DETAILED ON THIS DRAWING:

A) NORMAL BUILDING USE WITH COOLING. B) NORMAL BUILDING USE WITH HEATING.

6. THE EMERGENCY MODE OF OPERATION IS ACTIVATED WHEN THE WALL-MOUNTED EMERGENCY /NORMAL SWITCH IS MOVED TO THE EMERGENCY POSITION.
7. AEV05 AND AEV08 ARE NORMALLY CLOSED AND OPERATE AUTOMATICALLY IF THE COMPUTER ROOM SPACE TEMPERATURE RISES ABOVE 78T.

Q l 37" X 1" (TYP) L

8. INTERFACE WITH SAS/PPCS HALON SYSTEM (SEE DWG. 33013-2350).

ISOLATE THE SAS/PPCS COMPUTER ROOM BY CLOSING DAMPERS AES15, AED45, (THROUGH AEV05), AND AED48 (THROUGH AEV08) AFTER ALARM BY ONE SMOKE DETECTOR. AIR CONDITIONING UNITS AEP05 AND AEP06 WILL ALSO SHUT DOWN IN ORDER TO MINIMIZE AIR CIRCULATION. REFER TO EWR 4378 FOR MORE INFORMATION.

9. REFER TO THE PROPOSED OPERATING DESCRIPTION FROM EWR 4075 FOR FURTHER DETAILS ON THE HVAC SYSTEM.
10. THE INTEGRITY OF THE PRESSURE BOUNDARY FOR AEP02 IS SAFETY SIGNIFICANT CLASS, HOWEVER THE COOLING AND HEATING COILS AEA01 AND AEA02 ARE NON-NUCLEAR SAFETY RELATED.
11. WALL MOUNTED THERMOSTAT WHICH IS ADJACENT TO TC 5246 AND INTERFACES ELECTRICALLY WITH THE DOC CONTROL SYSTEM.

6 7 AEA15 H KITCHEN 8 AED52 Q 9 47" X 1" (TYP) NRC SECRETARY 10 Q 36" x 10" AED53 COMPUTER ROOM UNDER FLOOR w AEV08 COMPUTER DISPLAY AREA r.1 AED63 AED62 r:--..~--.~--.,..-.-'L--~~~~......... ~~'J Q )> f"'l 0 " 0 II ii I Iii 0 Ol ID )> f"'l 0 m CD )> f"'l 0 Ol " Iii 0 Ol Ol 47" X 1" (TYP) DATA DISPLAY AREA TC 5242 AED74 47" x 1" WESTINGHOUSE OFFICE II II AED84 ~------+- II "f:i II Iii 0 0 CD 0 "~ ) ~ I ~ I MEN'S LAVATORY 1fl ~ I WOMEN'S LAVATORY )> f"'l 0 m j E AEA14 TC 5244 )> f"'l 0 m AEV01 AED41 AED44 AED90 f ... H ~ AED91 Iii r_J--;===:'..-~w' l------'li---11 -~- ~, l ' 11----A-E.:.Dti,.9-2-ll g I AED93 8 'I L!J <O 0 x 1 1 12 24" x 48" ~HH-AES15 !Ha )> f"'l 0 -i> Ol (Tc\\ SEE ~ NOTE 11 47" X 1" (TYP) DATA DISPLAY AREA s FV37 Q TC 5247 AED47 j AED71 47" x 1" E w AED72 NRC OFFICE LOCAL PANEL OPEN END /ii LOCAL PANEL IS LOCATED o IN TSC MECHANICAL t, EQUIPMENT ROOM. i 47" X 1" (TYP) DATA DISPLAY AREA Q AED42 AED87 AEDBB 1---------j - w AED89 CAD FILE NAME: 33013-1256 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES /-? AS BUILT DATE RELEASED FOR ENGR. s ~ I '~ GINNA STA. R.E. GINNA STATION 9 SCS168 Fl6Qj TSCD19 I I AEF08 SCS169 OPERATIONAL L SUPPORT~ CENTER F SAS192 12" x 14" -~-THROUGH TSC DIESEL GENERATOR ROOM TO GOOSENECK EXHAUST ON ROOF 10 1 1 SCALE NONE TECHNICAL SUPPORT CENTER JOB NO. EWR 3391E HVAC P & ID DRAWING NO. 33013-1256 CCD 01 CONTROL COPY # 12 REV. A B c 0 E F G H J

A B c D E F G H I J VI O> 1 v r:---1..... 1-+----111M--, 577 549C 2 3 4 4-RC-2501 4-RC-2501 4-RC-2501 3-RC-2501 3 fj' H 01 537 577B 2~01 ~ 12240 v E---i~-~t-11--1... ~*----.,,, 577A~i~536 at $ t~ 12237 12425 L!J 3/8" SRC14 l ~ CONDENSING e 1; '~u 01 ~ 3 L!J D 3 4" 533 3/4" 510 3/4" 3 4" TRC01 PRESSURIZER I N ------ ~ M~NIFOLDI ~ r N N I I N ~ 2505 2501 I (N. N I I (...I I ~ ~ I I ~ ~I "' I ' I I I f-----1-J-----I I I f-----l*~J-----1 I I I 12231B I I L ______ _J L 12232B X952 X297 (D-6) 33013-1278-1 (H-4) 33013-1260 REACTOR COOLANT LOOP 8 HOT LEG (C-10) 33013-1265-1 (C-6) (SCH.140) 10-RC-25017 _J 3/4-RC-2501 2-RC-2501 PRESSURIZER SURGE LINE ~ 33013-1888 >~-------Hu~---------~u-------- x1'5J531~----- (D-6) l~33~0~1~3~-~1~8~88~_;.>---/f--j X15155 (H-6) 33013-1260 REACTOR COOLANT LOOP A COLD LEG (C-6) 3-RC-2501 ---t><H 33013-1888 >>------l.#f----------J'f----------,,11-~ - X15154 (E-6) 33013-1888 X15156 (D-4) 33013-1260 REACTOR COOLANT LOOP B COLD LEG 1 2 01~

<
: I ro ro 3-RC-2501 3

01 SRC13 CONDENSING POT 01 ~ 01 01 511A G I N I VI I ~ 71 N I ~I ~1 VI ID I f-----1-J-----I I I 12233B I L 3/8-RC-2501 3/8-RC-2501 4 _J 518 RR IMB 517 RR IMB 431A IMS [9 4318 IMB [ill 5 LOOP SEAL VI 00 G ------ --;;-i I N ~ I I VI (;J I I ~ ~ I I f-----1-J-----I o I 12234B I L ------ _J 441A 441B 6 G I N I VI I ~ N I ;<:: /\\.) '.-..)> VI 1 ::;! Z 01 ' " 'Tl r .:...,..o f-----1-J-----I

5 I

L _J 12235B (D-3) 33013-1890 X14286S'-------_,.- WD-2505 (F-10) 33013-2280 X1600E (D-4) 33013-1274 Xl 662.__ _____ _,.- (C-3) Xl~ 33013-1890 > VI I

u 0

I 01 441 7 ~

u 0

I 01 ~ H 3/4" 8 v I (E-6) I


'~----f-~~-----...~.-c><f-L __

~ 33013-1278-1 / VI " ~

u 0

I 01 547 A ~ C-2 151 3-RC-2501 3-RC-2501 4-RC-2501 43~ l[Q] 1 43~C [9 1 Q X950 (G-11) I I 2501 L __ 33013-1887 X14145S (E-10) 33013-1272-1 VENT HEADER rn !<f 2: TUBING l..J ~ RC-2505 Tl P120 TC i:'---1_.----. 495 3/4-RC-151 .---1..._ t---_.-4----'::J TC -l c z G) 01 9 10 1 1 12 6-RC-602

s2-RC-602

=/?EE NOTE 9 __ JNOTE 8 L-t.... --...oe------i"' 513 563 -~>---602 H 2501 I ;; <!F _ ~ 3/4" 514 5641 <119> 2* 527 l[Q] 151 v .j> I

u 0

I O> 3/4-RC-151 538 <fl9> .j> 12" 3/~ TC 545 -l c z G) 01 (C-10) --!hi-'---<< 33013-1263 00 I

u 0

I O> 3-RC-602 (G-10) --,ff-~----<< 33013-1263 6-RC-602 3/4' 3/4" OMB IMB O> O> E 3-RC-601 01 VI -l c z G) 3-RC-601 1-RC-601 01 00 I

u 0

VI I (A-12) 33013-1264 (B-4) 33013-1265-1 (H-10) 33013-1262-2 ~ (H-8) ~B ~ SAFETY CLASS SAME AS MAIN LINE \\__SAFEIY CLASS 2, 3, OR SAFElY SIGNIFICANT (Q) DETAIL-A 1YP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS ~


iv---<'°-:;;~~;;--i~~~~

0 33013-1887 I 01 (A-1) A B c D E 3/4" 3/4" TUBI~ r:----1 (E-9) T1 ~ I 2-CH-151 I ~~ ~ 5671 576 ~~ 2" 151 3/4" 33013-1260 550B 5 33013-1269 RMW PUMP DISCHARGE I 508 VI I iITJ[g ~ ! ~ I I


~--~

(G-11) 33013-1887 X14146S'---------- TUBING PRC01A SEE NOTE 4 <MO/RCP1A> REACTOR COOLANT PUMP A 6 TUBING SEE NOTE 4 3/4" 7 PRC01B <MO/RCPlB> REACTOR COOLANT PUMP B 151 8 L!J D (G-10) 33013-1272-1 REACTOR COOLANT DRAIN TANK 2-RC-151 \\_ 531 IMB 2-RC-151 3/4" 2" 9 1709A 526 IMS [ill 3 4* 3/4" SRC52 TRC02 PRESSURIZER RELIEF TANK 01 (H-1) r---U--<"~3~3~0~1~3-~18~8~7'.___j I X14139S F 3/4" 550A s (I-8) 33013-1260 ~ ,-------~ (D-4) NOTES:

1. FOR GENERAL NOTES, SEE DWG.:33013-2241.
2. THIS DRAWING SUPERSEDES DWG:33013-424.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. SEAL PURGE WATER LINE FOR FLUSHING #3 SEALS (DISCHARGES INTO #3 SEAL ASSEMBLY WHEN UTILIZED).
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
6. PRESSURIZER HEATERS' EIN'S:

EHTRRC01A EHTRRC01B EHTRRC02A EHTRRC02B G

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-H MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
8. LOOP SEAL INSULATION FOR SAFETY VALVES 434 AND 435 IS SS CLASS AND SEISMIC

--.,,.H---<< 33013-1888 ~ CATEGORY 1. X14103S

9. RCS VACUUM REFILL PUMP (CRC01) IS CONNECTED AT THIS FITTING WHEN USED.

10 11 CAD FILE NAME: 3P125801 CONSTRUCTION llMITED CONSTRUCTION: AS NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCJ\\1.£ NONE JOB NO. EWR 3391E REACTOR COOLANT PRESSURIZER (RC) P&ID DRAWING NO. 33013-1258 CCD 01 CONTROL COPY # 12 REV. I J

<~~:!*~~I ~-*-** ~-i><J-X1:l101

A B c D E F G H J X550B [Jl 0 1 2 (F-11) 3/4" 33013-1258 >-'3':.l.-4'--..:..R:.::Cc_-...:.1..::c5_:_1 --.-1.... 1--::J D L_ _____ RMW PUMP DISCHARGE 2" 2" LRC03 v 1" 1 * [Jl [Jl 00 rn 151 v 556A [Jl 0 [Jl rn 0J I

u 0

I [Jl SEE NOTE 10 PRC01B <MO/RCP1B> REACTOR COOLANT PUMP B NOTES 6 & 7 3 (VIEWED 4 (B-10) 33013-1272-1 R.C.DRAIN TANK 27.5"1.D.-RC-2501 5 3-RC-151 ---i c rn z G) 2" IMS OMB 0J 'ro-1

u 0

I [Jl 0 [Jl 523 524 541 503 7 8 2" 2-RC-2501 2" (C-12) 33013-1264 EXCESS LETDOWN X310 HEAT EXCHANGER (1-8) 33013-1888 X14131S (VIEWED OUTSIDE OF LOOP) I 29" l.D.-RC-2501 6 ()1 ()1 tO SEE NOTE 4 (VIEWED INSIJE OF LOOP) (H-1) ,,,-----------, 3-RC-2501 (VIEWED INSIDE OF LOOP) 10-RC-2501 (C-6) X14143S (C-10) 33013-1272-1 R.C.DRAIN TANK (C-10) 33013-1272-1 R.C.DRAIN TANK 1-11 33013-1887 (E-12) 33013-1264 REGENERATIVE HEAT EXCHANGER 1 -~-2-RC-2501 1~501 \\ 540 507 427 ITllFOI ~ ~ 2 506C ~ Tj I 01~ rj~ 0 0J .~ 11435B 0J [Jl ~+-----! L __ T~ _ _J 2501 TUBING 3/8" 2501 TUBING ~ Tj I 01~ r,~ 0 8"1~ 114~ D 11440B 0 I L __ T ___ _J 114~ D 0 ;u 0 ~ 2501 TUBING ~

u

'U 'ii fT1 0J ~

  • 0 l ;u 0

I N ()1 0 EMS01B STEAM GEN. B 3 -i:><t--<. 33013-1258 X431B PRZR SPRAY D-10 10-RC-2 01 33013-1262-2 X86 7 A '-----:S::-:A-=F=ETY=-=-""'1N'""JE=:C:=Tc-:IOc:-N. X721 PUMP DISCHARGE & ACCUMULATOR TANK 1-1 33013-1247 RH (B-10) --t::><.t-J 33013-1265-1 X295 eves CHARGING (H-1) 33013-1247 RHR 33013-1247 RHR (B-6) SCH.140 2-RC-2501 853A TC 3 4-RC-2501 33013-1278-1 X954 NUCLEAR SAMPLING E-1 33013-1262-2 X877A SAFETY INJECTION PUMP DISCHARGE X393 A-10 33013-1265-1 eves CHARGING E-1 33013-1258 PRESSURIZER SURGE LINE 2-RC-2501 2-RC-2501 1 -RC-2501 (SCH.140) OUTER INNER LEAKOFF

-\\

/ 3/8-RC-2505 \\ LEAKOFF 3/8-RC-2505 4-RC-2501 0J I

u 0

I [Jl 0 [Jl 0 tO rn [Jl 0 L __ _J


1-- REACTOR SHROUD z (/) VESSEL

~f:i RRC01 X431A ~ [Jl 0 0 G-1 fT1 33013-1258 PRZR SPRAY (F-1) 33013-1265-1 X383A eves CHARGING H-11 3-RC-2501 I (f) I "i5 10 ,§ I I I SCH. 140 r-3_3_0_1_3 ___ 1_2-78---1-..._ '>-~"'--/'- 2-RC-2501 SAMPLE ROOM (G-1) 33013-1247 RESIDUAL HEAT REMOVAL 1-11 33013-1262-2 SAFETY INJECTION PUMP DISCHARGE 2501 TUBING ~ v I I 3/4-RC-2501 LRCOS,I ~ '-C:s:::t--=-'---'-'-"--='-"-'---j I SEAL CHAMBER SEE NOTE 1~~ TRC06 1 2 NOTE 6 I J500B t SEE !LOI NOTE 15 MANIFOLD 1~ 11445L 1~ I~ I 6 596 33013-1262-2 SAFETY INJ. 10-RC-2501 SCH.140 (VIEWED INSIDE LOOP) 29" l.D.-RC-2501 I (VIEWED OUTSIDE OF LOOP) 4 X867B ~ <ill> Jil~! 590 592 592A LRC0 1 [fil [fQ] !J;Q] ~1"~ - Jil~I,~ 591 593 593A LRC02 _ i!5 1 [ill [E9 ~~ ~~ 2 J1E: _ _r-g.._ NOTES 12 r ~Lii AND 14 TC 5 PUMPS 6 7 27.5" l.D.-RC-2501 I (TE\\ ~ (VIEWED OUTSIDE LOOP) (F-11) 33013-1258 X550A '--------- RMW PUMP DISCHARGE (A-10) 33013-1272-1 R.C.DRAIN TANK 8 OMB 551 9 EMS01A STEAM GEN.A TUBING 2501 )>I ~I ~I I I )>I Z1 ~I o, 11441B 11442B ~D 114420 11443D NOTE 6 OMB 552 tO 2-RC-151 9 o-rn rn o-OJ OJ (1-4) 33013-2278 10 0 ;u 0 (/) (/) ~ fT1

u

'U 'ii fTl 0J ~ !='

u 0

I ()1 0 2* X11585 10 SEE NOTE 10 SEE NOTE 4 3 4-RC-151 1 1 12 NOTES:

1. FOR GENERAL NOTES, REFER TO DRAWING: 33013-2241.
2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-424.
3. LINE CLASS 2505, EXCEPTION TO SPEC.: 1" O.D. TUBE X

.220" MIN.WALL; MATERIAL IS A269, TP 316.

4. #2 SEAL LEAKOFF LINE (AT PUMP SHAFT). CLASS 2 ACTUALLY ENDS AT #2 SEAL, NON-CLASS BEYOND.
5. #3 SEAL LEAKOFF LINE (AT PUMP SHAFT). SEAL SYSTEM IS NON-CLASS BEYOND #2 SEAL, INCLUDING
  1. 3 SEAL, HOUSING, AND LEAKOFF.
6. THE 7 TEMPERATURE ELEMENTS WITH DUAL ID NUMBERS IN AREAS (D-9),

(G-8), (H-8), (D-3), (1-4), & (1-9) REPRESENT DUAL ELEMENT RTD'S.

7. TEMPERATURE ELEMENT TE-410B-2 IS SPARED. SEE DWG.: 21489-0504 FOR DETAILS.
8. FLOW ORIFICE LRC06 IS 1/4". SEE DRAWINGS:

21489-0501 AND 33013-1626 FOR DETAILS.

9. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 1 0328.
10. REFER TO DRAWING 33013-1265, SHEET 1, FOR eves CHARGING AND LEAKOFF CONNECTIONS.
11. MOV'S 852A AND 852B HAVE BONNET PRESSURE RELIEVING VENT HOLES IN VALVE FLEXIBLE WEDGES ON DOWNSTREAM SIDE AS INDICATED BY POSITION OF ASTERISK (*).
12. RCS VACUUM REFILL PUMP (CRC01) IS CONNECTED AT THIS FITIING WHEN USED. (OPTIONAL USE)
13. CONTROL ROD DRIVE MECHANISMS (CROM) ARE LOCATED ON THE REACTOR HEAD AND ARE A REACTOR COOLANT PRESSURE BOUNDARY.
14. ORIFICES LRC05 AND LRCD7 ARE 1/4". SEE RGE DRAWING: 03021-1419 FOR DETAILS.
15. LINE CLASS 2501, EXCEPTION TO SPEC.: SCH. 80.

1 1 [Jl ()1 0J OJ 1* v LRC04 2" 554 2* [Jl ()1 [Jl CAO ALE NAME 3P126001 CONSTRUCTION LIMITED CONSTRUCTION: /JS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR F"'-'lY GINNA STA. RocHESTER G>.s & El£crRlc CORP. t------------j NONE REACTOR COOLANT (RC) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1260 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 LOOP SEAL LT 921 11626 2505 894A 8948 (C-6) 33013-1270-1 (B-11) SEE NOTE 8 33013-1247 X857C._ _____ (1-1) < 33013-1270-1 (D-11) 33013-1891 X14369SL-_____ (D-11) 4" 2" 893A 151 2" 3" 8" ~=3~3~0~1~3-~18~9~1==::>-- X1437oc! 1 m ' 2 6" TSI01 REFUELING WATER STORAGE TANK 0 ' 6-Sl-301 357 2" 8938 I 11625 1~05 2" 2-Sl-151 3 (l-9) 33013-1870 AUX. BLDG. EXHAUST FAN 1 G ~ (F-5) 33013-1248 1 o" 8~ 8 REFUELING WATER CIRC. PUMP (G-5) 33013-1247 4 6-Sl-1501 X856 m 0 m OJ 916E ~ - 1/2" m 0 ri; 1 2" 5 6 7 2-Sl-151 1801 v 3-Sl-151 1733 2-Sl-151 (D-1) 10" 10-Sl-151 (F-1) 33013-1262-1 -C><t-1 33013-1262-1 x 1 817 l:'.::'.'.:'..'..:'.=.'..::':'.'.'=.'__./'"I I X8258 SEE NOTE 11 1------1.:::::<r-6-_;S;;_l-...;1..:.5.;...1 -( r---8-" ----,--i r-1 L )d-1 4" 858A ~ m ' C! OJ z 0 0 - [];QI PSl02A,<MO/CSP1A> LT 932 11623 25051301 3/4" 863A v 0 - CONTAINMENT SPRAY PUMP A SEE NOTE 7 1~-0>~ ~ v E---1-t--, l[1 _I._ ~ + 'f ,~ ~ 1802 ~ ~ TUBING~49E "' 1" "_I- ~ 2 ~ 3 4" 301 2" 8498 MANWAY TSI02 SPRAY ADDITIVE TANK 849C ---, 849D ~ (/) T 0 - 836A 2" D 3/4" _r-~~IS 6-Sl-301 863B 2" CONTAINMENT SPRAY EDUCTOR A SSI01 8734 IEQI 845A ~ 2" l-8-C7*3:}B-,--__.J'---I s7o f---8{;7*3AJ--=----1 881B Ol [bQJ ~ -":, 2" [QJ NOTE.JQ_I [QJ 2-Sl-151 ~T ~ 1: D ITE 10 15~1 87~C ~73D u:;g u:;g 2 2 0 - 2-Sl-301 Ol .... g;i s 881C !ill SEE NOTE 11 v ~ OJ 6-Sl-151 6" 8" I M) 4" '--"-=-T=-r:::<1--....:.....--c1--.....:...--'--I+- 3 43* 858B [];QI PSI02B,<MO/CSP1 B> ~ I Ul T CONTAINMENT SPRAY PUMP B SEE NOTE 7 2-Sl-301 6-Sl-301 3/4" 8737 )-.::.!-'------IV SSI02 CONTAINMENT SPRAY EDUCTOR B 2" ~ 831B [bQJ 2" 8~ 0 1" 859G [fil 860A IBLCI 2" 860B [fil IBLCI 6" E 2822A ~D 116 __ ~ 0 - c 21 z TC M 860D IBLCI ~ [§] 2 OJ z 0 860C IBLcl ~ Pl 0 6" L'-J D 6" t§ 933D 2823A ~ t:i~8_s_1 ____________ 1_-_s_1-_3_0_1 _____________________________________________________ ~ 2 3 4 5 6 7 (/) T 0 0 - 6" 8 (1-7) 33013-1266 BORIC ACID BLENDER (F-10) 33013-1272-2 R.C. DRAIN TANK PUMPS (E-10) 33013-1248 1/2" m I ~ I 0 - 862A 1/2" ~.-,:i 869F 862B 8 m I (/) T 0 - m I (/) T ~ - 1/2" ~ ~ 910B 1501 - 910A 9 (C-1) 33013-1262-1 SI PUMP DISCH. & ACCUM. TEST LINE PT 950 MANIFOLD ro SSl10 910D 0 910C Pl 933A (D-9) 33013-1262-1 SI PUMP DISCH. FULL FLOW TEST LINE Pl 2780 "' ~ ro OJ ~ 868A [QJ Pl 933B ro ~r, ~m I o I Ol O> O> OJ t~ 6" 6" D 3/4" >---.---:J TC 2861 3/4" f--... 1---:J TC I Ul -I 0 - 2862 mt 875B JBLOJ 8768 IBLOI ~ 876A !BLO! 2863 lbQJ 3/4" 2864 1" I 3/4" 6.. 6" h----'-----';__-1 ,,.10 co xz . );! OJ z r;;:: 0 "' 0z 9 ro -"' OJ ro OJ 10 CJ PT 944 ro - <O 0 ro 0 ro - <O 1 1 12 2505 2506 n 2505 2506 ro )> 4" 2505 UPPER CONTAINMENT SPRAY RING (90 SPRAY NOZZLES) SSI07 3" 4" F-2 33013-1863 POST ACCIDENT CHARCOAL FILTER (E-2) UNIT A C-10 33013-1863 POST ACCIDENT CHARCOAL FILTER UNIT A B-4 33013-1864 CONTAINMENT AUXILIARY CHARCOAL FILTER A 33013-1863 POST ACCIDENT CHARCOAL FILTER UNIT B (C-11) 33013-1863 Tl NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DRAWING 33013-425
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. CLASS BREAK OCCURS AT PIPE TO NOZZLE WELD. REFERENCE DRAWING:

PITTSBURGH-DES MOINES STEEL CO. DWG.: ES-56063-02-D REV. 1.

5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR NITROGEN LINES AND COMPONENTS IS BASED ON UP-STREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO INTERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
6. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
7. THE START SIGNAL FOR THE CONTAINMENT SPRAY PUMPS IS HIGH CONTAINMENT PRESSURE.
8. DC CONTROL POWER REMOVED BY KEY SWITCH.

~

9. REMOVED
10. EXISTING SCH. 10, 2" PIPE LABELED 2-Sl-301 NEAR SPRAY ADDITIVE TANK AND REPORTED IN CR-2007-000729 HAS BEEN EVALUATED TO SATISFY REQUIREMENTS OF SEISMIC UPGRADE PROGRAM DESIGN CRITERIA AND LINE SPEC.

CLASS 301 "DESIGN LOADS".

11. CONFIGURATION OF THE CONTAINMENT SPRAY PUMPS MECHANICAL SEAL WATER PIPING TO THE SEAL WATER HEAT EXCHANGER IS SHOWN ON DRAWING 33013-1246,2.

POST ACCIDENT CHARCOAL FILTER UNIT B 2863R A-4 33013-1864 CONTAINMENT AUXILIARY CHARCOAL FILTER B 1/~ ii ~ SAFETY CLASS SAME AS MAIN LINE ZSAF~ CLASS 2,3,0R SAFETY SIGNIFICANT (Q) 4* LOWER CONTAINMENT SPRAY RING (89 SPRAY NOZZLES) SSIOS 4" 10 DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS CAO FlLE NAME 33013-1261,1 3" CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES '2.- -15' AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION 1 1 SCAt£ NONE JOB NO. EWR 3391E CONTAINMENT SPRAY (SI) P & ID DRAWING NO. 33013-1261 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 2 3 (H-10) - -,,_~~~~-......... ~ " I 33013-1887 (H-1 O} 4 5 (J-10) .,_~~~---.......~ --C>< _:::l_-1, 33013-1887 >--,.. If-----, X14137S I X15064 '~ _;:- I 33013-1887 >-If- .. ----lf- .. ----1 .. 'f-----, l/P X15065L.._ _____ I v L....r-1* 945 " V-{-><l'f---"-(*'"'r--..~---'-,--r-------1~--'S~l--~90~3:._ _____ _..,.. ___ ---, ~ - ~* I ~

  • 945A 945 I FP120 ~ *~~

(F-6) Im _lJ 0 I 33013-1212-1 f---- I

  • I

~ - I 33013-1262-1 >---------------'---'_f',J--r l--C-:J---.-----1-------' X846 11 8623 n 8624 ~ (A-10) I t/) I 0 PT 941 903 902 I CJ) T ~ 6 v? = 830A ~r-J~152 ~ 1-Sl-902 PT 940 t-.J s:l'\\ 7 2 >* l 7 8 9 10 1 1 ~ SAFElY CL.ASS SAME AS MAIN LINE SAFElY CL.ASS 2,3, OR SAFElY SIGNIFICANT (Q) DETAIL-A 12 I \\..1...... I I ~ I ~ N= J, ~ 8" 0 TYP. SAFElY CL.ASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS 0 L!J TC (D-1) 1* <::~3_3_0_13_-_1_2_63 _ _;1-----------~-------~ L I I (C-10) 1J113 4-Sl-1501 2-Sl-902 TC f--r-.L_-I>(]-':......::"-""""--, 1-Sl-903 LT 939 833A TSI03A SAFElY INJECTION r--l ACCUM~LATOR <O ~ '-.---i;s~-:;i-2~--S~l_-~9~02=--~ -+--l-833B Y ff:' r i ~J~ G'l w D 3/4* DI, i84S I 33013-1262-1 >-------------r-----------------, X88BA -i--1 ~ t-- ~-+-*-*-+-~ > (') cl~ x [lJ I z r.::: Q p z _J ~-~ ~' 2505 1501 ml.....------ FT 924 E- ... 2** I I 124ozH Bz8A 12402L 8288 ~ 2505 501 {1-5) 33013 1888 sov 14123S ~---~- ~ 150~1-...,2~501 = 2" 1¥1 --t. 8788 IBLOI I CJ) ~,.. ~ N*il-

== 835~ [f9 1501 902 <t 878G 1" oo,' ~ I:: C)J. z 2-Sl-2501 w G'l s 2-Sl-902 2"

J TC 832A LJ LT 938 (H-5) r---jf--;------;{f---------,;{f---------,;{f-----~<==3~3~0~1~3~18~8~8~]1 V.....::i X14118S 2-Sl-902 2"

0 832B ~ ~,, ~

~

2 10iSl-902(SCH.140) 'f;~ ~ ~ 1" (B-10) _"_o~~o ~~::;:::---~-~-f----.-J:--lt---l.... _t----'----------------------------1: 33013-1272-1 892A _"'l. ~44A REACTOR COOL.ANT -~ [ill DRAIN TANK ~- tJ1 0 @) ~ ~ ~" D 90 51 (J_-_5_) __, 1 - !). L-"'.J ,.-------jf--,,------jf--,.--------H-33013-1888 ~ - ~ SCH. 1'!2_ 2501 1150\\ '" X~;, 2~s LSI01 ,~ 3F4-Sl-2501 ' I ' $H.140 ~ "'... - 11' I'----~ I 11------a-t3w9.,.A1----, Im ~ _ SCH. 140 D 1: (1-5) 2845 3/4" LSI02 ,r:-


</11-' -------</i1-' -----,,,.','------<< 33013-1888 f-txl-1

'I ------.. -*'r'..---t-~ X14122S D II I I I 2844 '------, IFcl ~39Bl 3/4" v I, ~ ~ 2843 SCH. l 4Q_ 2501 11501 I I (G-4) 2501~01 ~ I ~ ~~ J MANIFOLD D ~ I CJ) (H-1) 1:1f--<:::==3~3~0~1~3::2:18~8~7~],r-C><:::t-_ 867A I 10-Sl-2501 (SCH.140) I I (D-4) 33013-1260 LOOP B COLD LEG L 33013-1260 ,r------------------~8~ 7 7 ~A--1....-~~...... r---t..,.t--' LOOP B 878F "'m" ~ 878A G °' IBLDI HOT LE ~ T ~ 0 ~ PT 937 co l'!i1 CJ) JI o Bv.i *... " ~ ---:J X14136S ~8308 v ~1-i.

;

/ SI-~ ~ 1 rri. * ~ ffi~ 1-Sl-902 ~ = -+--+"'

g Sl-902 PT 936

<O 3/8... "' 9. - ~ 2-Sl-902 TC 837A TSI03B SAFElY INJECTION r--l ACCUM~LATOR n' 2 ,.::2~-~S~l-~9~0~2'---{;:8::J-'2~"-"r'.i..,"1, _3/ 8" LJ 838A ---,_.r-:l TC (H-11} LT 934 2" 2-Sl-902 I 33013-1888 >-If-.,---, X14164S 0 6 8378 -t--<-:---="'c:J' 1:-. c CD (]ljl z G")UJ D LSI05 l../1-3/4" - 1" DI, 2836 DJ ~ ~ I CJ) ,--1_-_S_l-_1_5_0_1 ___ ~,lf-- L_ ____ _.9,.._ _____ __J I I [E£J 83~8 <O ~ ~.: ~ c I T 0 ~ 1---~:i FT 925 MANIFOLD ,--+ - - -- - - -+-r I I 124058 I ~'17 o I ~~ l I TC . ~ :J 12404 co ,.. > 3/4" 3/4"~ 0 - 1501 902 01 0 ~101 ~.,,-------....... _j_J 4-Sl-1501 4" 9 _ I 33013-1262-1


;-;-:-.._----i-----t I t-------------------...,

u; (F-10) X888B T 150+--3 ~ ~~ I /\\

  • -f----l,_:::l-.*--,

\\§) 0 [@ ~, " it)1 ll~ " FCJ', ,.~ 2 601 ~ 150 I II.JI~=~ ~ ~ ~ "'mi** ' m-,i ~- 890 £-lr-1-i & 3/4" Pl 10 (G-10) I

_,-c3::-:3::-:o-1"'3--12::-:6::-:2::-:_-1--,}-'----------=i:~_J x819 I

1 2 ~, *.fl.*..

== D ~ T I -D 25~1 3 4 5 o~* Z w G'l s <t I " I a18t1 I 01~ ~I aJ 2-Sl-902 8388 10-Sl-902(SCH.140) 2" LT 935 SCH.140 2".. 6118 6 I <O 0 ~ 1'l: 7 I 8678 I 8 I 111 I 0 ~ v = 15~1 (H-11) 33013-1888 f-tx:J-X14165S T (E-11) (1-6) 10-Sl-2501 (SCH.140)


<! 33013-1260 >

LOOP A COLD LEG (G-11) ~---,:~1-------ff1-------ffH-----~:~1---<< 33013-1888 ~ X14162S (E-8) ~~~~~~~~~~~~~~~~~~~~___,,_! _3_3_0_13_-_1_26_0~)> LOOP A HOT LEG 9 10 1 1 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1262, REV.10
3. EXCEPT WHERE OTHERWISE INDICATED, SAFElY CL.ASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE NOTED, SAFElY CL.ASS FOR INSTRUMENT AIR AND NITROGEN LINES/COM-PONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE.

REFER TO INTERFACING AIR/NITRO-GEN DRAWING FOR SAFElY CL.ASS. RE'llSED PER ECP-I 5-CXJOM5-CN-001 MLS MZ MLS MZ 2/17/16 2/17/16 2/17/16 2/17/16 CAD FILE NAME 3P126208 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 2/17/16 ~ BUILT MLS DATE RELEASED FOR ENGR. ~ GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. SAFElY INJECTION AND ACCUMULATORS (SI) P & ID DRAl>lNG NO. REV. EWR 3391E 33013-1262 SHEET 2 OF 2 & CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 2 3 4 5 "' 2 1/2" 8621,i:Jf-- ATM 6 1-_1_-~S~l-~9~03"-------- ~----;~ ~ ~ 8627 N Q 7 8 9 10 (A-3) ---IHI I H i 944A ff-N ~ 1/2~ H; ! 1827 ~ ~ OO ~ ~ VI (J-4) ~ _, -? 621C ~ ~ ~ ~ (A-J) L3~3~01~3=-~12~7~4=>----__!1::_-~si::_-2~5~0~ 3 ------~~ I~ I l--f:><1--'--'---11,._ __ L __ _:_( ____,, _ _..,...,._--1*-*-<f-..i.--rJc-1'-"--L------J__-_,...t-~1"'-""s1"'-""90"-"3'---------------------------JI 33013-12s2-2 >.N- _lf44D NITROGEN 1827A ZWDOl 18278 8628~*44 8529 ~ 846 X8623 SUPPLY 2503 903 ~ [jJ IITJ (H 1) SEE NOTE 5 2" ~-----------------1----------------------------.. ----f 33013-1272-2 > SSl13 SSl14 (B-9) 33013-1261 X898 1 TS I 2-Sl-1501 2505 918A N ' 1501 '---'----'-.. ~ ~-----~~ 9188 ~ 3/4" g,_...._~_, 898A (C-12) -"-,-c.J , 4-Sl-301 0 0 .* ~ J 33013-1247 _,.,...,..~*-~---~-~-;~~*--~--~-~ Xl 816A ~-R-H_R_P_U_M_P~ DISCHARGE (D-7) 1-Sl-301 1 2" 1820A [!)) 891A 2* LS!08 1""- 1 /2"¢ II! 1501 1 151 1 2" 3/4" TSI01A 12406 i T ~F 'I ~ j~so5 TUBING I 1501 8741. 2 7 8750 J 1 v_ ~ /\\ l5, 3/4" '*1" ~ 1/2"¢ ~ v'P"O ~ ~ ~ ~ ~ X9081 33;~~~;230 Lill. (C-1) TC '5'~TUBING 3" ""'1

i:

~ 4-Sl-1501 0 0 0 0 0 0 f.'--.--=-------f::k1---------...::.----,-----r::x::-1--l--Q-----r--.W'-------------L-----'--......:-i 33013-1262-2 ' r--i_)k:::r----1t--'-+--) 1 888C SEE NOTE 4 1 " 0 I !ll I 0 0 0 890A [Q] TUSING 0 1817 "-~~-----::.-:::.-:::./ _____ 8_8_9A~I ~... ~ ~ 8[@ ~ [8 !".) FE924 PS!01A ~ o g 2" N

Q co iU SAFF.:TY INJECTION PUMP A TC

<M0/SIP1A> 2" 150~05 r!TUBING 34"~ SSI04 1/4" 1/4" 2" (H-1)


!133013-1272-2 >

AUX. BLDG. SUMP ~ ~ ~ I" ' (C-9) .. ~3-Sl-1501 I oo_t_ 1 L 33013-1261

i:'t' 898C FE910 >

1 1 12 < 33013-1261 J---~'4---LM<!f--'=:J TC 8748 N2" 914A 914C o SEE NOTE 4 0 t.... ~ _3/?"_ W ~TC ---.::O;f~:ING 1/2"¢ VE ~TV61NG 1/2"¢ 187560' TSI01C 8757 (D-3) 33013-1261 RV/ST j§ r, ¥' 0 I (fl , T 0 10-Sl-151 TUB~ v --j-11----...-.>4--* 2815 0 825A @!]I [fil °' ' § 0 TCJ-C}-3: "' T TC 0 3/4" 0 0 1~1r01 8-51-301 8258 IBLOI [fil 0 DI 3/ 4'~ TUB~ 0 0 0 0 0 0 0 0 SEE NOTE 4 ,, 890B I [Qj 0 0 0 0 0 0 1" 3/4" PSI01 C SAFF.:TY INJECTION PUMP C <MO/SIP1C> "-~l]J_s ____ ~/ PSI018 SAFETY INJECTION PUMP 8 <MO/SIP18> 0 0 0 ¢ 0 0 0 0 0 881 s 1* 1" 2"

oJf, z

C~ 1:1 884 l 879C ~ 1'\\ "' ~ "'.... * ( <_3_3_0_;3----~-'2-6-1 --,,_ __ s_/_4_-__ s1_-_1_5_1 ___________ I ______________,_J ' 2" RV/ST (G-3) 33013-1266 BORIC ACID STORAGE TANK A 827A [:@] 1" 8-Sl-301 0 0 0 0 0 2817H PSI01D SI ACCUMULATOR MAKEUP PUMP <MO/SIP1D> 2" COLLECTION RECEPTACLE 5/8" ~ - 2817F 3-51-1501 2849 ~505 1 2" TUBING LI

-1/2"¢ TUBING 4

101C ~ ~--------------------~3~ T ~D 8-Sl-301 0 0 0 0 3/4" i:;; 6-() I TUBING 2" 1/4" SSI05 3 4" j 2505 TUBING I 1501 (H-1)


1133013-1272-2 >

AUX. BLDG. SUMP 12407 915A ~ ~ 915C TC ~TC 114.. 913C o:i tu rn TC 87:l 3 4* 't 1/2" v 874C 6 ~ ~ ~ (H-i) 4-Sl-1501 i-,;:....;.;,._;.;..:.;__--f'::k:'.1--l.--~--{><]-.l...(~~-...,---l.~~~~~-_;_...;_:....;...:..;_-1._-1 33013-1262-2 Q ~ 8898 8888 888D FE925 I~ 8742 ~----<Or------- [!)) -! 33013-1230 X9082 (F-1) 0 0 0 0 0 0 0 3/8" t----t-,:J TC 28178 0 0 879 rill 2505 ~TUBING j 2505 -TUBING 3 8" 3TC 28170 ~ 3/8" --jD s "' "' "' ~ D~ 1/2"*) TUBING 3/4-Sl-1501 TSI018 8~ f----,----:)-'::Jv 8753 """- 1/2"¢ TUBING 8754 y (J-1) 33013-1262-2 ~ 'X872A SEE NOTE 0 8755 826A filQ1 ~ SAFETY CLASS AS MAIN LINE SAME [fil 0 0 0 C> 0 0 0 ~ TUBIN~ : L SAFETY CLASS 2,3,0R SAFETY SIGNIFICANT (Q) NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DWG: 33013-1262, REVISION 10.

3, EXCEPT WHERE OTHERWISE INDICATED, SAFF.:TY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A". 4, WELD PREPS ON BOTH SIDES OF VALVES 890A, 8908, 1815A, AND 1815B ARE SCH. 10S. WELD PREPS ON DOWNSTREAM SlDE OF VALVE 826A AND UPSTREAM SIDE OF VALVE 826C ARE SCH, 10S. ALL COUNTERBORING IAW EWR-3092.

5. V-8628, V-621C, V-944, AND V-8629 ARE ABANDONED IN PLACE. PRESSURE CONTROL IS NOW PROV!OEO BY VALVES SHOWN ON 33013-1274.
6. MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO

~ECHANICAL EQUIPMENT PER SFEWR 10328. 7, UNLOADER, Pl-928A & Tl-918 WERE PERMANENTLY REMOVED FROM THE SI MAKEUP PUMP SKID IN ACCORDANCE WITH ECP-13-000426. POL 10/24/15 CAD FILE NAME 33013-1262,1 CONSTRUCTION UMJTED CONSTRUCTION: AS NOTED ?REWMINARY NOT FOR CONSTRUCTION 1----+--'

  • ----;~

BlDDING i>U~PO&S 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 8" 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1822Aw o o DETAIL-A A_S 8UILT (G-7) 33013-1266 BORIC ACID STORAGE TANK 8 1 8278 [Q] 0 i 0 8-Sl-301 000000 Q 0 0 0 2 0 3 4 5 !o o 1 VJ,, 0 SEE NOTE 4 ~ 826C IBLOI [fil 0 6 7 8 9 TYP, SAFETY CLASS BREAK POINT FOR VENT, DRA!N & TEST CONNECTIONS 10 1 1 J REl.fASEO FOR GINNA STA. R,E. GINNA STATION NONE SAFETY INJECTION AND ACCUMULATORS (SI) P & ID JOB NO, DRAWING NO, EWR 3391E 33013-1262 SHEET OF 2 CCD 01 jCONTROL COPY# 12 A B c D E F G H J

A B c D E F G H J 1 I 2 I 3 (H-8) ,r--------- 17---J l 33013-1887 >-------h,,'------------1/-,,--, X8604A (B-1) I 33013 1262 2 SAFETY INJECTION ACCUMULATORS A & B (G-8) 1 " OJ ° 0 0 )>' ~ ~ 7 0 0 l' OJ ~ 33013-1887 >~--,11--'/ X8604B 1 I 2 --j c OJ I~ I PS 457 1/2" r--*...

  • -r--:i v 8602'A PS 458 3
  • <:> _ 1 /2" 86038 I

I PT 455 TC 4 TUB!~ ° '"'-- 3 I I 1 " ~ 8608A'

  • TC I

OJ ° 7 0 };1 ~ s;, * "' N N_ O> J>'

  • L!J D

5 TRC03A OVERPRESSURE PROTECTION ACCUMULATOR A I TC - OJ 01,

  • N '

6

' 1 1/2"

/' 1 1/2" '.- 8615B OJ ~ 0 N r-7~ ~** 1'.. ~ ~CR02 l~I 1" r-------t. I 8606B I r--.,--...---t,~-,,-1-1,,"°* 8612B 1-_,_ __..._-'---1 co PT 456 1 " 8608B'. TC OJ OJ O> 7 0 " OJ' TUB~NG (J> N 0 m*.. .f:..:: \\-------,--('~ l 86o9s 4 v D I 0 0> \\) TRC03B OVERPRESSURE PROTECTION ACCUMULATOR B 5 I 6 7 3/4" 7 I 8 TRC04A OVERPRESSURE PROTECTION NITROGEN SURGE TANK A 1" 1,_ I 8619A Isl I f----fv~*f--""1, I t-----1 8618A ~~~- g;1 r_. ~*.. N= L!J D 9 I .1.---r 8630A SEE NOTE 3 1 0 I 1 1 (B-11) 0t--:::-1 I~ 33013-1258 AOV-430 (B-7) 3/4",, ~ L---11,,"--J r--~-11-,,_,: I r-1 __,1.,_: -----<C1!"'iiill*--J111--<< 3301 3-1888 ~ 8620A X7067L TRC04B OVERPRESSURE PROTECTION NITROGEN SURGE TANK B I 8 I 3/4" t-~:~ A (C-11) J--"--:JV"v-C_,1~~3-30_1_3_-1_2_58~> I :r----c 8630B SEE NOTE 3 3/4""

11 rJ SAFETY CLASS 2 OR 3 DETAIL "A" AOV-431C (C-7) u

~""'i.*--11-u-~< 33013-1888 8620B SAFETY CLASS SAME AS MAINLINE TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN, AND TEST CONNECTIONS. 9 I 10 I 1 1 I 1 2 NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. THIS DRAWING SUPERSEDES CATALYTIC DRAWING A-202.
3. CHECK VALVES 8630A AND 8630B ARE PROVIDED WITH ORIFICES IN THEIR DISKS TO ALLOW CONTROLLED CLOSURE OF THE PORV'S, REFERENCE EWR 1660.
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

REVISED PER jJ /) /) A OCR 2DOD-0194 AJV3 NJ'l J Hf/J!t -:;i;;:.p PCR 96-079 i--:.=-f!...Uf<L./--IC--'-'---1---1 MDCN 1963 10/11/DC /o//ljN"' fo*-/t;,-d) l*/)b/._,, NUMBE!\\: R£VISlON CRAWN BY CHECKED SY RESP. ENG, RE:VIEWER CAD FILE NAME: 3P126301 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PREUM!NARY NOT FOR CONSTRUCTION BIDDING PURPOSES A B c D E F G H Pho/;._, AS BUILT

p; r-~-"-t-~--~--------r~~-1..____

DATE RELEASED FOR ENGR. rACiurv GINNA STA. ROCHESTER GAs & ELECTRIC CORP. SCALE NONE ROCH£:Sl£R, N£W YORk RCS OVERPRESSURE PROTECTION NITROGEN ACCUMULATOR SYSTEM P & ID JOB NO. DRAWING NO. EWR 3391 E 33013-1263 CCD 01 CONTRQL COPY # I 1 2 REV. J

A B c D E F c H J I 1 I 2 I 3 I 4 I 5 I 6 7 I 8 I 9 I 10 I 1 1 I 12 (E-10) .,,.--~-~--..... >-

  • I 33013-1891 X14207s'-------_,..-

X9B7 (FT\\ 3* (D-11) X1 -590-8[~~~~-~1~~~=>*~~d~-- ---~ 2" W-1) ~ ~ r--~========================~-----~-----4!=1~1~> 33013 1891 ~.....-+--- _:_~ ----11-1;::


1*------<: 33013-1270-1 trn ;:,

.<210 I PRESSURIZER RELIEF TANK (G-3) 33013-1278-2 I-I 0 I I -"' ~ I () I I v 2* -D-4.- 7 239B Pl 136 --1 c OJ z 0 12159B ~" iljo PT 6Dl-+----'-~l.S-i 3/4" AUX. BLDG. SUMP TANK f ~ ~ <j ~©I ,;* 'I' -*-----iht-' --1©/P r----1t1-)~< 3301(~=~~88 L,____...,_ (C-10) en r 5' ! L-' J (A-9) '.l> "' 6;.J>-I --~ 6249 133 -* -----~ 1 X'1°51'61 ~u o 135 y ~-- ~ ~ ';;;, c 203

S" (F-4) v 33013-1891 33013-1890

' =i ~ x1s9Q9'-------~~ L!J x14'204s-------~~ " I

r--:r>

__... f----------#-,,--------,,11-------""-,,-- ----------ff,,-----< 33013~1sas I 0 I I 3/ 4-CH-151 ------... l;> 145 z39A ~NoTE 4 Pl 142 I 2-CH-151 "' 7 ~ A ~---l-'><~:1----1-'><~:1----I F t<:"7 2so8 i5oc Y-. z500 I ()

r I

0 ~ Pl I '\\._ FCH07A LEfDOWN DEMIN FILTER "A" 137 ~' ) COARSE MEDIA --1 ~ 250 RR v N

uz IMB
  • Xl5162

--,fl--;'+J ' "~ " ~ ~:: ~, 0 _fl_'-~-" OMB j33' IFcl '50-';:'. E---13_4_*__ TUBING


i

.. ------------11 3301;~~:;2-1 > ,,,, + " ~

  • - §

~ ~,~ i~ " 8 ', ff 'f<_"------~-~--()- _________ 1 2 CONTAIN~J~)SUMP A ff ~!~ ~ 1/ 2" 1/ 2" r1 ';;; );! "' ~------!::! ~ P112 = 1~. --~-----~< __ 3~3~0~1~3~-~1~2~4_7_JI ~ 2" ""T ' L-J

: 2-cf:i:!601 2*?

D !Loi 2-CH-601 1 1,1--'~::.;__.:;;;:..:.._ __ .,---.1......<---.1-i)"::i--t-:~ r--'--r-i::-:J-.--T-:-::.:.:......::..:..:..,----t:<<J----.....,1---'-----------------------.l---.,--------=-..:.:.:,:;.:..:..--------, RHR LOOP 204B 7"',, 204A J,~ 371 --n ,----~3,,,J~4~"--1'1' ---~3,,_;/~.4~*__, ';' 314* (F-7) TUBING 151 204E 1135 204C 2" . ~ o '< r tiJ I. 2 ~ ----1hr-' -~< 33013-1888 ~ TE I z lQJ ~ - ""; ~ !Fcl I CJJ ~

0)

~

~

I -* ------~ 1 x14°168S 151, l~ 0 sifi 130 8 ~ iii ~ I A s S ,.,, A s S (F-7)

u t\\..)

0 Q:! L ~ \\->-/ ~ r-!110 ::5 -..; )-!ff/--, ~ \\~I N Piil ~...,,_.,,_,ff "' ~-3-3-0~1-3---1~8-8_8_, - ~---2_-_C_H_-_1_5_1 __ ~ VOLUMECONTROL ~~§ r-.> 6 NJ_ v Qi£1tv VII v ~LQJg v II gj_ 1g~~ _JlX-14169S TANK [-~1---._J ! m 8 (H-l) -1 ~ ~a ~ ~ B ~ ~ ~a 348 ~ 3/4" is1D -I c crJ 3/4 ~ I ~

o ~

~-----<: 33013-1248 I I REFUELING WATER X820 I g g 0 I I 0 TE 127 Pl 138 1--... ---1.:: N.., 1i173E N,., ~ ~ ~.., 0 ~~~,,...... :- A ~ : b ~ --~TUBING I I N CO VJ fTll.) ()1 z........, f\\. N 14201S c:l ,, 1t I L 14201S1 (A-12) (lYP) !l 'r~@-c:.~¥<6h~-.;1f-l/,'-P-\\@-=::-<:,,,--3-3-:B-1 ~-~-:-~8-9-,: f15S08 LH.::c::<::::=~3~30~1~3~1~8~8~9~ 112A I ff 1X15807 PURIFICATION PUMP ~ ,b SUCTION I t)_ '- 5- - 5- -- CG-1 J 8 T**L* __ :~~~~:;_-_*_-_-__ B_J*.... --~~~~~~~~~~~~~~s_:i:_J-....._-.-~ (F-12 ff


11U--<< 33013-1888 H?<;J:::

33013 1248 '~ - I


~X14167S REFUELING-*WATER X821 PURIFICATION PUMP I

I (B-8) DISCHARGE I


*-*------------------------f __

3/~4_"-~<~-3-3-0~1-3---1~2-6-0--,~ ~-----~ X544 r---~---------.._~CH-2501 El u TC

~.,~~

ro I )> ~ -~--te @:1: g'~ m~ ~~ ~ 6 ~ I ~ I "'3/4"

  • 1
  • NOTE 4 Pl 6248 I

~I ~ Q.-;v>----rl-ff---; ECH02A REGENERATIVE HEAT EXCHANCER -'--.L.----'-----r:><l-41 298c ~ 151 301 ~') I "" 301 1151 (A-1) ~~..1--,---'----------'-!:><l--l:x~(J--J F rC:>I 249-249A ~ 2s3P. 248B .c/ / 2-CH-151 \\" '~ ~.. ~- 2-CH-151 2214 I 33013-1265 2

.(256 3/4-CH-2501 ------.,

3/4"

  • .Iv 2210 CH-2501 (1-1)

RR "', ) FCH07 u 253 RR °' LETDOWN ~----------1' DEMIN (F-3) --j 33013-1278-2 3/4-CH-151 X974 A (A-9) 2" 3/4" 33013-1270-1 :1------l l---"----' WASTE HOLDUP TANK (F-3) FILTER FINE MEDIA _,,..-~-~---.2-AC-601 -i-X~J---<, 33013-1247 ,r---------~ X822A (E-10) /,,,..--~-~-.,. - 2-CH-151 r-~.. 11--<~_:3~3~0~13~~18~9~1!._J I X14208S (E-4) 33013 1907 2" - - 245 I 0 I I I 0 I I RR 228 RR 2* I 0 I I

o ~' ~
o ~J JN I

0 I I 227C RR " J-

o N

!___ Al );!

  • 2"

{~-~-

229 RR 1: 230 RR 395 RR N I 0 :r I RESIN FILL THIS DWG. (H-10) L~ I 0 I I fCH01B LEfDOWN DEBORATING DEMINERALIZER B 1------ -- m (;:;;:;\\ n MANIFOLD "" .....-+~- ~o~ I (J-10) I 33013-1267 I I 2" Ll L 237C RR 2" 3* I 0 I I 236 RR i3a8 RR 2" 226C RR ~~~ 396 RR N I 0 I I -"' ~ I 0 I I ~ c-:. 238C RR RESIN FILL THIS DWG. (H-10)~ RESIN FILL THIS DWG. (H-10) L -' 1 r N (A I J L () I I TCH01A LETDOWN CATION/DEBORATING DEMINERALIZER A NOTE 6 3* 2-CH-151 I 0 I I ~ 0 0 0 0 (A-7) 0 '----,----1: 33013-1267 ~' )~ eves HOLDUP TANKS ~ I rn* o I T D en 2-CH-151 RESIN FILL THIS DWG. (H-10) ~ ~ u ~ rr=l N

  • rl£?.J I

fj=} N 7Jtt.i ) ~ lQ.I ~J.. ;uO>J ~ I ¥,__ __,_-_,\\[: 1-CH-151 --- 378 N I () I I E N I () I I TCH02 LETDOWN CATION DEMINERAUZER BED x 7 u 0 ~ I vi I I 0 N ~ 00 RR N I 0 I I 0 I () I I Ol - 2" 0 0 I 0 :r: I (B-4) ---~~~----,,. - f--1.,.1--< 33013-1891 1 x14312s 0 2" (J-9) -= 0 r-~* <~~=:J 33013 1266 2276 1'1oc IFCj BORIC ACID BLENDER rn ~ rn MANIFOLD ~I ~+- ECH03 EXCESS LETDOWN HEAT EXCHANGER '~ ~E ~~ 122 3/4" 311A ~3/4" I 12276 PT 121 '~


,lf'/---------11//----<< 33013-1887 ~

~----~ 1 XW40S ECH02B REGENERATIVE HEAT EXCHANGER CH-25011 (]-- ECH02C REGENERATIVE HEAT EXCHANGER iJ I ~1 01- "'I

~

'---,,,ft-------~,,1---, ~:~ ~11 I (E-1) L+/-2=1CHs:2~5~0~1-+--_J_-<:::::~~~~~]" 33013 1260 I - I X427 ~ -ri' ~ () -~- 1,'~ 2 i

F:

/j D G') II Ljf-ff------t,,f--<, " il;P\\ ~--11--l 1---~,'f-- ,:. ~ ff ff 3/4" ---~=.'IL i

  • 33013-1888 I X15l87 (F-9)

,,,,-----~~~.,, - L._-,,,/f-----.. lf--< 33013-1888 1x15188 (F-9) L----fl"L.----fl- "--<::=~~~~~=}* -- L _3_1_1_G_ ------------ I 0 LJf I 0 :r I ~ 2-CH-151 ~ __r-., 1 -CH-151.--.. 1---+-1 214 E RR TCH03B LETDOWN I I 0 I I MIXED BED DEMINERALIZER B /\\ 2" 2" N I () I I Ol I __['"- 1" - t--Y---'---,_._.,_ 1---1-1 222 E RR TCH03A LETDOWN MIXED BED DEMINERALIZER I ()

r I **'

Ol ~ A

== 1 <O

  • D ff 33013 1888

'xHllOs (D-10) I 33013-1272-1 REACTOR COOLANT DRAIN TANK TCH16 RESIN BATCH HOPPER ~---~3/_4_-_C_H-_1_5_1 _________ 1 (C-1) 33013-1265-1 (D-10) > I I I I '--------------------{, 33013-1272-1 (1-9) 33013 1269 218 201 0 QUICK CONNECTION COUPLER FOR RESIN FILL ON THIS DWG., AND DWGS. 33013-1267 33013-1248 33013-1276 r~~,'~ DETAIL-A c SA~ETY CLASS 2,3, OR SAFETY SIGNIFICANT (Q) RMW SAME CONTAINMENT AUXILIARY BLDG. NOTES: REACTOR COOLANT DRAIN TANK 1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2. THIS DRAWING SUPERSEDES PORTIONS OF 33013-426 & 433.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DEfAIL "A".
4. VALVE 145 AND 112A FAIL WITH FLOW TO THE VOLUME CONTROL TANK.
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES IS BASED ON UP-STREAM INSTRUMENT AIR/NITROGEN VAL VE. REFER TO INTERFACING AIR I NITROGEN DRAWING FOR SAFETY clAss.
6. LETDOWN DEBDRATING DEMINERALIZER A (TCH01A) IS BEING USED AS A CATION DEMINERALIZER. RE

F. PROCEDURE

S-4.5.10. RJM /'fl Afl. C'.gA. 5/12/14 ')*12-1'1 <;*f2*(1f. &:1>-ILJ 33013-1264,1 CONSTRUCTION LJMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION lYP. SAFElY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NONE CHEMICAL & VOLUME CONTROL LEfDOWN (CVCS) P & ID JOB NO. DRAWING NO. REV. WASTE HOLDUP TANK (J-10) <~_33_0_13_-_1_26_7~1-SPENT RESIN [~(~G~-~*10~)~==>-2~"'__J

.. ;;
33013 1248 (E-8) 33013-1248

~;; X794 -*--*---*-*---1 X791 EWR 3391E 33013-1264 TANKS CCD 01 CONTROL COPY # 1 I 2 I 3 I 4 I 5 6 7 8 9 10 I 1 1 I 12 A B c D E F G H ~ J

A B c D E F G H I J 1 (E-11) ~ x 0 ~ 0 s;; I Z

o

-<IF-< ~1~ 0 z 0 I I 2 JJ00 3 t' 4 N I 0 :r: I N 01 s N 5 ECH02A ECH02B ECH02C L3~3~0~1~3=-~12~6~5~-~2~,;>~--::::::-~~~r.:;;;t-~r;:---:;r:!?-~.l.----:;~;!-~~~~... ~i-~~-::-J X384B II 370B ~ 370A 362C S (D-11) 33013-1258 v s* 314 I PRESSURIZER f ~


~ RELIEF N

-I', 151 2501 TANK ~ E-4 33013-1888 REGENERATIVE HEAT EXCHANGER 6 7 2-CH-2501 I P108 L!J TC 3/4' ' ~ 1" 01 3/4-CH-2501 l--------~=---'---::_:_:_-=:...::...:------------------------------ (D-11) _J_J 33013-1265-2 ~~ - - - _ _=J I (F-12) s* PIPING !UBING 2213 TUBING PIPING MANIFOLD 3/8" N <D f'l 293F 293D 293G 293C 2505 2501 MANIFOLD --33.. co ~ 3/4' 385F 385G 3/4-CH-2501 3/8" 385D 385C 38 6 3-CH-151 IFcl 0 s:: l'l, llJ OMB IMB 3/4' t--l~-11 D 2214 2" Ol N )> N I 0 :r: NOTE 6 ~ PT (I-1) I -J><J-j 33013-1887

>:.-----HH-------,1~1-----HH------1/~1--

I X14141S=-------~ I N 01 s I I IX14133S (H-10) 33013-1888 (H-6) 33013-1260 COLD LEG LOOP A

t 2501 N,

2501 v-12194D 2505 N 01 s 01 00 co )> I 0 :r: I N 01 s ~ 2" X14142S t' N N llJ 3/4' lt--..14--'-----t 'I 318B 0 :r: I N ~ ~{ s (I-10) 33013-1887 f'l I ()) f'l I 00 N I 0 :r: 3/fS' 3/4-CH-2501 3/8" 2501 306B I MANIFOLD 293M 293L 2~3H 2~3-!._ 2505 2501 MANIFOLD 3 8" - 385M 385H 2505 385L 385J co 01 A NOTE 6 ~ PT 174 12195D 01 s 01 00 00 llJ 8 NOTE 8 D D N N s 00 D t' 9 OMB IMB 392A 9315 IFcl N ~ -...... 01 -I', OM.a..,JMil I <21 I 2" I 294 9314 [ill t' 296 9313 IFC I N N ~I s °' J_ 'I DOMB I IMB 297 <D ~~D 250*BING (TYP. 3 PLCS.) 10 (G-3) 33013-1888 (H-4) 33013-1260 HOT LEG LOOP B (H-3) 33013-1888 (E-4) 33013-1260 COLD LEG LOOP B G-3 33013-1888 (F-1) 33013-1258 t~~~'~"~' AS MAIN LINE

ZETY CLASS 2,3 OR SAFETY SIGNIFICANT (Q)

DETAIL A - TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS CONTAINMENT X14108S X14109S X14107S L ________ I 3/4" v 11---....._-f v 1 2501N.1-: VI VI E sl'-. s OTE ~1~~ ~~ N 01 s 3/4" l----tie------11 v 2221A I N 01 s IMB, i,OMB "'-""H:v) NOTE 5 N s Ol (D v N (J1 s - -- - ----;UXILIARY BLDG.- -- - v 1 N N N 00 v N 01 s N c gi z G) 2" 2" TC I I J_j102 383B N 305A 3/4-CH-2501 1----Jr-~-+---~---~~---~ 3/4" 2219 ID l-3-t/,.4._*-l~~ING 2218 3/4" 3/4' 9306 v 11---....._-f 2502 1 2" 302A TUBING SEE NOTE 4 IMS OMS 3/4' .-.t4-1IV 2222 1 1/2" __/ 3/4" ~ 250jl-~~l---~~-IHXl-t---'-r2=2,.2*3--ll V N 01 s ~ PVcJ01A 30~A -+------+--+--_,-<--> ~REAC OR COOLANT IMB OMS

i H

_rl s <MO RCP1A> 12193D ai N PUMP A 2501 ~ D i!i 2217 ~SEE NOTE 11 i---..-i-==-= - _I_ -N. I ~)> "' 3/4' 1 1/4" 3/4' I § I~ l-~*--11 D I <D I ~ M I~ ~ 16 v~ 3/4" 1/2" L --- _J 5 12193B TUBIN~02

J TC TUBING

--i-- 9304 ~2502 SEE NOTE 7 SEE NOTE 4 3/4" 3028 N 01 s 3/4' 2216 305B 3/4' I IM~ i ?MB 1 1/2" 3 4" 309B 2501 TUBING 3/4' ---- 12196D ~REAC~U~PC~OLANT IMS OMB 3088 I PRC01B * <M?J;;RCP1 B> - _L_D - t~-SEE NOTE 11 I ;::; N I ~ N::O I~ co I~ s::

0) rn (V)---1----2501 I

~

r:

I 0 L r---.*--J _J 5 121968 3/4'

J TC SEE NOTE 7 9302

~ 2502 TUBING L ___________ ~ ~0~------- - AUX~~;~NB:~~~ -- ---- --------~ ~.--- --- --- --- --- -_ _J 2 N, FT I 1-----1 :2.1-4:5;s_----1 l ~ I 1-----1-l2-1:4:7:B_----1 l ~ l ~ N I~ l N N I~ N I ~ ~ ID I ~ ~ 10 ~ I ~ ~ _J5 I ;::!

! _J5

~ 3/4' DHl---.... H 2225 g; "',-----t:-::i:r--_l__:_ ___ _ (FE\\___ N '.;\\ 2988+ ~ D ~- "' 2502 2505 12146D -!>; '----c:.c1 3 4 5 2224 N I 0 :r: I 01 s N (FE\\___ ~- 6 I 1----_12:1:4:9:s_----I I ~ I 1-----1 __,2-.1-4:8;s_----I I ~ rr I ~ I~ I ~ I~ fll N -ri N T'.~i

r*~

10 I ~ 10 1:~ ~ ~ _J5 I ~ ---~ _J5 1- --- 3/4' ~D 3018+ 2502 2505 3/4' 12149D 2-CH-2502 7 8 2" t' 303A RR v 303C RR 2502 299C 2502 c gi z G) N 01 s N 3038 N RR ~ ~ SEAL INJECTION rn J_ -!>; FILTER A N <!) <!) 0 D D c gi z G) N 01 s N 303D FCH09 RR ~ SEAL INJECTION FILTER 8 1 12161B 3-CH-2502 275 [ill 9 t' t' (F-11) 33013-1265-2 X289 10 1 1 1 1 12 NOTES: 1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2. REVISION "r/J' OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1265, REV. 8.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "1'.'.
4. SEAL WATER INJECTION, BELOW MAIN FLANGE. CLASS 1 RATING EXTENDS THROUGHOUT #1 SEAL HOUSING AND INCLUDES THE
  1. 1 SEAL.
5. #1 SEAL LEAKOFF LINE (FROM PUMP SHAFT). CLASS 2 ACTUALLY BEGINS AT UPPER FACE OF #1 SEAL, AND INCLUDES THE #2 SEAL AND ITS HOUSING.
6. DIFFERENTIAL PRESSURE MEASUREMENT FOR #1 SEAL, ASSEMBLY IS CLASS 1 TO THE LOW SIDE OF THE INSTRUMENT.
7. DIFFERENTIAL PRESSURE MEASUREMENT FOR THERMAL BARRIER, ENTIRE ASSEMBLY IS CLASS 2.
8. VALVE 392A FUNCTIONS AS BOTH ISOLATION AND RELIEF (250 PSID RELIEF SET POINT).
9. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
10. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
11. REFER TO DRAWING 33013-1260 FOR RCP CONNECTIONS TO REACTTOR COOLANT SYSTEM.

CONSTRUCTION LIMITED CONSTRUCTION: l>S NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES l>S BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCALE NONE CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING (eves) p & ID JOB NO. DRAWING NO. REV. EWR 3391 E 33013-1265 SHEET OF 2 A CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 3 (D-6) 2-CH-151 L-3~3~D~1~3=-~12~6~4:____;;.>-------:::-~~:;;---:;:;-;;;;;:;;;--;---;-~--------1 X2274 151 TUBING TUBIN'-"G-;..,_ (A-1 D) 33013-1274 X1673HYDROGEN SUPPLY MANIFOLD 1" 3/4" >------l 15l1~-2 -,~,H[~~(IB~-~ 7)~~:>~___:1~*--{J---1CL..:::.2'_'_-c*'.l------c 33013-1274 X1657 NITROGEN SUPPLY MANIFOLD -X*9'6~9-A,_;-3-3_0_1~::-~-;2-~-~---2---->------------'-1'_' _____ 1_8_"~M~ I TCHD4 VOLUME CONTROL TANK X209 (B-4) 33013-1264 (B-11) 33013-1270-1 WHT (A-9) 33013-1267 HOLDING TANKS 3-CH-151 1-CH-151 1-CH-151 3" 1" 3/4" 264B 3-CH-151 1" 264A (C-4) 33013-1891 X142D6S (1-6) 2-CH-151 L~3~3~0~13~-~1~2~6~6 _ _;;.>--':__::;..:_...:..::...:__-j X368 X271 (D-9) 33013-1266 (1-9) 33013-1266 1-CH-151 1-CH-151 0 0 0 4 1 " 1~1NG 3 4" - I ---"!--"'--I><~ ~259 I 3 4" 2" 255A 2" 1275D 2* 2" j 255B ~---!Ir-'"-:---~ 255D 1 "

0.

267 ~ 2" ECH04 SEAL WATER HEAT EXCHANGER 321 5 193A 3-CH-151 265 3" 6 2D5A 9!.5 I ~"' 1~5 7 8 (B-8) 33D13-1267 > HOLDUP TANKS (H-9) }-t><l-r~ r-----fl------<:::::~3~3D~1~3~-~18~8~9~~-i;;;;i;;--

J X15819 4D7F 151 v

'-"' 319B ~ (E-1) 33D13-1273-1 WASTE GAS 152 COMPRESSORS (G-3) 33013-1278-2 (C-10) 33013-2280 X16DOB f---'-----'--l F 1----1 315B RR FCH03 SEAL RETURN FILTER 315A RR (1-3) ~ .... *---133013-1270-1 319A RR SUMP TANK (l-1) ....-"-'--*~-----~-----------! 33013-1270-1 3/4" SUMP TANK J-1 33013-1270-1 SUMP TANK 3/4" 2-CH-2502 12153 313 ITl 9 10 3-CH-151 MANIFOLD 12154B -~4D D 3/4" N 384A 142 384B ~,; ~ ~"'-*...---~[fQJ"o~--[Q]~~~--__, 2 384C r----r.::<<:::r----1..... ----..:.....-------lli----------~ "1. 8" 281A 287 1> (G-7) 2 Q c! 286 3/::f J.... 112BT1 ~ 33D13-1891 X14307S (B-3) -.--.1

i 33013-1261 X357.___ _____

112B 4" ~ ~ 4;1 I r---2-£7>9('Bf"3'.L2--f/ 1 " 2244 1" 1" '-----------------'----'-----! 33013-1270-1 NOTE 8 <$><$> SCH16B l I 1"-CH-151 ~ t-'--,---~fV'Vi~I----,----------, 00 I 0 ::r: I N {)l 0 N ~ I 0 ::r: I N 01 0 N 8 281B 3" l.!.J D N 01 0 N -I c OJ z G) 1 1 12 NOTES: 1. FOR GENERAL NOTES, REFER TO DRAWING: 33013-2241.

2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33D13-1265, REV. 8.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
5. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
6. CHARGING PUMP CLASSIFICATION SC/2 BOUNDARY INCLUDES DISCHARGE FLANGE, MANIFOLD, DISCHARGE CHECK VALVE, AND VALVE SEAT. REAMINING PUMP SECTIONS ARE SS CLASS.
7. PIPING AT NOZZLE MODIFIED PER PCR 2005-D015.
8. PER TE 2D08-D019, EPDM OR CORRUGATED STAINLESS STEEL FLEX HOSE MAY BE USED. PER TE 2008-D019, EPDM FLEX HOSE END FITTINGS ARE TWO PIECE, BUTT WELDED, SEAMED CONSTRUCTION.

C-1 33013-1265-1 REACTOR COOLANT PUMPS (B-9) 33013-1890 --._..::..::...:.....:.......c..::..::..:....__J x 1 5954 (B-9) 33013-1890 '--------' X15955 X370B 3-CH-2502 (J-1 O) l....---{:;:e::}-..:..... _____ ~33013-1265-1 [IQ] 1" I (B-1) 11 a: 2502 33013-1870 ~1:1284 358 (E-11) 33013-1266 X348B L---------- (A-1) ~ X2253 AUX. BLDG. EXHAUST (F-1) 33013-1273-1 2251 1" OVERFLOW (H-3) 33D13-1270-1 SUMP TANK 1 N N 01 0 1" 0 2-CH-151 0 0 1-CH-151 0 0 I 0 ::c I ~ 01 ~ 1-CH-151 1----11~1 ------------------~ 1-CH-151 3/4" TCH05 CHARGING PUMP SEALS LEAKOFF TANK 151 TUBING '--De(l--'-:J CONN. FOR NITROGEN PURGE W/ PORT. TANK 0 ~-.-"'---~-------~ 22~7 ~ Q 1-CH-151 2 3 269 1" ~ 0 OJ 3-CH-2502 N 01 0 ~ 2 288 8" '~Q SEE~ (H-1) 2245 1" L_E:.~-----=~:=:_:.:..:.::___:i.~I._l.2.___j 33013-1270-1 8-CH-2502 1"-CH-151 399 1/2" D E--iJi> 407H "PCH01C CHARGING 3-CH-151 PUMP C ffiJ 1/2" ~ ~ g I~ ~1 1" G) s ~I 2246 (E-1D) 33D13-1891 '-------_J X1 5915 4 1" 5 3-CH-25D2 ~ N -;:,.p01 N 2 c..,.i_..ll _..Q 01 ~ 291 8" N c,, (H-1) t-: ~ ,-----'----..C 00 1----'---I 33D13-1270-1 ~ 1" 6

r: J_

226D 2261 <MO/CPLRP1 B> PCH02B CHARGING PUMP SEALS LEAKOFF TANK RETURN PUMP B 00 I 0 ::r: I N 01 0 N 6" 3" SCH11 N <O 0 3/4" 24" CHARGING PUMP PULSE DAMPENER 289 3/4" (H-1) ~--------'----'--~----'-------'---133013-1270-1 <MO/CPLRP1A> PCH02A CHARGING PUMP SEALS LEAKOFF TANK RETURN PUMP A 7 2263 8 3/4" (A-2) 33013-1267 9 ~-ow*~" Afi MAIN LINE / ( t SAFETY CLASS 2, 3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT DRAIN & TEST CONNECTIONS X2267 10 SEAL INJECTION FILTERS 1 1 REVISED PER ECP-11-000789 -PCN-02-036 CAO FILE NAME 33013-1265 2 CONSTRUCTION LIMITED CONSTRUCTION: Afl NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 3 i '13 Afl BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCALE NONE ONTA.'UO, t£W YORK AUXILIARY BUILDING CHEMICAL VOLUME CONTROL SYSTEM CHARGING (CVCS) P & ID JOB NO. DRAWING NO. REV. EWR 3391E 33013-1265 SHEET 2 OF 2 ~ CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 3 4 151 TUBING 1" 0 (H-3) D [o o o o 406 ° 405 33013-1274 SCHED. 40 0 0 0 0 0 0 0 0 1-CH-151 ° 0 0 0 0 5 6 (B-12) o --<o ~~~;\\H><J-33013-1268 X1132 0 Q 0 0 (F-3) 33013-1274 7 X1656L 8 9 10 3/4" (H-9) .__3_3_0~13~-~1_2_69 __ >~----11R**------l/ I 1 1 12 ~*~~* r z ~SAFETY ClASS 2,3, OR SAFElY SIGNIFICANT (Q) DETAIL-A 0 0 0 ) O ~------l----+--- 400 402 RMW 359A LCH07 401 403 0 0 o N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PCH01 <MO/BABTP> BORIC ACID BATCH TANK TRANSFER PUMP (G-3) L_..:3~3~0~13~-~1~2~7~4'.___,;.>--'--- X1656K 1 2" v E--t~--.!L;~--1 421 TUBING 151 E 1/2" y 1" LCJ 1/2" LOOP SEAL (J-9) j;i f---1=2:0.2~-.2-B_-_----1 "'1 bl N r o 01 ~ N 0 N N r -I ~022D-D N N 0 0 (l) (l) cl [JJ z 0 N 0 (l) [JJ N 0 (l) 0 FF I 0 I I 0 0 at 0 0 0 w D ol_____j"'~~~ 3" E E ~;::====:':j::l!__ __ L 1------~3C"j------jil MANWAY 0 ~i EHTRCH02A BORIC ACID STOARGE TANK A HEATER TCH07A BORIC ACID STORAGE TANK A x OJ ~ 0 2" 0 ~i-1~1~2~"--j--------1 \\ 1.s1 ~ ~112" 0 0 0 (l) 0 0 0 0 I () I I 0 <.n N N... N 0 D 0 0 1-CH-151 ° 0 0 (G-3) (H-3) 33013-1892 .--~-~--xX15844'--------' 33013-1892 (G-3) 33013-1892 X15843'--------" 0 2" 0 0 0 I () I I ~ H-3 0 0 [al ~ ___.._._, J 0 0 0 3/4-CH-151 1--~

  • .--;r-- s 0

330A 0 0 0 2-CH-151 ° 398B 0 r-t---~---i-12019B FF 171L 0 0 N 0 (l) 0 0 0 0 105 3.i'.4-CH-151 IIT:i f-11---l/-- s o33ogoo 2-CH-151 0 0 0 398A 0 0 0 0 0 ~ 0 0 0 0 2" 0 0 33013-1269 0 I 0 I I X15841 X15840 0 0 (H-6) 33013-1892 (H-6) 33013-1892 0 0 (F-6) -CX::l-J 33013-1916-2 X6305 '--------' 0 LOOP SEAL 3" N I I Ul I 0 I 100 0 RMW TIC 100 ~ 375B 18" HATCH 397 MIXER 0 N I 0 I I 0 ("1 1/2" >-----+---! 0 ~cl 322 3/4" TCH06 BORIC ACID BATCH TANK ECH10 --~ BORIC ACID BATCH TANK HEATER N 0 0 2" 0 0 0 0 0 0 0 0 2-CH-151 (1-1) 33013-1262-1 X827A s 0 0 0 0 0 0 0 0 0 h I-O m 0 0 0 2-CH-151 ° 0 0 2-CH-151 0 o I 0 I I 0 330D (H-6) 33013-1892 ~------~x 0 0 0 <.n (l) <O 8-CH-301 0 0 0 0 0 3/4" 0 0 I 346A TUBING e ,. 151 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N I 0 I I <.n ~ 0 0 N 0 0 0 0 0 341 \\LO/ ~ 0 00 I 0 2-CH-151 ° 0 0 0 0 0 0 o 2-CH-151 ° 0 342 0 !ill 2-CH-151 o 0 0 0 J_~ 0 -I (l) 330C (J-9) 33013-1269 c__:::::.::_:_:::__:_:='--/ 0 RMW 0 0 0 0 0 0 0 0 N o I 0 I I 0 0


~o 0

0 0 0 0 2-CH-151 0 0 0 0 TCH07B BORIC ACID STORAGE TANK B PT 108 0 0 0 0 ... 0 );I t---~--I-z 12020B

==r;I OJ N 0 01 ~ N 0 N 0 r -1 ~200 - D LOOP 1" (G-3) 1/2" r--"-~,._-----,::1 v 421A 3"

I 1 /2" SEAL w

1/2" 0 1 1 2" v f7l 0 0 0 EHTRCH02B ,__ __ BORIC ACID STORAGE TANK 8 HEATER 0 0 0 0 0 TYP.SAFEIY CLASS BREAK POINT FOR VENT DRAIN & TEST CONNECTIONS 3/4" 1/2" l--__.~f--D'.--3 359B CHEMICAL ADDITION SCOOP (D-3) 33013-1265-2 CHARGING PUMPS 1" 327 TCH08 eves CHEMICAL ADDITION TANK I 0 I Q ~ 12201 I 0 I I LG 2680 12202 (B-1) 1" 3/4" f----L/'l'-'----l*~f---'----ll---':LC'----__J'-tl*4--133013-1270-1 271 272 273 WASTE HOLD-UP TANK 0 0 0 0 2-CH-151 ..f>.-'1-IFl--~-l--f'>.d-~-l-~~~~~_.~~~~~~~~~~~~~~~~~~~~.....-~~'4---'I-. 0 0 0 0 0 0 0 0 0 0 0 2-CH-151 (H-1) 0 0 0 33013-1265-2 3 ° 348B 347 \\_ 348A 0 0 0 0 (l) I 0 I o I 0 0 0 0 0 0 0 ~ FCH02 BOfrLfE~CID 3 4" .__...._-IHD 349A Pl 154 t-> t----\\ N2 GAS!:i f'1 z t ~ co TCH53 HYDROPAD

i Q

ACCUMULATOR f71~ t----\\ ~ 2240 (J-1) 0 8-CH-301 °.-------, 33013-1262-1 151 TUBING 8-CH-151 TCH54 X827B NITROGEN TRAP (8"¢-3.5 FT. LONG) I 0 I I ~ SEE NOTE 4 1 /2" E--'-'-"'--1_ SC~. 401 "' "' '" 0 0 0 0 0 -' 350 w 351 Pl 6243 s 14300S1 348C l/P 110A 3/4" 0 N 0 CHARGING PUMPS (1-9) 33013-1269 353 [ill RMW (H-3) 33013-1892 ~-------'X15846 (H-3) -ir---r-<'--~3~3~0~1~3-=..1.118~9~2~ X15845 s 14300S2 NOTES:

1. FOR GENERAL NOTES, SEE DRAWING: 33013-2241.
2. REVISION O OF THIS DRAWING SUPERCEDED DRAWING 33013-433
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

I I Ul I 0 I... 0 0 PCH03A <MO/BATP1A> BORIC ACID TRANSFER PUMP A N I 0 I PCH03B <MO/BATP1 B> BORIC ACID TRANSFER PUMP B ~--~~3/f'+/-4'.'._" -J1--i1 0 346B s x ~ 0

4. VALVE 110A CLOSES WHEN BOTH BA TRANSFER PUMPS ARE NOT OPERATING, AS REFERENCED IN EWR 4375.

X6366 (1-1) 33013-1916-2 3/4-CH-151 0 0 0 0 0 s ----1..... f-----l (G-5) 2 1/2" [s~K~3~3~0~13~1~9~1~6,~2~>i:ii:~~~f---{ 15 PSIG PROCESS 6343 STEAM SUPPLY (G-5) SK33013-1916,2 CONDENSATE RETURN 1 ZHS191 1" 6318 324 z I Ul m N 0 0 0 2-CH-151 ° 375A 3" 1 1/2" 2" 1 2" 360B ~o 375C ECH011 N z I Ul 360A N ' 0 0 0 0 2" 0 0 0 0 I () 0 I I 0 0 o I ~o 336 2-CH-151 337 rr;g [QI 0 0 3-CH-151 ° 335 0 I 0 :r: o I 0 0 0 0 X1801 (B-4) 33013-1891 X14313S,__ _____ _,,. (D-3) 33013-1265-2 CHARGING PUMPS 2-CH-151 368 0 0 o N I 0 I I 0 (A-8) 33013-1261 0 0 l__-..~-11-- s 0 367 0 7 B-11 33013-1267 v X1103B Pl 6241 111 s (A-4) 33013-1891 (B-4) 33013-1891 x <O N <O 0 0 0

5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.

"' "' °' 0 363A 2-CH-151 2@' 2" (G-9) --1 FT t-n;.;;;:--1-i;;,;:1--<::.___~3i:l3>Q0.1.:13~-=.!:12~6~9~ 111 360 359

6. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
7. NOTE DELETED.

M 2-CH-151 0 1108 ° [IT] 0 0 0 0 o RMW 3/4" 0 2238 0 BORIC ACID BLENDER 1-CH-151 -;;~--7E----7E-'--l----'-....::.-'-.:..;:..:...._~-t:x::J~~-j 0 SCH01 (ENLARGED PIPE) o~---------~o 0 0 0 0 2-CH-151 0 0 0 0 0 109 ° 1-CH-151 ~ (D-3) 1 °' 33013-1265-2 I 0 I 0 CHARGING PUMPS (D-6) 33013-1264 X110C 0 0 :; N '

8. VALVE 2243 IS A PERMANENTLY MOUNTED TANK VALVE FOR NITROGEN GAS FILL/

BLEED. CAD FILE NAME 3P126601 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. '~ GINNA STA. R.E. GINNA STATION SCALE NONE AUXILIARY BUILDING CHEMICAL VOLUME CONTROL SYSTEM BORIC ACID (eves) P&ID JOB NO. DRAWING NO. EWR 3391E 33013-1266 CCD 01 CONTROL COPY # REV. A B c D E F G H J

A B c D E F G H J 1 1121D 1122D 1 " 2 F-10 33013-1272-2 REACTOR COOLANT DRAIN TANK PUMPS (E -11) 33013-2275-2 1-CH-151 3 1100A X1281W 1121 c 1103C D 4 AUX. BLDG. WASTE DISPOSAL PANEL 1-CH-151 1122C 5 4-CH-151 (F-9) 33013-2289 P/1 3126 3-CH-151 6 7 8 9 10 1 1 12 (C-1) 1-CH-151 -J:><t-t 33013-1265-2 X264A.__ _____ 4" 2" (B-9) 33013-1269 4-CH-151 1122A 1121A X1247A 1103A (D-5) 2" 0 ~~ ~zf~ D ~ 33013-1264 >>- 0--- 0--- 0--- 0--- 0--- 0--- 0 X254 (D-12) I 0 2"


...-----11 °

~L 3/4" (J-9) (F-7) (F-10) 33013-1265-2 <D °' 00 I () I I (JI TUBING 2268 2267 ABANDONED AIN PLACE (D-9) 33013-2289 P/I 3126 0 )> _c.--- en x -u. 0 III en r )> 0 r0 -u )> ::;: Z)> fTI en r---< fTI X1656J (E-4) 33013-1274 NOTE 9A (A-3)

o fTI "'

33013-2289 >--fl--~ :;:: "' __) ~ ~ P/I 3100 fTI 0 (1-7) 33013-1890 ~-----~ X7381 AUX. BLDG. WASTE DISPOSAL PANEL 14233J 1100B [!;Q] '--------' X2265 33013-1889 33013-1890 X15800 '----------- 3" C-4 33013-1273-1 ~ 33013-1268 >>------------- X1133 ° 0 ~V 0 0 3-CH-151 0 1133A" 3" 0 0 0 (;J 0 -1>- <D 33013-1890 1732B 1049 1661 c 1.. 1100C [ill X12018 ~ ~ 33013-1274 (A-8) -c><t-i 33013-1265-2 3" X257 1100D [1QJ 010 '::1----=--='--'=-- ~ 2-CH-152 NOTE 8 ~::::j:::::::-~~::::::::::t~ - -1 12016B ABANDONED IN PLACE D I I I I I I 00 z G) X15969 151 1101C NITROGEN 2-CH-152 (G-7) 33013-1890 (E-10) 33013-2280 X1600G (E-4) 33013-1274 NOTE 8 ABANDONED IN PLACE D (JI

r:

12015B 0 Ul r 1101 B 2-CH-152 (F-7) 33013-1890 (E-10) 33013-2280 (D-4) 33013-1274 X1656G NOTE 9 /\\ X1600H ABANDONED IN PLACE 12014B D -1>- r o 2" X1656H (D-1) 33013-1870 NOTE 9 A McI 2-CH-151 (E-1) ~ 33013-1870 ~ l--2_*_... t-~2_-~C~H_-~1~51.:__ __ 3-CH-151 TCH09A eves HOLDUP TANK A 1123C [ill AUX. BLDG. EXHAUST (F-8) 33013-2289 P/I 3125


~

___,..,..~_: I I 1266 zs~1---~~~~~---+I y 3-CH-151 A _____________ _] TCH09B eves HOLDUP TANK B 1123B !ill AUX. BLDG. EXHAUST (D-8) 33013-2289 P/I 3125


~

fil 11655 I I A _____________ _] -1>-, TCH09C eves HOLDUP TANK C 1123A 0£] TUBING 151 3/4" 2-CH-151 24* I MANWAY AUX. BLDG. WASTE DISPOSAL PANEL 2-CH-151 1125 24* I MAN WAY AUX. BLDG. WASTE DISPOSAL PANEL 2-CH-151 24" ..----------t~l---1--------:---~IMANWAY 1129 1114 2-CH-151-~-1 2-CH-151~~~~! -1>-, I I tl ~ ~~ ).. I tl .1. I SUMP TANK r " ~ :1 _ --- -- -- -- -- -~ --_r_ 3 _:u_ 1 ~~-_ 1 1 _ -- -- --~~l_ - - _i __ (E-3) 33013-1270-1 I (D-3) c5 I I 33013-1270-1 I I I (B-8) SU_M_P_T_A_N_K _____________ 3-_C_H_-_15_1 ______________ ~- ----------------------------------------~ --~I 33013_ 1270_ 1 > L _2-c_H-15_1 _______ 1 v J_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _J C-12 33013-1889 1 X15811 l E-12 33013-1889 v X15816 <O °' 1 1 2" PCH04B <MO/SFP1B> GAS STRIPPER FEED PUMP B s c III z G) WASTE HOLDUP TANK N 0 NOTE 7 361 RR PCH05 <MO/RP> eves HOLDUP TANKS RECIRCULATION PUMP 4" D 1/2" 2" (H-8)


<< 33013-1266-1 h?:::t-X365B (A-1)


JI 33013-1273-1 >

VENT HEADER (D-10) 33013-2280 >-M-- ~------ X1600J (F-1)


;~_33_0_1_3_-_1_8_70 __ >

I 0 :r: I (JI AUX. BLDG. EXHAUST TEMPORARY CONNECTION TO FUEL TRANSFER CANAL 1.. NOTES: C-11 12011 B 1-CH-151 33013-2275-2 PCH04A <MO/SFP1A> GAS STRIPPER FEED PUMP A 3/4" SAFETY CLASS 2,3,0R SAFETY SIGNIFICANT {Q) \\~~~~Ase~~ LINE I

1.

FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2.

REV. "O" OF THIS DRAWING SUPERSEDES PORTIONS OF 33013-427 AND 33013-434.

3.

EXCEPT WHERE OTHERWISE INDICATED.SAFETY CLASS BREAKS FOR ALL VENT.DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A". 0 0

r:

o D 0 1105 159 1107 _(FE\\ ~ VE~.--..__-~~-;;><f~-'------' 12013 1152 (C-4) 33013-1268 CONCENTRATES FILTER FCH10 151 (A-11) 1180 RR 33013-1270-1 WASTE HOLDUP TANK 1 1" I () I I 01 1" FCH04 ION EXCHR. --;, FILTER 3/4" 1708J 2

o ;;;
o (JI

(;J X1281P 1164 RESIN FILL CONNECTION ON DWG. 33013-1264 (H-10) 1163 RR ~ _;_..--cH-151 (D-1) 33013-1270-2 SPENT RESIN STORAGE TANKS 3

o-
o"'

co ~ f\\.) I 0 :r: N I 01 1167 RR TCH10B CATION ION EXCHANGER B 1173 RR 2" 4 (H-4) 33013-1269 RMW 1170 RR 5 1" N I 0 :r: I 01 1172 1176 RR 1146 1147 +-::1 1144A RESIN FILL CONNECTION ON DWG. 33013-1264 (H-10) CH-151 TCH1 OA CATION ION EXCHANGER A 1171 RR 2" 2" 3" 6 (H-4) 33013-1269 RMW

o -
o ~

01 CXl )> I 0 :r: I 01 1-CH-151 1182 I I RR I 0 :r: I 01

o
o 1183 RR 3"

<D (JI 3/4" s RESIN FILL 3" CONNECTION ON DWG. 1184 33013-1264 (H-10) ~ CH-151 I 0 :r: I TCH11 B BASE REMOVAL ION EXCHANGER B 1188 RR 2" 1-CH-151 1-CH-151 1" I 0 :r: I 01 1186 RR I () I I DETAIL A TYPICAL SAFElY CLASS BREAK POINT FOR VENT.DRAIN, AND TEST CONNECTIONS

o-
o <O 0

1" N I 0 :r: I (;J 1189 RESIN FILL CONNECTION ON DWG. 33013-1264 (H-10) CH-151 TCH11A BASE REMOVAL ION EXCHANGER A 1187 RR 2" (1-4) 01 Y~--~c 33013-1269 1192 RR RMW (J-2) 3"


<< 33013-1264 DEMINERALIZERS R

-~~~~~~-.-~;r:;-~-L-~~~~---=-----<~~(J~-1~) ~ 2" 33013-1264 DEMINERALIZERS 7 8 9 10

4.

EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR LINES AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/ NITROGEN VALVE. REFER TO INTERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.

5.

ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 1 0328.

6. 3/8" SPACER ADDED TO ALLOW VALVE REPLACEMENT V-1127 ONLY.
7.

PER TSR 2007-0187, eves HOLDUP TANKS RECIRCULATION PUMP (PCH05) SPOOL PIECE IS SCHEDULE 40 WITH SLIP-ON FLANGES AT BOTH ENDS.

8. LT-156/154/153 AND ASSOCIATED INSTRUMENT AIR AND CONTROLLER EQUIPMENT IS ABANDONED IN PLACE.
9.

N2 BUBBLER AND FF-156/154/153 H/L USED TO PURGE o, & H, FROM eves HUTS. RJM t1'f CAD FILE NAME 33013-1267,1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES IS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION 1 1 SCALE NONE AUXILIARY BLDG. CHEMICAL VOLUME & CONTROL HOLDUP TANKS TO GAS STRIPPERS {CVCS) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1267 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H I J 1 2 3 4 5 6 (B-1 :J) 33013-1889 X15810 '-------------- 1-CH-151 0 0 0 X1650 1116 0 0 0 7 LT 151 E 'l ,---121328 ---1 I t;; t;; I I'-" 0::1 L'J L_~_ ---- -~-J ~D i----.....-::i v 12134 12132D 8 9 AUX. BLDG. WASTE DISPOSAL PANEL ~--_J -~---7~-~ 33013-1274 1-l>/'I- '------___JX1656E 10 1 1 1 2 2" (F-7) 33013-2289 P/I 3124 rn ~ 0 0 0 0 ~ 0 0 FF 151H 1-CH-151 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 ~ ~-------~ llJ (J> PI 148 0 0 ~ 0 ° CH-151 v 0 1 0 0 0 0 rn 0 I +- ~ (J> 0 ()) rn v 0 (J> O> 0 0 I 0 OI I 0 0 (B-12) 0 s (1-8) (l-1) 1157 0 FCH05 1 BORIC ACID 1124C -{XJ-~I X15809 (E-12) 33013-2274 BORIC ACID EVAPORATOR DISTILLATE COOLER N <D (J> --f><)- 33013-2274 X1128Bc_ _____ _,, v -l><J-- 33013-1267 X1296 ~-------' EVAPORATOR CONCENTRATES FILTER 3/4-CH-151 (D-7) 33013-2289 P/I 3124 D AUX. BLDG. WASTE DISPOSAL PANEL PI 165 1" ~ 1-CH-151 1-CH-151 '--~12~8~~,B--1{2>2~6B,_..:.--,-~....L..--,.-!_,,' ~ ,l------.-----'--""'--'-"'..'..--------1~2~2~6~A--------'--"-'-'--'-':'...'---------....-~1~29~4.fD....L..-..1...--f1>29<~0}-,/--1 F FCH06 _./ ~ CN t;; -f BORIC ACID w~ N

-,~~ ;t;;

Q v* EVAPORATOR

i>

DISTILLATE Q 1-CH-151 1" 2" FILTER (C-9) c rn PI z 163 ° 33013-1269 RMW N I 2" 0 ,-----------------**--*~---------i 'f (1-4) 33013-1907 CAUSTIC MIXING TEE (E-6) 33013-1269 RMW (J-4) 33013-1907 X4887 '----------- 1215 2" 2" 2-CH-151 2" 1207 2-CH-151 N N 223 1222 ~ N N (J> (J> 1" TCH12B BORIC ACID EVAPORATOR DISTILLATE DEMINERAUZER B N N N.,,. s 2-CH-151 TCH17B RESIN FILL HOPPER B ~~ -~--- 1228 I 0 I I (J1 1273 CH-151 I 0 I I (J> (B-5) A (D-1) 33013-1270-1 WASTE HOLDUP TANK (B-3) 33013-1270-1 WASTE HOLDUP TANK 2" (B-5) 2,, N N G N N 'f 33013-1270-2 U> SPENT RESIN TANKS 1205 TCH17A RESIN FILL HOPPER A 1229 1274 CH-151 v N N '-1 TCH12A BORIC ACID EVAPORATOR DISTILLATE DEMINERAUZER A N G 1204 < 33013-1270-1 i-l---- WASTE HOLDUP TANK 2" 1-CH-151 ~------~-; (B-5) 33013-1270-1 WASTE HOLDUP TANK (B-3) 33013-1270-1 WASTE HOLDUP TANK B-3 33013-1270-1 WASTE HOLDUP TANK 1 1" 2" 1201 1200 2 .3 4 5 I 0 I I (J> s 2" (B-1) 33013-1271 X9137 '-------_,... 3/ ~-CH-151 (A-4) < 33013-1269 RMW PUMP SUCTION (A-3) 33013-1270-1 WASTE HOLDUP TANK 6 2" 2" 1239 [9 (N I 0 I I <D <O TGH13 BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK 0 0 0 0 CH-151 1210 3-CH-151 MANWAY EHTRCH03 BORIC ACID EVAPORATOR ~--- CONCENTRATES HOLDING TANK HEATER (G-9) 33013-1269 >>-------- RMW 2-CH-151 0 0 0 0 0 0 (G-9) 33013-1908-3 MIXED BED DEMINERAUZER 3-CH-151 1-CH-151 1" 1255 1 9144 N ~ I -~; ~ 'i! AUX. BLDG. tv N, WASTE DISPOSAL DISCHARGE FROM CHEM NUC SKID SEE NOTE 3 20" MANWA~ PANEL (D-10) 33013-2289 PI 3127 O> I 0 I I (J> N v I 0 I I (J> PCH07A <MO/HTP1A> BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK PUMP A ~~o --i-) 0 111 7 0 0 N I 0 I I (J> 0 1141A ~ PCH07B 1-CH-151 <M0/HTP1B> BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK PUMP B L__o--f><l---1-o-+----) 1143 1-CH-151 0 0 0 1132 0 3/4-CH-151 o 3/4--CH-151 l--Ml-----11 s 1131A 0 0 0 0 0 (A-6) 33013--1266 Pl 186 1-CH-151 2-CH-151 (A-8) 33013-1267 HOLDUP TANKS (D-6) X404 0 1------+1-------------1~'l-------~h~ 1 ----~< 33013-1892 20" MANWA~ AUX. BLDG. WASTE DISPOSAL PANEL (F-10) 33013-2289 Pl 3127 1.--~ l~1 I N I I I L@;)_cn_11_~ 01 I 0 I I v (C-6) 33013-1892 ___JX15836 0 0 0 0 0 0 3-CH-151 3-CH-151 N ()) 20" H--- MANWAY N I 0 I I (J> 7 3" 3" 3" TCH14B MONITOR TANK B SEE NOTE 5 N 01 3/4" 1276 ~----~---------~151 TUBING 1" 1238 3-CH-151 (B-5) 33013-1270-1 1" 2-CH-151 SUPPLY TO _ CHEM-NUC SKID SEE NOTE 3 WASTE HOLDUP TANK 8 PCH06 <MO/MTDP> MONITOR TANK PUMP 9 20"1 MANWAY TCH14A MONITOR TANK A f SEE NOTE 5 1278 ~----~---------~1s1.1 JUBING ~ N _J ~ 12281 (l-6) 1 1/2"


~-~<

33013-1270-1~ X1762A ~ (E-11) -R--j 33013-1271 > 1249 WASTE DISCHARGE ~ UNE (C-4) 33013-1269 1252 [9 ~-~CH-151 (B-9) X1250 NOTES:

1. FOR GENERAL NOTES SEE DWG. 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDES 33013-427, 33013-428 & 33013-434.
3. CHEM-NUC SKID EVALUATED UNDER EWR 4999A, SAFETY ANALYSIS, "CHEM-NUCLEAR UQUID RADWASTE DEMINERAL -

!ZING SYSTEM".

4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICETD IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
5. SEISMIC CAPABIUTY OF MONITOR TANKS "P:,' AND "B" UPGRADED UNDER PCR 2005-0037.

CAD FILE NAME 3P126801 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. '~ GINNA STA. R.E. GINNA STATION SCALE JOB NO. NONE AUXIUARY BLDG. CHE~HCAL VOLUME & CONTROL BORIC ACID EVAPORATOR TO MONITOR TANKS (CVCS) P & ID DRAWING NO. REV. .__,..__ __ ~... --=2: ___ M*--I 33013-1259 > 1256A ~-----~ EWR 3391 E 33013-1268 [QJ CCD 01 CONTROL COPY # 10 1 1 1 2 A B c D E F G H I J

1 A B v c D E F G H I J 1 20" MANWAY 20" MANWAY I 2-CH-151 1283 4" I 2 v q TCH15 REACTOR MAKEUP WATER TANK (SEE NOTE 5) Al SEE NOTE 6 1284A 2 s 1 2" 1--'-~=-:i 1/2" >--~-:i 3 1286 1-CH-151 3 4 5 (J-6) 3" ~ 33013-1268 >>----------~ X1239 1285 N I 0 I I X372 X381 X792 X374 X376 X4881 (J-11) 33013-1268 (I-7) 33013-1264 (J-4) 33013-1264 (H-1©) 33013-1248 (J-6) 33013-1264 (I-7) 33013-1264 (E-1) 33013-1911l7 (G-1) 33(1)13-1264 DEBORATING DEMINER. B 1261 X1252 2" 1 1/2" 3-CH-151 2" 2" 2" 2" '1' 2" I 0 :r: I (ft 3" X1214 X823 6 (C-5) 3311l13-12711l-1 WHT PCHlll8B <MO/RMWP1B> REACTOR MAKEUP WATER PUMP B 3/4" PCHlll8A <MO/RMWP1A> REACTOR MAKEUP WATER PUMP A N (C-5)

j

~ 3/4" 0

< 33013-1270-11,__ __ -l c m ~ z 0 <.n WHT (G-1) 33013-1268 (C-1) 33013-1245 N.... OJ 0 7 1-CH-151 2" 2" 2" 1241 8 N I 0 I I 1--~F-x"l-~..l.-...-.... ---1 <.n 1257 2-CH-151 1-CH-151 2" X11 lll3A X1245 2-CH-151 X1248 X1124D X5©8 X1683A X1682 X36Ql X1141A 9 10 2-CH-151 (J-10) 33013-1268 .:....:___, X1256A (A-12) 3311l13-1267 (E-1) 33013-1268 (J-1) 33(1)13-2275-2 (D-1) 33013-2274 (I-1) 33013-2274 (F-6) 33(1)13-1258 (B-11) 33013-1270-2 (H-1) 33013-1270-2 (H-11) 3311l13-1266 (C-8) 33(1)13-1268 2" 1246 I 0 I I <.n 1-CH-151 2-CH-151 1-CH-151 2-CH-151 2-CH-151 Tq,1--..,e--, 1141 1" 0 0 0 0 0 0 0 N (J) N N I 0 I I <.n N I 0 I I (I-8) 2-CH-151 © i-------------------+----------J -~-----'c__[__,_ ___ _, 144 i------3~8~71f-------------------------e----~-J 391 J Hlll1 (H-3) ~ 33013-1267 X1191 (I-6) 33©13-1267 X1176 (I-4) 33013-1267 X1167 (I-10) 33013-1267 4 2" N I 0 :r: I 2" 1------------1 <.n t' t' 5 X9134 X359A X353 X201 X3758 X217 6 7 8 33013-1276 (A-9) 33013-1266 (E -11) 33013-1266 (G-1 Ill) 33©13-1264 (D-2) 33013-1266 (F-5) 33013-1266 9 3/4" 10 2" [lJ 2" 2" '[ 2" 2" I 0 I I <.n 2" 1 1 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 3311l13-2241.

12

2. REVISION "Ill" OF THIS DRAWING SUPERSEDED DRAWING 331/l 13-428.
3. ALL PIPING ON THIS DRAWING rs NON-NUCLEAR SAFETY CLASS.
4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

A B c D E F G

5. RMW TANK (TCH15) HAD DIAPHRAGM AND H

ASSOCIATED SUPPORTING HARDWARE REMOVED /\\ 6. 00 1 1 PER PCR 2004-0003. SEISMIC CAPABILITY OF REACTOR MAKEUP WATER TANK UPGRADED UNDER PCR 2©©5-0©37. CONSTRUCTION UMITED CONSTRUCTION: AS NOTE:D PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BU!LT DATE RELEASED FOR FN:nnY GINNA STA. R.E. G!NNA STATION SCALE NONE JOB NO. EWR 3391E CCD 01 AUXILIARY BLDG. REACTOR MAKEUP WATER eves p & ID DRAWING NO. 33013-1269 CONTROL COPY # 12 REV. J

A B c D E F G H J 1 EQUIP. DRAIN FOR BORIC ACID STORAGE TANK B EQUIP. DRAIN FOR BORIC ACID STORAGE TANK A EQUIP. DRAIN FOR BORIC ACID FILTER (G-4) 33013-1276 X9121 '---P-OL-IS-H-IN-G-~ X273 DEMINERAUZERS D-12 33013-1266 (1-8) 33013-1276 X9127 '--:..::.__ ___ ...../ (E-1) 33013-1870 AUX. BLDG. CHARCOAL FILTER (J-1) < 33013-1272-2 AUX. BLDG. SUMP 2" c:l OJ ~ 2 3 4 (G-1) "' EQUIP. DRAIN FOR ,,_C ~ ~ ~ CCW PUMP A ~1-i:J " --C><l-l 33013-1250-2 X806D 5 EQUIP. DRAIN FOR CCW PUMP B 6 EQUIP. DRAIN FOR AUX. BLDG. EXHAUST FAN A I~ I (H-11) ~ (C-12) 3 4" I 33013-1259 ~. 33013-1245 I ~ X737c t 314:;--r 1-301 (E-5) X1749 EQUIP. DRAIN FOR ~I (D-12) I 33013-1245 I X806C CONDENSATE RETURN PUMP r-:;;~E~-;:5;-;;:;::::;-""-.;,3if4'~' :::::J--y >--'-------! I 33013-1250-2 -c><1--1 33013-1250-2 I ~ X737D J-6 301 I 3/4~ (G-1) ,.,.,-,~I ~I y EQUIP. DRAIN X737B 3/4" 2" I ~ FOR BORIC ACID I 1 TRANSFER PUMP A ~3".J I J-o EQUIP. DRAIN ~.. L_ W-L FOR BORIC ACID I TRANSFER PUMP B 3} 3~ BORIC ACID I _j I--' uBATCHING TANK 3" EQUIP. DRAIN FOR REACTOR MAKEUP WATER TANK 2" !--'-----! I 33013-1250-2 H><J-33013-1268 ~ I X806B J-1 1~301 J-1 2" 33013-1268 >--"-.i_---, I 33013-1268 X1204 I -...__:_::.:_:;:__ _____ _, X1273 X1203 3.. J-1) 1-1 2" f- - 2".----~~-'-i><J-33013-1268 33013-1268 '----==.:.::.._:_:=__J x 1201 X1216 1-11 33013-1271 x 1 7 84 L_.:_:_:c:.::___:_::.:_:__....... (J-1) 33013-1268 X1274 '--==_:_=:___.... H-1 2" 33013-1271 X2613,__ _____ X2614 (J-1) 33013-1271 3" 3/4" 1-1 2".-----"---'-'-----,-, 33013-1268 1-r'><'I>- -...__:_::.:_:;:__::_:;:__, x 1207 311*. (1-8) < 33013-1268 r,_,,2_" l-~I 1 1 MONITOR TANKS & PUMP I I s-5 I I I 33013-1259 11 '-.-. ----~x1277B --1_1 r-.. I 1r11/2 13"1..-11 3/,:.4-~C~-~6~-, L - 33013-1269 K><J-2" 3" X1277C X799A X783D (F-7) 33013-1870 HEPA FILTER UNIT G (D-10) 33013-1248 (H-6) 33013-1248 4-WD-151


t-- -1 I

A-5 33013-1890 (D-9)

tJ~~~~~=>-=~

3/8" 33013-1247 ~ X686K&L (D-1) 3* - '----<:......_~3~30~1i_.:3:-:_i1!_2~61~_J

-------~B-5~-------r-----------t l~t----:-- t l~t R~~~~~ ftJ~R I

33013-1890 (F-8) CLEAN X15984 CLEAN ~-..JI-~- C-10 33013-1247 OUT OUT --=--. I 33013-2289 RESIDUAL HEAT REMOVAL 2" C-8 33013-1247 c:l OJ- .--1---~ I HEAT EXCHANGER A :r-3.. P/I 3117 I ~ ~ ~ 1---,--------------~--T- ---- "'..+------f--1--~""'i ~ ~ z "' t;) 12191 w I 3" I + \\-<;+ + I + ~ I~ ~ ~* II~ F-2 Q RESIDUAL HEAT REMOVAL HEAT EXCHANGER B I ~ ~ TWD09 AUX. BLDG. SUMP TANK 2" CLEAN I 33013-1267 OUT I w X1070 I CLEAN eves HOLDUP TANK A I OUT F-6 L 2" -J----<:..._~33~0~1~3=-~12~6~7_J I X1271 '-------~ I eves HOLDUP TANK B 7 2" 3" 2" 3" 1791 (G-10) {~~;!~~:::::::>---!4'~'--1 --J.x.1-, 33013-1272-2 X1001 WASTE DISPOSAL I E-9 ,. y PANEL L2" 33013_ 1267 1 _1___ EQUIP. DRAIN FOR GAS 2" I X 1270 I STRIPPER FEED PUMP A ~----6(1---'L...L:..' --Yx!---J----i I eves HOLDUP TANK c I 1119 1120 I I g PWD06B 1-1 _;r*_ -,- - - - - - - - - - - - - --- - L-D--y EQUIP. DRAIN FOR eves <MO/STP1 B> + j + HOLDUP TANKS RECIRC. PUMP ~ AUX. BLDG. 1 1 . T EQUIP. DRAIN FOR GAS BWD03 G-10 33013-1272-2 X1073 0 1" ~] 1074 I SUMP TANK I STRIPPER FEED PUMP B ~ PUMP B I~ 11uB1NG I.!. ~~ ~ I~ 1018F I ~~3" r-1 I B-2 33013-2274 ~3"]--o GAS STRIPPER CLEAN EI OUT EL_i ~3"-------------3--D-- ~ 4 ::"J..n EQUIP. DRAIN FOR WASTE CLEAN H _j v HOLDUP TANK OUT El_ ---JI -INSIDE SPENT RESINROOM 3* r - --0 EQUIP. DRAIN FOR SPENT 4" RESIN TANK B EQUIP. DRAIN FOR SPENT (]- - --1 RESIN TANK A I 3" ,---0 EQUIP. DRAIN FOR SPENT RESIN TANK A (G-6) 1" --i:><t-1{~33~0~1~3~-~12~6~5~-~2:::::::>---------2...--( INSIDE SPENT RESIN R.:.O.:.OM::.:_ __ X280B (F-6) 1 * --C><l-l 33013-1265-2 X280A 1-6 1" --i:><l-l 33013-1265-2 X280C --C><l-1 33013-1265-2 X281H (G-1) _____ _j L__ 4" I 1" I I 3/4" E~c-r <::~_3_3_~-~--.:.-~_2_89 _ __:---~ 1

~

15-4 G-f P/I 3118 (J-1) 33013-1265-2 X2256 1-WD-151 (A-7) 33013-1870 AUX. BLDG. CHARCOAL FILTER 3/4" 1734 1737 NOTE 6 1" 1762 2" r.l 1792A 3/4" 1" 2602 1610A 2-WD-151 PWD12 <MO/WEFP> WASTE HOLDUP TANK PUMP ~ Y 2 ~*792 1/4" _.__ 122:0 I (A-1) 33013-1271 D X1782 ~ 33013-1261 X881A 2" 3" 2" I 1---IllillNG >~~~~~d~~---+-[-D---i 4~* 3 ~ 1-11 L'. 1 -"-f>.<l----t 11 /2"r-~33;0~1~3=-~12~6;8;---':;>--t><lf- ~~t[~~(~D~-7~)~~>--'--~31Li: 4":____--i r1 - 33013-1265-2 X282B I I 2" I


1 I 2*

3/4" 1-- c5ec,.N E---t-[-- _3~ - ~ (H-7) 3/4" 2" --C><.J--1 33013-1246-2 X2719 (E-7) -{;><f-j 33013-1265-2 X282A f-19> (A-6) 2" E 4" I L..:3:.:.3.::..01:.:.3-_1...;c2_64~>>------_;__-----t- '--(]- - _J NON-REGENERATIVE HEAT EXCHANGER 1 2 (D-7) 3 4 SEE NOTE 5 FWD03 ULTRA FILTRATION SYSTEM 1762AL f----. WD-301 0 0 0 1650 0 0 0 0 0 0 0 1769 1653 1654A 5 0 0 X12281 (A-5) -...__3:_:3..:_0_13_-_1_2_6_8__. x 1116 6 (J-1) 33013-1270-2 k 0 I 7 4" I ~ I N 3/4" 1 1 2" 4* 3" 8 (F-10) 33013-1273-1 J-10 33013-1273-1 (F-9) 33013-1267 eves HOLDUP TANK X1610C X1610D 9 10 1 1 4" 3" I~- -r-0--,- t (J-1) )_L::-*-~ 2*~*<::.==3~3~0~13~-~1~2~6~7:::J I I I I I ll'.~ (D-2) 2,, I _j v 33013-1264 >>---- 1--;:::+.-, I I 2..

':J..n 2"

2" (C-12) 33013-1273-2 GAS DECAY TANKS A & B (F-12) 33013-1273-2 ~ GAS DECAY TANKS C & D 4" I t j t I u __ ~ v I I I L3.'._ ____ :J-o 2" 1" ~----i <i-----:J 3" 2" 2" EQUIP. DRAIN FOR BORIC ACID EVAPORATOR CONCENTRATES FILTER EQUIP. DRAIN FOR ION EXCHANGER FILTER EQUIP. DRAIN FOR BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK EQUIP. DRAIN FOR BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK TRANSFER PUMPS C-1) 33013-1265-2 (J-1) 33013-1270-2 (1-8) 33013-1992 12 X1610B X264B FIRE PROTECTION X9239 (F-1) NEW G:Jrn I I N ' 1/2" 2" 33013-1.866 --...__:::::=::.....:=:;:__J X6320H (F-1) 33013-1866 -..._=.:.:_:c___:_o__~ X9980 FLOOR DRAINS LOCATED ON EL. 271 '0" SAFETY CLASS SAME AS MAIN LINE l SAFETY CLASS 2,3 OR SAF£TY SIGNIFICANT (Q) DETAIL-A ~w DRAIN, WHEN NEEDED, / TO HAVE HOSE. RUN TO N _J TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES: AB SUMP TANK TWD10 WASTE HOLDUP TANK FLOOR DRAINS LOCATED ON EL. 271 '0" 4"

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1270 REV. 4.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO INTERFACING AIR/

NITROGEN DRAWING FOR SAFETY clAss.

5. THE ULTRA FILTRATION SYSTEM IS rnrnrn~R~N;sA~~~;N;r;~rnrnrn 1-<;

I-<; I"""' 1-<; 1"""* I ' 1"""* 1-t; I-<; I-<; NOT AN OPERATING PACKAGE AND ALL SKID ISOLATION VALVES ARE CLOSED.

6. Fl-1007 IS NON-SAFETY CLASS AND WAS REMOVED FROM SERVICE BY TSR 93-024.

L __ l __ _l_

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

I----~---------~' CLEAN

i OUT 4" CLEAN

~------'--:J OUT 4" ~-'----'-'-:J CLEAN OUT

8. 4" SURESEAL INLINE FLOOR DRAIN TRAP SEALER EXISTS IN GAS DECAY TANK ROOM FLOOR DRAIN.

CLEAN OUT r.l 4" 3/4" 8 (D-10) 33013-2289 P/I 3117 3* CLEAN OUT r.l (F-7) ---<< 33013-1870 CHARCOAL FILTER G aJ ~1 re, ox, 0* ~ SAFW RM 10:;: ~ r-I ~"' r6 r6 FLOOR TRENCH 1 0. A........,-;::-' r4_"_+- - --_J"; - _J"; - _J "'; 4-AC-152 9 12198 WASTE DISPOSAL PANEL LI 1001 10 (C-6) 33013-1245 "------~ X732 (B-1) 33013-1891 REVISED PER RJM AJ c. AJ'C \\ 1 F ADC-14-001038 <-=--+--.--,--+-~~+--~---i 11/5/14 11/JI ti.{ II JI llf. tdn l"J l1llAWl\\I BY CHECKED BY RESP. ENO. CAD FILE NAME 33013-1270 1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED (8-1) PRELIMINARY NOT FOR CONSTRUCTION 33013-1891 BIDDING PURPOSES "------~ X15946 1-'/'.11 :'!" c.:'~Ll-------"AS'-"'su,,,1Lr,____ ____ +'--"'-'""'-l 1 1 DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE WASTE DISPOSAL-LIQUID WASTE DRAINS, HOLDUP TANK, SPENT RESIN TANKS (WD) P & ID JOB NO. DRAWING NO. REV. EWR 3391E 33013-1270 SHEET OF 2 ~ CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 3 4 5 (G-4) (H-4) r A[ i~~~~~===::>---lf-"----------i"'/-------------/f"'---- Q ~ I 33013 1891 11 11 II X14319S


Ii"'--<~~' - -

C-- 33013 1891 1x14:31ls (A-4) I 33013-1274 NITROGEN (C-4) -l><f1 33013-1891 H X15934 (C-7) < 33013-2289 I H P/1 3114 (E-3) A 2" L...:3:.:3:.:0..:.1.:.3_-.:..1 2::.7...:6c__,.->--_:::..-, X9133 I (1-3) A ,.--~~------.. 2" , I 33013-1268 >--.....::_-l X9143.__ _____ / (J-3) I 33013-1267 ION EXCHANGERS (H-1) '>--'3'-"-'-- 33013-1273-1 11----- (H-10) X 1~ 33013-1892 >>---11//-- (H-10) f697 -ff - -/f - -ff-2" 2-WD-301 2-WD-301 MANIFOLD . ~ 122278 D .. 12227D LT 1005 I 1684 16~ ~ 151 I C-2 I 3/4" .,...-, 3/4" ,-0 '~. *Ooo 0-1; '" 0 "' '" 1; FF 1005L WASTE DISPOSAL PANEL !(Cc - -LI~ LI 10058 1005 1005 I FF 1009L WASTE DISPOSAL PANEL ~I - -L2\\l MANIFOLD r-+-- - --+~ 12228s 1009 1009 I I LI 10098 122280 ~. ~" r---; 1 009 r---1 "~ l

  • .--~(*~--~7)_...

L....j 33013-2289 3-WD-151 P/I 3114 3-WD-151 ~..., 2" -/f - -ff- ~C[S:J __.. ___ -,,-- "'-*------.~---~ '1---~2~*--4:41689 N, 2" 1699 1698 -l><l-1 33013-1892 >>---ll//-- -/f - -ff-7 7 r---t - X14277S r--t- -- (H-4) - -,.------~,>- I TWD05A SPENT RESIN TANK A 33013-1891 X1432 JS-----'-----~/ (G-4) ~ 33013-1891 H " X14318s>--------~ (A-4) I 33013-1274 [---- [=---- (F-9) _Q zc ~,Vl 0-f'l 0,.,, 00 ~,~ 0-rO ,.,, r,.,, 1700 l -If-I 0 I ~ 1641 15112505 -;/4" ~

/8",

1~59() i6s6 (C-6) _.----~(D_-_4~)--,X15936 I* PT 1006 33013-1891 E-4) I 33013-1891 X15S3i 1'------~ PT 1008 ~ L:::-Jt. ..=~ -~-f---1~ 1642 I 2505 151 - 3/8"'...-... 3/4" 1691A 1691 (D-6) 33013-2289 \\._ o~,~ Pl rl 33013-2289 P/I 3113 ,~ 10068 --D3/4"~ iss4v ~ 151 2505 12299 " 10088,., P/1 3113 )1650 ....... rri PC Pl ,, "1z29~@ 1008 WASTE DISPOSAL PANEL --i ~ 3/ 4 ::..-c_ Ok -..J....- l...J 2655 2505 151 -:. 7 0 ~LJ 1-WD-152 152 ---,-151 1" . ~ 1658 r-------~' I '>-----------~ 1/2" :

1/2"

_6 6 I 33013-1269 r~ ~ 7~ 10F6E8

  • ,,,, r T.F.. -:~ **;* :

2" c-::.i


11~-----...----- -

1682 PRIMARY MAKE-UP WATER (G-4) N I 0 I z G) 1---1.Hi,!----( 122296 )> z N

  • 7 N

z G) ~ ~ '~ 1702 TWD058 SPENT RESIN TANK 8 1-- N i 0 I 6 _o zc (/)I_, (/) 0 ,.,, 0,.,, 00 CIC Q1 rn 0-rO ,.,, r,.,, I x :;:17 ~l :i 0 (/) N i 0 I 0 7 8 9 10 1 1 12 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1-WD-151 0 0 0 0 NWD04 .---4'.--1'--- ... j65 'ij J 2657 0 r\\/ II ~ 1799A 2660 r-1 2661 r ~ ! 3/4" 17998 ~ 2678 2662 1.~r -D "3/4" 17980 I~ 1]99(: 2664 r-1 2665 2666 rl.-- 7 2667 .._ 1"Y"' / II [..J 1798~ ' 112". ~ 2676 - 2668 r-1 2669 17990 2670 1..,,,r., -D 1 f9is 1---:J.. v 2672 -1~1"'!'

  • .,.__1-rl.--_. 7

\\ v 2673 0 0 0 0 0 0 0 0 0

J 1654!J

.J 1" - ~J---la---1 s 2651 ~tT' 'T -_.2~"-,.__-l~-------j',.,-~*.._ _ _,__~1-_W"-"D_-~1~5~1 _ _,_l __ ~~t--i-----~<::==~~~~~~ 33013-1269 1797 1683A 3/8" O.D. TYP. Ill rn -/f -


11.:*~ ---*--t-3 1798CUS 1799CDS

~ - ---;+-,;' - -/f 1798CDS 1799CUS --ff - -ff- - * - fl-- -:r = -ff- =-If .,"-----11-.. "----H-- ~ ~____,..._;~ 1799DUS 1798DDS 1 = = = = = --ff - * - * - 71#--,+r'/ - * -

  • 1799DDS 1798DUS
  • -
  • _.,,.,"-----,If-;' - * --II,,"~-------t~l--+3 17988US 1799BDS

~ - ~ -


1,~1-------#-,," -

-ff- -11"-----11-"----7"1--- 1798BDS 17998US 1799EUS 1798EDS -.-------+3 1799EDS 1798EUS PRIMARY MAKE-UP WATER (G-9) 33013-1892 "'---------' X 14268S (G-9) 33013-1892 '-------'X14269S (F-9) 33013-1892 '-------~x14266S (F-9) 33013-1892 '-------~x14267S (F-9) 33013-1892 '------~X14265S (E-9) 33013-1892 '-------'x14264S (D-9) 33013-1892 -._ _____ __,X14262S (E-9) 33013-1892 X14263S (D-9) o o:,::""'1;------,"'1-----~"'---- _,~.... ~.... 33013-1892 "_::_::.::...:.::__..:..==--' x 14261 s 0 0 0 0 0 N, 1l99E -D 179sl\\ 2674 1798AUS 1799ADS 1798ADS 1799AUS (D-9) 33013-1892 '------~X14260S ~rnc-~c PS MAIN LINE / t -t_ SAFEfY CLASS 2, 3, OR SAFETY SIGNIFICANT (0) DETAIL-A TYP.SAFElY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1270 REV. 4.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFElY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE INDICATED, SAFElY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO AIR/NITROGEN IN-TERFACING DRAWING FOR SAFElY CLASS.

~ 33013-1891 >>---lil/~-- ~ r 0 X14316S I (E-4)

-N-1 33013-1891

>>---ll-#--- X15939 (E-4) ~ 33013-1891 >>---lf//---1------j"f---o 1t X15938 I (1-10) Lu..... -*"--" I > " I 1 FC ~ 33013-1892 >-,,,.,~1 v68o' X1069AH1 0 ') 1069A 10698 ~ ~ D 122~9D L r#r-\\ w~__, .. ~r---<w 2-WD-151 '°'"""~ ~ STATION) I: ,~ ~ 12293 (C-4) -:--/---<< 33013-1891 f-rxi-- X15932 " I FC (8-11) 1 ...o1111i;;--..Q ~ 2-WD-151 33013-1270-1 11------~---------------------~------------------='----------' TO WASTE HOLD-UP TANK (J-6) 0 0 0 0 0 0 0 0 0 1" 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0


~-~----,, 0

~, 33013-1270-1 1f----------------------------~*-.--------------------------------------' X1654A 1 2 3 4 5 6 0 0 0 0 (1-10) ---11-#--<< 33013-1892 1--i><r: ~-----~X10698H1 0 0 0 7 8 9 10 1 1 /\\ EVlSEO PER RJM AJ"C. AJ'C crp~ M c-13-000390 l--'*/~2~6/~1-31-~~3"'0~/"l3+/-'i'!-i"J~o'°13+/-'1=;o~,,-1 CAD FILE NAME 33013-1270,2 CONSTRUC110N LIMITED CONSTRUCTION: "5 NOTED PRELIMINARY NOT FOR CONSTRUC110N BIDDING PURPOSES '-1.30 i3 AS BUILT AJC.. DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE WASTE DISPOSAL-LIQUID WASTE DRAINS, HOLDUP TANK, SPENT RESIN TANKS (WD) P & ID JOB NO. DRAWING NO. REV. EWR 3391E 33013-1270 SHEET 2 OF 2 Ah CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c 0 E F G H J 1 2 3 r c1-6) ~ I 33013 1270 1 i1762 I a 1 WO 151 A X9144 L NOTE 4 NOTE 4 (E-6) _r 33013-1268 '---~M~o-cN1=cTo'"'R~TA-,.,N"'"'Ks=-' 1 9137 L lNOTE 4.--~(_l-_3)~----. 1782 2" 1" 9105 --1'C:>l 2"...._1',.:1_*.---1-~<iif- ~ 9105 1644 A I x'§104, 33013-1276 / 1" r (C-6) ~ 33013-1892

>~-----~h'I-' --~

X7036G '------~ LNOTE 4 I CJ I 4 1765 I 1-WD-151 1764 I CJ I -"' - r (B-6) ~ 33013-1892 X7036H

>~---*H---

2-WD-151 2-WD-151 LNOTE 4 NOTE 4 (C-8) 33013-2289 '--'-'-'--'-----'-__J' P/I 3115 (B-6)

33013-1a92 X15835 fD-6)

A I I 33013-1 392 v X15837 ~v vf' 1" LK_r-..,_l-+-... '--- 1 (.._..! 82s8G -(}- --:J 1--1'-"--' 8259G 1" 151 TUB-TUB-151 I.. 3/4" ING, ' ~ ~.--'----. J-L 'I 1768 i-r_-~ ING 3/4" 112"v--~ -~1~~? ~ f-------1 TWD11A WASTE CONDENSATE TANK A ~J,l.--- - LI LI 1012 1013 N' 0',l TWD11B WASTE CONDENSATE TANK B

  • r------J

~IT ~.?~ ~:~T LIV' ~SJ t t ~~" t~-11-" -=::.J - __ __,,"~---~'* (LC\\_:" 'w I~ ~I'°' I (10~~B~' '~1o~~A i ~NOTE_3 WASTE DISPOSAL PANEL,,


,,11---

3f4" k L (D-8) 33013-2289 L_ '-----~,--- P/1 3115 v 2611 1712 Tl 11000 Pl~ 1 /2" 1018G SWD20 2" 0 I f--t-_,oM--S 2607 151 C-1 ~,) 5 1" 9138 1-WD-151 2" 1" 6 I FWD01 ACTIVATED CHARCOAL FILTER I 1 1 --.i.+T.....-- s 2640 7 8 DISPOSABLE MIXED BED DEMINERAUZERS B -}--- O> DWD01 t:'

  • A

-}-- i---..--i_~- 2636 DWD02 f-_....__s 2637 9 EWD11 WASTE EVAPORATOR DISTILLATE -COOLER r---- 10 NOTE 3 3/4" D u 3/4" l.J'-,J--"---'-------'-ll><l-_1,__ _____ _,__~-~*x::i---------'-----'-~--'~-.._,~---:3 i- -t.--' 2641 2632 263 i L!.J (H-10) I 1 " 2-WD-151 f---~,.-/~,'--.-----fr------------------------=-_:;_=--_:_::_;___ ___________________ -<, 33013-1259 I., 1781 X1743 I ~ I - 2-WD-151 (1-11) /,.----'---"-----, - - ,-----------------~---------~------------------<, 33013-1268 I, - ( I WASTE DISPOSAL PANEL (D-5) 1"- '-t i6oo .JR\\__, -

  • '~-" isoi 1

.~ -'\\ r'.. ) - --------i I I I RM-18 I ~ I LIQUID WASTE DISPOSAL ~ MONITOR SKID I " I 1 1/2" ~l

r: -'

FILL E~----J u t;)i I~ H 0,l.J A D RE 18* r:1 1 1/2" I I

Jt'-:::'..

I g~ t-; ~. --- - 301 12518F v "'- ~, ~ 3/ 4" fT1 Fl 7 ~I ~I MONITOR X1249 TANK PUMPS 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DRAWING 33013-420 AND 33013-423.
3. EXCEPT.AS NOTED BELOW, ALL PIPING AND COMPONENTS ON THIS DRAWING ARE SAFETY SIGNIFICANT CLASS. THE EX-CEPTIONS ARE:

ALL INSTRUMENT AIR AND NITROGEN LINES (NON-SAFETY CLASS) LC-1012A/B, LC-1013A/B, Fl-1064, Pl-1018G/H (NON-SAFETY CLASS) THE SAFETY CLASSIFICATION OF EWD11 IS FOR THE SHELL SIDE ONLY 2"- 1713 ABANDONED IN PLACE A 4. THE WASTE CONDENSATE TANKS ARE ABANDONED IN PLACE. BOTH WASTE J,-11.. -_~J ..r - 1

  • I 1774

~---~ 2 ,I 3 3/4" .:::--:. 3 I 4" '\\. *" v 3/4-151 I

  • CONDENSATE TANK PUMPS & MOTORS HAVE BEEN REMOVED FROM THE PLANT. MAINTENANCE ON ALL EQUIPMENT WITHIN THE NOTE 4 FLAGGED BOUNDARY IS NO LONGER REQUIRED.

Pl~ 1/2" )--:.!....'.:..-(::]-- 2610 / 2~ ~ - 1\\2-WD-151t, NOTE 6,;* 330;:-~)895 I....- (D-10) 1Xl4i20S

5. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS AD-JACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

1018H s SWD21 2608 151 TUBING

J,O"'

0 (Xl.

I:.

1" 1" __..., 2" i7s3 ABANDONED l IN PLACE FT 1 064,,.) J i6o5 1785A 1" __.., 2" 1" - 2" 1785 [@ !H-8) E-. "1 I 33013-1259 >- -; X l795KL-,~::..:.:c__:_:=.:.___..,. (784 (B-6) L-1,~1---~<~3~3~01~3~1~8~9~2=]: ::...: X15833 . le-:>

~ 12"1 I 33013-1885-2 1 ]958

> VJ 18 L... 18A 1L.:.:=~...:..::=--=-_/" [@ f' ~ J DISCH. CANAL f; f; NOTE 7 p P (B-3) I 33013-1270-1 WHT T t f*)1~ ~~ 1" 1" 1".J:>. 2" __.:.__ 2" 2" 1:>---1~-~w~D~--"15~1'----'----~*r---._~'--'--__1.-'-__.,.. _ __,_:_-{f-1c~~l--_.,~-'---.--'-'--------------------------~-----------~*------------------l: 33013-1276 1 1716 1.. 118 91o7 POLISHING DEMIN. (1-10) =i 1 - 33013-1259 2" '---------------~---------~------------------------=---<, J v NOTE 4 :::J 9146 4 5 6 7 8 9 10

6. THE LINE DOWNSTREAM OF 18 FITS THE LINE SPEC. 2-DW-151, EXCEPT IT JS SCHEDULE 40, NOT SCHEDULE 1 OS.
7. VALVE 18A IS BURIED AND SECURED IN OPEN POSITION.

CAD FILE NAME 33013-1271 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTEO PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES (5 AS BUILT A 1 1 DATE RELEASED FOR

ENGR, GINNA STA.

R.E. GINNA STATION SCALE NONE OHll\\RIO, NEW 'lQiK WASTE DISPOSAL-LIQUID LIQUID WASTE EVAPORATOR SYSTEM & WASTE CONDENSATE TANKS (WD) P&ID JOB NO. DRAWING NO. EWR 3391E 33013-1271 CCD 01 CONTROL COPY # 12 REV. A B c 0 E F G H J

A B c D E F G H J 1 (D-6) 33013-1864 1A AUX. FILTER KIDNEY PLENUM FLOOR DRAIN EL. 235'-8" (A-4) 33013 1863 CNMT. RECIRC. FAN B (1-1) 33013-1863 CNMT. RECIRC, FAN D (H-10) 33013-2278 z ~ FLOOR DRAIN EL. 235'-8" 2 FLOOR DRAIN EL. 278'-4" FLOOR DRAIN EL. 253'-3" ~---J 4" z FLOOR DRAIN EL. 253'-3" ~ ~----+ L------, I 4" FLOOR DRAIN EL. 278'-4" I I I I FLOOR DRAIN EL. 253'-3" I l I I "' I I 3 FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 274'-6" 2" FLOOR DRAIN EL. 235'-8" 151 4 FLOOR DRAIN EL. 278'-4" FLOOR DRAIN EL. 23$'-8" FLOOR DRAIN EL. 253'-3" 5 2" FLOOR DRAIN EL.278'4" FLOOR DRAIN EL. 293'-4" z 0 ;;: ~-+- 2" 151 ~--------! ' FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 274'-6" 3 8" FLOOR DRAIN EL. 253'-3" FLOOR 6 (8-6) 33013-1864 18 AUX. FILTER B KIDNEY PLENUM DRAIN EL. z 253'-3" s 4" N ' f'l (B-1) <~-3~3~0~13=-~1=8=63_~ CNMT. RECIRC. FAN A (A-12) 33013-1264 STEM LEAK-OFF FROM VALVE 0133 (8-6) 4" _,.c_ ______ ~-~< 33013-1863 CNMT. RECIRC. FAN C 3/8" [---< I ~ ~---_J L_.,._ __ 1 ____ :.::_j L - _!:l?T£_3 -


1.,..,__ -- -- -- -- -- -- -- I FLOOR DRAIN EL.

274'-6" 4" FLOOR DRAIN EL. 253'-3" FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 235'-8" 3/8" FLOOR DRAIN EL. 274'-6" 4" ~ ~ _s.:.,._ !_y_' - - -4:'.'._ - ~ L I 6" FLOOR DRAIN EL. 253'-3" (A-3) 33013-1262-2 STEM LEAK-OFF FROM VALVE 945 z 0 ;;: I I I I I I I I I FLOOR I DRAIN EL. 235'-8" I~ i - - - - - -- - L - -1 ,__6_" I ~ 1 I Q T I I 3/4" ..--__.,..-=-3*_* --+- - - - I 2-WD-151 >~-- -~~~--- --~~---------, ~~ t.... I I I I I I I I I~ I PWD19A z ~ FLOOR DRAIN FOR REACTOR f'l FLOOR I COOLING FANS I '-" DRAIN EL. EL. 235' -8" 235' -8" PWD198 <MO/VSP18> CONTAINMENT SUMP PUMP 8 N. <MO/VSP1A> CONTAINMENT SUMP PUMP A FLOOR DRAIN EL. 235'-8" I I I I L __ _ ITl ITJ LT 2039 3/8" 1:---1 I I N ' 7 3/8" [---1 u ' 8 2" 3" 3/8" t-'--:J 3/8" t-'--:J I I I L ___ J_ ___ _J I CLEAN OUT I I- - J L ___ J I 0 N 3/8" r--:J I I I I I I 3/8" i:---j (.N c 2" -i ~-+---!- I I ~ 1" 1" 2" 2" 9 3/4" 3/4" 1 0 (J-8) 33013-1260 A RCP #2 SEAL LEAKOFF X554 (8-4) 33013-1260 REACTOR VESSEL FLANGE LEAKOFF (C-10) 33013-1262-2 A SI ACCUMULATOR DRAIN X544A (E-1) 33013-1260 8'-RC_S_L_O_O_P_D_R_A_IN___, X540 (E-1) 33013-1260 B RCP #2 SEAL LEAKOFF X559 (F-12) 33013-1264 EXCESS LETDOWN (DIVERTf312 (G-12) 33013-1264 EXCESS LETDOWN (DRAIN) X3 l l G CLEAN OUT . _J C--J_ __ I_ f----. _J_ ___ _J FUEL TRANSFER CANAL DRAIN CONTAINMENT EL. 235' 8" _I - L - ~ CLEAN OUT I ?11 4" I (/) - () I I

r: (/)
,. T o_

(/)~ 10 I M I I NOTE I f-2.:_ _L6~ 1 1/2" 1" 151 _t ,-----'--'-=-------'!~ 1712 N 1716 OJ v Ol 0 <O v () D 1 " 1" (G-10) 33013-1262-2 10 8 SI ACCUMULATOR DRAIN X844B N

  • 2" (D-8) 33013-1258 PRESSURIZER RELIEF TANK 151 X527 3/8-WD-2505 1717 (1-8)

~ 2" 151 --- ' ----=------'-'-'----<< 33013-1258 ~ ~----~ X526 PRESSURIZER RELIEF TANK ~~ ,.)-,--~-~-~--~--.-~ LT 1003 I 151 I 1715 1714 2" TT 1058 TWD01A REACTOR COOLANT DRAIN TANK -i c ~ z TC f-~ 8429 [QJ OJ 0 4-WD-151 4" 8431 3" 1002 ~ ~ L_ s I 0 I O> - _J FL. EL. 210'-0" -+--10 J I __ _ 6s- - - - - - - - _J L - ~"- - _[_ - 6" 1 2 3 6" CONTAINMENT SUMP A 4 5 6 7 8 9 1 0 (/) ()

r:

0 1 1 ()I,, 0 c z x ". z I °' r f'l I o z 0 -l ~129 P123 12 3/8-WD-2505 ~~- (B-1) 33013-1272-2 GAS ANALYZER P143 4" 3" (D-1) 33013-1272-2 REACTOR COOLANT DRAIN TANK PUMPS (G-1) 33013-1279 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1272 REV.6.

3, ALL PIPE EXCEPT WHERE NOTED SHALL BE SCHEDULE 10S STAINLESS STEEL SEAMLESS OR WELDED ASTM SPEC.A312 TYPE 304 WITH SCHEDULE 1 OS STAINLESS STEEL SEAMLESS BUTT WELD FITTINGS ASTM SPEC.A403 WP 304.

4. ALL PIPE, DESIGNATED BY NOTE 4, SHALL BE SCHEDULE 40S STAINLESS STEEL SEAMLESS OR WELDED ASTM SPEC. A312, TYPE 304 WITH SCHEDULE 40S STAINLESS STEEL SEAMLESS OR WELDED, BUTT WELD FITTING ASTM SPEC. A403 TYPE 304.

X1716A X1655 X1721 X1728

5. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT AS PER SFEWR 10328.
6. ORIGINAL 3" SCH. 1 OS DRAIN PIPING FOR THE B SI ACCUMULATOR IS BURIED, SEALED, AND

/\\ ABANDONED IN PLACE. SEE ECP-2008-0044 AND ~ DRAWING 33013-2954 FOR DETAILS. 1 1 j\\ REVISED PER M ADC-12-001180 CAO FILE NAME 33013-1272, 1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCA!£ JOB NO. NONE WASTE DISPOSAL-LIQUID RC DRAIN TANK (WO) P & ID DRAWING NO. REV. EWR 3391£ 33013-1272 SHEET OF 2 ht CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 (B-3) v 33013-1890 X15986 >-----..,'/-------.., N / X1608 (D-4) 33013-1274 (A-12) -C><t---1 33013-1272-1 X1716 (B-12) -J~><t--1 33013-1272-1 3 4" 152 1" 1716A 8 Pl 11023 PC-i~__Jl,.:-;:{Xh 1016 1014 2* 152 ~ u; N L!.J TC ~ z 2505 3 c ID z " 1713 1793 [ill X1717 1655 2505, 151 X1810A (D-3) 33013-1247 (C-5) 33013-1890 X14282S.__ _____ / 6" 151 (C-5) [~33~0~1~3~-21~89~0~=::>--------!f-------i X14284S D 3" (B-12) 4" 3" 4" ~3~3~0~13~-~1~2~7~2~-~1=::>--~---l~---[1-----l'><'l----i~-------L_, X8431 1721 (E-4) 33013-1248 FUEL TRANSFER CANAL DRAIN (D-5) -1><1-j 33013-1890 X14281S [jJ [E9 3-WD-151 1722 [ill r~ D

>=~----------~u----------------ffn-I 0

I 3/4" 4 1787 [E9 ITl 3" NWD07 SEE NOTE 5 s 5 17AAI ~~ v T 17~1 [Eg~ PWD10A <MO/CDP1A> REACTOR COOLANT DRAIN TANK PUMP A 6 (C-3) 33013-1890 B-3 33013-1890 D-3 33013-1890 151, 1.2505 BWD05 Pl 1018A X14289S X14285S X14290S 2" 151 f-----llf-----l'-..J-----'"----.--'"'-'-~~-_.L_--t*'.l~-, s w D NOTE 11 1724 1725B 1726 N ' 1724B 2" 2* 7 8 152 1675 3 8"-2505 1020 151 601 1811A 151 601 1811B 9 (G-1) 33013-1273-1 (G-10) 33013-2280 10 X980A L-. _____ _,- X1600A (A-7) 33013-1247 >-tx:J--- ~----- X1812A (E-7) >-tx:J--- ~----- X1812B 33013-1247 ~ (C-4) 6"


___ ------------~6_-~W=D_-~1=5~1-----------t------l>------<<:: 33013-1247 151 f-c><r X1810B (D-5)

~ 33013-1890 X14283S >~----,~Y---------~-----+rH------~--- (A-7) X14295S [~33~0~1~3:-21~89~0~=::>----H---------------,!f--------------i EX.FLOOR - DRAIN BOX SEE NOTE 6 S.S. BOX ~ I tWA~tlNG PUMP ROOM SUMP PUMP PUMP LOCATED IN FLOOR DRAIN I *- 1;2* x 11;4* ~ SCREWED '--'--:;=l)~:'_-S.S.REDUCER (E-3) 11/4" PVC-I.__ ____ 11; 4* PE ~ 33013-1279 >>--------------t X1723 (E-10) 2-WD-151 NOTE 3 33013-1262-1 >~-----------------~ SAFETY INJECTION PUMP B (C-10) 33013-1262-1 SAFETY INJECTION PUMP C 2-WD-151 NOTE 3 1001 N I 0 I ~ v T NWD06_/ SEE NOTE 5 10~ 2" 6" 4" 1/2" s PWD10B <MO/CDP1B> REACTOR COOLANT DRAIN TANK PUMP B N 1725 3/4" l~I~ 151 J1016A 3-WD-151 2" 2" 2" 2" N ~1708':.l "; ~ 1727 B-10 33013-1262-1 SAFETY INJECTION 2-WD-151 NOTE 3 EQUIPMENT DRAIN 1" 6" 11/2" (/):;'. ;;E (/)'.;::

  • NOTE 9 PUMP A PWD20 CONTAMINATED STORAGE BLDG. SUMP PUMP 151 151 NOTE 3 ID(/)o I r-io g~z ~

(C-6) . i!) ~ I EJ [~~~~~:=::>----t-_:2r" ____ -l"' z -t:><J--l 33013-1247

i:;

X711B X711C RHR PUMP B o (F-6) 33013-1247 RHR PUMP A 2* E 2" (C-1) ~-- SUMP TANK 1 3" 2 RESERVOIR FOR 151 (NOTE 3) CONTAINMENT SPRAY PUMP B EQUIPMENT DRAIN RESERVOIR FOR CONTAINMENT SPRAY ~PUMP A 1" 2" 151 NOTE 3 I

ii 0

I ~~-----~--~---'----!~ 4" T p 2" 2" TRENCH J-lct--=---------------------~~-. DRAIN 1780 NOTE 10 ~ el ID 5 WATERBOX----~I AUX. SUB. BASEMENT EL. 219'-o" 4-WD-151 3 EL 232'-3" ~~ o SEE g* NOTE 9 3" 4" 4" 6" ---3 4 5 1" SEE NOTE 9 ~I~ ~ 1 LWD03 1 D 6 2"151 11 4" N 2* SEE NOTE 6 7 3* ~x :r 0 r N LS 2043 3-WD-151 2-WD-151 2" 1" 1073 4-WD-151 (B-8) 33013-1261 (D-8) 33013-1248 (A-2) 33013-1267 HOLDUP TANK (F-1) 33013-1270-1 (E-6) X1733 X798B X1100A X1707 151 '------------------133013-1270-1 PWD05A <MO/ASP1A> AUX. BLDG. SUMP PUMP A PWD05B <MO/ASP1B> AUX. BLDG. SUMP PUMP B 0 L 3 4" N WASTE HOLDUP TANK (J-1) 33013-1248 SPENT FUEL POOL PUMPS FLOOR EL. 219'-0" AUX. BLDG. SUMP 8 9 10 1 1 12 ~=- AS MAIN LINE ~ l ~ SAFET CLASS 2, 3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1272, REV. 6.
3. WHERE NOTED, PIPE FITTINGS FOR SMALL BORE PIPING SHALL BE SCH. 1 OS SEAMLESS, BUTT-WELD PER ASTM A403 TP304.
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN

& TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCOR-DANCE WITH DETAIL "A".

5. NWD06 AND NWD07 ARE A "WAFER-TYPE" STRAINER WITH 1 /16" NOM.DIA.

RODS WELDED TO IT AND USED TO SUPPORT A SCREEN.

6. SUMP PUMP IS INSTALLED IN CHARGING PUMP ROOM FLOOR DRAIN BOX AND DIS-CHARGES ANY OIL SPILLAGE THRU A 11/4" DIA. POLYETHYLENE PIPE THAT IS LOCATED IN THE INSIDE OF THE FLOOR DRAIN PIPING SYSTEM. THE PIPING EXITS THE EXISTING DRAIN SYSTEM AT DRAIN BOX #2 AND TRAVELS OVER THE FLOOR TO THE HATCHWAY OF THE RHR PIT AND EVENTUALLY TO THE AUXILIARY BLDG.SUMP, LOCATED IN THE RHR PIT.
7. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED UPON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
8. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT AS PER SFEWR 10328.
9. THESE DEVICES ARE SAFETY SIGNIFICANT FOR FLOW RESTRICTION AND BACKFLOW PREVENTION QUALITY REQUIREMENTS.
10. CONFIGURATION CONTROLLED PER SAFETY ANALYSIS OF EWR 4764.
11. 1 1I4" STAINLESS STEEL RESTRICTION ORIFICE TACK WELDED INSIDE PUMP CASING DISCHARGE FLANGE.

1 1 M REVISED PER RJM AJ c. A TC

  • 1 t-OC-15-000242 1--'~___,ec...."--T-+--T"-T-c-t-"7-~-t 3/31/15 3 "

15 3 31 )5 3/., '" CAD FILE NAME' 33013-1272 2 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 5 31 /5 AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION JOB NO. EWR 3391E NONE WASTE DISPOSAL-LIQUID RC DRAIN TANK (WD) P & ID ORAWING NO. 33013-1272 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

.A. B c D E F G H 2 (!J-::} I J~1J-12~1 ):.-~~~~~ eves t!Oi..DUP TNC;.;s {E-!} ~i.!:.~~~-i/>-~~~~~~ SFEUTRES!N ~JOH<\\G( !.Al':KS 2 3 3 4 5 ti 8 9 10

    • t-------***-u***--*-*--*-**---ff*-**---**--**--r----*---G~~~:J;;~5 1--~*-**~~~~~~~~~~----;J~1J~~;J-2 ;~

4 5 6 7 8 9 10 12 NO:IZ5: 1 na 1;Et.;£FAL NOlru m:n:R ro n:tAwitm !1!1013-1241.

2. nus ~R.t.Wlt:G Sl!P£R'..ilOCS P..::1?t10t-S Of 3301l-12"1J RtV.B
l. fOR MATERW. SP[C. IN iHIS MEA SEE J:1,lft'I~ 0-JSJ-525 P.E'W.1.

'4. OcurlWti[fif:D'!liOM'l.'ii::tf.lli:AT(D'SN"ElY Cl,.ASS UiH:i'Jfl.Al EXctWICffi 'SNETY Cl>S5 INDICATU'l f"C.ISC Si-'EU.SIDEG<<l..'f.

6. OCEPI WHERL omOM15[ ttmr:.-.m>. WETY Cl.ASS F'OR iN5TRllJIOfl A:R MID Nr.TiOGE.'l UNt'S/COMPONIJlT'S IS 6'SCO 0!4 UPSl:IEAM 1Nh"TNUME.NI IJH/NITHOrn'.N \\'...,,.\\'E. Rffffl TO

!lfl'f.RfAQt-.'G Ai>>iW!RL>Gf.N ORAW!t4G H>P ~~U'fO.~ J. WCiHIC' uororc flf\\I~ FOO MECl"\\Ah:CH..

QUIF-lilENT AR( [)tp;c
ra> !t4 8FiAO:Ka5 AA:J.CENT TO ~ECHAN:CAL EC1.;IFM£.'t"i PER SfF.Vrli 103.28.

~--1/'4 CL-300# FF f'l..JJlCE IHL£T/iJun.£f OE\\~TES FR0'4 UHE SPEC. kt. ""1TTYCV.OS...., ll!irl1NE 2~~'~ a>U(~ lW.sr.sETY ctAss~W"K:~r F~ vwr DIWN A TEST CONlfECTIONS 11 WASlf. OOiPO!W.. - GAS (1(J)

-~~~r~~~;~!--~*;;-1-1 GCO 01 i CONiROL CoPY ii 12 B

c D E F G H

A B c D E F G H J 1 (F-10) 33013-1871 (F-5) -t><J-1 33013-1889 X14244S (G-7) I I 2 /J REUSE 3 2-W0-152 1" 1618 [ill 1" 1630 X 1~ 33013-1889 (D-10) -t><J-1 33013-1889 X15814 (G-5)

>~--~n,_ ____ _

-t><J-1L._3_3_0_1_3-_18~8~9 __ :>>--~h~'----- X14248S (D-10) ~ 33013-1889 X15815 (F-5) >>---11-"---- It -t><J-1L_3_3_0_1_3_-_18_8_9 __ >>-----"H------ x14243s (G-10) I.33013 1273 1 1" (8-10) < 33013-1273-1 '-I ~3~1~4--~w""'D--~ 1 -"' 52"-- (G-5) -ff -ff - -ff - -t><J-1L_3_3_0_1_3-_18_8_9 __ :>>--~h~' ---- - if- - X14246S (D-10) I-- x~ 33013-1889 > H if- - (H-5) -t><J-1L_3_3_0_13_-_18_s_9 __ >>--~n~--- x14249s if-(H-5) -t><J-1 33013-1889 >>----i>//'------ X14250S (D-10) ~ 33013-1889 >>----1/,1-' ------ X15813 (G-5) -t><J-1L_3_3_0_1_3-_18_8_9 __ >>--__,/~/------ X14247S ~-9) 171 ~ 33013-1889 >>-----Jh+-' ___ __,,fl'- X15821 ,ie _r-PC 0 (!)' v II 16068 II ~ 1037A II V'J 1629 1606A 1036A 1620 [ill 1632 JJ JJ ~ 1" n_


i..x-J

~ 1606D 1039A I C---' 1626 II I ~ 1625 1-WD-152 1" II I ~ 1628 ,--., 1-WD-152 1619 [ill II REUSE I' 1631 II JJ 1" y 1606C 1038A 1" II I ~ 1627 t-----:L~ 3/4" 1022B .. JsL,<§~ ~~ JJ o'~ 16'oio~~"~"' ~ ..p..: Ul <µ, N O>> --j ~ c O' 7 Q:! 0 z "':. ~ G")

>---3 1039 4

II JJ ,,~T 1711 I " ~~Q+--#--11-+---11--,,- 1607c 0 "' ~:o"~~ ~ --j 017 c 0 -1':1 > z z "'--:1 G") ---11--1 P°T\\ ~038) 0 11.. T ~ 1048

..,_Jr+----1~1------~11-----

r::- t.:: lf __ 711 1048A (F-9) ~ 014' t ~ 33013-1889 >>-------11n--------Jh"-' ------ X15820 l!.l 2-WD-152 .J ~ .----!../;.....- ,--f1,.XJ-- 1659C 1656C ITRLI .J ~ v I v """1 16590 1656D jTRLI CD Z r --l om G") ;u 1-WD-152 SWD08 ~ 3/4-WD-152 -cJ-5 CD )> 'c ox

p.

1624 ?1*jL--=2~*__, JJ 1-WD-152 I H II 6 (F-3) ---,11-r _JI 33013-2289 > P/1 3120 JJ PC 1037 A/8 E-+----fl"~--l Pl II 1037 WASTE DISPOSAL PNL ~ SWD09 ~ 3/4-WD-152 <}-- ,,"1------1-- if- - 1-WD-152 I (D-3) r--1111"~----1: 33013-2289 P/I 3120 PC --fl- ,,---'----IH,,---,----/, ,,"1----l 1 03 6 E--'----1,~1--,--1 A/B Pl 1036 WASTE DISPOSAL PNL SWD10 Ji 3/4-WD-15<r-1622 l1'i'---=2~*----' II 1-WD-152 if- - I I I 0 0 0 I I I ~ ~ ~ N N N SWD11 ~ ~ I 0 I ~ N JJ N (F-4) 71 l 33013-2289 L_ _____ _/ P/1 3121 PC --1,;1--*~--ll-lii-~---111"/-----I 1 039 A/8 H L II Pl c:--'-----1,,1----1 1 039 WASTE DISPOSAL PNL (D-4) I 33013-2289 > P/I 3121 PC


~,,"f-----L-~,,"i--.J.---~---11-~---J 1038 A/B Pl E--'-----1,,1----1 1038 WASTE DISPOSAL PNL 7

8 1 WD 152 1-WD-152 SEE NOTE 3 SEE NOTE 3 SEE NOTE 3 SEE NOTE 3 (1-7) I 0 I N 0 0 rn 0 ~

u 0 0 ;;
:

0 0 ~

u 0

0 ;;:: GAS DECAY TANKA TWD14A 1-WD-152 9 3/4" 3/4" 3/4" I I 0 0 I I N N 0 0 3/4" GAS DECAY TANK 8 TWD148 1-WD-152 1-WD-152 10 ~ 1" 1638 ~ _J 1" 1637 1646A 1646B 1 II c--(J--~ . ~ 1645A 164SB 1" 1640 1 " 1639 I 0 I N 1 1 12 2* (B-9) -~--------1133013-1270-1 > (8-4) 33013-1274 I 1685 NITROGEN GAS DECAY TANK C TWD14C GAS DECAY TANK D TWD14D II JJ 10398 // 103sB II 1-WD-152 1" 1648A 1648B (B-9) 2.. 2" E---t---=---------1: 33013-1270-1 1-WD-152 1" 1647A 16478 I I 0 0 I I N N 0 0 (A-7) H < 33013-1889 ~BS (8-7)


i/11-' -~< 33013-1889 ~

~-----__J X14240S (B-7)


,~1--~<:"~_3_3_0_13_-_18_8_9_~~

X14241S NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1273 REVISION 8
3. PC-1036 A/B CONTROLS VALVES PCV-1036A AND B IF WASTE GAS TANK A IS SELECTED FOR PRESSURIZING. TANKS B, C, AND D HAVE SIMILIAR PRESSURE CONTROLS.

A SECOND TANK CAN BE SELECTED FOR STANDBY.

4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
5. DEAD LEG TEE INSTALLED.

II if- -ff ___,/11-/ ____ ____:__ij! ~ ~ I 014H1 15961 14233K I < 33013-1890 H?:9:- ~-----1X7381 ~ r------**----~ - 103l8 L __ _J WASTE DISPOSAL PNL (B-7)


!hf-' ---<< 33013-1889 H><r-X14239S 10368

" '~ 1025 - _Q .97/'7 3/8"-2505 F f---t.>1<'.~f-----.::!l.-"'--~~'--------l: 33013-2280 FWD10 1022A GAS ANAL yzER (F-10) ~'>--tx:., ~ X1047A DATt CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED ----1---1 PRELIMINARY NOT FOR CONSTRUCTION ----1---1 BIDDING PURPOSES />S BUILT RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE ~ -

1~------.J WASTE DISPOSAL -

GAS (WD) 1659A 1656A lTRLI (1-l) 3/4" 33013-1273-1

i------------------'-------------ll...---!~/l!--'"-t~'x~a--------_J 16568 lTRLI 1659B 1

2 3 4 5 6 7 P&ID JOB NO. DRAWING NO. REV. EWR 3391 E 33013-1273 SHEET 2 OF 2 ~ CCD 01 CONTROL COPY # 8 9 10 1 1 12 A B c D E F G H J

A B c D E F G H 2 2 3 (A-7} fT 17UU. <*-*) < JJOt:l-1206 FF1D41i.l 3 4 5 [C-B) --l!=.!L itM8 --~13-IZ7l-*1-*

  • p,df;i~

(C-1 33013-1275-! 1* X1831tMll:ICDI~ 1174C ~ fEJEr~~ L. 1"-1~2 3301~~~72-2 J/.. t----'--..:....:::~---]*** X1014 ArAClOR COOi.NiT 1608 DfWtfTNf( ~ TtJll"Y' 4 (C-8) 33013-1287 FF 1SJH,1. (C-1) JJQ13-1267 FF t56H,L I 34* 5 6 7 8 9 10 11 12 A B IGS? JlOtl-126.~ 1/llUJOICCOlf!ROt. - 1* c

  • ----r--~

,-----1881~---I----------~ X1~18 D u--*----- ~--- E F ~ I. rem ClNl"RM... NOTES RrrEA Ta CIRAW~C lJOJJ-2241. 2* ~~~ ~~~ ~~~4:50. J.OEl.tT!ll H

4. =-~oi:'~~~m.rs W>.Stt OISPGSAl.-tJ.S 1"

,....... ~"r:m~' 1804 !EOG FlU 6 7 8 g 10 11 12

A B c D E F G H J 1 F-2 33013-1899-1 '.'::'-------~ O> O> 0 (/) r'l z ~.. (C-4) 33013-1274 NITROGEN SUPPLY AUX. BLDG. 2 Pl 11A 1836A 0 0 ~ t 3 4 H-2 --j;><J--j 33013~ 1899-1 X15653 (F-2) 33013-1899-1 ---.:=:..:.::_.:.=:._:........i x 15658 3/4" v i:,...----n 1-'-'-_'.__j 10202v 0 0 x 1,0202W 10202Y 1 2" 1" 0 0 rn O> Ow 1" (/) 0 :r: c. 0 0

u

~ 0 0 " " "'

u

'jj "' 0 z "' 5]:;;: (/) 0 :r: 0 0 x (/) 0 0 " " "' "' " " "' (/) - 0 - r:::;io; "' '--" (/) z OUTSIDE 1830B AUX. BLDG. C-1 r-r-.-:i 1079 ADJ. MANIFOLD REG. 2 STAGE PRESS. CONT. (A-2) H~r--1 33013-1275-2 1080A lill 0 N 0 0 Pl 12B )> 1830A 3" DIA. 'o / GUARD PIPES~ ~ NOTES5&6 X8423 C-1 V 1" 3/4" 3/4" 1830D C-1 PT~ 1830E 2971 1* OXYGEN L..:...-L,-'f----4-+:J TRUCK 1830F 1830G rn )> r-c ox 0 0 N :r: 0 CONN. c ul 0 1" 1" 10202N ~TC FWD02 10203T 10204B (B-3) --11-H--<< 33013-1892 L.-.._,.,__


'x'i58'.l2 H-2.

-[><..I_, 33013-1899-1 NITROGEN BOTTLE (F-2) X15654 33013-1899-1 ~-----~x15559 (G-2) --=3~3~0~1~3_-~1~8~9~9--'-1-'X 15655 1" v i:--t* ~---,--i 10203J 1/4" 0 0 0 i------11~--+-----11>1-3v ~ 1 0203G ~ 1 0203E ~ 0 4>; v 0 0

r:

~ "Tl 1 2" 1 2" ~---.HHf--.l._ __ ~.._---'---L.....jHlt---lXJ--'--l l-'~--1 (H-2) -C><.J--t 33013-1899-1 X15657 (C-10) 33013-1889 X15817 '------~ (C-5) l/P~ 5 ~ 33013-1899-1 >>---------#ff----- X14401 K'------- D-5 10202T II.. H II 11409 H r I H

  • H if II II 0

0 r-H H H w v FE 1B s 10200S 0 0 0 L!J~ v 5 .if if 6 7 D-2 33013-1899-1 x 563>6'--------_.,. (C-1) 33013-1275-2 X8435 10205S1 x~ 1

  • if (C-5) 33013-1899-1

~------~ X14401 L (D-11) -+--~_Jil 0 c ~1 ~ TC TC r.1 1084A 10209S1 lill Ill (F-1) 10209S 33013-1275-2 X8427 0 0 (/) 0 ~ (/) - (G-1) 2" _,,--'----~----, 33013-1275-2 X8425 33013-1899-1 >>-----1>H'---- .. // D-11 H 33013-1899-1 x 14426-"-'-'-'-'---'-'-""----~ --=====:::;-i (D-5) 33013-1899-1 X 14401 H 3301 ~~~;99-1 01J HRACP ."-::~:--+------11-------j/'-----<.._;3~31Q0.!_:13~-::_11~8~99~-::_11_J X14 01 G HYDROGEN RECOMBINER A *coNTROL PANEL 1 2 3 4 5 6 7 N 0 0 - rn 8 Pl 14A 0 ~ 0 ;u "' 0 .. 0 =o ~ II 9 v -r.i 0 0 v 8 10 1 1 12 D-2) 33013-1899-1 X15639 3/4* ~ 3 4 1 l--'---l~~-'--t-----11...-3v Pl 2937 Pl 2716 0 0 0 0 0 "' 0 r-0 0 ~ ~ ~ = = 0 0 0.,, 1

  • 10200E 0

0 0 0 1/2" 1/2" ~ \\V ~ 10200B v ' - r.lf ~ 0 ~ 0 1 1/2" ~.. w 2" 10200A 0 0 0 0 -~~~~~~~~~f (C-2) 0 0 0 A 1 1/2" --ttH--~<33013-1899-1 ~ X15635 3/4" 0 N 0 - 3/4" v l:~-4----1 f----lf----1 i----....-3 v 10201D 10201C 0 0 - 3/4" r----l~~i-----t-...... ~3v 10201H 10201F 1 2" 2" 1" 0 "' g (B-10) r-;-'-,_~3~3~0~13~-~1~2~7~4:____ X1878 HYDROGEN 4" DIA. GUARD PIPE SUPPLY 1" 1" (D-2) --lh'I-' ---<< 33013-1899-1 ~7 (C-8) ---ll#--<<33013-1899-1 ~ ~------X15644 v ROOF 10211S1 10211 s 10210S .-+--.--Ill 0 c ~1 ~ 0 ~ w ------~-1~*------- (f) i:-~---r 1-.------------- H t 10213S 10201P 10201S wt; O> HRBCP N ' 1* 3 4" 1" ,----------j--------'---( ~---l rv w (E-8) H 33013-1899-1 ~ /---,; \\_ SAFETY CLASS 2,3, OR ~ SAFETY SIGNIFICANT (0) (D-8)


h~'---~<33013-1899-1 f--txJ--

DETAIL-A Pl 7B (C-11) 33013-1899-1 X15648 TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF. THIS DRAWING SUPERSEDED PORTIONS OF 33013-1275, REVISION 3.
3. EXCEPT WHERE OTHERWISE INDICATED SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. SOLENOID VALVES 10214S AND 10215S RECEIVE CONTAINMENT ISOLATION SIGNALS, BUT ARE NOT REQUIRED TO ACHIEVE CONTAINMENT ISOLATION AS DEFINED IN UFSAR TABLE 6.2-15, THEREFORE THESE 2 VALVES ARE NOT INCLUDED WITHIN THE SAFETY CLASS 2 BOUNDARY.
5. TWO SECTIONS OF THE OXYGEN SUPPLY LINE GUARD PIPE ARE MISSING AND THE GUARD PIPE FUNCTION IS NOT MAINTAINED.
6. DEAD LEG TEE INSTALLED.
7. PLANT ORIGINAL THREADED CONNECTIONS ON VENDOR SUPPLIED PIPING AND VALVES FOR THE HYDROGEN RECOMBINERS DEVIATES FROM THE 152 & 152N LINE SPECIFICATIONS. REFERENCE VENDOR DRAWING SERIES D10881 & D10882 (FABRICATING ENGINEERING) FOR CLARIFICATION.

(\\ REVISED PER RJM

5 I- <.i)

M ADC-13-000784f-::-71"'1"'1;':-,1"°3 ~"1:,11, "-3.-P.:;r.,/r./~h9-"°"1*"1!." CAD FILE NAME; 3?127501 CONSTRUCTION LIMITED CONSTRUCTION: AS NOlED ~------4'14426C PRELIMINARY NOT FOR CONSTRUCTION 711/ I (C-11) DATE BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. 33013-1899-1 X 14426~,_*-___ G_IN_N_A_S_T_A_. _ ___, R.E. GINNA STATION (D-11) 33013-1899-1 ~------X14401 SCAlE NONE JOB NO. WASTE DISPOSAL GAS HYDROGEN RECOMBINER (WD) P & ID DRAWING NO. REV. HYDROGEN RECOMBINER B CONTROL PANEL EWR 3391E 33013-1275 SHEET 1 OF 2 & CCD 01 CONTROL COPY # 8 9 10 1 1 12 A B c D E F G H J

1 A B c D E F G H I J 1 2 3 4 5 (E-1) __l_j p 210 1* SCH.80 OR XS COPPER PIPE ~ 33013-1215-1 >>---------------------11 I r-----.-------r::><J----j X1080A -n 8423 I I ~ !LOI 8423A (B-6) -J:><l-i 33013-1275-1 X1076A (D-6) -J:><l-i 33013-1275-1 X1084A (E-7) -C><l-i 33013-1275-1 X1076B (G-7) -[:><f-i 33013-1275-1 X1084B 2 3 I~ t~' I NOTE 4 z w 0 TC c! I NOTE 4 I~ JJ P304 T~ I NOTE 4 3/4" t (lJ gi z TC r.i -i c TC gJ r.1 _f 8435 [Q] 8433 [Q] -i c gi L E--+---' 3 4" E--'-'"-'----1 ~ z n1

u 0

0 fTl z 0

g
s z fTl
r:

fTl ro I z c -J ~ 10" x 23" ~I G) I NOTE 4 ~ I ',,,, __l_j 3/4" t' NOTE 4

r:

TUBING PIPING H l----T-14-* --il~I w~ ~w" CWD01A HYDROGEN RECOMBINER A BLOWER DUCT PIPING 10200V 1" 3/4" -152N -i c gi TC z r.1 _r cu... N ffiABANDONECT; IN PLACE ~ 8427 8427A [Q] 2" 152N 8425 8425A [Q] E--+--~ (lJ E--+--~ TUBING PIPING 0 c ~ 3/4" E-~~---< ~,I~ 3/4" 2B ~~---f~-::i 10" x 23" 1/4" H~r-14*--'---!~l~lt-----1 4 CWD018 HYDROGEN RECOMBINER B BLOWER 5 6 1" 152N \\/rGNITERS SWD03A HYDROGEN RECOMBINER A \\/rGNITERS SWD03B HYDROGEN RECOMBINER B 6 7 SIGHTGLASS 2501 3/4" SIGHT GLASS 2500 7 8 9 8 9 10 (J-5) 33013-1863 t'-~CDY °~ ' AS MAIN UNE ~wm '~"*"' SAFETY SIGNIFICANT (Q) DETAIL A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN AND TEST CONNECTIONS 10 1 1 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1275 REV. 3
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORD-ANCE WITH DETAIL "A".
4. THE PIPING SAFETY CLASS CHANGE INSIDE THE CONTAINMENT IS AFTER THE PIPE SEAL WELDS AT THE PENE-TRATIONS.

CONSTRUCTION LIMITED CONSTRUCllON: PS NOTED PREUMlNARY NOT FOR CONSTRUCTION Bl001NG PURPOSES AS BUILT DATE RE!.£ASED FOR ENGR. GINNA STA. R.E. GINNA STATION JOB NO. EWR 3391E NONE WASTE DISPOSAL - GAS HYDROGEN RECOMBINER (WD) p & ID DRAWING NO. 33013-1275 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 RE.V. A B c D E F G H J

2 .3 B c D E F G H 2 3 <J;01~10-2} SPENT flE'SlN STOfWiC fNiil< 4 JJ01.l-t264 (H-10} Rf:S!N Fll.L CONNECTION 5 6 ~ O\\Jr310l SHl[U>;t-1~ W>U w.sm~WN:L t------1 3-*0-l!Sl -L--*-*--- 9100... z* 7 OEWlt<£AAUZ£R ~ 9101 8 <=*~~~,.._, 1--~~i*~~.__-+-.-~~..-i-~ W.H.T. i J {B-t) 00~;;;-* W.4STE CONDfJ&lE TN<'<'1---+...,--l 33013-1278-2 TUBING P206 ! LL 1 600-1 5733 600-1 ---+1--*

  • ~N"""'o"'T=E""""5 5749~

TIJBING~ STEAM GENERATOR SLOWDOWN SAMPLE HEAT EXCHANGER A ~ I -

5' -MS-600-1 I :5' -MS-600-1 s
  • I 33013-1893 I :5' -MS-600-1 1 I :5' -MS-600-1

~:~ P321 I u

5'-MS-600-1

-...__ _____ _. X5738S I L!.J (JI _-3/4" ~ (JI (JI t;l - Ol s s I L!.J D

5'-MS-600-1 L!.J Li},

NOTE 8 L_ NOTE 8 UJ D I I I I NOTE 5 5701 3* [Q]l738 ~ ~ 'c! ~ t. ~:~ L!.J

o !D D

OJ OJ Zgi 5 5 G'l G'l G'l

  • I.

~ I ~ I L!.J LJ[p--Ol--~-m-'---De:::J-Y1--i NOTE 9 I () PSB02A 5777A 5776A 5779A ~ -Ii tJ 5778A IP DI [ WATER --~l::.;.._-0-----'I' 5751A 5780A 5776C (JI Ul s > L!.J I 1TUBING 600-1 I-3 ....==tki-~h~ 33013-1278-2 (G-10) 33013-1899-1 X5736S Li}, 1> N_:>_T_E~8..._E_:__::*::.::_:=l::......:..~---l<-=====~ 5777D )- 1-MS-600-1 lEQ) T LU SLOWDOWN SAMPLE P2Ll 573~ STEAM GENERATOR 3/F!' HEAT EXCHANGER B .--1---~~~~~~+-0...:J-~-1....!1---~~-Mf--j 1 57541 3/4"--- D 1 ~ ISl I c! gi z G'l EMS01B STEAM GENERATOR B 2" - MS-600-1 57806 2 2" -MS-600-1

1~

al I CD P322 (JI ~ m J L!.J Li}, NOTE 8 ia-=MS-60.~-~--i---.---i I 2" -MS-600-1 NOTE 8 600-1 TUBING ~ 3" -MS-600-1 NOTE 5

5' -MS-600-1 5702 NOTE 5 L

O-TE 5 ~-- -1 ~U 5776D (JI Ul s all..!..I D 57786 3 4 ~ s I

5' -MS-600-1 NOTE 5 "I ;"-MS-600-1 G-5 33013-1893

-...___;:_:;..;:..:..:.._.:..:..::.,::_--' X5737S 5737 [Q][l) UJ 5 D 5728 5727 6 7 NOTE 7 I t'--~.-----;- 5730 5729 6 122036 MANIFOLD- - (JI


;;:J s

OJ 3 4* 3 4" NOTE 7 MANIFOLD- -


~ -

al 4" ~ '5741D "l. L!.J v 7 8 9 (C-3) .------------------=------1 33013-2711-4

5' -MS-600-1 SGBCP SSB02 I oE12391 I

5 I I'-) I VJ L_co s NOTE 7 L!.J (C-6) .-------------------==---i33013-2711-4 SSB03 D !;-..--; ~ DE-..--; 12395 ~ 12, 389 I 5 ~ ~ L_co L_oo c! "'" '------,---""00_, ~ G'l Ol s s I - 3" -MS-600-1 SGBCP (JI Ol co al 8 L!.J NOTE 7 Ol s s I - TO SECONDARY SAM PUNG 9 X1406C X1406D 10 G-1 (C-1) 33013-1277-2 10 X5768A 11 -i_ SAFETY CLASS SAME AS MAIN UNE DETAIL-A SAFETY CLASS 2 OR 3 12 IYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS X5767A NOTES:

1. FOR GENERAL NOTES, SEE DRAWING:

33013-2241.

2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING: 33013-1277, REV.8 *
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. ALL SAFETY CLASS UNES ARE SEISMIC CATEGORY 1.
5. MS-600-1 UNE SPEC. APPUES, BUT SEAMLESS 2 1/4" CR-1MO, ASME SPEC. SA335, GRADE P22 PIPE IS SUBSlITUTED.
6. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN UNES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
7. ELECTRICAL SIGNAL IS SAFETY SIG-NIFICANT, PRESSURE BOUNDARY IS NON-NUCLEAR SAFETY.
8. WET LAY-UP SYSTEM HOSES TO S/G'S ARE INSTALLED CONNECTED AND OP-ERATED ONLY WHEN PLANT IS IN MODES A

B c D E F G 5, 6, OR NO MODE OF OPERATION. H LOWER DRAIN VALVE IS CAPPED AND UP-11 PER CONNECTION IS A SUND FLANGE,

9. WET LAY-UP PUMPS, PIPING, AND VALVES AS IDENTIFIED AS SEISMIC ARE PERMANENTLY MOUNTED IN THE CON-TAINMENT.

CONSTRUcnON LIMITED CONSTRUcnON: />S NOTED PREllMINARY NOT FOR CONSIRUcnON BIDOING PURPOSES />S BU!Lt DATE RELE:ASEO FOR 1-"'""'---=G.::;.IN"'"N""A'-S;:;..;T..;..;A~. ----l ~ G\\s., ELEl:nm: O>RP. SCAt£ NONE JOB NO. STEAM GENERATOR SLOWDOWN (SGB} P & ID DRAWING NO. REV. EWR 3391E 33013-1277 SHEET 1 OF 2 ~ CCD 01 CONTROL COPY # 12 J

A B c D E F G H J X14541S 1 (D-7) 33013-1894-2 (B-7) --i;><:.f-l 33013-1894-2 X14527D (A-12) --1:><f-l 33013-1894-2 X5743BH1 (D-7) 3/4" D E-.....---1"' 5796A I (/) 3/4" I v E-c~t--i,~ 5794C 0 I 2 I TSB02B MIXING CHAMBER 57756 3 Pl 4114 DE:i12~3-<118t-3-J--i--{ J ! 5775D ~ ~ OJ 3" 4" -CD-300-1 ~ 33013-1235 ~>------ ---,-----------------____, X9512B~-----~ 3/4" TC 4 TC >---+------1 I i---~-----J 5 TC 6 (D-1) 33013-1233 LSB01 \\ LSB02 \\..+/-:MS-600-2 LSB03 5767 DRAIN HEADER (D-10) 33013-1894-2 (E-2) 33013-1924 L.P. HEATER 3A X5767B MAIN CONDENSER A HOTWELL 6-ES-150-1 5722 2" v [--l I l--IM--=--J 5722F 6" -MV-150-4 2" 7 ATMOSPHERE ~L!J L'...I 5791 B 8 5791A 1" DE--lMi-1 5796S (H-1) 3/4" 1" 2" 1" 600-1 150-4 E 1---c<<J------'-------------'--------1 (H-10) -t:><l-l 33013-1277-1 X5741D (C-11) 3/4" vE-..4---l 5775E -l><l-1 33013-1894-2 >>------ih'I-' -- X14527 3-MS-600-1 5767A ~ 0 OL!.J D 5710 II Pl 4112 33013-1904 ZGS07 (B-12) ~ 33013-1894-2 >>------11//--- X5725BH1


11-J-------l#r'--~t 5~7~0*L-H-.--t D E_,12~3...

81-7+-~--_, J I TC (C-7) --C><l:i~33~0~1~3:-21~89~4~-~2~;>---/f---1 X14542SL (C-7) --[:><f-j 33013-1894-2 X14542S (C-10) ~ 33013-1894-2 X14527A (B-12) 5770P >>-----"H-- ~ 33013-1894-2 >>------11H--- -~'l-x5725AH1 (C-10) 3-MS-600-1 33013-1277-1 X5741Cc_ _____ __.. 3" -MS-600-1 (S-7) --1?.:Sl::i 33013-1894-2 >>---ll-H-X14527C 3/4" DE..... 4-l 57976 5770T 3/4" v E_.,.4-1 5795C II ii 5768A 0 '° 0 L!.J D II Ii OJ LSB04 r--..,..-_ _._ __ --11 Hf--1.---l 5725v 1 I 5790 f--- SEE NOTE 5 4-MS-600-2 ~I 5770M t 5725A LSB05 OJ v t-:------to--'-----; I Hl---'----i I I 5789


l f--- SEE NOTE 5 4-MS-600-2 8-MS-600-2 (E-10)

--,tt-~----th1-' --<< 33013-1894-2 ~ X5768B 5723A 5740A c' SSB01 OJ CONDENSING 1'5 POT~ a> 5724A 1/2" 5739A 1" TUBING 0 v y ~[~ ~ ~ CJ °' t-+-.4--=:J D b 12379 i--__ ~112205 ,,-----.../ "' "' '° "' L!J TC 0 r LT 4108 122086 MANIFOLD ~[~- ~ a> H--.4--JD 0 12377 PT 4104 TSB01 S/G SLOWDOWN FLASH TANK 8-MD-150-2 1"-150-1 2" (B-11) NOTE 4"'"' 33013-1252 ~ ~ SGSCP 5745 Pl 2686 57408 6" 0 I TC i--.-1-J 12397 1" 3/4" DE........, 5797A X5744C MAIN CONDENSER S 57446 5744 5740 3" c_ __ (B-12) (E-10) '° "' "' "' 5742 ~ 33013-1894-2 >~------1/,1-1 - X5743AH1 TC TC TC 33013-1885-1 150-2 150-2 X3678 (F-12) 33013-1231-1 MS HEADER (E-1) 2" 4" TS802A MIXING CHAMBER LSB06 OJ LSS07 4-MD-600-2 LSB08 "' '° 0 5768 CIRCULATING WATER (1-11) 33013-1259 \\_4"-150-2 SEE NOTE 7 NOTE 7 PSB01 <MO/STP> S/G SLOWDOWN FLASH TANK PUMP v I 0 0 I 0 I 9 I 0 I 0 I 33013-1233 X1738V 5716 5717 C 2" --11----+----Mf---'---"---->4-__J DRAIN HEADER MAIN CONDENSER A HOTWELL 1 2 3 4 5 5715 5714A 6 7 8 9 1" I 0 I 0 I... 10 1 1 12 S/G SLOWDOWN CONTROL PANEL (C-11) H < 33013-1894-2 i----+------<C><J-- X 15854 (D-4) ---~1~1----<< 33013-1895 ~ X15301 I 0 I 0 I... (J-8)


<< 33013-1278-2 (D-7) 1"


<< 33013-1235 4"

8" (H-8) 33013-1231-2 (J-7) 33013-1922 J-10 8" NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241
2. REVISION Q" OF THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1277, REV.8
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. FLANGES ARE CARBON STEEL.
5. LINE 600-2 WITH EXCEPTION FOR MATERIAL.

PIPE AND PIPE COMPONENTS MATERIAL SHALL BE STAINLESS STEEL A312 TP304L. ,___ ___________ __, 33013-1885-1

6. ELECTRIC MOTOR EIN'S ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

DISCHARGE CANAL 10 1 1

7. PRESSURE/TEMPERATURE RATING LINE IS 150-2 WllH EXCEPTION FOR PIPE MATERIAL. MATERIAL IS CrMo P22.

CAD FILE NAME 33013-1277,2 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 11//S AS BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCALE JOB NO. NONE STEAM GENERATOR SLOWDOWN (SGB) P & ID DRAWING NO. EWR 3391E 33013-1277 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

5 10 11 12 A ©----3~*" i:-i-L--~ *. A s.:,i J/:l-SL-4~0:.

  • l.?.~.!~;~~1~.:'.~.. ::~~

B B JiO-t'AS-.i~' D [J t-t-------11---~(;;;~:~~=~*-rx~ J(~<4-4ili'S E E t G t H H t i;-.:~<} **------------------- fl.O* 4 8 lO 11 12

1 A B c D E F G H I J 1 2 3 (B-11) ,..._.,.,__, 33013-1278-1 X927C (8-11) 33013-1890 SOV 14304S (J-5) 9568 tO OJ 3/ff 33013-1247 e..::.3<-8:c..-....:S:..:L'--""-2"-50:..:5'-l!M--:J [-1------~ c___ _____

b8 959 I

RHR LOOP IFcl )> ~ 601 2505 c [Tl II] ?< I i" (D-11) l><'.t---133013-1278-1 X9278 (E-11) 1><:1--; 33013-1278-1 X927A (SEE NOTE 4) aJ I aJ I r r g 01 0 3 8-SL-2505 3 8-SL-2505 960 3/ff' 956A EAC05C PRESSURIZER STEAM SPACE SAMPLE HEAT EXCHANGER 956C 151 ---.-i-o-- (C-2) 33013-1264 LETDOWN 974 ,._. I rn)=o. ~ DEMINERAUZER rc1 fTI I ox ;o OUTLET~ 0* I. 15 3/ff 0 TC E-911~--...--------, 9878 987A 4 3/ff' EAC058 REACTOR COOLANT LOOP 8 HOT LEG SAMPLE HEAT EXCHANGER 3/ff' EAC05A PRESSURIZER UQUID SPACE SAMPLE HEAT EXCHANGER 3/ff 989 151~505 (A-2) I 3/8-SL-2505 33013-1264 >--Did--4-.--'-------11... ----' 2 987 ,._. I LETDOWN

'.S DEMINERAUZER INLET m

I ::o ~ )> 5c I rn 0?<1r 0 0 r-_(_B_-7_) __,3/ 4" ~ -t:><l--133013-1265-2

J E-...,__,..-1---~

)> z X975 VOLUME CONTROL TANK c ;;i ?< I i" rn I rn 3/8-SL-2505 ~ ~I~ I (A-4) 3/4~ 33013-1277-1 X5735 '---------,... STEAM GENERATOR SLOWDOWN 1A 3/8-SL-2505 (F-4) --;:><l--133013-1277-1 X5736 STEAM GENERATOR BLOWDOWN 1B 3 992A w 992C w L 4 988 2505 EAC04A S/G SLOWDOWN SAMPLE HEAT EXCHANGER A EAC04B S/G SLOWDOWN SAMPLE HEAT EXCHANGER B 5 964C 9648 964A 963C 9638 963A 6 RC LOOP 8 HOT LEG SAMPLE PRESSURE VESSEL TSS20

i-vvf __... ----'

962C 965A PRESSURIZER UQUID SPACE SAMPLE PRESSURE VESSEL 961C TSS21 Nvt----1... ----' 9628 9618 9658 PRESSURIZER STEAM SPACE SAMPLE PRESSURE VESSEL TSS22

i-vvf-11... ----'

962A 965C 961A r----- 994A 7 8 9 (B-1) AUX. BLDG. 1" -I-N-TER-. BLD-G. 969A l/2" E-t~--------'---------'-L-=----, 33013-1265-2 VOLUME CONTROL TANK I OJ CS> OJ 983 982 3/ff 986 9998 CX> 968 3/ff tO CX>.... I I I Ul Ul Ul r r r I I I OJ OJ OJ CS> CS> CS> OJ OJ OJ 3/ff SAMPLE l ROOM -HOO~ 985 971 972 3/ff t 3/8" 1" 969 I _ TUB~ 3 4" 1/2" (H-4) 33013-1279 OUTSIDE SAMPLE ROOM INSIDE SAMPLE. ROOM 3/4" w I rn 51 5 G"l G"l (C-1) 33013-1259 CHEMICAL DRAIN TANK (F-10)


11----c 33013-1908-3 10 X4268

"----------' X5030P UNES FOR PERIODIC SAM PUNG (A-6) 33013-1259 SAMPLE SINK LAUNDRY AND HOT SHOWER TANK A TSS23 VOLUME CONTROL TANK SAMPLE PRESSURE VESSEL OJ 9948 tO ~--+----< "?, )> 151 9738 TUBING '-"-"'>+--- 990 (B-1) 33013-1259 RADIO CHEMISTRY LABORATORY DRAIN TANK (G-1) ---,-__.,..__J_..ie----< J-----1------E 3/4" .. 11-----; 33013-1273-1 3/ff' 9928 992D J 5 977 978 ~--~ 979 992E NOTE 5 992F NOTE 5 <O <D ~ I (/) r I OJ CS> OJ OJ <O G"l 3 ff 976 co I (/) r I OJ CS> OJ 995A 996A 9958 9968 S/G 1A CONDUCTIVITY CELL & TEMPERATURE COMPENSATOR S/G 18 E~------< 6 3/ff 3/4" 3/ff 7 INSIDE SAMPLE ROOM OUTSIDE SAMPLE ROOM S.S. 301 WDG (E-9) 33013-1908-3 DEMINERAUZED WATER 12519A c.s. 301 RM-19 STEAM GENERATOR SLOWDOWN PROCESS MONITOR SKID NOTE 3 OJ [Tl FILL f7l v f7l 1/2" 1-'--"--V-r-----'--t---Cl---t--_,,,,.-__ _._ ___ _L__..,,.l-3S 6798A 1" 6796 ~ 125198 (E-10) 33013-1277-2 S/G SLOWDOWN FLASH TANK 8 12519C X5763 9 10 11 1 1 12 NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1278 REV. 9.
3. RM-19 AND RE-19 COMBINE TO PERFORM A SAFETY SIGNIFICANT DETECTION FUNCTION.
4. AOV 959 IS NORMALLY DE-ENERGIZED (FUSES PULLED) AT POWER.
5. VALVES 992E AND 992F ARE THROTTLED TO MAINTAIN PRESSURE LESS THAN OR EQUAL TO 150 PSIG TO MAINTAIN OPERATING PRESSURE AND PROTECT THE FLOW INDICATORS AND RADIATION MONITOR.

CONSTRUCTION UMilED CONSTRUCTION: />S NOTED PREl1MINARY NOT FOR CONSTRUCTION BIDDING PURPOSES />S BUILT RE1£ASEO FOR G_IN_N_A_S_l_A_. _ __, R.E. GINNA STATION SCA1.E NONE JOB NO. NUCLEAR SAMPUNG (SS) P&ID DRAWING NO. EWR 3391E 33013-1278 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 RE.V. A B c D E F G H J

A B c D E F G H I J 1 2 3 4 5 6 7 8 9 10 1 1 12 (J-10) 10102B

cl

--i><1-j 33013-1899-1 :>~---*ff-------11-H---------ilH----------ti\\~' ----,l X14413S (J-10) u: PIPING TUBING X14412S 10015 __ __iI_-::1_1 ) ___ _ I 33013-1278-1=::>r----- (H-10) 3 8-SS-153 TUB~ I~,, --[:::tj-C]-----* 10025 10097E I~ l0097F z G) TUBING T-211-58 T-211-5A ARGON BOTTLED GAS (A-1) 33013-1899-1


1/--------fl--------H-------~---

1/4-SS-153 33013-2281-1 X14416S X10102J (H-10) 3/8-SS-153 33013-1899-1 3/8-SS-2505 10001 X14417S (C-11) 33013-1278-1 TUBING TUBING ~ ESS04B t:==., -[XJJQ~,u8"lpvvvj~~I-112" 10026 10056 10030 L'J (I -10) 33013-1899-1 >----//---------------//*---*--**-* --- -*-*//-*--*-*---------!'!----- N I (/) (/) I N °' G> X14414S (H-10) 33013-1899-1 X14415S (B-11) 33013-1278-1 10002 (B-7) 33013-1890 X14296S (B-7) 33013-1890 X14294S 10003 3" (G-1) ~-~-~--; 33013-1272-2 (C-7) -£><f-1~_3_3_0_1_3_-_18_9_0 __

>r----I~--+

X14293S 10040 X14292S X1002 X10024 (B-5) 33013-1890 (C-12) 33013-1272-1 CONTAINMENT SUMP PUMP DISCHARGE (F -11) 33013-1888 1 D ['------1 1<ll72 P107 I. BUILDING LCONTAINMENT e e N I (/) (/) I (.}; N I (/) (/) I (.}; iJ) IT] IT] z 0 -j IT] (~ PSS01 CNMT. SUMP A SAMPLE PUMP 11/2-SS-151 10036 [ill 1-SS-151 (I-10) 33013-2252 I~ (/) N I (/) (/) I (.}; CONTAINMENT SUMP A 2 l 3/8-SS-153 10013 3/8-SS-2505 1 2-SS-153 10012 L'J 1/2-SS-153 L'J (D-11) °' TUBING TUBING TE 302 10095 FT 303 10096 10016 // (H-5) 33013-1899-1 X15673 (F-5) 33013-1899-1 '--------' X 14 719S (H-5) < 33013-1899-1 ~s 2" < 33013-1259 3/8'~ I ~-- - - -- -- - -- - - -- - - -- - - -- - - ---D---~0~ 1 ;-cJ-- -J~l-1 1 3301~~;;81-2 POST ACCIDENT SAMPLE COOLER RACK 1/2-SS-2505 X1001 10039A (A-1) 1/2-SS-153 1---------i 33013-2281-1 ---lr-----t><l-Jvvt--1 ><I--~ 10039B 10038 1 /2 COPPER 1 /2-SS-155 AUX. BLDG. INTERM. BLDG. (F-8) 33013-1893 X14429S (E-11) Al 33013-2281-2 (E -11)

  • -1><.l--< 33013-1865-2 I--------~-------~--------~

X1598 10010 1/2-SS-2505 (J-5) 10089 10100 --l'><f--1 33013-1899-1 X14401S (A-10) 33013-1278-2 1/2-SS-2505 4268 426 426A L'J L'J L'.J L'J (1-5) --J:><f--1 33013--1899-1 X14406S (J-5) --t><t-{~~~~-=_1899-~r--~n~-------11-#-------~Jr/-------~H~-------11-fi X14404S (I-5) -*C><]-f 33013-1899-1 X14403S 10052 (I-5) X14402S ,..c..--8 5> <D (E -11) 33013-2281-2 (I-1) 33013-2281-2 j 1/2-SS-153 33013-1899-1 ~ '-------~><f----'-------'- f----1><~ 10006 10044 1/2-SS-151 4 5 6 PSS02 PASS WASTE TRANSFER PUMP 10045 7 10004 8 LE 301 (/) iJ) iJ) G> TSS19 PASS WASTE HOLDUP TANK N I (/) (J) I (.}; 2" (A-1) 33013-2281-2 (I-8) 33013-1875 (F -11)


<< 33013-2281 -2 INTERMEDIATE BUILDING RETURN DUCT 1/2-SS-153 N

I (/) (/) I (.}; 10008 ~~T\\ 10047 r*L2J--~ BSS02 9 1 2-SS-153 10059 1 2-SS-153 PSS03 PASS WASTE HOLDUP EVACUATING PUMP 10 10034 TANK N I (/) (/) I (.}; 1 1 1/4-SS-153 1/2-SS-153 (E-5) 33013-1899-1 X14718S 10011 10042 10018 10041 1/2" l 10043 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "0" OF THIS DRAWING SUPERSEDED DRAWING 33013-1141.
3. AIR DIFFUSER WHICH DISTRIBUTES AIR MOTOR EXHAUST AND PREVENTS DEBRIS FROM ENTERING EXHAUST.

CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION >-----+----*-~-*--"- BIDDING PURPOSES AS BUILT RELEASED FOR '~ GINNA STA. R.E. GINNA STATION SCALE NONE 01/TAAOO. NEW YORK POST ACCIDENT SAMPLING SYSTEM (SS) P&ID JOB NO. DRAWING NO. EWR 3391 E 33013-1279 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

LOG IC SYMBOLS (REF: NEMA STANDARD IC!-1959) SYMBOL t r>a.. *. r' L R LOGIC FUNCTION ANO NOT OR OFF RETURN MEMORY RETENTIVE MEMORY TIME DELAY ENERGIZING TIME DELAY

    • ~ DE-ENERGIZING COINCIDENCE (2 OUT OF 3 SHOWN)

RE TENT IVE MEMORY WITH MANUAL RESET DESCRIPTION R DEVICE WHICH PRODUCES AN OUTPUT ONLY WHEN EVERY INPUT EXISTS. i!ii:l)-,.~*;c.*. *.*,_,,_,.. i*Y' A DEVICE \\IHICH 'PRODUCES RN OUTPUT ONLY WHEN THE INPUT DOES NOT EXIST. A DEVICE \\IHICH PRODUCES RN OUTPUT WHEN ONE (QR MOREi INPUT EXISTS. A DEVICE WHICH RETAINS THE CONDITION OF OUTPUT CORRESPONDING TO THE LAST ENERGIZED INPUT, EXCEPT UPON INTERRUPT ION OF POWER IT RETURNS TO THE OFF CONDITION. A DEVICE WHICH RETAINS THE CONDITION OF OUTPUT CORRESPONDING TO THE LAST ENERGIZED INPUT. R DEV ICE WHICH PRODUCES AN OUT PUT FOLLOWING DEFINITE INTENTIONAL TIME DELAY AFTER RECEIVING RN INPUT. A DEVICE WHICH CONTINUES TO PRODUCE AN OUTPUT FOR A DEFINITE INTENTIONAL PERIOD OF TIME AFTER THE INPUT HAS BEEN REMOVED. A DEV ICE WHICH PRODUCES RN OUT PUT WHEN THE PRESCRIBED NUMBER OF INPUTS EXIST HoXAMPLE: 2 INPUTS MUST EXIST FOR AN OUTPUTl A DEVICE HAVING THE LOGICAL FUNCTION RS INDICATED BY THE DIAGRAM BELOW. RCTURT ING SIGNAL I MANUAL RESET (MOMENTARY P.B.l 212 x ADDITIONAL SYMBOLS /PC'~ 'Y'<s l_ LJ INSTRUMENT CHANNEL (SEE SPEC. G6751G4 FOR CODE LETTER EXPLRNATIONl INDICATES THAT THE DEV ICE OR INSTRUMENT CHANNEL HAS A BISTABLE LOGIC OUTPUT WHEN: - PARAMETER MEASURED IS GREATER THAN A PRESET VALUE - PARAMETER MEASURED IS LESS THAN A PRESET VALUE - PARAMETER MEASURED DEVIATES FROM A PRESET VALUE BY MORE THAN A PRESET AMOUNT -, J#-oR VoR "']...- SAME AS ABOVE EXCEPT WITH AN AUTOMRTICALL y ....t::::J

J

.--L SET VARIABLE VALUE ALARM ANNUNCIATOR (ALARMS ON THE SAME SHEET WITH THE SAME SUBSCRIPT SHARE A COMMON ANNUNCIATOR WINDOW) REACTOR TRIP "FIRST OUT" ANNUNCIATOR TURBINE TRIP "FIRST OUT" ANNUNCIRTOR DEV ICE FUNCTION NUMBER 52 I Pl?- CONTROL CIRCUIT, CHANNEL OR COMPONENT ITEM NUMBER LOGIC INFORMATION TRANSMISSION ~-- ACTION CALLED FOR BY LOGIC INPUT ~ COMPONENT CONTROL CIRCUIT / INDICATES THAT THE INSTRUMENT CHANNEL HRS RN OUTPUT RS FOLLOWS: P - PROPORTIONAL TO THE MAGNITUDE OF THE PARAMETER MEASURED p R - PROPORTIONAL TO THE RATE OF CHANGE OF THE PARAMETER MEASURED I l_ ~tSV~~~LE.l:::f oR roR -:Jc INDICATE SAME AS EXPLAINED ABOVE I ac, tc bo, ta 00 be a 10/. b 10/. INDICATOR LAMP T - TRIP STATUS LIGHTS P - PERMISSIVE STATUS LIGHT B - BYPASS STATUS LIGHTS POSITION SWITCH DEVELOPMENT 0 FULL TRAVEL - I I I I I I I I I I I I I I I I (VAL VE CLOSEOl (VAL VE OPENl DETAIL "A" TITLE REACTOR JRIP SIGNALS TURBINE TRIP SIGNALS DEV ICE FUNCTION NUMBERS ANO LETTERS (REF ASA STANDARD 372-1956 ANO NEMR STANDARD SG5-1959, SEE O\\IG. 10905-7) 1 - MASTER ELEMENT (CONTROL SWITCH) 20 - ELECTRIC OPERATED VAL VE 33 - POST ION SW ITCH SUFFIX LETTER } oc, oo, be, bo - LIMIT SWITCH SEE DETAIL "A" to, tc - TORQUE SWITCH FOR OPERATION 4 3 - MANUAL SELECTOR SW ITCH 52 - AC CIRCUIT BREAKER OR CONTACTOR SUFFIX LETTER o - AUXILIARY CONTACT - OPEN WHEN MAIN CONTACTS ARE OPEN b - AUXIL IRRY CONTACT - CLOSED WHEN MAIN CONTACTS ARE OPEN (c) - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO CLOSE VALVE lo) - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO OPEN VALVE (eel - BREAKER CLOSING COIL (tel - BREAKER TRIP COIL (uvl - BREAKER UNDERVOL TRGE TRIP COIL 63 - LIQUID OR GAS PRESSURE, LEVEL, OR FLOW RELAY 69 - PERMISSIVE SWITCH 72 - DC CIRCUIT BREAKER OR CONTACTOR SUFFIX LETTER a - RUXIL IARY CONTACT - OPEN WHEN MAIN CONTACTS ARE OPEN b - AUXILIARY CONTACT - CLOSED WHEN MAIN CONTACTS ARE OPEN (cl - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO CLOSE VALVE (ol - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO OPEN VALVE (eel - BREAKER CLOSING COIL Itel - BREAKER TRIP COIL (uvl - BREAKER UNDERVOL TRGE TRIP COIL 86 - LOCK-OUT RELAY SUFFIX LETTER P - PRIMARY BU - BACK-UP INDEX SHEET NO 02 03 SUB 3 2 4160V BUS AUTO TRANSFER 04 3 EMERGENCY GENERATOR START ING 05 3 SAFEGUARDS RCTURT ION SIGNALS 06, 07 5, 3 SAFEGUARDS SEQUENCE 08 5 FEED ISOLRT ION, AUX. FEED PUMP 09 5 NUCLEAR INSTRUMENT TRIP SIGNALS 10 2 NUCLEAR INSTRUMENT PERMISSIVES & BLOCKS 11 4 PRESSURIZER TRIP SIGNALS 12 3 STEAM GENERATOR TRIP SIGNALS 13 2 REACTOR COOLANT SYSTEM TRIP SIGNALS 14 5 ROD ST OPS & TURBINE RUNBACKS 15 4 NOTES: PROTECTION CHANNELS 1 & 3 ARE CONNECTED TO INVERTER SUSSES. AS BUil T REDRAWN PER EWR 4777R ORIGINAL ND. REVISION INITIAL DATE CAD F ILENRME 3Gl3530! M~W l/3191 BR 12116182 DRAWN BY CONSTRUCT ION §JO l*I0-91 JCL 12/16/82 CHKD LIMITED CONSTRUCT ION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION B IOO ING PURPOSE$

e(.

.C.._ /~I'd*'!/ GG 12/1£/82 RESP. ENG. T111'1 1-11-~1 GWD 12117182 ENG. MANG'R RS BUILT TH IS DRAW ING INCLUDES PORT JONS 'o 11.AS UEJ OF CLASS IE ELECTRICAL SYSTEMS. RELEASED FOR ENGR. REFER TO NOTES AND SPECIFICATIONS FACILITY GINNA TO DETERMINE SPECIFIC QR If------*------' ROCHESTER GAS & ELECTRIC CORP. PROGRAM APPL !CAB ILITY. SCALE NONE ROCHESTER, NEW YORK THIS DWG SUPERSEDES Ji DWG 8820612 JOB NO. CCD 4 LOGIC DIAGRAM INDEX & SYMBOLS DRAWING NO. 33013-1353 SHEET REV. 01 /1\\

0 8 2/3 TURBINE AUTO STOP OIL (SHT. 03) 2/2 TURBINE STOP VALVES CLOSED (SHT. 03) PERMISSIVE P-9 (SHT. 11) PERMISSIVE P-7 (SHT. 11) (SEE DWG. 33013-2095 SHTS. 3 & 34) R D24 ~----13/31---~ll-----' R D32 1 /2 + 1 /2 UNDERFREQUENCY (BOTH 4KV BUSSES) -----i. RT11 ~ACK 3 ~---i RT12' (SHT. 04) L 2/2 r---.--, 1/2 + 1/2 UNDERVOLTAGE (BOTH 4KV BUSSES)


i-___J I

RACK 3 (SHT 04) 1/2 I RT11 I R D16 1-----~-i RT12 +-, ~ THOT < 500°F (REF. 10904-204,205) ZIRCONIUM GUIDE TUBE INTERLOCK 1/2 HIGH FLUX SOURCE RANGE (SHT. 10) 1/2 HIGH FLUX INTERMEDIATE RANGE (SHT. 10) 2/4 HIGH FLUX (LOW & HIGH) POWER (SHT. 10) 2/ 4 PRESSURIZER LOW PRESSURE (SHT. 12) 2/3 PRESSURIZER HIGH PRESSURE (SHT. 12) 2/3 PRESSURIZER HIGH WATER LEVEL (SHT. 12) 2/3 STEAM GENERATOR LO-LO WATER (SHT. 13) EITHER LOOP DELETED PER EWR 4773 1 /2 MANUAL TRIP (SHT. 14) 2/4 OVERTEMPERATURE ?T (SHT. 14) 2/4 OVERPOWER ?T (SHT. 14) RANGE LEVEL 2/3 REACTOR COOLANT LOW FLOW BOTH LOOPS (SHT. 14) 2/3 REACTOR COOLANT LOW FLOW EITHER LOOP (SHT. 14) SAFETY INJECTION (SHT. 06 & 07) I - 2/2 r---.--_J R D8 NOTE 1 R D30 TRIP LOGIC TRAIN A ~ TRIP 0 LOGIC TRAIN B (SAME INPUT AS FOR LOGIC TRAIN A) TRIP TRIP 260V A.C. BUS 52 (UV)/BYB 52 (UV)/RTA 52 (UV)/BYA 52 (UV)/RTB 0 52/BYA ) 0 52/BYB O) 0 ) 52/RTA ) 52/RTB ROD DRIVE SUPPLY BUS TRIP 52/BYB EACTOR TRI BREAKER TRIP 52/RTA TRIP 52/BYA EACTOR TRI BREAKER TRIP 52/RTB THIS DWG SUPERSEDES DWG 882D612 ./ / ) M-G SET ROD DRIVE / /

0) 0 M-G SET POWER SUPPLY
I 2121 2/2 THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS.

REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. TO TURBINE TRIP BATTERY 1 B VIA 20/ET (SHT. 3) TO TURBINE TRIP BATTERY 1A VIA 20/AST (SHT. 3) 0 NOTE 1: ZIRCONIUM GUIDE TUBE INTERLOCK UNDERVOLTAGE TRIP BELOW 8% POWER AND 500° F. Jo/z/1$ AS BUILT DATE RELEASED FOR ENGINEER f\\ REVISED PER ill ADC-13-000669 RJM /511;' l?nf J/<6 10/1/13 1*!)1! 10/1/r?: 1o/t/13 REV REVISED FOR 1--~----------4 DRAWN CHECKED RESP REVIEWER FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 33013-1353,2 ONTARIO, NEW YORK LOGIC DIAGRAM REACTOR TRIP SIGNALS ELECTRICAL JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 2 ~ CCD 4 i ICNTRL COPY#

v v VA.. -... . v v v (11P1/1G)~~.J--N--il--O~FF~L=IN~E _________________

  • _v_v v_-_v_v __

v ~* v v v v GENERATOR MULTIFUNCTION

  • , ____ TRIP DISABLED

?:J-ON LINE > GENERATOR MULTIFUNCTION (11P2/1G)--.____) A A A A A A A A A A A A v AT RELAYS A A A A A A A A "'-<"-,_-"--..A/'-~--A~,A, GENERATOR TRIP LO~IC INPUT SIGNALS ( \\ r GEN. DIFF. (87 /G) MCB ' l ) ) } 0... MCB 0.. GEN. GRD. (59/N) --------:~~-=-"*'-"'"!*-~ PIPE CABLE FAULT ~ r-- -;;,.. 1--~ll---~ co (87P /PC PLUS 50 FD/87P-PC) UNIT AUX. TRANSF. DIFF. (87T/11T)-----~ LOSS OF ELECTRICAL LOAD (STA. 13A) ~ [L~ 3 I /T\\ K26 N N N -... P-9 (SHT. 11)------.---l-_l 1-----i-;;rr---------1-_ _J (J) r LOSS OF ELECTRICAL LOAD (STA.13A) UNIT DIFF. (87 /GT) NEG. SEQ. (46) MCB _____________ __,.-i DISTANCE (21) MCB ~~----i DIRECTION POWER (32) --------~ 0 --1------' MCB 3 1G13A72 OR 9X13A72 CLOSED '---.j/~ 4KV BUS , -;---. ;1-------<119-------- AUTO TRANSFER .----l'-'--_./ (SHT. 4) LOSS OF FIELD (40) =M=CB~-------~ UNIT AUX. TRANSF. OVERCURRENT (51/11T) ----~ /T\\ K26


i[>(f-------------0.,.1-~---,r---~

SEE DWG. SEE DWG. LLi LLi (/) UNIT AUX. TRANSF. GRD. OVERCURRENT (51N/11T) ---~ UNIT GRD OVERCURRENT (51G/1T)-------- GEN/UNIT GRD (59G/1GT) ------------' STA. 13A PIPE CABLE FAULT----.-*1 S- ~------ OUTPUT BREAKER FAILURE TO TRIP---. TURBINE TRIP LOGIC INPUT SIGNALS ( r CIRC. WATER PUMP 1A BREAKER OPEN 52/CWP1A (UNIT 3) 'T D CIRC. WATER PUMP 1 B BREAKER OPEN §l ~ 52/CWP1 B (UNIT 28) 0 ~ - Tl STM GEN. FDWTR PUMP 1 A BREAKER OPEN ~ > 52/FP1A (UNIT 7) LLi w (/) STM GEN. FDWTR PUMP 1 B BREAKER OPEN -... 52/FP1 B (UNIT 25) N 1G13A72 OR 9X13A72 CLOSED N [L i--~x ,____I N LL. N A K18 ~ IX>--~ 0 I "' 0 O> 0

z

~~-~ 03021-1011{AMSAC -------------------------@-------------------------I~/ <e ~


------------1---- -------.!- -;---./1------0~;::;-N 10905_0115 { MANUAL TRIP

'--__./ (AT CONT. BD.) /T\\ s REACTOR TRIP K3 (SHT. 2) @ ______________._ _________ _ REACTOR TRIP /\\ ~ COLJ~ N (SHT. 2) @ '~ \\ ............. ~ '.:::- ;1------0~ 0 0 i---- ~'-..__/ N ~ LOW COND VACUUM 63/LV l_ /T\\ K2 TURBINE BRG LOW OIL PRESSURE 63/LBO I '-------------i v (63XT2)LOW AUTO STOP OIL PRESSURE----- (N-T/5501 S3) TEST SW TURB. AUX. GOV.-------i I 1 I I I I I N l_ I -=-r-:= - - - TRusT BRG FAILURE 63/TB - ---= - =F -,---- = __,... ~ OVERSPEED OS -- -- -- -- -- -- J ,~ _r ~- -- _J llll


B----_J L MECHANICAL -HYDRAULIC SIGNAL HAND TRIP (AT TURBINE)

K17 K9 K1 K25 W. DWG. 461 B820 SHT. 6 I I r I l ___ J I 0 N CD 0

r:

(_) N '-.. 1-----~ I '"' (/) <D 0... O>

r:

(_) /A\\ 1 129 v 0 N I <"? v (/) <D 0... <D N <"? 0

c

(_)

A\\ 1 129

---i ~ ;;:;. !-------------~ (/) = 0... /A\\ 1 129 /A\\2 130 ~ ~-------------- §~ G L:S(/) u N N N N ~ N N v 0 0 I "' 0 O> 0 NU1 <D <( ""~ 0,_ ~ ~°". 8 ,___ _____________ u>- N L:SU'i et::~ 0,_ I THIS DRAWING INCLUDES PORTIONS I i OF CLASS 1 E ELECTRICAL SYSTEMS. I REFER TO NOTES AND SPECIFICATIONS I . TO DETERMINE SPECIFIC QA I PROGRAM APPLICABILITY. THIS DWG SUPERSEDES@DWG 882D612 Kif..,,,,,,

14{"{13 AS BUILT DATE RELEASED FOR ENGINEER f\\ REVISED PER

~ ADC-13-001146 RJ M }(R{ -r'R{ f'(/\\ 10/15/13 lrJ/ts-/t3,,fr.;-1!3 10/,,/13 ,__R_EV~ ___ R_EV_IS_ED_FO_R __ ___, DRAWN CHECKED RESP REVIEWER FACILITY GINNA BY BY ENGR SCALE NONE CAD FILENAME 33013-1353,3 R.E. GINNA STATION ONTARIO, NY TURBINE TRIP SIGNALS LOGIC DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 CCD 4 I ICNTRL COPY#

i TRIP

  • 52/AVP-98 UNIT 29 TRIP 52/FPlB.

UNIT 25 ~160V BUS llB 7 VOLTAGE SEE OWG. 10905~16 2 -l/llB 4160\\i :SWGR 1_---UNIT 21 _ __,.,.. 212 MCB AGA S2/27 l11B \\.. '.,/ LO; ON PICK-UP 15 SEC. 52b/BJPl*B 52b/12B . ~ 112) 52/12AX 52/12BX ~ 112) y SYNCH CHECK 25BX *

i.

212 FROM SHEET 3. 4160V BUS llB

  • FAULT 86/HB MCB SEE DWG~

10905-44 4160V BUS llA FAULT 86/llA MCB . SYNCH CHECK 25AX 212 52/12AY 52/12BY 52b/BIA-8 52b/11A f l/2' ' --- --- -I 86XI

  • l 112 I TRIP TRIP 52/RCPlB

... 52/HDP!B UNIT 24 UNIT 27 TRIP 52/CPIB UNIT 26 81-1/llB 4160V BUS llB FREQUENCY 4160V SWGR TRIP 52/CWP!B UNIT 28 81-2/llB i--- UNIT 21 ---t. 1.. 1--+......,.1---e BUS DIFFERENT IRL 868/128 x 12B BUS FAULT 86/12B x '~--...,..-.----. TRIP

  • TRIP 6/6

~ 112) ~ --- CLOSE TRIP . 52/EFlB. 52/15SS

  • UNIT 30 52/8TB-B UNIT 20 52/118 UNIT 23 81-1/l!A 4160V BUS llA FREQUENCY 4160V SWGR 81-2/llA i--- UNIT 11 ---i UNIT 22 SEE OWGS.

10905-15 t. 37 112) .TRIP 52/l!A UNIT 10 .. iX 6/6 CLOSE 52/8TA-A UNIT 12 12A BUS FAULT 86/l2A x BUS DIFFERENTIAL 86B/l2A.* l 112 I TRIP TRIP 52/FP!A UNIT 7 52/RCPlA UNIT B 4160V BUS !IB. VOLTAGE 4160V SWGR 27-3/l!B 27-4/llB TRIP 52/HOP!A UNIT 4 27-3/llA TRIP 52/CPIA UNIT 6 1160V BUS llA VOLTAGE 1160V SWGR 4160V BUS llA 27"'1/llA VOLTAGE 'I.. 4160V SWGR L--- UNIT 10 --...i 27-2/llA 2/2 MCB AGA. 52127 /llA \\. J T.O. ON PICK-UP 15 SEC. ~ l/2 I TRIP 52/CP!C UNIT 5 27-4/llA TRIP 52/EF!A UNIT 9 TRIP 52/CWPIA UNIT 3 SEE OWG. 10905-15 TRIP 52/!3SS UNIT 1 TRIP 52/AVP-9C .UNIT 2 NOTES: 4525. l 4160V SWGR ~l_.{ t THE UNDERFREQUENCY RELAYS ARE SET TO TRIP AT 57.7 HERTZ. THE TIME DELAY BETWEEN REACHING THE s.r.R. ~IN. I VALUE ANO PASSING ON THE SIGNfll TO THE RCP TRJt!.., 'UITS IS APPROX. 0.5 SEC. ~**, =*.,.*

2. 27-'l/llA <Bl ANO 27-2/llA (8) ARE SET AT 82 VOL TS,

<'1200-120 PTl l TIME LEVER. ...,__UNIT 22 ---i SEE DWG 10905-48 t. 317 i--- UNIT 10 _ __, 27-3/!lA <Bl ANO 27-4/llA <Bl ARE SET flT 90 VOLTS M 200-120 PTl; RACK 2 ' S!Xl \\. \\JJB I T -~ RACK 4J SlX2\\ ., 11B.' ~-T~ <NOTE n .I 112) "( ~-------. RACK 1 J SIX! ' 1 llA 1 T 212 REACTOR TRIP LOGIC <SEE SHT. 2) RACK 3 {S!X2' , l!A J T I 112 > I RACK 2 27X3/11B AGA .2 SEC T.D. DROP OUT

1.
1.

RACK 4 /\\. 27X 4 /118 /\\ ~ RGA ~ ,,__>r-.,,, .--;i-- \\ I J.2 SEC T.D. \\ , l -.., V DROP OUT, "- :,.." j 112 RACK l 27X3/llA /\\ AGA ~ .....-4~ .2 SEC T.l). ~.I DROP OUT -., ~ (NOTE 2,3) 212 REACTOR TRIP LOGIC <SEE SHT. 2)

1.

RACK 3 . 27X4/11A /\\. RGA ~ .,..._,r.-, .2 SEC T.ll. \\ . J DROP OUT.* "'- V l/2)

3.

THE UNDERVOLTAGE CONDITION GENERATES A LOGICAL CONDITION OF 'TRUE" (VALUE OF 1), WHICH IS DELAYED BY 27X3/11A(B) & 27X4/11A(B). THIS DRAWING INCLUDES PORTIONS OF CLASS IE ELECTRICAL SYSTEMS.. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. THIS DWG SUPERSEDES 11. DWG 8820612 1~~1 ctlANGE PENDING REVISED PER ADC-13-000890 ORIGINAL RJM 8/5/13 INITIAL BR JC:L GG GWO ORTE 12116/82 1Vl6/82 *J2/16/82 12117182 NO. REV.IS ION. DRAWN CHKO RESP. ENG. i-C~AO~FIL-E-NA_M_E-~36=!=35=3~04~.~_, BY ENG. MANG'R CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED.. pREUMINRRY NOT FOR CONSTRUCTION 81DO'IN6 PURPOSES AS BUil T

  • ffe?

ATE RELEASED' FOR ,. ENGR * . FACILITY GINNA IR.E. GINNA STATION! ONTARIO, NY j SCALE NONE LOGIC DIAGRAM ELECTRICAL PROTECTION LOGIC JOB NO. DRAWING NO. ,~ SHEET. REV. 33013-1353 04 4

  • ccn 4 I I

27 /17 27D/17 480V BUS 17 UNIT 25A UNDERVOL TAGE 27-B/17 27D-B/17 l_ ~ ~---~ 2/2 SI SIGNAL <SHT. 6) TRAIN B


----- ---------- --- 27 /16 27D/16 480V BUS 16 UNIT !!A UNDERVOL TAGE 2/2 27-B/16 27D-B/16 480V BUS 18 UNIT 31A UNDERVDL T AGE

~- ---- ----- -


~

e-- -- -- --1-------1------1--e----1--- ----@t----1----@>----------------1-----~ T TRIP 480V 52/*

  • S\\JGR l_ 52/S\\JPI~ ~NIT 27C 52/S\\JPID UNIT 27D SEE D\\JG, 10905-82A & B A

{ (/) Q_

0 Q_

°" w f- <[ w u ~ °" w (/') I 1/2 TRIP l_ I 2/2 SI SIGNAL TRAIN A TRIP --1--- 112 I ~ 2/2 2/2 TRIP TRIP 52/ll: *

  • 52/BT 17-18 UNIT 28B

<BUS TID 52/17 UNIT 25B <480V) 52/17 SS UNIT 18 (4160V) 52/FP UNIT 26D 52/IH!B UNIT 27 A 52/IHlD UNIT 27B 52/MCC-G2 UNIT 26C SEE D\\JGS. 10905-80, 91 & 100 ( °" CJ f- '-"' CJ (/) "" °" O::::'. w:=: w (/') z: ~~w n..._wDLJ

c :c
0

_J o...wzo "" w °" w<r:WI-Q,::'.j--0::::'.:Z -zUO L,,_,.__. (/) LJ I I I TRIPPED SEE D\\JG. 10905-63 52/17 SOLID STATE OVERCURRENT TRIP (74-1/17) IX <ON GENERATOR B ONLY) 480V S\\JGR 52/EGIB3 <MANUAU /~NOTE 2) SEE D\\./G. TRIPPED 10905-29 SEE D\\./G, 10905-6 7 I -l/EGIB2 <AUTO) 2/2 1/2 4/4 -1/EGIB2 <MANUAL) CLOSE i CLOSE 4~~)EJi~¥R foE9E05~Yo~ UNIT 25C CLOSED CLOSED 2/2 480V BUS 17 <TRAIN A ENERGIZED 27 /18) 27 /17 I 2/2 CLOSE 52/S\\./PlB DR 52/S\\JPlD <PB4) START PUSHBUTTON MCB I SEE D\\JG. ( 115 l 33013-710B \\:_;/ 43/EGIB-~ <REMDTD R3 RESET 3/3 <PB6) 1/EGIB ST ART START PUSHBUTTON MCB LOCAL l/EGIB <PULLOUT>

  • x I

43/EGIB- <LDCAU 2/2 112 2/2 2/2 TRIP 52/16SS UNIT 17 (4160V) 480V BUS 14 UNIT !BA UNDERVDL T AGE l_ 2/2 1/2 SI SIGNAL TRAIN A TRIP TRIP TRIP 52/16 UNIT llB (480Vl 52/BT 16-14 UNIT 12C <BUS TID 480V 52/BT 16-15 UNIT 12B mus TID M 212 I y <NOTE 3) / TRIPPED SEE D\\./G. 10905-66 TRIPPED SEE D\\./G. 10905-62 SEE D\\./G. 10905-61 2/BLB 40 SEC. START DIESEL GEN, B ST ART <Rl OR R2) CIRCUIT DIESEL GEN, B ALTERNATOR OUTPUT 480V I y > t=lO SEC. MAX. TO SAFEGUARDS SEQUENCE <SHT. 8) SEE D\\./G. 10905-27B l/EG1Bl I (AUTO> t l/EG1Bl - <MANUAU CLOSE 2/2 1/2 414 480V 52/EG!Bl UNIT llC CLOSED 52/16 SOLID STATE OVERCURRENT TRIP <74-1/16) x CLOSE SEE D\\JG. 10905-102 480V BUS 16 <TRAIN A ENERGIZED 27 /14) 27 /16 I { 112 2/2 TRIP 480V 52/CCPIB UNIT 16B SEE D\\./G, 10905-72B Q_

J Q_

z: - _J CJ Cl (_) f-

z:

w

z:

CJ Q_ CJ u I \\ 112 TRIP 480V 52/*

  • 52/CHP!B UNIT !SB 52/CHPlC UNIT !SC 52/PHBG UNIT 16A 52/SFPP2 UNIT 17A SEE D\\JGS.

10905-71, 90 & 108 { (U Q_ °" w

0 f-CL

<[ (/) w a... f--- 0.. :c :=i 1--1 CJ CL ~Ct::: ts _J 0.... k:l w L:J 1--1 Q_ :::J

z: Ct::: ~

w.... I L'.J (/) ~ 1-Q:'.: (/) (._) Z: <CW<CW I Ct::: IXl 0.... u Q_ V') I I I \\ TRIP 480V 52/ll: *

  • 52/S!PlB UNIT 12A 52/SIPlCl UNIT 13A 52/CF!B UNIT 13C 52/CF!C UNIT 14A 52/MAFP!B UNIT 14C 52/RHRPIB UNIT 15A SEE D\\JGS, 10905-73B, 74, 77, 78B, 94 & 95 A

{ I I l l { 2/2 R-lD RELAY TRIP MCC D UNIT 4B NON-SAFE GUARDS LOAD SEE D\\JG 10905-118 A °" '-"' w zC-

z:

""w _JLJ ~

0 _J

""CJ . °" Xf-

0 z:

<[CJ u °" CJOo'. f-CJ Uf- <I: CJ w"" °" I THIS D\\./G SUPERSEDES \\J D\\JG 882D612 NOTES: L SHO\\./N FOR TRAIN B <DIESEL GENERATOR B). TRAIN A <DIESEL GENERA TOR A) IS SIMILAR. <

REFERENCE:

33013-652 480V ONE -LINE DIAGRAM,) 2 BUS 17 4160V/480V STATION SERVICE TRANSFORMER BKRS.

3.

BUS 16 4160V I 480V ST A TIDN SERVICE TRANSFORMER BKRS. CLASS 1 E AS BUILT I DATE RELEASED FOR ENGINEER As BUILT PER ocR RMs c~J11 -:r.11*'"' ~ 2001 -0051 REV'D R3 RESET SYMBOL 3/6/01 l~h! '3/~(;!/ '3/C/{Ot 1--R_EV-'-___ R_E_VI_SE_D_F_OR __


J DRAWN CHECKED RESP REVIEWER FACIUTY GINNA BY BY ENGR 1-s_cA_L_E ----c-cN_O""'N'""'"E-,-----1 ROCHESTER GAS & ELECTRIC CORP.

CAD FILENAME 3G135305 ROCHESTER, NEW YORK ELECTRICAL LOGIC DIAGRAM EMERGENCY GENERATOR "B" STARTING JOB NUMBER DRAWING NUMBER SHEET REV 5282 33013-1353 s£ ~C_C_D_4_ ICNTRL COPY#

i~"'=**~,,,_7--**"w>""--'*'""""""""""""'"'"*-*"*~"'=""--"""">"=---~,..-"'*'"'""""~-**-""""'"""==="=l'-.*'-~...,..,,_,=w.--"'-~-"..,_"".:="""'"'~=,,,...... "'.""'"*~'-'"'*~-=-=,-=-,,.~"'-~-,,,=""'"=-=""=~~"'"'..,,_._~~-=-=~*~-=*=~'~-~.,~~~~==ii,,,,,,,,,,,,,,,,,,,,,,.==w~~==='""'~----~--~-~~~~=---~=-=---,--~-~*==<.1~-, ... -=.. =-=,~*==-'-=,,_---"-""-"'*==~*==""~=,,, ..,,=~-m=-.-'"-~*===-=,-~-~-,~~-=~----~-~--"""""~~~-~---*~~~*--~ .. ~ .. -....~--=---~~=-*-,*~*! I 2/4 LOW TAVG (SHl 14) T 1 (Fc\\ ~~ 1/2 SEE DWG. 33013-661 2 LOOP A 2 _r G26 --& SEE DWG. 10905-396 2/2 MS1 (TR. A) MS2 (TR. B) SEE DWGS. 33013-660 & 662 STEAM LINE 2/3 SEE DWG. 10905-396 llil-.,/R 021 SEE DWG. 10905-378 3 ~ __[ T HI 1/2 PRESSURIZER LOOP B SEE DWGS. 33013-661 & 662 3 1/2 G31

  • -&SEE DWG.

11/1905-397 SEE DWGS. 3311113-660 & 662 2 SEE DWG. 10905-396 2/3 SEE DWGS. 33013-660 & 662 --~ MANUAL SI BLOCK 1-. 2/3 (MOMENTARY) NOTE 2 r RESETS S!-B1 SI-82 1/2 +---cv --~LJ~ l~ Sl-B1 (TR. A) SI-82 (TR. 8)


~-*-----------

2~ ~l D22 <t't-& SEE DWG. L ___ 10905-379 ~~~--~,...,..,._,,.,, SEE DWGS. 33013-660 & 662 ~---~ 2 3 l T ~ C27 SEE DWG. ........... ~~~ 10905-371 2/3 2/2 D19 -.& SEE DWG. 11/1905-378 J I *----0 SI-A 1 (TR. A) SI-A2 (TR. B) 1/4 ---{ii) R L R L SHT. 07 SI-M1 (TR. A) Sl-M2 (TR B) MANUAL RESET SI (AUTO + MAN) PB/PSI 2/2 SHT. 07


SI-10X--~~--*--------8 (TR A)

SHl 07


*~-------*---

1/2 SI-20X ,---* -------~--------------**------- --**---*-*-----~---*~-~--J (TR. B) I ------------------------------------*-------.--------*-----------------~. ~----------*-----~-~~--------~. ------*-*-----~-----*-------......

  • ~-----------**- ------*------~-------

~- --=-- ----------0 SHl 07 r-**-------~. ----*~-- I ~----------------*---*--------*--*---- -----~-----*---.. --.. -=----~~~~-------- -------=~~ ------------------0 SHT. 0 7 T '~--~o-W*~~~*= .. ~* _,.-~~'*'*~---='-'"'-' ,_,_,~,~*~*=-~--~------ -*.e'-c--- EMERG. DIESEL (SHT. 8) ~ 1~ ~~ ~-&G~~E DWG. ~~G~~E DWG. c & -OTHER ACTUATIOI~ '1 10905-394 I 11/1905-39;) i r SIGNALS (SH. 9) ~ I I r S1EAJ LINE J [-STEA~~ LIN.El c* FfEDWA~ER-ISOLATION ISOLATION ISOLATION LOOP A -** LOOfl!_____ J~HT_._ 9_)_~ REACTOR TRIP LOGIC (SHT. 2) OTHER ACTUATION 1---~-------------------*---*----**---*---**-*------~---~---------. -----~.

  • SIGNALS 1**----**--**-----*-*------.-------~-----~--. -

(SHT. 9) l" r-* ~-------*~* - _J__ -- [ __ i<. __ J ~***

        • ------~ c: __ 1= _____ L::__ - ---~*

AUXILIARY SAFETY SERVICE WATER RESIDUAL HEAT FEEDV(~~~R 0UMPS INJECTION --- FAN COOLING-- P~~A~-START REMOVAL PUMPS SAFE GAU RDS SEQUENCE FINISHED (SHl 8) THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLJCABILITY. THIS DWG SUPERSEDES W DWG 882D612 NOTES:

1. PC-479A IS FED FROM A SEPARATE INVERTER (MQ-483)

SUPPLY WHICH JS CONNECTED TO 1A BATIERY.

2. MANUAL SI BLOCK IS A 3-POSITION SELECTOR SWITCH.

IT IS MAINTAINED IN THE BLOCK POSITION AND IT SPRING RETURNS TO NORMAL FROM THE UNBLOCK POSITION. THERE IS, ONE SWITCH FOR EACH TRAIN

  • - INCLUDES LEAD/LAG COMPENSATION FOR PREVIOUS REVISIONS SEE MICROFILM p:.;--:-12~ q 3* *..

==~~~--- ~=""""=~,,..,-,_,,<>=c_.._ AS BUI.LT EWR 41151'.> 1'111.t!> DATE RELEASED FOR E'NGINEER 6 ~. ~. 11 AS BUILT PER DPM 8D S\\ l\\B f¢.B EWR 47738 '-1-S- ~3 ~-9 AS SHOWN 3/22/93 '1-8~ REV REVISED FOR

==!DRAWN CHECKED RESP ENGR FAC!UTY GIN NA BY BY ENGR MANAG SCALE NONE ROCHESl ER GAS & ELECTRIC COR I I I I I ' I ! " I I I I I l i ! i ' ! I I !1 ! I I I ! i I I I I f; ' '

PC 945A 3 947A 2 PC '949A SEE DWG. --r-~- 10905-0371 2/3 HI 2 PC 946A 3 PC 948A ~I C~51 I -~-/ ~3 CONTAINMENT SEE DWGS. 33013-0660, 0661 & 0662 NOTE 1 4 PC 95111A I HI-HI C25 1 PC 945B C25 3 PC 947B 2 PC 949B JT 2/3 C25 HI-HI A28 A 6 NOTE 1 3 4 PC PC 948B 950B ~ A. C25 C25 SEE DWG. 1091115-0363 2/2 CONTAINMENT HI-HI PRESSURE SIGNAL 2/3 5 A C25 HI-HI A28 A 6 SEE DWG. 33013-0662 MANUAL SAFETY INJECTION PB/MSil PB/MSI2 1/2 CONTROL BOARD SEE DWG. 33013-0663 MANUAL STEAM LINE ISOLATION LOOP A PB/MMSl MSl (MS2) MANUAL STEAM LINE ISOLATION LOOP B PB/MMS2 MS3 (MS4) SEE DWG. 33013-111664 MANUAL MANUAL SPRAY CONTAINMENT ISOLATION PB/MS1 PB/MCl PB/MS2 PB/MC2 2/2 i n--*---------- 1 I AIR PARTICLE ~ 11 CONTAINMENT RADIOACTIVITY DETECTORS K850 Rl 1 I SEE DWG. 33013-111664 RADIO GAS MONITOR RC K850 12 R12 _f E16 SEE DWG. E16 10905-0038 1/2 TRAIN A SI TOXIC GAS A MANUAL r CL NH3' ISOLATION TRAIN A TRAIN A PB/ X6850J8J CR1A I 1/6 CONTROL ROOM RADIATION MONITOR TRAIN A TRAIN B 8 R46 I SEE DWG. 10905-0546, 1 D28 ~------- --------------------------------------------- A SHT. 1116 SHT. 06 R B SHT. 06 SEE DWG. 10905-038111 SHT. 06 81----------------- ------~ SHT. 06 8(;\\ SHT. 06 GI--------------* SEE DWG. 33013-0662 Sl-17X Sl-16X SHT. 06 0----------------- rni=~~~l 52/14-UNIT 18B 52/16-UNIT 11 B NOTES:

1. PC-950A AND PC-950B ARE FED FROM A SEPARATE INVERTER SUPPLY WHICH IS CONNECTED TO 1 A SUPPLY.
2. THIS DRAWING CONTAINS A PORTION OF 33013-1353 SHT. 6, REV. 2.

~---NORMAL SUPPLY 480V BKR TRIP -r-~~ SEE DWGS. 10905-0664 2/2 THRU 0675 MCB CLOSE SERVICE NON-SAFEGUARDS ISOLATION VALVES 42/* *

  • SHMV-lAl (SHMV-1A2)

ABIV-1 Bl ABIV-182) ABIV-1A1 ABIV-1A2} ACIV-1A1 ACIV-1A2 TBIV-1A1 TBIV-1 A2 TBIV-181 TBIV-182) MANUAL RESET (MOMENTARY PB) 2/2 I /\\ A27 ~SEEDWG. 10905-0362 CONTAINMENT SPRAY THE CONTENT OF 33013-1353 SHT. 7, REV. 0 HAS BEEN REDRAWN TO 33013-1353 SHT. 8, REV. 2. THIS DWG SUPERSEDES '!{ DWG 882D612 2/2 MANUAL RESET (MOMENTARY PB) I 2/2 A26 r----& SEE DWG. SEE DWG. 33013-0664 _J 10905-0362 ~C-0-NTAINME~-l ISOLATIO~ MANUAL RESET (MOMENTARY PB) 2/2 2/2 CONTAINMENT VENTILATION ISOLATION A25 A SEE DWG. 10905-0362 1/4 PURGE 1/ HS-88 SEE DWG. 10905-0542 CONTROL ROOM PURGE AKD01, AKD04 - OPEN El 1 SEE DWG. 10905-0384 RESET A TRAIN CREATS START AND CONTROL ROOM ISOLATION AKD02, AKD03, AKD21, AKD22, AKD23, AKD24 - CLOSE CREATS FAN AKF10A STARTS THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. TRAIN B SI TOXIC GAS CONTROL ROOM RADIATION MONITOR ~~A MANUAL r CL NH3 1 ISOLATION TRAIN B TRAIN B TRAIN B TRAIN A ~ X685~ X6853J R46 R45 1/6 SEE DWG. 10905-0546,2 El 1 SEE DWG. 10905-0384 RESET 8 TRAIN CREATS START AND CONTROL ROOM ISOLATION AKD02, AKD03, AKD21, AKD22, AKD23, AKD24 - CLOSE CREATS FAN AKFl 0B STARTS AS BUILT DATE RELEASED FOR ENGINEER f\\ REVISED PER PCR LD 2003-0037, REV. 1 1---REV~ ___ R_EVI_S_E_D _FO_R __ _, DRAWN CHECKED RESP REVIEWER FACIUTY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD flLENAME 3G135307 ONTARIO, NY ELECTRICAL LOGIC DIAGRAM SAFEGUARDS ACTUATION SIGNALS JOB NUMBER DRAWING NUMBER SHEET 33013-1353 7 CCD 4 CNTRL COPY# REV

I

r:

u; . CJ en (/) c "' rn

0

(/) rn CJ rn (/) CJ Ci) ro ro N CJ

0) -

N c... 0 co z 0. w wo (S) :0 ,_. :0 w"" I z ,_. G"> Wz CJ1 0 w (]) (S) I CD hi (/)

D

'1 rri, G)C) CG)

I)_
on CJ

(/)CJ (/) ::D rr1 G) o:o c:o rr1 3: z n rr1 15 Ci) z: z: rn z:

D zm rn r

"' m n o~

o n 7'< n 0 :0
o 0 ()
0 I lJ ffl z 0

1-i z (j) 2/871A \\.. I,.) 3 SEC. SEE DWG. 1090S-620 CLOSE MCC C POS. llC MOV 871A SI SIGNAL TRAIN A (SHT. 6l I Sl-10X SAFEGUARDS TRAIN A 480V BUS 14 UNDERVOLTRGE 27 /14 270/14 I l._ ~ 1/2 2/2 278/14 270-8/14 I l._I 112 ) y 52/SIPJC2 OPEN 278/16 270-8/16 I l._(112) T SAFEGUARDS TRAIN B 480V BUS 16 UNDERYOLTAGE 27 /16 270/16 I l._ ~ 1/2 212 x --""". x ~ 52/SIP1C2 .. I ALM SWITCH x 313 2!2v ~ SIS SEE DWG. ~----~J--~~t-1 PIA *. 1090S-73A \\. I.) 2/1C2X 30.SEC. SAFETY INJECTION PUMPS SAFETY INJECT ION PUMP lC RESIDUAL HEAT REMOVAL PUMPS SERVICE WATER PUMPS CONTAINMENT A IR RECIRCULATION FANS CONTAINMENT AIR RECIRCULATION FANS MOTOR OPERATED AUX FEEDWATER PUMPS z: 0 - _, [TJ (/).. 480V SWGR 52/SIPlA UNIT 20A 313 CLOSE x .-x..__ _ ___. 2/SIP1C2 \\.I.) S SEC. SEE DWG. 1090S-7S CLOSE 480V SWGR S2/SIP1C2 UNIT 19A 2/RHRPlA \\._ l,.1 10 SEC. SEE. DWG. 1090S-78A CLOSE 480V SWGR S2/RHRP1A UNIT 22A lS SEC. \\ J 2/SWP!A 52/SWP CLOSE SIGNAL TRAIN A (SHT. SJ I 112) SSS-TWO POSITION SWITCH TO SELECT EITHER PUMP lA 212 CLOSE 480V SWGR 52/SWPlA UNIT 29C 2/CFlA \\. L/20 SEC. SEE DWG. 1090S-94 CLOSE 480V SWGR S2/CFJA UNIT 23C 2/CF!D \\..I,.) 25 SEC. SEE DWG. 1090S-9S CLOSE 480V SWGR S2/CF10 UNIT 20C 2/MAFPJA \\.. L/ 30 SEC. TO AUX. FEED PUMP 52/MAFPJA (SHT. 91 2/SFJ \\..L/1-2 MIN SAFEGUARDS SEQUENCE FINISHED (SHT. 6J OR PUMP IC SEE DWG. 10905-81 SEE DWG. 10905~?6 SEE DWG. 33013-662 112 2/2 CLOSE 480V SWGR 52/SWP!C UNIT 29D 2/8718 \\.. l./ 3 SEC. ~12 SEE DWG. SIS 1090S-738 P IB SEE DWG. 10905-621 CLOSE CLOSE 480V SWGR 52/SIP!B MCC D POS. llC MDV 8718 UNIT 12A 2/2 2/SIPlCl \\ J? SEC SEE OWG.~t CLOSE 1090S~74 480V SWGR S2/SIP1Cl UNIT !3A 2/RHRPlB \\ ..I 12 SEC SEE DWG. 1090S-78B CLOSE .480V SWGR S2/RHRP1B UNIT !SA S2/SWP CLOSE SIGNAL TRAIN B (SHT. Sl 2/SWP!B \\.. I_/ 17 SEC ~ 1/2) 2/2 CLOSE 480V SWGR 52/SWP!B UNIT 27C l SSS-TWO POSIT ION SWITCH TO SELECT EITHER PUMP 18 I 112 OR PUMP ID SEE DWG. 1090S-82 2/2 CLOSE 480V SWGR 52/SWPID UNIT 270 2/CFJB \\.. l./ 22 SEC. SEE DWG. 1090S-9S CLOSE .480V SWGR 52/CFJB UNIT 13C 2/CFJC \\..I,.) 27 SEC. SEE DWG. 1090s~94 CLOSE 480V SWGR S2/CFJC UNIT 14A 2/MRFPIB \\.. l./ 32 SEC. TO AUX. FEED PUMP S2/MAFPIB (SHT. 9l 2/SF2 \\ 1 1-2 MIN SAFEGUARDS SEQUENCE FINISHED (SHT. 6) I SEE DWG. 10905-77 SEE OWG. 33013-662 SI SIGNAL TRAIN B (SHT. 61 I Sl-20X I I

I STM. GEN. A 2/3 HIGH LEVEL (SHT. 13) FCV-466 (MAIN) 1/2 F-10X (F-20X) CLOSE FEEDWATER ISOLATION SI SIGNAL (SHT. 6) STM. GEN. B 2/3 HIGH LEVEL (SHT. 13) SEE DWGS. 33013-665 10905-274 10905-733 THRU 736 I 1/2 TRIP 52/FPlA (NOTE 1) 4160V SWGR UNIT 7 TRIP 52/FP1B (NOTE 1) 4160V SWGR UNIT 25 SEE DWG. 10905-30 F-30X (F-40X) F1 CLOSE CLOSE F3 (F4) CLOSE (F2) FCV-480 (BY-PASS) FCV-476 (MAIN) MAIN & BY-PASS FEEDWATER CONTROL VALVES (NOTE 3) FCV-481 (BY-PASS) TRIP CLOSE FEEDWATER ISOLATION VALVES /\\ 3994, 3995 ill SEE DWG. 10905-0833 52b/FP1A FEEDWATER PUMP BREAKERS OPEN 52b/FP1B .-------1-. 2/2 SEE DWG. 10905-317 I 2/2 SEE DWG. 10905-76 AUTO 1/MAFP1A t 0iJ 480V BUS 14 REMOTE 43/MAFP1A - -S-I-SI-G-NA_L ____ ~ ~-ENERGIZED SI-11X 27/ 14 TRAIN A -x~ REMOTE (SHT. 6) 43/MAFP1A SAFEGUARDS SEQUENCE TRAIN A 3/3 (SHT. 8) 5/5 START 1/MAFP1A MANUAL START PB LOCAL 43/MAFP1A -~. 2/2 I OPEN ASSOCIATED PUMP DISCH. VALVE AFDV-1A (V4007) MCC A SEE DWG. 10905-659 CLOSE ALL BLOWDOWN ISOLATION VALVES OF STEAM GENERATORS V5737, V5738 SEE DWG. 10905-739 SHT. 1 & 2 START 52/MAFP1A 480V SWGR. 2/2 STEAM GENERATOR A 2/3 LO-LO LEVEL (SHT. 13) AUXILIARY FEEDWATER PUMPS STEAM GENERATOR B 2/3 LO-LO LEVEL (SHT. 13) LOSS OF 4KV VOLTAGE 1/2 2/2 SEE DWGS. BUS 11A 10905-15 & 317 (NOTE 2) BUS 118 (NOTE 2) SEE DWG. 10905-16 4160V SWGR. 27X1/11A UNIT 11 27X2/11A 4160V SWGR. UNIT 21 27X1/11B 27X2/11B SEE DWG. 10905-77 I T 1 I AM SAC 62/11A \\_L) 3-15 SEC. 67/11B \\_L} 3-15 SEC. 2/2 480V BUS 16 (2_;iJ AUTO 1/MAFP1B MANUAL OPEN __ ----------~ V-3505A OPENS MANUAL OPEN __ V-3504A CLOSE ENERGIZED-~ ~-----SI-SIG-N-AL-27 /16 SI-21X V-3504A & V-3505A REMOTE ~x TRAIN B 43/MAFPl B (SHT. 6) SAFEGUARDS - SEQUENCE TRAIN B REMOTE 43/MAFP1B START 5/5 1/MAFP1B (SHT. 8) 3/3 MANUAL START PB 2/2 START 52/MAFP18 480V SWGR. CLOSE ALL SLOWDOWN ISOLATION VALVES OF STEAM GENERATORS V5737, V5738 SEE DWG. 10905-739 SHT. 1 & 2 OPEN ASSOCIATED PUMP DISCH. VALVE AFDV-1B (V4008) MCC B SEE DWG. 10905-600 LOCAL j~*43/MAFP1 B _,.I---'~ 2/2 I THIS DWG SUPERSEDES W. DWG 882D612 10 ON TDAFW AUTO START ONLY ALL BLOWDOWN ISOLATION START TURBINE DRIVEN AFW PUMP THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. VALVES OF STEAM GENERATORS V5737, V5738 SEE DWG's, 10905-0739 & 10905-0740 8/ i 4-1 <>B DATE NOTES:

1.

FWP BREAKER TRIP CAUSES CLOSURE OF ASSOCIATED PUMP DISCHARGE MOV. V3977 FDV-1 A MCC A (V3976 FDV-18) MCC B SEE DWGS 10905-654 & 655

2. 2 CONTACTS PER BUS.
3. 2 SOLENOID VENT VALVES PER FCV.

DE-ENERGIZE TO VENT.

4.

THIS DRAWING CONTAINS THE INFORMATION THAT WAS PREVIOUSLY FOUND ON 33013-1353 SHT. 8, REV. 1. AS BUILT RELEASED FOR ENGINEER REVISED PER AJV3 /41-L-e.nj

f,4,/

OCR 2008-0148 PCR 2004-0057, REV.1 8/7/0JJ ~Ji{rf(, '}t1/c$ ?/r4fccg r----REV ____ R_EVIS_ED_FO_R __ DRAWN CHECKED RESP REV!EwEF FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G135309 ONTARIO, NY LOGIC DIAGRAM FEEDWATER ISOLATION ELECTRICAL & AUXILIARY FEEDWATER PUMP JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 9~ CCD 4 I ICNTRL COPY #

RACK 1 () R~K l r ' N('\\ _J I 31£/ TR IP BYPASS x l/N 318 -e-...t (NIS RACKl SEE DWG. 10905-383 313 RT 13 RT 14 RACK 3 l/N 33A LOGIC TRAIN A l/N 338 LOGIC TRAIN B SOURCE RANGE REACTOR TRIP LOGIC SEE DRAWING 33013-2i:J95 SHTS. 5, 6, 15, 36, 37 & 46 RACK 2 MANUAL BLOCK

  • MOMENTARY l/N 33 P-6 (CONTROL BOAROJ (SHT. lll DE-ENERGIZE SOURCE x

RANGE H-Y (BOTH A & B LOGIC TRAINS REQ'OJ e-___,... RACK 2 ENERGIZE SOURCE RANGE H.Y (EITHER LOGIC TRAIN) p ~ 112) .--"fiR D26 HIGH NEUTRON FLUX REACTOR TRIP (SHT. 2) SEE DWG

  • 10905-380 RACK 2 r il"'NC\\_J 1 32.!ll B

X RACK 2 -...i TRIP BYPASS 3/3 RT 13 RT 14 RACK 3 l/N 32B (NIS RACKl SEE DWG. 10905-383 RACK 1 TRIP BYPASS x l/N 35A ----t i-~ (NIS RACK) L ~E7 SEE DilG. l t 10905-383 TO IR ROD STOP (SHT. 11)

  • l/N 38R LOGIC TRAIN A l/N 38B LOGIC TRAIN B 313 INTERMEDIATE RANGE REACTOR TRIP LOGIC SEE DRAWING 33013-2095 SHTS. 6, 13, 37 & 44

.------RACK 2 RA.::.-2 I J NC' 1 36F j MANUAL BLOCK

  • MOMENTARY l/N 38 (CONTROL BOAROJ

~.---P-10 I 212 x (SHT. JD OTHER LOGIC TRAIN I t 2/2 RACK 2 -~* ( ) rx-~ _*.,..._ RACK 2 .---1 TRIP BYPASS l/N 36R 8 RT 13 RT 14 RACK 3 p TO IR ROD STOP (SHT. Ill ~ 112 _,R Dl8 HIGH NEUTRON FLUX REACTOR TRIP (SHT. 2l SEE DWG. 10905-378 E7 L ~ l 3/3 TO IR ROD STOP RT 13 ($HT* II) RT 14 RACK 3 (NIS RACK) SEE DWG. 10905~333 T POWER RANGE REACTOR TRIP LOGIC SEE DRAWING 33013-2095 SHTS. 4, 6, 35 & 37 Gr T Gr

  • l RACK 4 MANUAL BLOCK
  • MOMENTARY l/N 47 (CONTROL BOAROJ 112 )

...; ~- P-10 (SHT. 11) 2/2 OTHER LOGIC TRAIN I + ) 2/2 2/4 RACK 4 (114) x E27 e I ASEE DWG. ""110905-385 2/2 m SEE DWG. Dl010905-376 HIGH RANGE REACTOR TRIP LOW RANGE TRIP RT13 RT14 RACK 3 ~ 112 HI NEUTRON FLUX REACTOR TRIP (SHT. 2) NIS RACKI NIS RACK 2 NIS RACK 3 'NCI. {NC, JNC\\ s \\!_IR / s \\!_2R t s \\.!_3R I . ~19 i;_J9 !il9 T 1--_._,.~A. ~ \\.!) lJ;l.l, 2 2 2 SEE DWG. 10905-385 2/4 NIS RACK 4 ,!"'NC\\ r 44.V _J El9 A \\.!} ~ 2 RT! RT2 RACK I ~ D2 SEE DWG. 10905-374 HIGH RANGE TRIP

  • l/N 47A LOGIC TRAIN A l/N 478 LOGIC TRAIN B SEE DWG. 33013-2095 SHTS, 17 & 48 THIS DRAWING INCLUDES PORTIONS f\\

OF CLASS lE ELECTRICAL SYSTEMS. LJ REFER TO NOTES AND SPEC IF ICAT IONS 11----:---r-----------+----+--+---..+--_. TO DETERMINE SPECIFIC QA f\\ PROGRAM APPLICABILITY. LJ CHANGE PENDING /\\ AS BUil T - REDRAWN PER M§.--MJw ~ D !ZLC. -!'\\\\-\\"\\ ffi EWR 4777R EWR-~----- ~~=+-------,,--,--!---+-'--'-'-f--'-..:.:.-t-'-_:_:_m INITIAL 0 ORIGINAL DATE 117191 l-!0-91 /-/d*1 f 1-1<.A\\ ( BR JCL GG GWD 12/16/82 12/16/82 12/16/82 12/17 /82 DRAWN RESP. ENG. BY CHKD ENG. MANG'R NO. REVISION CAD FILENAME 38135310 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES RS BUILT DATE RELEASED FOR ENGR. ._F_AC_l_L l_T_Y _G_IN_N_A ____ __, ROCHESTER GAS & ELECTRIC CORP. SCALE NONE ROCHESTER, NEW YORK THIS DWG SUPERSEDES II_ DWG 882D612 LOGIC DIAGRAM NUCLEAR INSTRUMENTATION TRIP SIGNALS (~ ~, r--J=o=-B-:-N=o-. ---,,------=D-=-RA=-w""'1N"""G~No=-.---~S-HE_E_T~R-E-V.~ 33013-1353 10 11\\ CCD 4

RACK 1 RACK 2 _f ff----@ SEE DRAWING 33013-2095 SHTS. 12 & 43 SEE DRAWING 33013-2095 SHTS. 1©, 11, 41 & 42 RACK 1 ff----@I NUCLEAR POWER RACK 2 2/4 >Z% RACK 3 POWER RANGE NIS BISTABLES RACK 3 2/4 RACK 4 P-1© (SHT. 1©) RACK 4 NUCLEAR POWER RACK 4 RACK 1 HIGH COND PRESS _f LOSS OF CIRC. WATER PUMPS RACK 3 RACK 4 52 52 AX BX l_ T 2/2 l_ F2l SEE DWG. -&. 1©905-389 2 F21 SEE DWG. -&. 10905-389 2 RACK 1 pg (SHTS. 2 & 3) C0 RACK RACK RACK RACK 1 2 NC 41N I T p 1-----1 3 4 NC NC 43N 44N I I 2/4 > Y% RACK 1 P8 (SHT. 14) CD SEE DWG. 33013-2095 SHTS. 9 & 40 RACK 1 INTERMEDIATE RANGE RACK 1 RACK 2 POWER RANGE RACK 3 RACK 4 P-6 PERMISSNE 2 3 4 SEE DRAWING 33013-2095 SHTS. 7 & 38 INTERMEDIATE RANGE ROD WITHDRAWAL STOP /\\ SEE DRAWING NOTE 1 ~ RACK 1 ff----@ MANUAL RESET MOMENTARY 1/N 39A-- 1/N 39B 2/2 NOTE: _f RACK 2 1/2 2/2 33013-2095 SHTS. 13 & 44 _f RACK 1 RACK 2 FROM IR BLOCK LOGIC --JIY-----, (SHT. 10) FROM 1/N 36A ~-IR BYPASS (SHT. 10) FROM 1/N 35A IR BYPASS (SHT. 10) SEE DWG. 33013-1606 SHT. 4 3/3 3/3 1/2 RS1 ---1A E13 HIGH NEUTRON FLUX (SHT. 15) & NOTE 1 SEE DWG. 10905-384 PERMIT MANUAL BLOCK OF SOURCE RANGE TRIP (SHT. 10) ._-(p INTERMEDIATE RANGE PERMISSNE 6 (SHT. 10) RACK 1 2/2 RACK 2 _f 1/NC41L MANUAL BYPASS NC 42L 2/2 POWER RANGE RACK 3 _f 1/NC42L MANUAL BYPASS 1/4 NC 43L 2/2 RACK 4 _f 1/NC43L MANUAL BYPASS NC 44L 2/2 E21


IA SEE DWG.

OVERPOWER ROD STOP (BLOCK MANUAL ROD WITH-DRAWAL) (SHT. 15) & NOTE 1 10905-385 _f 1/NC44L MANUAL BYPASS -TS 1+TS M.R. NC1/41K NC _f 41K M.R. B -TS 1+TS NC1/42K _f M.R. B -TS 1+TS NC1/43K _f B M.R. -TS 1+TS NC1/44K _f B 2/2 A E7 1 SEE DWG. 10905-383 2/2 A E7 1 SEE DWG. 10905-383 2/2 A E7 1 SEE DWG. 1©905-383 2/2 A E7 1 SEE DWG. 10905-383 B TRAIN ONLY ---<D (33013-2095 SH.45) NIS ROD DROP SIGNAL (1/4) B TRAIN ONLY (SH. 15) /\\ NOTE 1 ~ SEE DWG. 33013-2095 SHTS. 14 & 45 1/4 E28 <11------IA SEE DWG. BOTH A & B TRAIN ---<D 10905-385 <D---A TRAIN ONLY ROD BOTTOM SIGNAL---- (33013-2095 SH.14) (ANY ROD) FROM MRPI SYSTEM (33013-1601) C14 SEE DWG. 10905-370 A TURBINE POWER MISC. RELAY RACK M1 1/2 ROD DROP SIGNAL (SH. 15) NOTE 1 (FIRST STAGE TURBINE PRESSURE) RACK 2 T p PC I 485A SEE DWG. 33013-2095 SHTS. 8 & 39 2/2 > X% RACK 4 P7 (SHTS. 2, 12 & 14) 8 THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPUCABILITY. THIS DWG SUPERSEDES @ DWG 882D612 NOTE: & SAME WINDOW AS ALARM 1 ON SHT. 10 NOTES: CD---A TRAIN ONLY (33013-2095 SH.14) NIS ROD DROP SIGNAL (1/4) A TRAIN ONLY /\\ (SH. 15) ~ NOTE 1

1. AUTOMATIC ROD WITHDRAWAL DISABLED PER ECP-2009-0015.

SEE MICROFILM FOR PREVIOS REVISIONS AS BUILT DATE RELEASED FOR REV.PER ECP-2009-0015 33013-1353, 11 -002 (000) ENGINEER ,__REV~~-_R_EVI_S_E_D _FO_R __ -< DRAWN CHECKED RESP REV!EWE FACIUTY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G 135311 ONTARIO, NY NUCLEAR INSTRUMENT PERMISSIVES AND BLOCKS LOGIC DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 11 & CCD 4 CNTRL COPY#

T SEE DRAWING 33013-2095 SHTS. 19 & 50 PRESSURIZER LOW PRESSURE A I RACK 1 RACK 2 RACK 3 RACK 4 PC l PC l PC l PC l 29 30 431 49 F27 F27 F27 F27 T I\\ T I\\ A A L..B::J. L..B::J. 1 1 1 1 SEE DWG. 10905-390 T P7 (RACK 4) 2/ 4 (SHT. 11) 2/2 RT1 RT2 ~ D20 REACTOR TRIP (SHT. 2) G SEE DWG. 10905-378 PRESSURIZER HIGH PRESSURE RACK 1 RACK 2 RACK 3 _r F26 A 2 SEE DWG. 10905-390 PC _r PC _r 30 31 F26 F26 T 2/3 RT1 RT2 A 2 ~ 6----a-fR T D12 SEE DWG. 10905-376 REACTOR TRIP (SHT 2) G A 2 PRESSURIZER HIGH WATER LEVEL RACK 1 RACK 2 RACK 3 _r F28 T A SEE DWG. 10905-390 LC 27 T 2/3 RT1 RT2 _r F28 A


tlR LC _r 28 F28 T

A 3 D4 SEE DWG. 10905-374 REACTOR TRIP (SHT. 2) e \\ SEE DRAWING 33013-2095 SHTS. 16 & 47 SEE DRAWING 33013-2095 SHTS. 18 & 49 LOW PRESSURIZER PRESSURE & LOW PRESSURIZER LEVEL TRIP LOGIC (SEE SHT. 6) THIS DWG SUPERSEDES @ DWG 8820612 THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. 12./n ~* I AS BUILT t-'-+'-'~--+--+------------j-* DATE RELEASED FOR 6 ~~=::~~A~S:-::cBU~l~LT:--:::P~ER=-----t-:::-D~P~M-:-t-i:;t;7T;\\J*~-t-j-G-P~l%\\c--~-~ OCR 97-0332 & PCR g 7-01.c=2. ______ +-12/_16_/9_7+/l_,_*1 /-+1f-'-'f/1t-+1_)l_n:__r._,t-J;,-*f7_.f_)--I t--R_EV~ ____ R_EVI_S_ED __ FO_R __ __, DRAWN CHECKED RESP REVIEWEF FACILITY GINNA BY BY ENGR SCALE NONE ROCHESTER GAS & ELECTRIC CORP. t-C-AO-Fl-LE-NA_M_E--3-G1_3_5_3-12 __ ROCHESTER, NEW YORK ~------------~-------------- ELECTRICAL LOGIC DIAGRAM PRESSURIZER TRIP SIGNALS JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 12 ~ CCD 4 I I CNTRL COPY #

STEAM LINE PRESSSURE REACTOR TRIP <INCLUDES LEAD/LAG COMPENSATION) <SEE SHT. 6) RACK 1 fLc\\ ~ l_ G28 T\\--...._-IA 3 LOOP A RACK 3 fLc\\ STEAM GEN. LO-LO \\JATER LEVEL SEE D\\JGS. 33013-2095 SHTS. 23, 24, 54 8. 55 AND 33013-1606 SHT. 9 RACK 4 RACK 1 (lc\\ (lc\\ LOOP B RACK 2 (lc\\ ~l_ ~l_ ~~ l_ ~~ l_ G28 G28 G30 G30 T A 3 2/3 T,___..,.___,A 3 I T,__....,___,A 4 RT3 RT4 RACK 4 REACTOR TRIP <SHT. 2l 0 T A 4 2/3 --tR RACK M2 LLSGBA LLSGAA RACK Ml \\ RACK 4 fLc\\ ~~ l_ G30 T A D-6 4 SEE D\\JG. 10905-317 RACK M2 LLSGBB LLSGAB RACK Ml y TO AUX. F D\\JT R PUMPS CSHT 9) SEE D\\JG. 33013-661 I RACK 1 (lc\\ ~!Y' T LOOP A STEAM GENERATOR HIGH LEVEL A RACK 3 (lc\\ ~~ G4 G4 A T A T 9 9 2/3 G12 R RACK 4 (lc\\ ~31 SEE D\\JG. 10905-393 CLOSE MAIN & BYPASS F.\\J. CONTROL VALVES CSHT. 9) { RACK 4 (lc\\ ~!Y G4 A T 9 SEE D\\JG. 10905-392 J LOOP B STEAM GENERATOR HIGH LEVEL A RACK 1 (lc\\ \\t'.~ G6 G6 A T A T 10 10 2/3 Gl4 R RACK 2 (lc\\ ~~ SEE D\\JG. 10905-394 CLOSE MAIN 8. BYPASS F.'v/. CONTROL VALVES CSHT. 9) G6 A 10 SEE D\\JG. 10905-392 THIS D'v/G SUPERSEDES _'v/ D'v/G 882D612 THIS DRA\\JING INCLUDES PORTIONS OF CLASS lE ELECTRICAL SYSTEMS. REFER TD NOTES AND SPECIFICA TIDNS TD DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. AS BUILT DAlt I RELEASED FOR ENGINEER f\\ AS BUILT PER PCR /__Jj, 97-061 AS NOTED RMS Qt! 10ll3 Jf!/' a/J1/9s 7/.?/.fJ' ~-i-'t>I 9lsn* REV R_EVI-cS_ED_FO_R __ -i DRAWN CHECKED RESP REV!EWEF GINNA BY BY ENGR FACILITY SCALE NONE ROCHESTER GAS & ELECTRIC CORP. 1-C-AD-"-FI-LE-NA_M_E --,-3G.,.-1-c3.,,-5.,-31-=3,-----i ROCHESTER, NEW YORK ELECTRICAL LOGIC DIAGRAM STEAM GENERATOR TRIP SIGNALS JOB NUMBER DRAW[NG NUMBER SHEET REV 4777A 33013-1353 13 fu CCD 4 I ICNTRL COPY#

SEE DWG. 33013-2095 SHTS. 29 & 60 RACK 1 MT1 -1 RACK 1 RACK 2 MT2 -1 RACK 2 MT2 -2 OVERTEMPERATURE ~ T SEE DWG. 33013-2095 SHTS. 21 & 52 LOOP A RACK 2 TC j" 406C LOOP B OVERPOWER ~ T SEE DWG. 33013-2095 SHT. 20 LOOP A LOOP B RACK1 RACK2 RACK3 TC ~ 405 TC ~ 407 RACK4 TC j" 40S C26 C26 C26 C26 A F23 T )---ili--IA F23 T l---illl--IA. F23 T )---ili--IA F23 F32 T )---ili--IA T,.........,,_,,A F32 T,__.,,_,,A F32 T }--@1--iA* 2 F32 T }---lll--IA 2 RACK 1 TC 4050 2/2 9 9 9 9 --.-'--....,__ MANUAL SEE DWG. 10905-371 2/2 2/2 TRIP (MAIN CNTRL BO).___,~ P.B. RT9 RT10 RACK 2 1/2 P.B. RT9 RT1 0 RACK 2 SEE DWG. 10905-374 TO REACTOR TRIP CKT (SHT. 2) OVERTEMPERATURE ~ T LOOP A LOOP B RACK RACK 3 RACK 4 1/TC405D MANUAL BYPASS 2/2 1/TC406D MANUAL BYPASS 2/4 2/2 1/TC407D MANUAL BYPASS F31


IA BLOCK AUTOMATIC AND MAUNAL ROD WITHDRAWAL (SHT. 15)

TC 40SD 2/2 1 1 2/4 RT5 RT6 RACK 1 1 SEE DWG. 10905-374 REACTOR TRIP (SHT. 2) 1 2 SEE DWG. 10905-3S9 2 2/4 RT5 RT6 RACK 1 D 11 R SEE DWG. 10905-376 REACTOR TRIP (SHT. 2) 0 SEE DWG. 33013-1606 SHT. 6 OVERPOWER HIGH ~ T RACK 1 1/TC40SD MANUAL BYPASS SEE DWG. 10905-390 START TURBINE LOAD REFERENCE REDUCTION (TURBINE RUNBACK) (SHT. 15) 2/2 LOOP A LOOP B RACK 3 RACK 4 1/TC405B MANUAL BYPASS 2/2 1/TC406B MANUAL BYPASS 2/4 2/2 1/TC407B MANUAL BYPASS F30


IA BLOCK MANUAL ROD WITHDRAWAL (SHT. 15) ffi NOTE 1 TC 40SB 2/2 1/TC40SB MANUAL BYPASS SEE DWG.

10905-390 SEE DWG. 33013-2095 SHTS. 27 & 5S SEE DWG. 33013-2095 SHTS. 29 & 60 REACTOR COOLANT LOOP A RACK 1 RACK 2 B27 T;-..---1.A 3 B27 T~--1A 3 2/3 RC1 FLOW RACK 3 827 T A 3 SEE DWG. 10905-367 RC2 RACK 3 2/2 RACK 3 LOOP A RCP BKR OPEN 2/2 829 A RACK 4 52S RCP1B LOOP B RCP BKR OPEN T SEE DWG. 10905-367 1/2 RACK 4 P7 (SHT. 11) -~ RACK 4 P7 (SHT. 11) RACK 1 PS (SHT. 11) 2/2 07 Rk-----$ SEE DWG. 10905-375 RT9 RT10 RACK 2 LOW TAVG SEE DWG. 33013-661 LOOP A RACK1 RACK2 LOOP B RACK3 TC 403 RACK4 TC 404 F7 F7 FS FS T,__.,__..,.A T,___.,,___,,A T )---ili--IA T,__.___,A 7 7 s s 2/2 017 2/2


l'R\\----*

SEE DWG. 10905-377 1/2 RT9 RT10 RACK 2 1/2 RT7 RTS RACK 2 BOTH PUMPS TO EITHER PUMP TO REACTOR TRIP CIRCUIT REACTOR TRIP CIRCUIT (SHT. 2) (SHT. 2) G G SEE DWG. 10905-3SS 2/4 LOW TAVG INTERLOCK (SHT. 6) SEE DWG. 33013-2095 SHTS. 2S & 59 REACTOR COOLANT LOOP B FLOW RACK 2 RACK 3 B2S 4 4 4 SEE DWG. 10905-367 2/3 RT7 RTS RACK 2 015 2/2 RC3 RC4 RACK 4 .----'---$---- PS RACK 1 -r-~~ RT7 (SHT. 11) 2/2 RTS RACK 2 023 SEE DWG. 10905-377 SEE DWG. 10905-379 1/2 NOTES:

1. AUTOMATIC ROD WITHDRAWAL DISABLED PER ECP-2009-0015.
  • ALARM ON ELECTR. TRIP ONLY TRAIN A TRAIN B RACK 1 IS RR-1 RACK 2 IS RW-1 RACK 3 IS RB-1 RACK 4 IS RY-1 RACK 5 IS RLTR-1 RACK 1 IS RR-2 RACK 2 IS RW-2 RACK 3 IS RB-2 RACK 4 IS RY-2 RACK 5 IS RLTR-2 DATE THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS.

REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. AS BUILT RELEASED FOR ENGINEER REV. PER ECP-2009-0015 33013-1353,14 -003, (000) AJV3./JP Vi 5/17/11 ;;-h*)<< 5 20 /. sin/<< l--REV_.__ __ REVI_SE_D_F_OR __


1 DRAWN CHECKED RESP REVIEWE FACIUTY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G 135314 ONTARIO, NY LOGIC DIAGRAM REACTOR COOLANT SYS TRIP SIGNALS JOB NUMBER DRAWING NUMBER SHEET REV THIS DWG SUPERSEDES W DWG 882D612 4777 33013-1353 14 &

CCD 4 CNTRL COPY#

HIGH FLUX (1/4 POWER RANGE) (SHT. 11) ROD STOP SIGNALS HIGH FLUX (1/2 INTERMEDIATE RANGE) -------e--~ 1 (SHT. 11) '--------~(r1/~f---------------~ 1.-------f\\o HIGH OVERTEMPERATURE t;, T (2/4)------~_:._____:___J (SHT. 14) HIGH OVERPOWER fl. T (2/4) ______ __J (SHT. 14) I '--~~~~~~~~I---~ '-----~~~~~~--iO { TC I fr 01 --L_J e---tA 1 F15 1x~* 2/2 ROD DROP SIGNAL FROM TURB A TAVG. DEVIATION TC I fr 02 --L_J e---tA 1 F15 1x~* 2/2 TC I fr 03 --L_J 7_,.~1 F15 1x~* 2/2 TC I fr 04 --L_J __,,JA\\1 F15 1x~* (NOTE 1) 2/2 RELAY-NIS OR MRPI (SH.11) ----------------------~ TRAIN A ONLY (33013-2095 SH.14) NIS ROD DROP SIGNAL ( 1j4) { (SH.11) TRAIN B ONLY (33013-2095 SH.45)


'-----------'--------~

TC-401 L ROD SPEED CONTROL ANALOG RACK FOXBORO CD-12 SH.2, BD-15 SEE DWG. 33013-1606 SHT. 6 SEE DWG. 10905-389 BLOCK AUTO WITHDRAWAL BLOCK AUTO INSERTION NOTE 2 \\ y BLOCK MANUAL WITHDRAWAL ROD CONTROL LOGIC CABINET TURBINE LOAD REFERENCE REDUCTION A I OVERTEMPERATURE HIGH fl. T (2/ 4) OVERPOWER HIGH fl. T (2/ 4) (SHT. 14) (SHT. 14) ~2 TIME DELAY RELAY LOGIC (CYCUC) ON OFF STD 30 SEC. I" "I __\\ 1-- 1.5 SEC. SEE DWG. 33013-1606 SH.6 REDUCE LOAD REFERENCE AT 211JllJ%/MIN (CONTACT CLOSURE) TURBINE GENERATOR HORIZONTAL (X) & VERTICAL (Y) HIGH VIBRATION FOR BEARINGS NO. 1X,1Y.... 9X,9Y ( T K1 Ill 1/18 2/2 TO HIGH VIBRATION TURBINE TRIP (SH. 3) NOTE: A J19 MCB BLOCK/ARM SWITCH FOR HIGH VIBR. TURBINE TRIP 1 /HVTT ARMED

1. MANUAL BYPASS (M.B.) IS PROVIDED FOR EACH TAVG. DEVIATION CHANNEL.
2. AUTO ROD WITHDRAWAL FUNCTION DISABLED AT ROD CONTROL LOGIC CABINET PER ECP-2009-0015.

THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. THIS DWG SUPERSEDES @ DWG 8820612 AS BUILT DATE RELEASED FOR ENGINEER j\\ REV. PER ECP-2009-ii\\JV3 ~ If?& {)//Ir... ~ ~~J51ii°ii50~13-1353, 15-5/11;11 5lt'l/11 s/rt/11,-/,./,, f--REV_L.._ ____ R.::...EVI.::...S.::...ED_Fc.:Oc.:_R ----1 DRAWN CHECKED RESP REVIEWEF FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G135315 ONTARIO, NY ROD STOPS & TURBINE RUNBACKS LOGIC DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 15 ~ ~C~C~D------'4_ IC NT R L C 0 PY #

BATTERY A MAIN 125 voe ----JDISCONNECT. *----~ VITAL - BATTERY A CLASS 1 E <DCPDPCBD1A> 'SWT 14 I E49 I I E2 I I BATTERY A MAIN FUSE CABINET <DCPOPCB02A> ~2 MAIN DC DIST PNL A <DCPDPCB03.A> SWT 15 ~I -E5~o~I I 52/MCC1C ) BUS 14 POS 22C I CLASS 1E I MCC C CLASS 1E MCC I ) 52/INVTCVTA POS 16D I I c2499 I 52/MCC1A I BUS 13 ) POS 88 I NON CLASS 1 E MCC A NON CLASS 1 E MCC I ) 52/CVTAUX POS I 4K ~


r - INvrcvri\\l

) B800 I 1-1~ MCB DC DIST PNL A <DCPDPCBfJ4A> I I INVERTER I 120 VAC 7.5 KVA <INVTA> INVERTER A I ~CVTA


480/120 VAC

~7.5KVA ' ' ! ' - '1¢ I I l-~----1 ~ _s_TA_T_1c_s_w_ITC_H_~~-~--~ I I I I L B4 I I MANUAL BYPASS SWITCH f __,,-........ I I I I i ~CVTAUX


480/120 VAC

~7.5KVA I ' 1¢ MAINTENANCE SUPPLY J l ' I ) 52/CVTA1 POS 4H C640 1 J. CVTA1


480/120 VAC r-..r-..r--,r-, 7.5 !<:VA

{ y '1¢ 12s voe BA~~~Y B VITAL ---;DISCONNECT f------, BATTERY B CLASS 1 E I 52/MCC10 <DCPDPCBD1B> I E71 I BATTERY B MAIN FUSE CABINET ) BUS 16 POS 16C MCC D I CLASS 1 E CLASS 1 E MCC <DCPDPCB028> SWT 2 I E76 I MAIN DC DIST PNL B <DCPDPCB03B> I SWT 15 I E123 I I I ) 52/INVTCVTB POS i 40 I I lc2Ls I 1-1)81- - - - - - I I t- ') 8800 I INVERTER I 120 VAC 7*5 KVA INVERTER 8 I I <INVTB> i ~CVTB 480/120 VAC ~7.5KVA I

  • 1¢ I

I B2 B3 I _,,-... ___ ~I _s_TA_T_1c~sw_1_Tc_H __ 1--,,--..._~ i ~ - -~MA-N-UAL-_-BY-~~ 1 AS-~-S-W-ITC-~~ ---~- 4 I I I I I I J i SWT 14 I E217 I


1 -------

. _____ __j El/INVTCVTA NORMAL i f MAINTENANCE NORMAL NORMAL El/MQ483 I 52/MCC1B ! ) BUS 15 POS 4A I NON CLASS 1 E MCC B NON CLASS 1 E MCC MAINTENANCE i ) 52/CVTA2 POS i 7K I I I i I I cs;oo I ~CVTA2 --~- 480/120 VAC rv-v-v\\ 7.5 KVA I 1¢ I I

NORMAL I c2507 I UVD-1

@) I@ 1-CJ!-~2~00 I.1 C2f ~~------*------------~ C2510 11-----------------------*----------l~t~3 I - M~l~,T.cE._N_A_,N_cCcE_.*, ** _______________ 11 C2511 f---*--.--***-----*-**-**-**----***-* ----*-*****--------------*---=C=2~50-4-, SEE NOTE 5 '-' )- - -.'.j UVB-1 / )- - ~ SEE NOTE 5 El/INVTCVTB / )- - - ~ I r---(Dj MCB


*---------------------------------IC2512f--------*-*---.---***----------*-------------*-**-~--i--'---+'7"'

ANN E30 El/CVTAUX / )- __ -j MAINTENANCE ~ INVERTER <MQ483> 10904-0458 LOCATED AT BOTTOM OF MQ-4000 INST BUS A MCB o=:=n--*-/ INST BUS B IQl-1~1~fl--.-/ INST BUS c PWR DIST ANN E14 PWR DIST \\!:y PWR DIST PANEL PANEL PANEL CB-AR CB-BW CB-CB <IBPDPCBAR> <IBPDPCBBW> <IBPOPCBCB> 17,Sl ___ _/ INST BUS D ~ PWR DIST SEE NOTE 5 PANEL SEE NOTE 5 CB-DY <IBPDPCBOY> I C3593 j 1 B CET DISPLAY INCORE #4 <IC4> 33013-1569 1A CET DISPLAY I BKR 2 I C2517 INST RACK R1 (RED) <R1> PW-2 BKR 3 IC2518I INST RACK R2 (RED) <R2> !Fl PW-3 BKR 4 I C2519 I INST RACK SD <SD> PW-11 BKR 6 I C2521 I /\\ 00 BKR 4 BKR 5 -~-, C2566 I IC2520 INST RACK PLP <PLP> !Fl PW-13 v BKR 21 I C2536 f I 1*---*-**-----***-*---*------- -----r--_-:_-::_*:::=~====~----=~~:::::::::::::::::::::::: *---------------------1 I BKR 4 BKR 2 I BKR 3 BKR 8 I BKR 5 BKR 21 I I El/MQ400B ~ I N/A I C2542 C2540 C2541 I r--N~/A-. -,I I C2543 I C2559 I INST RACK RIL <RIL> ([)PW-10 INST RACK W1 (WHITE). <W1> PW-4 INST RACK W2 (WHITE) <W2> CD PW-5 I INST RACK RCS2 <RCS2> PW-16 I SPARE I c3~92 I I c2~13 j I I I I L0870 I lc2633l C2631 C2630 I I C2~32 I 0 I ~3 I C2617 j I C2651 DIST i BKR 6 I BKR 4 Pl),~~L I l BKR 10 I BKR 9

BKR 2

- - -,----J__ -r* .......1........ -** -**--****** -* - -,,. I BKR 1 I I <IBPDPCBA> I 1 ,--*---_J BKR 11 [ BKR 5 I L0869 I D ~ El/MQ400A MAIN CONTROL BOARD AOV 836A 62AST <MCB> 11300-0174 C2513 I BKR 1 ~ MAIN CONTROL BOARD RK-12A <MCB> 11300-0606 i ...,'.... l ' I BKR 4 I C2615 j INST RACK CVCS2 <CVCS2> PW-19 C2522 I BKR 7 INST RACK RSC <RSC> PW-12 I C2524 I BKR 9 BKR 18 -~-, I C2589 I INST RACK RCS1 RACK RVLMS-1 <RCS1> !Fl PW-17 SPARE BKR 14 FOX 1 RACK RECEPT CNMT ISOLATION PB RESET PANEL ~ <CIRP> 21489-0670 C3502 j BKR 15 BKR 8 C2523 L _______ _J EVAC FLASHERS 10905-0437 C3580 BKR 16 BKR 17 -=-c, BKR 22 .--=-c, C2537 I I C3581 RACK NIS RACK <RMS1>

  1. 1 (RED) 33013--1618,5

<NIS1 > 33013-1843 @1045F71 AND SHEET 2 TOXIC GAS A <RVLMS1> 33013-1583 <FOX 1> 10905-0546,1 I c3~94 I ~ ~ ~I c2~21 I ~5

  • -***,-... ~ ---- __ J --- ----. -. I l i BKR 4 I BKR 3

---isKR 2 I BKR 1 ----- ______ J _____.. -**** L__..... '.,,.. -* L..... ' -- DIST PANEL "E" <IBPDPCBE> I I \\ DIST PANEL "B" I SPARE SPARE ~ 4 BKR 2 I BKR 1 I BKR 3 ! BKR 11 I BKR 9 ! BKR 8 l L 1 c 5 r:~;~--- ~-;-------- --:r~:;- 6 _____ ~-~------ _ <IBPDPCBB> EHC REMOTE FOX 3 CABINET BATT MON RACK IN CNMT <EHCC1> IBKR 18 I C3583 f UV RELAY UVB-2 ISOL RACK <VBRM> I BKR 8 I C2547 I SAFGD RACK SIA1 ~ <SIA1 > 34500-0132 SHEET 5 I BKR 1 I C2514 MAIN CONTROL BOARD RK-45 TC-3040 RLY ZXC I BKR 9 I C2548 I I Rx LOGIC TEST RACK RLJ('.1 00 <RLTR1> 34501-0138 SHEET 9 I BKR 15 I ZC1 FIRE SYS SATELITE STATION "A" \\BKR 10 C2550 I MISC RLY RACK M1 <M1> 33013-1606 SHEET 15 BKR 16 -~-, ZC2 FIRE SYS SATELITE STATION "8" <FOX3> --'-"BK_,R 11 I C2551 RELAY RACK RW1 (WHITE) M <RW1> 34501-0132 SHEET 8 I BKR 17 I ZC3 FIRE SYS SATELITE STATION "c" I BKR 12 I C2552 I I RELAY RACK RW2 (WHITE) M <RW2> 34501-0143 SHEET 7 I BKR 14 SPARE IBKR 19~~1 fzcooo4f fzcoo18I FIRE SYS FIRE SYS ALLISON CTRL PNL CTRL PNL M <ACl-A888> BKR I L0873 j 11 IBKR 10 !BKR 9 SPARE SPARE \\BKR 8 SPARE .BKR7 IBKR6 SPARE SPARE (SPARE) MAIN CONTROL BOARD (TIM.TIN) RELAY RACK RR2 MED) RELAY RACK RR1 ~ED) <MCB> ~11300-0729 <MCB> 11300-0174 <SSA> 10907-0206 <SSB> 10907-0206 <SSC> 10907-0206 I 10907-0051 10907-0055 SFP-7 SPARE <MCB> 11300-0147 G733A <RR2> 34501-0141 SHEET 7 I C2526 <RR1> 34501-0131 SHEET 7 I BKR 24 I BKR 23 SPARE SPARE BKR 20 IBKR SPARE 13 IBKR 7 SPARE I BKR 6 C5600 11 C2544 I I I BKR 2 I C2564 I INST RACK* B1 (BLUE) <B1> PW-6 I I BKR 3 C2565 I INST RACK B2 (BLUE) <B2> PW-7 BKR C3501 I 10 IBKR 9 'BKR 3 I c5J5s I I C3501 I FOX 2 SEE RACK NOTE 4 <FOX2> MAIN CONTROL BOARD RK-12C <MCB> 11300-0606 BKR 5 C2567 I INST RACK ADFCS r--'--.,-..LC.BK~R 7 BKR 8 C5600 11 C2569 I C2570 I I NIS RACK

  1. 3 (BLUE)

I INST RACK SA <ADFCS> /\\ 33013-2521 00 SHEET 2 <NIS3> @ 1045F71 SHEET 6 <SA> PW-15 i i BKR 6 I C3595 I RACK RVLMS2 <RVLMS2> 33013-1583 ' BKR I C3505 RACK <RMS3> 33013-2295 AND TOXIC GAS B 10905-0546,2 11 BKR 7 I LD871 I l El/MQ400C I BKR 21 I C2583 I ' I i l I i DIST PANEL "C" BKR 22 @) El/IBPDPCBCB 0 HZM/IBPDPCBCB El/MQ400D ~ 0 I BKR 3 I C2588 I INST. RACK Y2 (YELLOW) <Y2> pW-9 BKR 2 I C2587 I INST RACK Y1 (YELLOW) <Y1> !Fl PW-8 BKR 6 I C2591 I NIS RACK

  1. 4 (YELLOW)

<NIS4> @ 1 D45F71 SHEET 8 BKR 5 I C2590 I INST RACK CVCS-1 <CVCS1> PW-18 I I R933A I I c2r61 I ~ I C2~66 I M I C2664 I BKR 21 -~~ C2607 I . DIST PANEL "D" SPARE SPARE I I BKR 1 !BKFI R 2 '1' BKR 6 I BKR 4 BKR 11 ~ I BKR 9 i BKR 7 k--- I I 11.. - - - - i BK~l~~~/_B_K_R_3 ____ ~----------~-----~--------* -------'------* <IBPDPCBD> SPARE SPARE I G1499 I I BKR 19 BKR 1 BKR 9 BKR 10 BKR 11 BKR 17 I SPARE I C2516 I I C2595 I [rC-2~5-96-,[ lrC-2~59-7~1 rC-2~60-2~1 I RRMSR01 NOTE 8 SPARE SPARE SPARE SPARE IBKR 24 IBKR 22 IBKR 8 IBKR 4 I BKR 23 I BKR 20 I BKR 7 SPARE SPARE SPARE BKR 18 -~-, I C3586 f MCB RECORDERS & PERMISSIVE LIGHTS ~ <MCB> 11300-0174 BKR 12 lr-c-25~98..,f SAFEGUARD RACK SIB1 ~ <SIB1 > 34500-0138 SHEET 5 BKR 13 -~~ I C2599 f Rx LOGIC TEST RACK <~> 34501-0148 SHEET 9 BKR 16 r-~-, I G273 I MISC RLY RACK M2 <M2> 33013-1606 SHEET 17 BKR 15 -~~ I G272 I TURBINE EH PANEL ~EHCC1> IWl 721J299 I UV RELAY I C2665 I iE3KR "--**-*** __ *--*-* __ ___ ___ *--------******----- ------~ _ _J RELAY RACK RY1 RELAY RACK RY2 FW XMTR PANEL TURBINE GAUGE PANEL I BKR 14 IBKR SPARE 6 BKR I G300B I I 14 I BKR 23 BKR 1 SPARE IC2515 MCB TIC PT-2021 PT-'2014 PT-2023 PT-2024 LT-2006A <MCB> 11300-0147 IBKR 24 M IBKR 18 IC2504CI NOTES: I UV RELAY (ANN E22) uvc <MCB> 11300-0729 MCB AOV 836B & PROT RELAYS <MCB> 11300-0174 I BKR 16 L66B I UV CTRL CABINET BUS 17 10905-0056 SHEET 1 <ARB2CC17> <AR82RC17> I BKR 9 I C2322 I CNMT RECIRC FANS A,B, C,D VIBR SMB 25 24189-0748 SHEET 5 BKR 13 r-~~ I L674 I I UV CTRL CABINET BUS 16 10905-0055 SHEET 1 <AR81CC16> <AR81RC16> I BKR 11 I C2573 I I RELAY RACK RB1 (BLUE) ~ <RB1> 34501-0135 SHEET 7 I BKR 15 I C3584 I I OUTLETS FOR MCB CNTRL'S & RECDR'S <MCB> 11300-0175 I BKR 12 C2574 I I RELAY RACK RB2 (BLUE) ~ <RB2> 34501-0145 SHEET 7 I BKR 17 AHC58 I I ISOL DAMPER CONTROL PNL <IDCP> 33013-1415 BKR 20 ,.---'-"'-C, I MEC4 I I SAFWP-D INST PNL <SAFWPDIP> PW-10 I BKR 19 SPARE UVD-2 11300-0901 (YELLOW) (YELLOW) T @) <RY1> 34501-0137 SHEET 7 <RY2> 34501-0147 SHEET 7 <FWTP> 33013-1627 <TGP> SK60983-W El/IBPDPCBDY THIS DRAWING SUPERSEDES 21946-0269, REV 0, 21489-0270, REV 5, AND 21489-0271, REV 6 AS BUILT DATE RELEASED FOR I. " I ENGINEER REVISED PER ADC 000341-CN-006 & ECP 000198-CN-001 RJM O!ir- {J/.i..,.,, 0 ~ El/MQ400E BKR 19 BKR 13 BKR 11 C2525 f BKR 10 El/MQ400F I NIS RACK

  1. 2 (WHITE)

RACK RMS-2 1)@ - WESTINGHOUSE DRAWING REFERENCE

2) CE) -

FOXBORO DRAWING REFERENCE

8) ALTERNATE POWER SUPPLY. NORMAL POWER SUPPLY IS ACPDPCB09/02.

,__R_EV_~ ___ REV_IS_E_D_F_O_R ___ -< DRAWN CHECKED RESP REVIEWER BKR 28 IC2500C UV RELAY (ANN E6) UVA <MCB> 11300-0729 BKR 27 F I 0 HZM/IBPDPCBAR El/IBPDPCBAR BKR 26 I C2528 SMOKE DET XFER SWITCH (SEE NOTE 3) 33013-0462 I I C2572 I BKR 10 BKR 25 I G300A I MCB TID PT-2020 PT-2027 PT-2028 PT-2031 PT-2032 <MCB> 11300-0147 BKR 24 -~-, MEC3 SAFWP-C INST PNL ~ <SAFWPCIP> PW-1C BKR 23 -~-, L673 I UV CTRL CAB BUS 14 10905-0054 SHEET 1 <ARA1CC14> <ARA1RC14> BKR 20 -~-, L667 UV CTRL CAB BUS 18 10905-0057 SHEET 1 <ARA2CC18> <ARA2RCl8> BKR 1~@1 I C2527 :1-;..:;:.;r ~ r---coF"°IR""E-,1 PZ42 RELAY I LOB74 I PANEL M <FRP> C2527A 33013-2460 M, SHEET 2 ~ 25 El/IBPDPCBBW SPARE /\\ <NIS2> @1045F71 SHEET 4 I <RMS2> 33013-1618 I*

3) PYTRONICS SYSTEM
4) 120VAC POWER TO 1 B CET DISPLAY IS ROUTED THROUGH FOX 2 RACK WHERE CIRCUIT C3501 TIES TO C3593 AT TERMINAL DECK
5) MECHANICALLY INTERLOCKED SO THAT ONLY ONE OF THE TWO BREAKERS CAN BE CLOSED. THE AUXILIARY POWER SUPPLY IS FOR MAINTENANCE PURPOSES ONLY.

USE OF THE MAINTENANCE BACKUP POWER SUPPLY SHALL MAINTAIN CHANNEL SEPARATION INTEGRITY.

6) ENCLOSURE EIN'S ARE PLACED WITHIN CARETS TO FACILITATE RECOGNITION
7) CIRCUITS C5599 AND C5600 SUPPLY INSTRUMENT AND CONTROL POWER TO N-32 DRAWER IN RACK NIS2. POWER IS SUPPLIED FROM INSTRUMENT BUS "C" AND BOTH CIRCUITS ARE FUSED (7 AMP) IN RACK NIS3.

(PCR 2002-0044) FACILITY GINNA BY BY ENGR SCALE NONE R.E, GINNA STATION CAD FILENAME 03201-01 02 ONTARIO, NY ELECTRICAL 120V AC INSTRUMENT BUS ONE-LINE DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 4777 03201-0102 1..... CCD 3 1 Ct~I Rl_ C20PY i

125 WC eATIERY A CLASS 1E <BIRfA> AUX BlDG DC DIST PNL ta <DCPDPABOJA> MCC K MCC B MCC H CNTRl ROD DRIVE MG SET A CN1RL PNl ISOPHASE ClG SYS RLY BOX Af:N 4529 GEN EXCITER EQUIPMENT PNL BUS 11A NORM, BUS 12B EMERG BUS 12A NORM, BUS 11 B EMERG BUS 13 NORM, BUS 15 EMERG MOV 3505A FW PMP A DC OIL PMP PA INVERTER eATT RM VENT CN1RL PNL BR\\/-1 BUS 14 W CNTRL CAB NORM, 16 EMERG, SSAUVLOC MCC E MCC C MCC C AUX CKT BKR CAB BUS 14 NORM BUS 16 EMERG SI PUMPS FAN CNTRl PNL H2 RECOMBINER A CN1RL PNL WASTE DISPOSAL PNL SECT W1 Rx TRIP SWGR UNIT 1 BKR RTA.BYB CNTRL PWR I) eus 14 l'OS 22C llCC c I aASS IE aASS 1E ll:c j)POS 160 8800( ~CVTA --- 480/120 VAC rY'(V'\\ 7.5 KVA INSTR BUS A <llll'!l!'CBAR> 03201-0102 I 111 <INVrCVTA> 5 SPARE 6 5 SPACE 6 SPPCE SEE NOTE 1 125 WC 1SC eATIERY NON CLASS 1E <BIRYlSC> eATTERY A MCB VOLTMETER & INVERT RL)' RL-6 El/PG 00 A CNTRL PNL NORM SUPPLY 00 8 CN1RL PNL EMERG SUPPLY BUS 17 EMERG SUPPLY BUS 18 NORM SUPPLY DFPCP AR-100 RELAY A BUS 18 W CN1RL CAB NORM/17 EMERG PPS SWGR TRAIN A DC POWER MAIN XFMR ANN STATION UNIT XFMR 11 ANN STATION AUX XFMR 12A ANN MCB ALM SYS A TS SG DMP VL\\IS TB-DCDC POWER TRAIN A LOCKOUT & DIFF RLYS BUS 11A IN RLYS H2 MON ISOL VLV 921 H2 MON ISOL VLV 922 MCCN SIA1 DC PWR (SI TRAIN A) RA RACKS DC POWER MQ 483 INVERTER DC PWR Rx TRIP TARGETS RLY BOX CNDST 8STR PMPS RLY PNL AVC-5 CIRC W1R PMP TRIP UlGIC RLYS RCS OVERPRESS HEAD VENT VL\\IS TRAIN A CR EMERG LTG DC FUSED XFER SWT CNMT !SOL RLY RACK RLTRt RACK I:t.i:: ~p ~/RX TRIP 43/11A 43/12A 83/00A 83/13 83/12A 83 E201 <83/J'Sc> AUTb TRANSFER SWfTCH ) ) G=*~ TURBINE EMERG DC LUBE Oil PUMP CIRC W1R PUMP A DISCHARGE MOV 3150 CIRC W1R PUMP 8 DISCHARGE MOV 3151 GEN AIRSIDE DC SEAL OIL BACKUP PUMP 4KV BREAKER TEST CABINET AUTOMAllC THROWOVERS 83/008 83/16 E168 E64 83/128 E200 50 KVA REGULATING TRANSFORMER ~-1---~ <PXCD001> 00 8 AUX BKR 183 CABINET D G 8 CN1RL PNL NORM SUPPLY D G A CN1RL PNL EMERG SUPPLY TRAVELING SCREEN CNTRL PNL MCC G BUS 18 EMERG SUPPLY BUS 17 NORM SUPPLY BUS 17 IN CNTRl CAB NORM/18 EMERG PPS SWGR TRAIN B DC PWR S'IM DUMP VL\\IS TDAFWP GOV IND & TB-DC TURB DRAIN VLVS LOCKOUT & DIFF RLYS MSR VL\\IS RLTR2 SIB1 DC PWR (SI TRAIN B) RA RACKS DC PWR CNMT EVACUATION ALARM H2 MON lSOL VLV 923 H2 MON ISOL VLV 924 CIRC W1R PUMP TRIP LOGIC RLYS MCB ANN AA CNDST DEMIN CTRL PNL (AVC-1) BUS 118 W RLYS RCS OVERPRESS HEAD VENT VALVES TRAIN B CNMT !SOL RLY RACK 81 CNTRl ROOM VENT FAN MCB ALARM SYSTEM 8 83/ANN SPN:E SPACE llCC D eATT 8 MAIN DISC SWT PNL <DCPOPC001B> aASS IE ll:c ')POS 4MM SEE NOTE 1 I )'*JS 1s POS 16C llCC D I aASS IE aASS IE llCC ')W INSTR BUS C <IBl'lll'C8C8> 03201-0102 CN1RL RM EMERG LTG TRANSFER SWITCH CN1RL ROD DRIVE MTR GEN SET B CNTRL PNL MCCJ MCCP MOV 3996 BUS 11B NORM BUS 12A EMERG BUS 128 NORM BUS 11A EMERG BUS 15 NORM BUS 13 EMERG FWP 8 DC Oil PMP BUS 16 lN CN1RL CAB NORM, 14 EMERG AUX BLDG H & V CNTRL PNL MCC D GAS ANALVZER CNTRL PNL BUS 16 NORM SUPPLY BUS 14 EMERG SUPPLY MCC D AUX CKT BKR CAB H2 RECOMBINER B CNTRL PANEL WASTE DISPOSAL PNL SECT W2 CCW PMP SEAL ORN TK PMP HI LVL AlM Rx TRIP SWGR BKR RTB,BYA CNTRL PWR <INVTCVlll> 125 WC eATTERY 8 Cl.ASS 1E <SllMI> CNMT EMERG LTG PNL H2 SEAL OIL UNIT CNTRl PNL MCC A MCC f PRI W1R TREATMENT PNL IBELIP ARE RLY PNL--i_~l!_JHH-<llL_JJp-9' AIR COOLED PENET & EQUIP HATCH lEMP AlM PNL NUCLEAR SAMP PNL 'IDAFW PMP DC WBE OIL PMP NOTES: t) ~~~r~1fl~~= ~JEME.

2) ~

~~~3;tJ83XViGSl-{;Aili~ 2 FOR

3) ~TT A-B MANUAL TTiROWOVER ES ARE KEYLOCKED. A & 8 SIDE SWICHES OPERATE INDEPENDENTLY. TWO KEYS ARE REQUIRED TO CLOSE BOTH swrrcHES SIMULATANEOUSLY.

I xxxx I - NO CIRCUIT SCHEDULE ASSIGNED FOR PRE.V!OUS RE.VISIONS SEE MICROALM AS BUILT RELEASm FOR M RtVISED FER ECP-1~ RIY RtVISED FOR DIWlll CIEKBl RESP IEIDER FACllJIY GINNA 11( 11( ENGR SCILE NONE R.£. CllNNA STA1ION COD F11.ENA11E 03202-0102,1 otrrNl!(), tit 125 voe POWER DISTRIBUTION SYSTEM ONE-LINE DIAGRAM JOB NUMBER DIWllNC NUMBER SllEEI' REV EWR 4777 03202-0102 M CNTRL COPY#

L 4160V BUS NO. 128 I I L __ 1l!!!!. e&/129 33013-1949 33013-1~ 3:!013-1951 33013-@52 THIS DRAWING IS INTENDED FOR USE IS A PURVIEW OF PlANT OPERATION. FOR COMPLETE EJN'S OF COMPONENTS, REFER TO a.EMENTARIES OR CCD DRAWINGS COVERING THE SPECIFIC AREA REQUIRED T~ r+=-t--l I I I r I I '--""" <r:~ I 86"/128 2 1 I ,--~~ I I WI. I I I I I I I I I I l WE I 200/11T-12B I 6,.;;~,~:~ l ' I ' I SS 1----------------------1 4160V BUS NO. 118 I,,---,.'1?- 1 y ae/118 ',.J ! 5(, I 15$$ I I I I o I FlF __t"'JOS T,.,,...,,,_,.., 480V BUS N0.15 TRIP JU. FEEDER BR£AICERS ON BUS 11A. TRIP A1. nED£R 9RFJ.K1'.RS ON BUS t ta IU. FEEDER ~ ON at.IS 121... ALL fEEDER BREN<EJIS ON SUS 129. Kl>-< 1HIS DRAWING INCWOES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES ANO SPECIFICATIONS TO DETERMINE DPECIFIC QA PROGRAM APPLICABILITY. STA. SERY. XfMR.

  1. 15: a..G. FANS 480V BUS N0.17 KDGOtB DIESEL GENERATOR B ro 115KV swm:t<<ARO
  • 11--j/

<I* r----1 l<N-7 ""'-" I 1C I I I I ~~ ""' ) -'i>'°'


1 x

y @ -- """"-.... ~----.----<~ ~>--,,, -----lCJI-----, ____.+/-_~~-------- L ___________ _ ! ~A--T,--+-------~ i i 118 ' *ltit-I 88/118 ~t---9----1------------------------! SS t---- ~ >+-+---' 86/11B I I I I I I I ~- 4160V BUS NO. 11A i 3-CrS nA KV-1 -1 -@t """"'*W<CE """" f.::\\_ __________ ( ~~t~ ~IOC-2151 I I I I I '-I I I I I I I I I I I (61)- ID T ------ I I I I I I I I I I I I I TO STA. AhN..J_ !IOro T87P/PC I -2.&X T.-.P) I I I I I r----Utai:-- __________________ J 1 IS11lU(


~---1 I

I I I I I I I SEE. 33013...Q;U 878/12.1. s i ~'1--t--+--~-~ 4160V BUS NO. 12A 5 ffe.,, I~ I l~

11ii! & i ____ -.---. T ""'

i T1I +~~~,. 3-CTS

  • 1A-1 jf85l(/1G I

l:=t---JC;A.:L_j_... I T-' I

--~'
. ----

I I I I I I I Alll11 I I _________.J I *,__.,,.. I <00-5 I BYZ lB!p oo !!! OCK M}BTA--A 52/12ll'f I 100-5 ~------L-----~~ L ~~ ~ I I I I I I I I I I I I I f-l I 60/74/1G --1----;!f---- I I I I I I L_--lJ _ _____j__.,__ ___ --L ____ __':=====::::'il;__~60>--~-~-J I I I 1-- 87G I I I I I I I I I I I r -.I- :;tf---f-i;<-T~~ I I 152 I I t I ZA i ~*[__ __J __ _ I I I I I I I I I I I I L-1 I I I I I I I I I I I I I I I I ~----,-, I I I I I I I I I I I I I I I I I I ___ 20.000 NIP BUS r-- 1 I I I ,.,, 1 - 1 1 1 a?G ~H~I I coo I I ~-1 ~~ 41/lG I I I I OUT?Ur 'flJf: : I +- ---- -----, I I I t-r- ---- I I l *--r- --i-l--+-1=+- -+---'--- ~- __ LL_ -*-- ~---i-- / I: *--lf-'l°'/I/ ---- _l ___ ~----:__ "" r-... I 1 I ll,"I 'to


--:-.-lf-.--lf-

.l J_ 11 I // I" I "" P9-cr=P9-2T I 1 L - _I f...LI\\_ I 1G1372 1G -t H --, I L-J~.. J I I I I ( I I I ' P1t-1..Lpg_2..L I 1 r- _. l I l ! I L _ _!X".!!72 __ _ L-~ 11 i. j_ I I I' L _____ _ A I t TP&-1 P8-~ I I I ¥t:"* I I I I I I I m r-I....L ...L I ~J:r rH-...., I ii L.='. "~ : ~ - --t' I #-w I I 1 I 1 1.., I..., L... I 11 "--"'I i.10 _l_-;o I 111 '">r1T T w II IL_L - "' I


;lf--

--;ff------ 80/74/tG IUF-* l<P-m l<A--24*


If----


1 TD-1 Wl

--H---.!.-t---- ~ 861'~ 10: ro?f-I ~ ...... \\ #~ ~~!~ ..,. ~ ro / I / I I / I / / I l'Z, TRIPS ( r - _J lO sua SrA.13\\ I I I I --' I ~-------~ I _ _J I I I I


i---w-.

I ro-1 MIN I I I r~/ r~I

  1. =
  2. =

I I +----r-1 : I I I I ..L,,,. J_.,,J_,,,. --¥w T* T* T* 'f"" I I I I .l_B.JX.l..63X_LMX J.t~ T' T' T' ~* I I I I 480V BUS N0.14 480V BUS N0.13 ~ i iH-i _ _J~ 1 r--4-- 1 I I I I ~~tll'.Cl'RCN.. JI I I t I I 11 I 11 I I I c~ STA. SERY. XfMR f14 ClG. FAAS c !!!!;;;! c KH-1 c !ilH KDG01A DIESEL GENERATOR A 480V BUS N0.18 l<<J-4 FROMST<>3' _:J I I I I j 1 I I I I,,..I I ..,...,,..1 I I I FRCN STA. 1JA I I I I


j-'

~"!.".:"1 I I ..,.,._.I I r--. I I DFT..L.§6..l... I I T ex-r I I L-4~! i ,... -1 I I I I I L_t-rl f-t--'""+---' I I I I I I I I I L----:-- 1 I \\11P1/1 L __ _______ J ~ 'f. ~ ~ KCD01 )-"- s s ~,= ,i;,'li 1~ 1,~ I, ~-------~---h] ~

~ : L_~~~

r I I r--+---, 14 ...L ...1!/41-<<B'....L ...L ....L T 11P:1/rnT -, eBP/mT-"T"' BRIJSHt£SS~~~ l SYSlBI 4=11P2/11>#88X/1G 1 I

  • 1[4.141JI I

I ,_ __ l __ _, I I I I I I I I : N /0 It 13 I I I I AS BUILT DATE RELEASED FOR ENGINEER j\\ REVISED PER /J!A ADC--13--01228 RJM 10/16/17 to/1<(13 ,__REV_~ ___ R_EVJ_s_ED_F_o_R __ --1 DRAWN CHECKED RESP FACIUlY GINNA BY BY ENGR SCA1E NONE R.E. GINNA STATION CAD FILENAME 33013--0623, 1 ONTARIO, NY MAIN ONE LINE OPERATING DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-0623 ~ ~C~C~D_3~ ~C_N_T_RL_C_O_P_Y~#--~~

FROM 12A CT's TO BUS 12A TO SYNCH METER TO BUS 12B FROM 128 CT* ~ ~ ~ ~ ~ REMOVABLE UNKS


OPERATE UNE


TRIP LINE


CURRENT OR POTENTIAL LINE TH!S DRAWING SUPERSEDES 33013-480, SK-500-63. N*D SK-500-96 THIS DRAWING IS INTENDED FOR USE AS A PURVIE OF PLANT OPERATION. FOR COMPLETE EIN'S OF COMPONENTS, REFER TO ELEMENTARIES OR CCD DRAWINGS COVERING THE SPECIFIC AREA REQUIRED 3000A BUS DUCT 1/12AX-SYN J0lol0A BUS OUCT BLOCK CLOSING 62/12[1)(

~~~-..~~~~~~--1~~~~~~~~~~-e-~~~f--'~+-~~-t-~---t------- 52/12BY BLOCK CLOSING 52/12AlC 52/12AY


+-~-t-~~--1~~)-~~~~~~~~~~~~~~~~~~~~~~~1-~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~*

OPERATt STA. 13 ANNUN. OPERA.Tt STA. 1 l ANNUN. "'"'"'} 86/12-B ll6T/12A - -- --\\ 86TBU/12A 868/128 c ON asr 86B aemu aerau ee 21x ccx ""'"' ""' - - -II- - -1 I-- -;W-- - -+!'- - -+!'- - -:lf- - -;W-- - -:lf- - -1 I- - - - - - - - - - ~ l SS 12A 128 12A 128 128 12A 128 51fl CiFH-' t2AX 1°2AX AUTO OPEN- - -j t- - -j --~'\\--'-~ 12BX ~ ~~AL - - -J 1- _j 1/12AlC 52/12AX I ,---r-1f.. - - - -WJ. I SS 52/12AX I 12BX L -1 f- _ -~~AL 'l'J"' ~ Bf>T/128 86TBU/128 868/128 86/12B 76702/b 52/12BX CCX 27X B6 s,6, e~u ~o/ 861'BU ON c '- - - - -H- - -+F- - -J,l'- - -;n- - -;11- - _,,r-- -J,l'- - -H- - --1 f- - -~;, 12B 12B 128 128 128 128 12A A 1/128X 128X ~t1. - - - ~k-52/128Y _..§§._ I ~JJAL- - _J 1/12AY .:u,,. }- alITSU/12A BBB/12A 66/12A 7T1352/b \\ I I I 52/12AY 52/12BY --0"'"' 86T8U/128 S68/12A ~/12A 78702/b CCX 2,76 ~~ 86B 8~).I 8eT 8~wi ifN C ---~~--,n---,n---.,fl'---;ff---,if---,rr--~f----1f---~, 12.ll 12B 12A l2A 128 12B 12A SS/128Y 1/128Y OFF' 52a C BSTBU ON SST 8Slffi1U 85 868 27X C~X 1; / "' ---11---:lf---H---;ff---:tt---:lf---Jf---jf---li--------- CLOSE 1/12AY 128 A 12A 12A 12A 12A 12A 12A T ~-I~ - --1 f- - _.,,,,, °'" 1' 11 2.i_ 12AY JJ 128Y ~2J'J'.:120v 1 L - -1 r---- - -MANUAL OPEN I I I I I I I I I I I I I I I I I I I I I

  • R y

x 600A J000A BUS DUCT PXY0012"'. STA. AUX. XFMR. 12A 34,500 - 4160 - 4160V 28/41.S. MVA 3.44% IMP 0 14 INA HV/LV

  • 6S'C RISE 1200-5/SKORT SUPERV!SOIW

!SOL.AUD 12A MWH TO --§J AND STA. 13 CPU REl.AY TONES ,_,,, 1 +2e0-120v T FUTURE l {FUSES f!EUOVED) 1200/Sl30-5 '~--"'>---* I 'iiiV 1-S ~:L_ _ _J-;----L:;.J -*~

g.

1 GEN. NET MW I TO P.C. "" >------; s f----- ,,, L--1,---Y COMPUTER 1200-5/SHORT SHORT 2-Prs i 4200-1Z0V T FUTURE l (FUsgs REMOVED) 7651\\ 0 30KV j__ !RIP ANO BLOCK "'=" s2(7T13s2 -m OPERATE --- -- --#---------1 STA 13 ANNUN 7T 4JOTT I NoFm" I TRIP ANO BLOCK 34KV B 52/7T!J52 ---*~---------- OPERATE ~ 85TT/)T/1J'I---------- STA.13 l\\NNUN, """'Jn } Mo, 86L(7r52 66TSU/12A

  • ---*----- 52/7T1J52 66T/12A

~ MAN. OPEN II s2/1v.x I 52/12AY 62/7Tl::352 II s~/TI~x -- - - - - ~---s~r~--+')!!l'-J.--- s2112BY ~! I STl\\.~UN. / AC!".L_ I 50T-, L-----------------------------------------------------------~' ~' 3 12A ;osc I TRIP AND BLOCK 52/12A)( 52/12AY 52/711352 OPERATE STA. 13.>J-INUN. ALL ITEMS SHOWN ARE PREFERRED POWER SUPPLY, NON-CLASS 1 E. '/.......,, 12A TRANS -~--------<t----\\1-----<~ MTRS K1J1B "'" ~ <~-c:J-7, SP~~O~gES ~ v ' *+/-o ~ OISC/7T1 J5J SI 1275 0 40"C 34.6 KV 1200 CONT 25KA 1C 6-1KA MOM 1500A 0.WC "Y"'" ~ SHORT 2E K1323 1/12BY PXYC012B TRIP AllD BLOCK

m~}

52/BTB-B 52~5 J.3013-623,1 62/17SS - STA. 13 ANNUN. j /LJL_'-_"f1J;'/.......,, '\\."\\-"""L ~ ~}-~>-~~--t~~~~~~~~~~12B TRANS MTRS. SPARE FUSES K1J19 REMOVED +/- " "+/- 34 KV, BUS 2 POTS v 115\\111-¢ STA. AJJX. XFMR. 128 34,500 - 4160 - 4160V 28/41.8* Ill/A 3.541C IMP 0 14 MVA HV/LV

  • 65'C RISE y

20,1211 - 115/81 - 11s/e1V 3-4KVA )(PT/167CA XPT/767CB XPT/767CC 127SA 0 40'C 34KV 1200 61M MOM 1200 CONT s I 25KA IC 61KA MOM 1500A 0 40"C J4 KV BUS 2 76701 1 1200-5/SHORT $7[ -------1 INSUl SKORTS-<1> PW TERM t 87LX/767 67LX 16102 PILOT WIFlE ~--<>-~-TO STI\\. 1JA HOUSE SERVlCE ~/87l/767 ,,,,,,, T.~

  • --+".,=,_--;

115VAC BllLC 1 sfc I 4 2X/87L/787 -{" 94/6T 94/BU/6T 52/76702 ---------- 86T/12B BfiltU/12B MAN. OPEN 34 KV BUS 2 POTS 1200/600-5 12~0-5/SHORT 128 MWH TO -- SUPER\\4SOIW ANO STA. 13 CPU 1 GEN. NET MW TO P.C. COMPU1ER x 600/:>00-5 R I I I I I I 8STEU 86T/ { I 76703 2-25~KCM 12s 1129 I '- - - -:;if- - -;t1- - ~~f I 50T..L ' ~

  • ~

I I I TRIP ANO BLOCK I I I 52/76702 ~ I 52/12AY I '\\. STA. 0f5R1TiNuN. I ~--------------------------------------------------------------~ 128 A9C l-------------------------------------------------------------~:~& I TRIP AllD BLOCK 52/128)( 52/12BY 1>2/16702 OPE~ATE STA. 13 l\\NNUN. AS BUILT DATE RELEASED FOR REVISED PER AJV3 OCR 2006--0202 & PCR 2005--0029 9/26/'6 REV FACILITY SCALE CAD FILENAME JOB NUMBER CCD REVISED FOR GINNA NONE 3G62302 DRAWN CHECKED RESP REVIEWER BY BY ENGR R.E. GINNA STATION ONTARIO, NY MAIN ONE LINE OPERATING DIAGRAM DRAWING NUMBER SHEET REV 33013-0623 3 CNTRL COPY#

~-----A-----~ I 3A u~5-1 i 12-PT'S 480-120V 2 480V-3¢-60Hz BUS 15 3 4 5 6 7 480V-3¢-60Hz BUS 13 8 9 B CAB CD ABC DAB CD ABC D A 8 C D ABC DAB CD A 8 C D

  • 1 1 k 1

/1' 1 ~l i----i-r--1 --1~i~J -~~J-~ ~ -l 1111' J*~~~"';:*====~4Jr--iJ~-----TJ-~1 1 k 1 k 1 1 1 ~ ~ 1 I I I I I I 1' I I I I I I 1' i I l I I I I I I I I I I I. I ) 52/ ')521 )52/ )521 ')521 )521 1.)52; ')52; ')52; )521 ') )521 ')521 ')52; 1.)52/ I )52/ )52/ ')52; 1)52/ ')521 ')521 ')521

  • )52;

)521 ')52; l)52/ ')521 ')521 1)52/ 1)521 )521 ')52/ I)~ I. ~WI"'" ~""~II MCClF~rnO ~~ I'"" ~~'"~ ~~ ""~. "'" ~ [,~'"{' -~I "~~H 1~~ 0~*::~ f~"-' I ~=,,-~,,,_, .,._,,, -~-1 ~*"~"' i '~"I'"'"~'" I~ I""~"'~" i "" I I .L J, 5 J, I I), ! f ! r f. f ~ ! < Y ~y )/ ~ Y ~ ~ Y Y ~ WY'J)/ ~ wy 1wy ~

  • Tw Y,*

Y,

WT~~ Y y

~ Y 10 B K15-2 6A Busl 15 II @I I I TSIC LT.G i I I

~ !

I I I @H'~ ~ IMCCA,"C21 I I I i I 0JSEP-11P I ~ ~ MAJN jMcC el (1(;0\\ SPACE PWR !Mee El (60\\ LTG I WELDING/ MAIN ~ jMcc Al ~ LTG (1(;0\\ (1(;0\\ ~

~b~~~,

P <MCCF> !~fg3 <f[~:of5> ~ E1.i~R~ <MCCB> ~ - 01068 PNL <MCCE> ~ <~~~ogg> -0502 I ~~s Wo~~ <MCCA> ~ <f[~:Oa~> ~ ~ ~ CRD IA -0097F I -0088 A/C PWR -00978 IA SEP-4G -0097E CTRL -0553 CTRL <MCCAVC2> -0106A !rt~ A/C -0097A AB SPLY -0087 SERV IA CRD BUS 13 SUPPLY -0064A STA SERV XFMR 15 COOLING FANS 10905-0566 11 UNOERVOLTAGE SCHEME BUS 15 -0053 3 © 5 CV-8 GROUND DETECTION SCHEME -0050C i MTR CMPRSR WA'rER SPLY CMPRSR <SEP-4G> ROD ROD I oogJA WA'rER AHU AIR CMPRSR MTR GEN GEN B CHLR -00938 C -05638 SHROUD SHROUD 1 CHLR <AAF09> CMPRSR A SET A 'I SET e <CIA02B> gt:J,B B!fG B <CIA02C> I FAN B FAN A A -0086 <CSA02> <CIA02A> <CRDMGA> <CRDMG8> -00838 sJ:i~cH FR ----i CMPRSR -0D83C <ACF058> <ACF05A> CMPRSR -0084 -0083A -007QA -0070B I <SCI038> GE BETZ WATER TREATMENT SYSTEM -00968 -0096A GE BETZ WATER TREATMENT SYSTEM <SCI03A> <43/COHTB01 > I -0085B ~ B TRAIN TRANSFER SWITCH A TRAIN TRANSFER SWITCH -0085A SECURITY I I <43/GEBETZ-B> <43/GEBETZ-A> FEED I I 10905-0563A TURB <ACPDPWW36/04> I I l BLOG I CRANES (OFFSITE POWER) I . I I I I . I <COHTBQ1 > <ACPDPWW36 02> <ACPOPWW36 01>1 <COH~B02> (OFFSITE POWER) GE BETZ WATE: {i\\ii~TMENT SYSTEM (OFFSITE POWER) GE BETZ WA'1R fR~JMENT SYSTEM -0092 <GEBETZ-B> <GEBETZ-A> 480V-3¢-60Hz BUS 16 -0107 -0105 480V-3¢-60Hz BUS 14 I STA SERV XFMR 13 COOLING FANS 10905-0566 15 16 13 14 17 23 22 21 20 I ---i---\\2~---- __l_ ____ _,1_i,:i~----- UNDERVOLTAGE SCHEME BUS 13 -0051 3 I L I L@. 4 13 CV-8 GROUND DETECTION SCHEME -0050A 18 ~-----A-----~

  • ~----- A-----~

B c rA I B c 1 A B c A B c A B c A B c A B c ~ i c B A c B A c B A c B A re I - B A' c B -!-K-16~---6K16-1 K16~-- k k +-1 + -+ ---+ -~-+ ** --*i~1---+ ----1 ~--~+ ~ + -I J k + + + k i -~+~-~~~~1 -~+ + -~ + --~"'°;-.....:J~- i k 1 1 ,!~-'kF---~--i ..... 1 __ _,k,_----,6-~-,4---3 -- 1 ,-! -~-4--,-- 1 ---~4-5 2A ' 2A 2A ~ 1)£1 )~I I ')~/ )£1 )~I l)~I ')~/ I)~/ I) )~/ )~/ )~/ )~I I)~/ I)~/ l)~/ !)~/ )~/ )~I I)~/ I)~/ )~/ ')~I !)~/ )~I )~I

)~I

)~I i) !)~/ !)~/ I)~/ I)~/ l)g/ I I)~/ l)~/ 1)£/ , __ T ~~""'I= ~l;;="'l'w ~l~I- \\W ?oo'"~"" I $",_,,I ITT,._,.. ""' ~"'" I ~'" ~"' ' ~ -*~m~m I '""". '"~~oo ~ ~~~'?"'" 11~ """' ~ '"""~:r,1, ("' ? '"'" I ~'" (~'\\- ' -"~mo f '"~'" + ~ I I ITT"-'~"~j,~"' :)lj; ~f= ' ~"7,w ~"7,w I " I~

h.

I I I ? l ? I ~ I I I + + + :i + r r '1 ~ { ~ . J, I ~*-* 0~1 6 6 ~1 6 2 0~1;_ 4 ~ i I I i1 I I I 1-cT r-_ ~~ 6 b~f (d I I I lcVJf (Aj I ~! ii 1-cT 11 1 I I I I I I T I 1 I K16-7 i I I ( 1' I /\\- I I I i I ILJ' 1' II ~~~p~~ i CVL @ L.J i I I I @ I PPCS l sPkE ~@215 510 Mee c i~! @oo cs@o'o sP!cE i @) ' I I I -oos5 0-JG. 11

  • _:1 I

15 A I 350 ~us 16 TO I_ @~o\\ I @ @~o @oo S0P1A1C0EB 300 @~o 125 @25 ~- @' !Mee Dl SPARE 0110A @ 300 @~o @so I BUS 14 TO 11 ,1* CPT HP BUS 15 TIE 1 HP I P HP HP HP HP HP HP P <MCCD> P _gfJ"98 P P _gfJ"9A HP HP <MCCC> HP HP HP HP HP I BUS 13 TIE 1 I 1.5 v:./A -0061 I -0098B 0098A l -0060 l I T 480-SI SI cs CNMT CNMT AUX RHR CHG CHG PRZR ccw SFP SAFW SAFW CNMT CHG ccw PRZR RHR AUX AB CNMT cs SI I I' II* MCB BUS 16 240/120V PMP B PMP c ' PMP B RECIRC RECIRC FW PMP B PMP B PMP c BU PMP B RECIRC PMP D PMP c RECIRC PMP A PMP A PROP PMP A FW EXH RECIRC PMP A PMP A I METERING j SUPPLY <PSI018> SPLY C1 ! <PSIQ28> FAN B FAN C PMP B <PAC01B> <PCH01B> <PCH01C> HTRS <PAC02B> PMP B <PSF01B> <PSF01A> FAN A <PCH01A> <PAC02A> HTRS <PAC01A> PMP A FAN G FAN 0 <PSl02A> <PSI01A> BUS 16 -oo56 -00738 i <PSl01C> I -0079B <ACF08B> <ACF08C> <PAF01B> -00788 -0071B -0071C -0090 -0072B <PAC07B> -0446 -0445 <ACFOBA> -0071A -0072A -OD89 -0078A <PAF01A> <AAF04> <ACF08D> -0079A -0073A -0055 3 I -0074 -0095A -0094B -0077 -0108 -0094A -0076 -0112 -0095B I I 1 *{0 x/J!v16 I 1 1 1,.,-. CPT 1.5 KVA T 48Q-240/120V Lcv-8 cJ:i5G I

  • -----------------~--~*~---------~-1---

GROUND I I D~~~iN ~~~------~---~-~-- ~~~L~ <KOG018> ! I ! ! I l /!' TO BUS 16 -0102 I AKR-50 )52/EG1B3 I (MANUAL) ~ BUS 16 TO BUS 14 TIE -0062 OG A <KDG01A> BUS 14 TO BUS 16 TIE -0554 S! SPLY C2 PMP C -0075 STA SERV XFMR 14 COOLING FANS -0054 DG A SPLY TO BUS 14 -0101 GROUND DETECTION SCHEME -0050B UNDERVOLTAGE SCHEME BUS 16 -0055 (NOTE 3) ~NMARKEO - ? TYPE 08-25 ACB

  • - ? TYPE OB-50 ACS 25 480V-3¢-60Hz BUS 17 26 27 28 480V-3¢-60Hz BUS 18 Q -

? TYPE OB-75 ACB ? TYPE OB-50 DUMMY ACB UNDERVOLTAGE SCHEME BUS 14 -0054 (NOTE 3) r------A------.. l ~!~it I ~ ~ Ii~ ~ ~ B ~

  • ----'Cr-~-

D B A

2) DRAWING NUMBERS LISTED BELCW BUS UNITS REFER TO CONTROL SCHEMATICS (21946 SERIES) UNLESS OTHERWISE SPECIFIED. SEE REFERENCED CONTROL SCHEMATICS FOR PT, CT, RElAY ANO METERING EIN'S.

5

  • ~--r-
3) OPERATION OF ANY (ONE) 27 RElAY Will CAUSE ANNUNCIATION. OPERATION OF TWO OR MORE 27 RELAYS Will INITIATE A DIESEL START AND GENERATE A BUS TRIP.

MCB METERING BUS 14 -0054 /~ I)~/ I I) 1)52/ 1)52/ 1)52,.; ~c\\'~'i'2ov 1 ~/ (G1B21 \\ (CC1G{2' FP I IH 8 ~~21o i l i 1,.** l l.)s21 i)s21 I)~/ l)52/ ~~m ~ ~rn ~ mM* ~""

4) UNITS 24C, 26A, 28C, JOA AND 300 HAVE EMPTY CUBICLES.

2 PT'S 2-PT'S ~-120V h0-120V I = =

0.

K17-6 6A ~ MCB METERING BUS 17 -0056 K17-2 6A UNDERVOLTAGE SCHEME BUS 17 -0056 (NOTE 3) 1)17~ ! ~~ ~ ~

W I
w :-].,

~ YJ., r r 1 '!' r 1 I l I 3-Cr'S~ 200-5 3 BUS 17 I I s_ubb6~ l, ) I A ! SP~CE I @) I Lf64\\ l! -0111A <J I XFMR T1 ~ j I ~48'1(48DV-3¢-60Hz CV-8 II p <1115 KVA <PXSH007> GROUND I I MO DETECTION l FIRE SCHEME DG B PMP I XFMR T2 -OOSOE SPLY <PFP02> <] ~ 480/240V-3¢-60Hz TO -0080 <] rvy'I\\ 45 KVA BUS 17 1 1 <PXSH001> -0104 I ~~3~~v MCC G SPLY G2 <MCCG> -0100 cw INTAKE HTR B <EHTRCW01 B> -00918 ~ ~og~~EJ=(b3 I <l.. I.. XFMR Tl ~48'1(480V-3¢-60Hz <l I ~~xs\\roi9> <l I XFMR T2 ~480/240V-3¢-60Hz <] r'fYY', 45 KVA I <PXSH004> I s.33 KW 5~ 240V cw INTAKE HTR D <EHTRCW01D> -00910 r r, r 1'

  • x. 1 3-CTStt (j) l

@I L __, __ J 200-5 I A 3 350 BUS 17 TO I XFMR T1 HP Bu:0)ii3nE <I VJJJ 48'1(480V-3¢-60Hz s~~ ~~ <I~ ~~xs~~i6> PMPB PMPD I <PSW01 B> <PSW01 D> I XFMR TZ -0D82A -00826 <J VJJJ 480/240V-3¢-60Hz <lT~x~i11> ~33 KW 5~ 240V cw INTAKE HTR A <EHTRCW01A> -0091A MCC G SPLY G1 <MCCG> -0099 UNOERVOLTAGE SCHEME BUS 18 -0057 (NOTE 3) ITE-J13

REFERENCES:

33013 0623, 1 33013-1952,1 33013-2539 34480-0100 & 2 & 2 MAIN ONE LINE OPERATING DIAGRAM THREE LINE DIAGRAM - 4BOV SWGR ONE LINE WIRING DIAGRAM - PLANT LCAD DISTRIBUTION 480V SWGR INDEX SCM.E CAO FILENAME STATION #13 AS BUILT R~ F'OR NONE 33013-0652 480 VOLT R.E. GINNA STATION ONTARIO, NY ONE LINE WIRING DIAGRAM JOB NUMBER DRAWING NUMBER SHEEf REV 4777 33013-0652

~~~@ 52/ 13SS 3-CT'S 200-5 3 2 52/ A\\/P9C 3-CT'S 75-5 3 3 52/ CWP1A 3-CT'S 300-5 3 50 51 C0-8 50 --@ 51 COM-5 SG SG w A 3DAA5 3DAA5 1-cT..+-. BYZ 100-5 1 50G ITH 1 -CT,.+----, BYZ 100-5 ITH <1 4160/480 <1 ~30-60Hz 5H0P0 MO/AVP9C STATIO~ CONDENSATE SERVICE BOOSTER XFMR 13 PUMP C AA/FA <PC001C> Z-5.75% 21946-0038 1000/1333KVA 1 -CT,.+----, BYZ 100-5 ITH 2000 MO/CWP1A HP CIRCULATING WATER PUMP A <PCW01A> 21946-0031A <PXTBSS013> 21946-0028A 1200 KVAR~E-4400 V, Y VAC CAP/CWe1A 17 4160V-30-60Hz BUS 12B 18 3-CT'S 4000-5 1 9 4 . 52/ 1HDP1A 3-CT'S 75-5 1-CT BYZ 100-5 3 3-CT'S 200-5 SG KA-241 1-CT BYZ 100-5 400 MO/HDP1A HP 5 52/ CP1C 3-CT'S 200-5 I SG 3 I 50 _L~ 6 51 COM-5 MG-6 ITH I I I KA-2411 I I I I I I I I 1-CT BYZ ___ J 100-5 1500 MO/CP1 C HP 6 52/ CP1A 41 60V-30-60Hz BUS 11A 7 52/ FWP1A 3-CT'S 800-5 I SG 3 I 3 8 52/ RCP1A 3-CT'S 1200-5 3 3-CT'S 75-5 50 _1_~6 51 COM-5 MG-6 50 - ---04' 51 \\J COM-5 SG 50P __ ---041 51P --v.J SG ITH I A I I KA-2411 I I I I I I I I 1-CT BYZ ___ J 100-5 KA-241 3-CT'S 1200-5 1-CT BYZ 100-5 50G ITH A KA-241 1-CT 3YZ 100-5 1500 MO/CP1 A HP 5500 MO/FP1A HP 6000 MO/RCP1A HP 9 52/ EF1A 3-CT'S 4000-5 3-CT'S 3000-5 r-@ I SG 3 I 1 0 52/

  • 11 A 50

_j_~6 51 COM-5 MG-6 I I A. I KA-2411 I I I I I I I I I ___ J INCOMING SUPPLY FROM UNIT XFMR 11 SEE 33013-062J, SH... 350 MO/EF1 A HP HEATER DRAIN TANK PUMP A <PCD03A> 21946-0035A CONDENSATE CONDENSATE FEEDWATER REACTOR COOLANT PUMP A AUX BUILDING EXHAUST FAN A <AAF08A> 21946-0036A BUS 11A SUPPLY (52/11A) 21946-0023 3-CT'S 3000-5 20 PUMP C <PCD02C> 21946-0034 PUMP A <PCD02A> 21946-0032 PUMP A <PFW01A> 21946-0030A 21 <PRC01 A> 21946-0037A 3-CT'S 400*0-5 22 87 ~ PERIPHERALS 3 {FOR 11T SEE 33013-HU-1 0623, SH.1 l 3-AUX,.,._~ CT'S 5-5 11 A 2E K1305 '-"../ 2-PT'S T4200-120V 6A '--.--{27-1 27X1 11A 11A TO SS BUS 11 A CV-7 62X2 11 A .t: 1303 '-A../ 1-PT If" 4200-120V ~ UNIT 11 MG-6 TO 3-CT'S 2000-5MR 1200-5 TAP X SIDE OF UNIT XFMR 11 SEE 33013-0623. SH.1 TO SS BUS 11 B (NOTE 3) 6A r~ TO I 3 51 11 A C0-8 A ~------ 81-2 B1X2 11A 11A KF TRIP I ANO I TO SS BUS 11A BLOCK I ~;t-- 1 I I 3 L 50S 51S C0-5 51N 11 A C0-B BUS 11A DIFFERENTIAL LOCKOUT RELAY 21946-0044A ~~TO SS BUS 11 A (NOTE 3) 23 UNDERVOLTAGE AND UNDERFREQUENCY SCHEME 21946-0015 ---7X4 11 A KV-1 AGA 4160V-30-60Hz BUS 11 B 24 25 t 3-CT'S 3000-5 12 52/

  • BTA-A 3-CT'S 3000-5 FUSE REIVEO K1309 T

CPT 5KVA 4160-240/120V V' UNIT 12 26 BUS TIE 12A TO 11 A 21946-0020 3-CT'S 4000-5 13 3-AUX CT'S 5-5 TO 87B/12A SEE 33013-0623, Sr.2 DUMMY ~+-~ BREAKER 3-CT'S 3000-5 FUSE REMOVED 12A I K1304 -.J._, 1-PT If" 4200-120V ~ UNIT 14 3 HAND RESET 'Y 51 I 12A FUSE C0-8 REMOVED 86 12A WL I ,_L 1 I TO MOB FOR CONN DIAGRAM SEE 33013-0623, SH.1 INCOMING SUPPLY FROM THE Y SIDE OF AUX XFMR 12A OR 12B FOR CONN DIAGRAM SEE 33013-0623, SH.2 DUMMY BREAKER (DX12A) 21946-0025 51 N __ J 12A C0-8 BUS 12A OVERCURRENT DIFFERENTIAL LOCKOUT RELAY 21946-0045 41 60V-30-60Hz BUS 12A 14 1 5 c-----; 52/ c-----; 52/ K1307 '-".; 2~PT'S If" 4200-120V ~ UNIT 15 3-CT'S 200-5 TO TRIP AND 18SS BLOCK 3 KP-241 3-CT'S 400-5 14SS 3 50 51 C0-8 WI--~ KP-241 27-2 12A 6A I 27-1 12A ITE-27N I ITE-27N 1-CT..+---, BYZ 100-5 1 -CT..+---, BYZ 100-5 ALARM 27-2 VP9 1 6 c-----; 52/ AVP9A 3-CT'S 75-5 3 50 --@ 51 COM-5 TO SS BUS TIE 11 A TO 12A A 3DAA5 25A --8 CVE 1-CT,+---, BYZ 100-5 SG 50G ITH ITE-27N <1 4160/480 <1 ~3i1l-60Hz STATION SERVICE XFMR 18 1000KVA AA-150"C Z-5.753 PXSHSS018 21946-0029A ITH <1 4160/480 <1~3i1l-60Hz STATION BUS 12A. 128 SERVICE UV ALARM XFMR 14 SCHEME 1500/2000KVA 2' 946-0049 AA/FA 150'C Z-5.753 PXABSS014 21946-0027A 500 MO/AVP9A HP CONDENSATE BOOSTER PUMP A <PCD01A> 21946-0039 27 28 29 30 31 TO 87B/12B SEE 33013-0623, SH.2 2E K1308 2-PT'S tf"'-A./ 4200-120V ~ UNIT 21 2E K1306 '-.AJ 2-PT'S T4200-120V 3-CT'S 3000-5 3-CT'S 400-5 1-CT BYZ 100-5 52/ 16SS 3 KP-241 1 50G ITH <1 4160/480 <1 ~3o-60Hz STATION SERVICE XFMR 16 1500/2000KVA AA/FA 150'C Z-5.753 PXA8SS016 21946-0027B 3-CT'S 200-5 1-CT BYZ 100-5 52/ 17SS 3 DUMMY >-+-~ BREAKER 3-CT'S 3000-5 3-AUX CT'S 5-5 12B >---<lf----1--< w 50G ITH INCOMING SUPPLY FROM THE X SIDE OF ALJX XFMR 12A OR 12B FOR CONN DIAGRAM SEE 33013-0623, SH.2 <1 4160/480 <1 ~3o-60Hz STATION SERVICE XFMR 17 1000KVA AA 150'C Z-5.753 PXShSS017 21946-0029B DUMMY BREAKER (DX12B) 21946-0026 52/

  • BTB-B 3-CT'S 3000-5 HAND 3

RESET 51 ~6 128 12B 1 C0-8 WL I I l 1 I TO 51 N J TRIP AND 12B BLOCK C0-8 /!' FUSE REMOVED I K1310 l...A..J CPT tf"5KVA ~ 4160-240/120V V' BUS 12B OVERCURRENT DIFFERENTIAL LOCKOUT RELAY 21946-0045 BUS TIE 12B TO 11B 21946-0021 27-1 12B -1 ITE-27N : ~~ I 27-2 I 12B -j I ITE-27N I ALARM TO SS 1----1 BUS TIE 11 B TO 12B (NOTE 3) 6A BUS 12A, 12B UV ALARM SCHEME 21946-0049 6A 3-CT'S 3000-5 52/

  • 11 B 3-AUX CT'S 5-5 3-CT'S 75-5 52/

EF1B I SG 3 I c-----; 52/ RCP1B 3-CT'S 1200-5 3 c-----; 52/ FWP1B 3-CT'S 800-5 3 c-----; 52/ CP1B 3-CT'S 200-5 I SG 3 I c-----; 52/ HDP1B 3-CT'S 75-5 3 .--~...., 52/ CWP18 3-CT'S 300-5 3 c-----; 52/ AVP9B 3-CT'S 75-5 3 c-----; 52/ 15SS 3-CT'S 200-5 3 50 --f'.74\\ 51 -\\J 50 52/

  • BTA-B 3-CT'S 3000-5 3

50 _j_~6 51 COM-5 MG-6 SG SG 50 _j_~6 51 COM-5 MG-6 SG Sr, COM-5 COM-5 SG 51 00-8 CVE ~ 11 B w INCOMING SUPPLY FROM UNIT XFMR 11 SEE 33013-0623. SH.1 51 ~6 11B 11B --1 C0-8 WL I I TO TRIP 1 I ANO BLOCK 51 I 11B C0-8 I I I 13 ~ 50S ~ 51S HGA C0-5 1-CT,+---, BYZ 100-5 KA-241 50G _J f----127-4 _ ~7X4 11B 11B KV-1 AGA BUS 11 B SUPPLY (52/11 B) 21946-0024 BUS 11 B DIFFERENTIAL LOCKOUT RELAYS 21946-0044B TO SS UNDERVOL~T-AG_E_A_N_D------------------~-1 BUS 118 UNDERFREQUENCY (NOTE 3) SCHEME 21946-0016 ITH 350 MO/EF1 B HP AUX BUILDING EXHAUST FAN B <AAF08B> 21946-0036B 3-CT'S 1200-5 1-CT,.+---, BYZ 100-5 ITH KA-241 1-CT,.+---, BYZ 100-5 50G ITH KA-241 1-CT,.+---, BYZ 100-5 ITH KA-241 ___ _J 6000 MO/RCP 1 B HP 5500 MO/FP 1 B HP 1500 MO/CP 1 B HP REACTOR COOLANT PUMP B FEEDWATER PUMP B CONDENSATE <PRC01 B> 21946-0037B <PFW01 B> 21946-0030B PUMP B <PCD02B> 21946-0033 NOTES:

1)

- @ 50-DH-350 ACB 1200A SOLENOID BREAKER

2) * - @ 50-DH-350 ACB 3000A STORED ENERGY BREAKER
3) SS -

SYNCHRONOUS SWITCH. SEE 33013-2206

4) FOR
5) SEE AND TRIP AND LOCKOUT BREAKER SCHEME SEE 33013-0623.

REFERENCED CONTROL SCHEMATICS FOR PT, CT, RELAY METERING EIN'S.

REFERENCES:

33013-0623.1 33013-1951 33013-2205 33013-2206 33013-2409 33013-2539 34000-0100 & 2 MAIN ONE LINE OPERATING DIAGRAM THREE LINE DIAGRAM - 41 60V SWGR 4160V METERING SCHEMATIC SYNCH CHECK SCHEMATIC ONE LINE WIRING DIAGRAM - AC ELECTRICAL SYSTEM ONE LINE WIRING DIAGRAM - AC SYSTEM DISTRIBUTION 4160V SWGR INDEX KA-241 1-CT,.+---, BYZ 100-5 50G ITH 400 MO/HDP18 HP HEATER DRAIN TANK PUMP B <PCD03B> 21946-0035B 1 -CT,+---, BYZ 100-5 2000 MO/CWP 1 B HP CIRCULATING WATER PUMP 8 <PCW01B> 21946-0031B VAC ! 1200 KVAR 4400 v. y CAP/CWP'B A 3DAA5 1-CT,.+---, BYZ 100-5 50G ITH 500 MO/AVP9B HP CONDENSATE BOOSTER PUMP B <PCD01 B> 21946-0040 1-C:T,.+---, BYZ 100-5 50G ITH w KP-241 BUS TIE 11B TO 11A 21946-0022 <1 4160/480 <1~3i1l-60Hz STATION SERVICE XFMR 15 1000/1333KVA AA/FA Z-5.753 PXTBSS015 21946-0028B 1/bO AS BUILT DATE RELEASED FO.::i ENGINEER ,__R_EV~ ___ R_EVI_S~E~D _F_OR __ __, DRAWN CHECKED RESP FACILITY GINNA BY BY ENGR SCALE NONE CAD FILENAME 3G065301 STATION #13 4160 VOLT R.E. GINNA STATION ONTARIO, NY REVJEWER ONE LINE WIRING DIAGRAM Joa NUMBER DRA1//ING NUMBER SHEET ! REV 4777 33013-0653 CCD 3 CNTRL COPY#

A B c D E F G H J 1 g\\~ z 11"'1 ~ "' I ~I~ ~ NOTE 10 2 3 4

J 8

D I _CALORIMETRIC r71 TEST CONNECTION 5 ~ 3509 6 J ROOF T

il VENT STACK 14-MV-150-4 (TYP.4)

~ 3511 I J 6 ROOF T 0 ~ I VENT STACK 14-MV-150-4 (TYP.4) ~ 3513 6 J ROOF 7 VENT STACK 14-MV-150-4 (TYP.4) ~ ~ i 3515 6 ~ ~- ~~ ROOF T 0 ~ I 8 VENT STACK 14-MV-150-4 (TYP.4) 9 10 11 12 3" 3615 (H-8) FE pi°1 I TUBING 600-1 3455 NOTE 6 30-MS-600-1 I I I I I I -0 T .~ - -0 T~ 6 _6 di -~ T."'_, -~ TT~ TT~ -0 T *' --~'~!----<<'.",_3_3_01_3_-_1_8_9_3~ 30-MS-600-1 NOTE 6 (B-1) 3/4" 3405 SMS03A SMS04A ri1 3 4" 12362B -.:: N ~I~ '" 0

c r r-...-_,

0 '----+---~ E ~ =<! "' 0 0 _,.I ~- ~N =<! "' "U 0 .;':; (J) 12362D 3/4" 3404 SMS03B SMS04B TT1 3/4" L!.l ~+-D 12365B E EMSOlA EMS01B 3401 SMS06A SMS05A 3/4" r71 12359B E 3400 SMS06B SMS05B m 40 3 4" ,)'2--1£ 10 12368B E c <I1 z " CALORIMETRIC TEST CONNECTION £ <I1 0 N

I::

~§ 3 3/4" 0 L!.l 3505D D 11 2" 11 2" .---I I f-(] I I I ~¢¢ ~ I.:: 0 I - ~ I... f D VENT STACK ~~~12-MV-150-4 1* I I 1* ¢¢ 0 ~.---I--'] LOCAL J> 3413C SAMPLE 'j' 0: (A-8) <I1 fc!:;--=i::-_t-J 33013-2711-1 <I1 X1406A ~ : 0 L!.l '-- _J - 3/4" 12361 L 3 I 1--~---. ~ N 0 0 -+~ ~ D 12361H MANIFOLD I 30-MS-600-1 TUBING 600-1 g: 0.... <I1 3 4" I.:: VJ I ~ 0 I - I g: I~ I I I I I I I I I I 3 4" 1--~-'-t--] L ____ _ A-2 33013-1231-2 NOTE 8 1 1 2" 3/4" 3411S IZ/3411 3411A c f.- 1.... 1---11-------ll--C><l-'---l.f------11-----..,1/---(f-------I~ TMS10 3504D TUBING 1150-4 9001A E-8 TMS09 33013-1893 X9003 '------../ 33013-1236-2 FEEDWATER CONTROL FLOW SIGNAL PZ/4269 "' 8 - 0 3/4" TMS08 TMS07 NITROGEN BOTTLES INTER. BLDG._ TURB. BLDG. 0 \\;' Tt.4S06 ROOF VENT STACK 14-MV-150-4 (TYP.4) ROOF VENT STACK 14-MV-150-4 (TYP.4) 11 2" 0 ~ L_ __ TMS05 ROOF ~- 0 - VENT STACK 14-MV-150-4 (TYP.4) ~ L!.l D ~ T

il 3510 6,.

T

il 3512 6,.

~ 1 1 2" t 0 I -"' 'i'... 3508 6 J f D T

il I

-0 T~ _;_:...__'VENT STACK 12-MV-150-4 LOCAL SAMPLE ~ 6 T T ~ ~ I -0 T~ ~ 6 --~ T T:.. 3514 6 T 1-MD-150-4 (B-10) E--1.... 1---~---lL~3~30~1~3~-~2~71~1~-~1...../ 3412C X1406B CT-.--~1,-~M~S~-~60~0c-~1-.-----*"'t--'3v

o.
:

< VJ le "' I g.... 3671 TEMPERATURE COMPENSATED SUPPORTS (TYP.4) N ' INTER. BLDG. --+- TURB. BLDG. N - 33013-1232 351~ IITl lfil 2 3 FOR CREVICE ZMSOB 3 4" 2" CLEANING I ri)ir;J-j I f{j}i I 1-----"N+::M7SO:,.::B __ -C-::l-r2"-",--.--f'--35*2... 1A1---'] ['--I 1---~ 2" g I 3673 (1-1) 33013-1233 MAIN CONDENSER A 1" 1" 3675 (1-1) 33013-1233 MAIN CONDENSER A 11 2" 3605 3674 LMS29 ORIFICE BLOCK r ~ 1" ~525 NOTE g ~ P.> 3523 t.1 ~ ~'i ~<ff ~ ' ill ZMS09 !.{, '? H::-:1-1 I f{j}i 11--=-D,iNi"'M'-"'S0:::.:9'---1::.:::J_J N ' 3607 NOTE 9 " ffi 3603 NOTE If-II..._--' 12 35218 3/4" 3609 1" 1" 3617 ~ 3676 I 3677 3683 1" 1"-600-1 NOTE 9 3604 3/4" 3608 r1' :x:H I f{j}i I NMSl 9 360 ZMS 1 o 3602 1 2" ~ -.\\, 1f D NMS10 3/4" (1-2) _,---~~---. 11 2* 33013-1233 P~~_u_[)f;:<<JJ I ill I 1" 2" 3616 3524 3522 1" MAIN CONDENSER A 3610 N N VENT STACK 14-MV-150-4 (TYP.4) TEMPERATURE COMPENSATED SUPPORTS (TYP.4) 2" r--___,, __ _, 11-J 35208 r 1" ~ ~~3_67_0 _________ ...J 0 TURB. BLDG. INTER. BLOG. N ' 3" 3" 3614 2" (1-1) 3678 ---1, 33013-1277-2 E'-----L,-_..,___, "' "F--'--ft-'-f::<<:J-...J ~ ~--TURB. BLDG. YARD (C-12) ~ 3672 I -0


~~------~~~-----~~.--------<<'."~~3_3_0_13_-_18_9_3_~

T~ 30-MS-600-1 NOTE 6 (C-1) 33013-1232 ---~-:i

  • ~

IITl 3 351~~--+ 35~ [§] 2 3 'if NOTES:

1. FOR GENERAL NOTES, REFER TO DRAWING: 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDES 33013-1231 REV. 44.
3. SAFETY CLASS BREAK POINT FOR EACH VENT, DRAIN, OR TEST CONNECTION SHALL BE AS INDICATED AT EACH CONNECTION POINT.
4. ALL SAFETY CLASS LINES ARE SEISMIC CATEGORY 1.
5. DELETED
6. IN ACCORDANCE WITH EWR 5114, 30" MAIN STEAM LINES FROM PENETRATIONS P401 AND P402 TO THE TURBINE ARE HIGH ENERGY LINES.
7. DELETED
8. THE EIN REFERS TO THE NITROGEN CYLINDER LOCATION THE NYTROGEN CYLINDERS ARE INTERCHANGABLE.
9. LINE SPEC. 600-1 ARE STILL IN EFFECT, PIPE MATERIAL IS CHROME MOLY, P22.
10. RADIOGRAPHY SOURCE ACCESS PORTS ARE 3/4", 3000 LB., SW COUPLINGS.

3410S ...--+-'.:"=+L~- ~"-L-- - _L _ - - - -i

~ I I

N> "'I ;<:; "'1 0 ri; N I~ I !f ~I~ I 12370B ?!I§ I I I I I I I I I I IZ/3410 6-MS-600-1 14915 3410T3 3410A 3/4" l~I 9006 3 - ~

11. DELETED
12. SPOOL PIECE (MID# 5008869) AVAILABLE FOR CONNECTION BETWEEN 3521 B AND 5722G. ~~----~--~--.----~----1

{llJ:s' CAD ALE NAME 33013-1231,1 CONSTRUCTION JTC><P~l~"l1--..-~~-.-~~-3~1r4-*~-,-~.---,~--, 9012 0 0 N LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT F"OR CONSTRIJCTION BIOO!NG PURPOSES ENGR. AS BUILT DATE RELEASED FOR I L---------~ I STEAM GENERATOR B 1 2 (F-5) 1 - - - --l 33013-1236-2 > I I I L------~ ,------~ I ~ I PZ/4270 I ~ L-----------------~ I FEEDWATER CONTROL FLOW SIGNAL 3 4 5 9000A X9002 TUBING *I* 150-4 E-12 [=3~3@0~13~-~18~9~3~:::::>----11--CI-----' 6 7 <DI°' rr oO NOTE 8 8 TMS16 Th!S15 TMS14 TMS13 TMS12 TMS11 NITROGEN BOTTLES 9 10 11 GINNA STA. R.E. GINNA STATION JOB NO. NONE MAIN STEAM (MS) (SAFETY RELATED) P & ID DRAWING NO. EWR 3391E 33013-1231 SHEET 1 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 VENT TO ATMOSPHERE 1 I 2 (E-5) 33013 1231 1 (H-9) I 33013-2285 (CLOSE) (1-9) I 3 I 4 I 6MS6001 I 33013-2285 >~--i-L -~I'" (OPEN) 1/2" PAF03 TURBINE DRIVEN AUXILIARY FEEDWATER PUMP (SEE 33013-1237 FOR PUMP DETAIL) SAF03 TDAFWP GOVERNOR SEE NOTE 5 "'J TURBINE t I f I f OP/9519E NOTE 5 I c___J 9519E SEE NOTE 5 ! l I 1/2" (G-6) I 33013-2285 LEAK OFF Y' \\7 YNOTE 4 3 \\/ 1 HAND .---_,,,,~;,---,--i-----D-~-,1-c-E'l,-------~-L-J1WHEEL L...',3652 TRIP LATCH ~* t (G-6) (G-9) µ I 33013-2285 I 33013-2285 ~ le__ _____ __ TRIP CYLINDER TRIP DRAIN LATCH HOLDING PRESSURE 3-MS-600-1 I en I 0 0 I 5 I 6 7 3570 I 1/4" 600-11150-1 150-2 I 3/4" ZMS16 .---------~-----<'i--t>:::J-l'f---1/<AJ----~T ' 3586 " 3586A I 3/4" '(

\\538 3634 3642 600-1 i150-1 150-2 1/ 2" ZMS15 1 112.. ~

,--------'-----+'1-!><J-fl--~';:-<f-----IT 1--1~1~'2'-'l"~.l---tx.1-'-"-='-l---l " 3585 " 3585A 363l 3633 V 600-1 600-11150-1 1/4" 3641 600-1,150-1 150-2 0 I N ZMS14 ~---------------------------------------1~/_2"_,,f-t;<<::H'l---{':0.:::-l------IT 1-----1*~-~*--i:x*::i-~1/~2~*-l----l ' 3579" 3579A 3636 3632 Pl 2935 c OJ z Gl ~0-1 3640 1/4" I 0 I g I 600-11150-1 150-2 N (J) 0 0 I ~ 1/2" ZMS13 - J 1/2" ~--------------~---------------------------1'1-l><H'l----C:--(l------IT 1----l""'}-'-~-C><}-'-=--l---I 11 3574 11 3574A 3635 3631 8 4" 1/4" INTERMEDIATE BLDG. TURBINE BLDG. (G-10) I L---~: 33013-1277-2 Pl 2512 600-=! 11.50-1 600-,11120-1 1/4" ~ 3639 9 I 3/4-150-2 3570D (J-7) I 33013 1237 LUBE OIL COOLER SW DISCHARGE 4" ___) LOOP SEAL 1" 125-1 1/2" ~---------------~---~-----------<! :1---~-::-:::r----1:><~}--------------------'--------------------------' 3S70B 3570C 4" 2 1/2" 2 I 3 I 4 I 5 I 6 7 I 8 I 9 I 10 TCD04 TURBINE DRIVEN AUXILIARY FEEDWATER PUMP QUENCH TANK 10 4" I 2 1/2" 1" I 1 1 I 12 NOTES:

1. FOR GENERAL NOTES, REFER TO DRAWING:

33013-2241.

2. THIS DRAWING WAS CREATED FROM 33013-1231, R8/. 44.
3. SAFETY CLASS BREAK POINT FOR EACH VENT, DRAIN, OR TEST CONNECTION SHALL BE INDICATED AT EACH CONNECTION POINT.
4. STEAM LEAKOFF IS CHANNELED INTO A COVERED FUNNEL THEN TO THE FLOOR DRAIN.
5. SEE FCMS DESCRIPTION OF EACH EIN FOR FUNCTION.

REF. DWG.: LB112541. 1 1 &ORIGINAL 2;11;13 a1u1r~ '"'".*;-o: a 11/13 CAO FILE NAME 33013~1231,2 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR. '~ GINNA STA. R.E. GINNA STATION SCAt£ NONE JOB NO. EWR 3391E MAIN STEAM (MS) (SAFETY RELATED) P & ID DRAWING NO. 33013-1231 SHEET 2 OF 2 CCD 01 CONTROL COPY # I 12 REV. A B c D E F G H J

A B c D E F G H J 1 (1-1) < 33013-1233 MAIN CONDENSER A 2 3 2943 (F-3) 1" <~_3_30_1_3_-_1_9_0_4~t-----------~ GLAND STM. COND. (G-1) 3/4" <~_33_0_1_3_-_1_2_3_3~r---~-----~~ .. 1-------- MAIN CONDENSER A A-7 --C><f-1 33013-1918-1 X3558B'--------___? D 0 " OJ ~ (/) D 01 (D-1) 3/4" 2911 4 ,,,--~-G--- 7~-,X15352 33013-1894-2 D 01 ED 01 D (!) cu 5 M 3601A SEE NOTES 6 t;l AND 7 0 3869 "' cu <O 6 LMS06 (A-12) 33013-1231-1 MAIN STEAM SYSTEM 30" 36" --{.><J- ~ 33013-1918-2 > ---PA __ N __ E __ L--~ X3830 11000 y X3518 (G-12) 33013-1231-1 MAIN STEAM SYSTEM (G-1) 8 33013-1918-1 HP EXHAUST TO MSR 1B (B-12) 33013-1918-1 X355l MOISTURE SEPARATOR REHEATER 1A (E-12) 36" s INTER. BLDG. TURB. BLDG. 1" 1" TC E----i-r---i---.---j TC 8" 3571A 8-MS-600-1 8-MS-600-1 3571B I (/) 33013-1918-1 X3550 MOISTURE SEPARATOR REHEATER 18 X3552 (E-12) 33013-1918-2 MOISTURE SEPARATOR REHEATER 2B (B-12) 33013-1918-2 H-11 33013-1921 X3249 MAIN CONDENSER B 8-MS-600-1 0 D I H-6 150-4 6"r----' 2* 600-1 600-1 C-1 Ol 0 ~ .j>. I (/) I Ol D D I X3884 150~0-1 01 D u '-.. I .J>. N ~ 600-1 X3885 1-1 33013-2249-2 33013-1904 TUBING 600-1 E--t----t~----l 3856B "' "' ~ 01 f11 4" w D 4"' f---~--------------~----j'-.. C-1 600-1 E---+-.---~--~ (H-1) 33013-1904 (F-1) 3851 "' <D cu D F-1 TURBINE SHELL HEAT FLANGE (TYP.) 11 2" 33013-2249-2 F-1 33013-2249-2 GLAND STM. COND 11/2" TW KMS02 HP TURBINE (G-1) 1" <~_33_0_1_3_-_1_9_0_4~f----"'-- 3870 3545A 1" --j1--1::x:1---~~----11-------'---'--JL GLAND STM. COND SMS19 MAIN CONDENSER PRIMING AIR EJECTOR A 3837A VJ cu "' "' L!J 600-1 D TUBING 600-1 E-+-__,,,...___,""1.;--1 3461 vE--+..._ __ _.,,._. 8534 VE-..4-1 3526 2* 600-1 L---i 6" 150-4 (H-5) (!) 01 L!J TC 3 4" 7 2" NMS17 D <D ~ 3846 "' 4.. w D 2 1/2" 6993 TURBINE SHELL HEAT FLANGE (TYP.) TUBING 600-1 D °'-!-----' 1* L 6" 1" 3658 4* L 8 X15353,--~ 1 -~7~---.... --c><t-t 33013-1894-2 (1-7) 33013-1894-2 D 0 .j>. OJ 9 10 2942 2945 (1-2) 3/4"


~~-------------------;___33_0_1_3_-_1_2_3_3~>

.j>. 600-1 C-1 3/4" 'I ~ (/) 0 .j>. 2940 NOTE 5 C-1 33013-2249-2 (D-1) .-----LL---<<:33013-2249-2

==='==~L========~L~ 3/4" 3/4" MAIN CONDENSER A J-2 33013-1233 MAIN CONDENSER A G-1 33013-1233 (D-5) MAIN CONDENSER A ---;L>--------~L------~L---~<33013-2249-2 (F-1) 2912 11/2"


'-"-=--------..... 0------------ll 33013-1233 11/4" (A-1)

--;L-------tL------tL---~<33013-2249-2 O> ' (A-1) --~L------~L-------<L---~<33013-2249-2 600-1 C-1 600-1 MAIN CONDENSER A (F-3) ~---f><l:- 1------~ X3883 Ol D ~--<"' ~ 8" t 36020 8" f71 D 600-1 C-1 ~ ~I~ '------r--...e----j cu Ol 3857 1 1/2" (C-1) 33013-1918-2 HP EXHAUST TO MSR 2A (J-1) 33013-1904 X3886 1 1/4" (F-1) _J ,-----(--F--_3--)-----'--'-'-'-------11 ... ----------1~3--3 0 __ 13 __ - __ 19 __ 0 __ 4~> GLAND STM. COND. ---LL-~i<:::33013-2249-2 (F-3)


+---~r(:33013-2249-2 L

L I (1-5) ~. tL,.----<< 33013-2249-2 1 1/2" (G-1) _____ ___::::::===========:::_ ___ _'._:.!.;.'.:_ __ -l... ~------------1 33013-1233 (H-1) ~----


tL---<< 33013-2249-2 MAIN CONDENSER A (1-2) 3 4" NOTE 5 D

D cu L!J D D 0 H-1 33013-2249-2 8513 L!.I D 3/4" NOTE 5 3543 MS-150-2 SEE NOTE 9 33013-1903 33013-1922 ATM. VENT HOR. <D 01 3580 g: I ~ 3581 <D 01 33013-1922 ATM. VENT HOR. (H-6) 12* 600-1 1-1--------------------------'-"'--"'""'---'----------------j 33013-1918-2 <D (") FLooi0/ DRAIN. I 0 I 150-2, I.600-1 3 4* 1/2" 3420 600-1 TCE... 4--1"' 3421 1' (/) I D D I <D rn 3-MS-600-1 4* D-10 33013-1896 3-MS-600-1 1/2" 3424A 11014 600-1 TUBING 1/2" 1/2" ,---------~.----:-.-'"--c-1-:---r-----i l-.... 1-j ~ ~ ~ 3424B <D (]1 2" <D 01 cu x 33013-1896 x15437'--------___? F12515 9518U [-----, 3299B 2" NOTE 5 <t~ ~ N '°to '----, "' 0>D 11 ;2* NMS14 01 ~~~ 3582 3584 <SiJ l~n' ~ ':::; 1 1/2" 0> ATMOSPHERE ~0-1 '---9>4-- D A-4 3527A "'.-.-.c 33013-1251-1 L__Jr'j ___ ~ ~ ~ ....._ _____ _.X4798K c--------<~-~ ~ "';. £ ECD07C AIR EJECTOR SAMPLE COOLER 125-8 150-1 2" 3215 .j>. " cu L!J i;; D 150-1 C-1 ~ i ~ 1/4" j

J

~16 TI1M ~t -j[><J 3* ~D _ 3231 9519M v 1/2" £ ZMS03A Tc-------~ 3/4" (F-4) JJ _;...__~~--:-i _ ___,I L!J 33013-1251-1 y \\2Ql><J I...

  • I

~1'71 <D <D <D D N U 3234 3233 3232 3231 1/2" 1 1/2" 1 1/2" 1 1/2" .j>. .j>. .j>. s FLOOR DRAIN LOOP SEAL 4* ~ _,.-- 2 1 /2" ---'--.-----------1----, ~~jj I 3236 ~* ~ 3* X3214 1 (A-12) (G-8) < 33013-1233 MAIN CONDENSER B (D-7) 33013-1252 SS ZMS03 t--'--~----; ECD07B MAIN CONDENSER AIR EJECTOR AFTER COOLER 1--~ 1---~1-~M~D~-~15~0~-~4 ___ __.;l><Hlf-[l};ll-{><r------1~"-_, 3235C 3235 2 3 4 150-1 C-1 Ol D D I -i c ~ z G) 5 0 0 I -i c OJ z G) 3214A 6 L!J 1 /8" L!J 1/8" .j>. 1/4" ECD07A MAIN CONDENSER AIR EJECTOR INNER COOLER 7 4-MV-150-1 4-MV-150-1 4-MV-150-1 4-MV-150-1 1-MD-150-4 8 9 .j>. D -i c rn _J~ S f o N I ~ 0 I STEAM DUMP TO CONDENSER 1B (A-6) 33013-1904 GLAND STEAM SUPPLY (H-11) 33013-1921 MAIN CONDENSER A H-11 33013-1921 MAIN CONDENSER A 1----_.~j TC VJ 11034 j ~ c TC E1-11~011131-5-~-~-I ~ i: N~O I ~ 10 (G-11) 33013-1921 MA,IN~C_O_N_D_E_N_S_ER_B__. X3244 G-11 33013-1921 MAIN CONDENSER B X3246 (G-8) 33013-1233 MAIN CONDENSER B 1 1 12 NOTES:

1. FOR GENERAL NOTES, REFER TO DWG.: 33D13-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DWG. 33013-534.
3. IN ACCORDANCE WITH EWR 5114, 30" AND 24" MAIN STEAM LINES UP TO AND INCLUDING VALVES 3544 AND 3545 AS WELL AS THE 12" LINES UP TO AND IN-CLUDING VALVES 3532 AND 3533 ARE SAFETY SIGNIFICANT CLASS FOR HIGH ENERGY CONSIDERATIONS ONLY. CLASS BOUNDARY FOR ALL BRANCH LINES IS AT THE CON-NECTION TO THE MAIN PIPING.

ALL OTHER PIPING ON THIS DRAW-ING IS NON-NUCLEAR SAFETY CLASS.

4. PT-485 AND PT-486 ARE CLASSI-FIED SAFETY SIGNIFICANT BECAUSE THEY PROVIDE TRIP SIGNALS TO THE REACTOR PROTECTION SYSTEM (RPS).

PRESSURE BOUNDARY IS NON-NUCLEAR SAFETY.

5. LINE SPEC. 600-1 IS STILL IN EFFECT,EXCEPT PIPE MATERIAL IS CHROME MOLY, P22.
6. THE MOTOR OPERATORS ON VALVES 3601A AND 3602A ARE ELECTRICALLY DISCONNECTED. THE VALVES MUST BE OPERATED USING THE MANUAL HANDWHEEL.
7. VALVES 3601A AND 3602A ARE IN A THROTTLED POSITION.
8. STAINLESS STEEL SPOOL PIECE WITH FLANGES FOR RADIATION MONITOR.
9. LINE SPEC. 150-1 & 150-2 IS STILL IN EFFECT, EXCEPT PIPE MATERIAL IS CHROME-MOLY, P22.
10. PLANT ORIGINAL SCH.40 PIPE DEVIATES FROM LINE SPEC. BETWEEN VALVES 3545 AND 7792 REVISED PER

~ ADC-16-0126 CAD FlLE NAME 33013-1232 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES '1S BUILT DATE RELEASED FOR c ENGR. GINNA STA. R. E. GINNA STATION SCALE NONE JOB NO. EWR 3391E MAIN STEAM NON-SAFETY RELATED (MS) P & ID DRAWING NO. 33013-1232 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 2 I 3 I 4 I 5 I 6 7 I 8 I 9 I 10 1 1 I 12 EXHAUST HOOD SPRAY v ©-~ ~ EXHAUST HOOD v ~ SPRAY ~ (E-7) [~3~30~1~3~1~8~9~6==~>---~,,"'---------i x1543o1 (F-7) " "'I [~3~30~1~3~1~8~9~6==)>----lf-,,_l-l X4Z63H11 I (G-6) I 33013 1236 1 I FW PUMP B RECIRC. LINE (E-7) ~ I 33013-1896 X 15431 L......:...:..:c..(.c:E _-7..:.).:...:..c___,,, I II II 4" ~ D*

  • gA.._

L'.I D ~ 4263 X42B2H11 33013-1896 (E-6) I 33013-1236-1 MAIN FW PUMPS RECIRC. DUMP LINE ~ PT [ill o' 2020 -J TC L'.I 6" v£. ~t;.. ~,_@ '4262' D it;' ' TUBING 300-1 (A-5) 33013-1924 (F-5) 600-2 I x5B11 1 PG &:ii ~ f-'-IXl-**__j__~---+-r*~r-14*--1:iTI] 6402 11253 9523G - [J~~~~==)rJ,10f*~* v I 33013 1924 X5615 {J-2) 600 8" v ~ I 33013-1924 X5619 .---~(~B_-_11~)-,1.:.0-1 7

4429

33013-1922 (B-7) 1 1/2" _j 1r-:ru~:14-....>--...:i1.:..i* x:3863B1 33013 1904 NCD02 KMS01A 600-2 (B-6) 3-BD-600>12 I v ~ I 33013-1277-2 X5767 DRAIN HEADER 1 /2" I 33013-22s3 '-J (F-3) 20" r SEE NOTE 4 (B-3) .J er


~

IDO v ~ I 33013-1923 / '- X4143 ~ "'gl (J-1) ECD01A CONDENSATE HEATER 1A ECD02A CONDENSATE HEATER 2A

...::: : 33013~1277~2 I

X5768 (F-3) ~ ,r-3_3_0i1c..3-~19_2_3-~'>- lO-HD-600-Z x414s 1L.....::..:.:--'--'.:..:::c=----- (1-3) I v I 33013-1923 X1919L.....'-'-'-------..../ (H-10) I 33013-1905 GLAND SEAL LJ'>/1 WATER RETURN 40528 (G-10) -........_ 6-HD-600-2 3-MD-150-1 J---......---1 '4o52 1-FW-900-1 I. - 4361 133013-1236-1 FW DRAIN (1-4) - {J~~~~==)>-------J1_.1_1L/~2=._l:IH~S=.1.c15~0~4~--i v ~ I 33013 1915 X7974 600~-~1c-i_,,6=00-2 TYP. 4 TYP. 4 ECD03A CONDENSATE HEATER 3A (B-11) ~I ~>-_....1__,,1~/2~"---+---------~ Xl7S6 1 33013-1232 / (E-11) 1 1/2" -,r- ,-~-~--....., v ~ I 33013-1232 >--'---'-....'.:.---+---------~ X7792 (B-1) 3/4" - -,.--~~~--..... X2911 I 33013-1232 >-__--'-'-----+---------~ (B-11) -~-~--..... 3/4" ~ I 33013-1232 />-----'-'-----+---------~ X2912 IL__ _____ _/ (E-7) . -,.--~~~------ v ~ I 33013-1894-2 />---/1-,,-------/1-,,--, X15005 (H-1) I 33013 1234 SOV4316S (J-1) v 33013-3124 3/8-C-2 ~v-::: X9500S of::,_tv (C-9) OT ' ---'*' 2 1/2" - ,. ~~ 4-rl-i-!... r---'-'--'-'~-~ I 4.. ~ ~ I 33013 1908 3 L:'.J,....,_7"T"4-l:0>4d2 Hf-~~,~'-,[ 1>40<4'1-3-.l,---j NORMAL MAKE-U:/ t;., 431 TREATMENT ~ ABANDONED 2 1/2-DW-150-5 ~ IN PLACE 0-:;:-L.........=2_....,._ _____ _J ~ 600-1 4044 1 o" 1 1/2" ~ ,600-1 (F-8) ~~<~c-_8~) __ 1 1 /2" \\ ~ ~ I 33013-1231-1 I t..-' -.....i v~ 1 33013 1231 1 X3616 X36051"-600-1(NOTE 5)'.:\\ '\\3/4"-15~2(NOTE 5) (E-11~) - (D-8) 33013-1232 1 v ~ _ 1[~~~~~~),_j_j X3542 v ~ 1 33013 1231 1 \\ 600-1 (A-11) X3684 (A 1) 600-11 3 /4" 33013 1232 1. 1X2909

  • ': 33013-1232 3! 4" r150-2 (A-11) xfo10 c___ ____

L3*i_/+/-'.4':_' _\\l_,/-:;:;;-;-:~~-;--i (E-1) 150-21 33013 1232 5 7 I v ~ I X3601 33013-1232 !3/4" (J-6) k---<~~~;=-;--i1. - \\_ 33013 1918 1 'X4181 (D-10) 3/4"-150-2 (NOTE 5) ,.--~-~--..... 4" ~ ~ I 33013-1919-2 >-:::_-I X2423 (H-10) (D-10) 4" ~-~-~---., * '[~~.:2~~!::::),._+/-4"=---{I--_:.--<,.- 33013-1919-1 v I 33013 1919 1 1)(24()7 X2415 (H-10) SEE NOTE 7 ~l-~ _ ____'.41:'.'."--<~3~3;;;0-;"13~1~9~19;::::2;--i:f--x1-::.2<431 1 0 DRAIN HEADER I 2 I ECD06A MAIN CONDENSER A 3 ~* r -'°a

a

~ <D, r: CJ> co~ l -l y ~ 9519P 1 1/2" (C-2) l---=~"l------::::;i:::::---ll-"--<C~~~=1 - ,, Q " 33013 1896 I v ~ X15427 TC 2621 4066 ) rc-n 8 --~~~, 1" ... : I 4333 X1S423 33013 1896 ] 1 /2" 1-....:2::..:1:.t.,/,::2_" --1 4065 11/2" 4062 1" I ; ;.. ~ I 4334 II TC 2622 4063 KMS018 LP TURBINE B 1 1/2" Tl 2015 TAH TAH 2002 2003 TRAP HEADER 11 /2" > 11/2" 3/4"-150-2 NOTE 5 8"----:1 (J-6) E---~L<_~~~*. (G-1) 33013 1918 2 1 v ~ 1 3/4" X4182 x3'5?5.__3_3_0_13_-_1_2_3_2 _ _,... J 150-2 3/ 4.. (C-12) / (F-12) f-'-'.\\_--<, 33013-1918-11 * - 3/4" X3625 L.:.J I 150-1 1" ' / (F-3) X4403C 4067 11 /2" 11 /2" 4064 150-1 l fB-8) 1 1 /2" [r~~~;~==)>-lli-11---' v ~ I 33013 1922 X4430 ~3~3~0~13~1~9~1~8'=21__,:>-=-'-j-l 150-2 X3534 150_ 2 --~(C_-_1~2)'---- 3/4" I \\_ 33013 1918 21 " ~ (F-12) I *..: CA 33013-1922 I.. - TRAP HEADERf 3/4-300-3 l"\\ 150-1 (F-5) (E-4) ~:..s_;,:::--1~3;3~0~1~3~19;;:2;:2;--i: v / 33013 1904 X4404C ,..-- 150-1 (F-10) ~ A_" ~~--~-'-'.L_~ / 33013-1922 I ::- ...__::..::_:...:..:c......:..::..::::_ilx4447 (G-11) I

  • 13/4-300-3 j

(C-4) I-'--<" 33013-1904 13/4-300-3 t. (F-4) 33013-1904 33013-1922 I...--... X4443 °' I I Xz922 I I v X2930 8" TRAP ZGS03 (J-5) ~r-<::~~~~~==J-' - _J I 33013 1922 'x441'4 1 1/4-300-ll (B-7) 1112" 1" 1----:...:..L-=-----11-----'----<C 33013-1904 6* ,..,~-l,,_.'G:...-...:1co2,,_)_~ 1 LGS02 ~ 33013-1922 I... '-:.:.:~_.:.:..::..:: _ _J X44 73E (A-6) 300-1 8" I .--=-'--"--I, 33013 1252 6 v X3956 6" ,~~(~H-_1~) __ 300-1 >--Cx":J-- i-.:=---'----l, 33013-1234 v ~ 0 ' X4055 CONDENSATE REJECT fH-1\\ 1--3-0-0---1-~2~"__,:[=3~3~0~1~3~1i23~4~==>--;;:~~:t-X4053 18 CD 300 1 v (G-11) 33013 1235 GLAND STEAM CONDENSER (A-3) 150=1., . *c ,~~~~~=>-.Ll ...-11~* x44DlAI 33013 1922 !G-8) 150-1 - r~~~/4!'.'..L"7~ ~ L33013 1922 X4448 (G-8) [~~~~~:::::~2J11/~2* y ~ l 33013 1922 { X4444 (A-6) 150-1 ~ : 33013-1922 >-1'-.. ~-I X4402A ,-----'ri""B_-,,_.9 le____, 1.. I 33013-1904 -->-c1-- , 11/2" LGS03 3/4" X3627 33013 1918 2 j 150-2 150-2 1114.. (B-8) (G-11) ~-.... 33013-1918-21 v ~ 1/2" X3667 33013-1903-2 j 1" 1 "' 150-2 150-1 er-~" (J-3) I 8,, 1 1 /2","' 8,, \\_ 33013 1904 I XJBiJ2 9.

~_

9.:,.,~, 2 1 1/2" 150-2 150-1 (l-l) SEE NOTE 5 c 33013-1918-2 I (A-7) L'.I l.!..J 1 :::. 0"---<_,...~-3~3~0-1~3~--1-92-4--,: I


'xs61o 20" 600-2 v

X3620 X5643 20" -~(~F-_7~) __ 10" I , --"'~-1 v -,.. 'L..:.3..:.3..:.0..:.13:..-_..:.1 9:;:2:..4..:.___,...-.>- X5614 j 600-2 (J-3) 6-HD-600-2 ~-~~~---.,

  • L.....--"===="----<, 33013-1923 I * -..,

X1923 (F-8) (B-6) 11/2" 1" l----:...:..L-=-----11------'--<, 33013-1904 LGS01 ~ (TI\\__ ~ rt;,. ~ 1/2" ~*~ / 14" 14" 18" 14-CD-300-1 Pl 2008 ~ l~'~: 7 _ _,__{SEE NOTE 4 o~ ~'-.... {fl'. l.:6~":__-<:=::~~-;;_~~=1 I 33013 1922 , x.44l4E (J-10 ) ,r--~-~-~, 8" v ~ L~3~3~0~13~1~9~2~4~_,;>-~J----j X5618 600-2 (G-1) 11 /2" I 1----.---'---I 12" v 1/2" * ,} '3960 (C-12) 1-CD-300-1 I ~-----------!, 33013 1909 11072 v ~ 3/4" r:.. v L: 4243A 1/2". 4243 ---© 1/4" Pl 2551 Pl 2011 (F-6) 11 / 2" / 33013-1903 \\.-=:::: x565'3 I

  • l 5D-2 NOTE 6 Pl 6403 v

OXYGEN ANALYlER 14-CD-300-1 3963 't' ~--~=~---~--I FT ~, 7 1104BB

, cL 2003 0

OJI

c f!'

11;2*~~)-~ ~ 33013_ 1903 o--..***---1 TUBING IPIPING 'x564'8 1* *104-9 150 2 ~1 7--" ~ ~--~ q. *[ '2-~~(=11-21~1)~==>----====---~8:'.'.:I.'.-;:,i,_--l ~ ~ v ~ I 33013 1923

I H,

~ 3965A X5065 Pl 2012 300-1 TUBING Pl 2010 300-1 ........ 12" 1/4" - 1/2' ~ 4242 3/4" ~...; :Jv 4242A X4122 ~ (B-6) TE 11/2", f-'-\\'-<::____:3~3~0'!_1 :'._3 ::.1.:19~0~3'._j

  • 6406 3

TW 2013 (J-11) ~rw '~m--'>-,-_j x:322S 1 33013 1232 __ I I \\_ 1X1967 NOTE 6 (A-6) r-:- 1 ~ 1 l\\2~"<::___*_:3~3~0'!_1::_3::_i_:19~0~3'._jr-1><*::i-1 \\_ 'x19n NOTE 6 (C-6) L!-1 _,__, 1 1~2r"<:33:3\\Co~1 ~3 ~19:lCoi33:---i * ,..._ _____ __JI X-196'2 (D-6) C7 11 /2" _,,,~--""---""'--~, - 33013-1903 ~------X':f 959 TRAP HEADER D ' Pl 2056 4249 (H-10) 11 / 2" 33013-1903 \\_1~-2 (H-8) 11 / 2" 33013-1903 \\_1~0-2 (E-8) 11 / 2" 33013-1903 TT 2060 I 'x566'3 I 'X5658 I X5638 11 /2" ,..,~-("'E'---'-11'--'-)-~HD<l-33013-1903 I ~------'x5633 TRAP HEADER I 4 I 1-MD-150-4 _j 12" ~ 3965 I 12" ~ E 1 /2" Pl 2013 I 0 1/4". - 1/2" 1/2" 4247 ~~---:J ECD04A CONDENSATE HEATER 4A E.--1*~-I--{ 9500C ) <}- 1"

J TC o

Pl I 4246 - I A" / (J-10) ~ r 8 300--1-~-~-2-0-1 ~4 1 33013-1252 1f-fX v~:1-- ..._ _____ __JX3502 1 /f." - 3967B Pl 2057 v ~ 4248 v E ~, 9500B 1/2" ECD04B CONDENSATE HEATER 4B 11/2" TT v E-1.IMIH--i 2061 3997B ~..; :Jrc 9500A 11/2" ~,, I-" ~,.. _....... y m->. NJ ffi~ ~ TW 2014 3997A ~* ~~ i>* ~ ' '1---...1.....:.':,--{*)~><'.-1---..:.12~*-*---CJ--.-.L.~1~8-"..LJ~-:r---r*~(}--.--'-~' r-- 13969 ~ '396l ~ 3966 ~ 3968 ~, ~ ~ o;

    • io c.o

-...J.. ()) )>L'.I 3966B \\;: (E-3) D 18-CD-300-1 33013-1236-1 ~ FEEDWATER PUMPS ~~ ~ g I 5 I 6 l.!..J D 7 I 1_1 /_2" . ~ 9500E 8 ECD01 B CONDENSATE HEATER 1 B ECD02B CONDENSATE HEATER 2B 300-11 TUBING ::'.., D

jJ..

.., I 33013 1918 2 X3499B (B-3) 150-2_} I 10" v-... I 33013-1923 J X4144 600_ 2 _..r I i!i 'f--t-'-1-"_t:e:*j--+,---t*::<<:J-r-<~*f-l I 4Z39A I 11078 ~ (D-1) 11/2" -C><':H1 33013-1918-2 ':>-'-.:..!...::,_-j XJ499A I _}

l NCD03 7

0 ()1 ~ -...JJ.. CJ> PG 6405 I I X4146 V}--_...,.........=:J TC 11076 PT 3201A 150-2 (C-3) 33013-1923 _} 10" 7 5oo-2 DRAIN HEADER ~------_,.l-_.'.'.10~C~D_:2:15~0'.:_21~--<::::~~(~G-~l~)~;-:=J

  • 33013 1234 I,

~ X4059 CONDENSATE MAKE-UP ECD03B CONDENSATE HEATER 3B ECD06B MAIN CONDENSER B 9 (B-10) 1" 150 4 33013 1904 I __J LGS04 ~ ~o~,!:!Ql~~_J_J.L+/-::.._~:=+/-_-----<:'°~~(~F-~5~):,g:Ul NOTE 6 1 1/4" 150 4 1 33013 1922 I ~ 1"....... 3 D 9514G X4427 95108 (G-11) f-'6'-"-j~~~~t:=6:-" __ 6~0~0~-3E1~-----<..__23~3~0~1

'._3::.1.:19~1'._11~1'._J 1.

I

  • j_

SP863 'x9515E 150-17 0 ' ... _.1/4", -D-i I.1---tv><1~.'.L.2._J'---< 9591G (F-10) 33013-1905 I v o~ 8" 9507E LCD03 '-D:, ~

1H1h-J1:

~ I LCD01 LCD02 ' 1 ~ 150-~D-1 8-CD-900-1_i -,, (SCH.SO)

1

..J v 9514E (F-10) ' ~-~-~--,. - 33013-1236-1 I v-..,, X9507D NOTES:

1. FOR GENERAL NOTES REFER TO DWG. 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. CONDENSATE HEATERS 1 B AND 2B ARE IN THE SAME SHELL.

CONDENSATE HEATERS 1A AND 2A ARE IN THE SAME SHELL.

5. LINE SPEC. 600-1 ANO 150-2 ARE STILL IN EFFECT PIPE MATERIAL IS Cr-Mo, P22.
6. PART OF THIS PIPING LINE WAS REPLACED WITH CHROME-MOLY PER ECP-10-000528.
7. UNLESS OTHERWISE NOTED, PIPING CONNECTED TO "A" CONDENSER DRAIN HEADER IS CARBON STEEL.

REVISED PER KCL nJ:r-,r ftl';j.ff,.,f:/Y) ECP-10-000528 10 1 1 At>c-1~-000<<>1 11/11/15 11/11/IJ 11fi,{1!" /J*lf*t<' NUM~ CAO FILE NAME 33013-1233 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 11-Jl-f.J AS BUILT DATE RELEASED FOR ENGR. Gl_N_N_A_S_T_A_. _ __, R.E. GINNA ST A TION JOB NO. NONE CONDENSATE LOW PRESSURE FW HEATERS (CDST) P & ID DRAWING NO. EWR 3391E 33013-1233 CCD 01 CONTROL COPY # I 12 REV. A B c 0 E F G H J

A B c D E F G H J 1 2 v r.1 N ' VENT 3 4 5 ~ r4-CD-150-1E 1 2 407 L!J 6 8" 150-1 VENT VENT CD, 7 y <O 0 N

i:

<O g; ~ N CD r NOTE 6 125-uJ "Y' 4" E...,....., __.:....__---, 4076 l.!J N ~-11 4400 2* li:Ql 2-CD-150-1 ~ lLOl 2" 4075 INTER.BLDG. SERV.BLDG. 4074 (G-6) 2* 1 2*

JV 33013-1237 4857A NOTE 6 3/8" 150-1 TUBING lLOI AFW PUMP DISCH.

lLOI 10* 1----11><] t-'1=0_-~CD~--1=5~0-_1'---.-----11><] 1------1 3 4* 9510C 9500G 10-CD-150-1 20* TCD02A CONDENSATE STORAGE TANK A 4071A SERV. BLDG. 4070A (E-10) TUBING ~(-IP_E _~


~--8~*-_,,_,

3 8-CD-A1 11/2" 8282.. INTER. BLDG. 10-CD-150-1 li:Ql ~= 4071 ~ 33013-2252 X8274 ~-------' ~ ~ ~ '-------------~ D 1/4" X4015 H-1 33013-1237 4* 1/2" 11151 <O llJ 4319A <O


~(E_-_1_2~) ------, 11I4" ~

--j)<J--< 33013-1915 7997 X4019 X4018 X9671 B-1 33013-1237 E-1) 33013-1237 4" 4* (D-9)

>~--2~1/_2_-_D_w_-_1_5o_-_5 ________ ~

I 33013-1908-3 9517Y (D-11) INTER. BLDG. [~~2i~~==>~--------------11-~CgD~-~3~0~0~-J1 _______ ~ JT~U~R~B~*lB~L~DG~.'-1 33013-1238 F-12 1/2" 1

  • N 4070 N '

4068A 33013-1905 1 4-CD~ 150-1 V 4058A " [h£] 1--~-1--3 D 4071B (G-8) ---C><:t-1[~33~0~1~3~-~18~9~4~-21:=:>----if--------{f----------ff------i X15506 1/4-CD-150-1 33013-1905 (F-12) TC (F-11) if~ <:::~-3-3~0-13---1~2_3_3_-;... ________ ~----~r------i 1 0-CD-150-1 MAIN CONDENSER B HOTWELL D-1 33013-1252 H-5 1058 4315X,_----------~-t .. *----'6"-"---j 4059 ~ -1:><J-l 33013-1894-2 X15360 (B-10) 4315Z 4315H1 4315S ~ 33013-1896 >~-~,~1-------uu--~ X154341~---~ (C-7) 33013-1233 (G-1) 33013-1233 AOV 4316 (B-3) -C><J-1 33013-1899-2 X4316H1'-------~ (C-7) 6-CD-300-1 2-CD-300-1 4317Z 4055 4316S 1/2" 40571 300-1 -~*~i"'*~-150-1 4317 REJECT 4311X 6" 4056 300-1, j, 150 1 -1 0 I 0 0 I -"' 0 I 0 ' N I 0 I CJ> 0 I - 2" ~~ TCD02B CONDENSATE STORAGE TANK B "' lLC I o ~ 4319C 20* !~ 11/2" .'_. 4318A t, ~"' i m ~ ~NOTE 8 "----------1f---C-c!--l Pl 1--~2"-125-1 11151A 2808 Q 8" 3/8-CO-A1 0 "' I I~ 0 (F-10) 33013-2252 X8275 829~K t, CD 0 (1-10) E. l-j~J;------<::::::~33~0~1~3~-~2~25~2~r-t::><J-8299J X8281 3/8" (J-3) 33013-1912 CNDST. DEMIN. BLDG. TURB. BLDG. <O g N N 2 1 2" 3/4" N I 0 0 I tn 0 I <O 0.,, T AM-6406 AM-6407 v -----i.... 1------i I () 0 I 0 I w TOC SILICA 9513D ~ (A-7) 3/4" ~ 33013-1911 >>-------~~-- x9s38A1~----- 2 1 2" NOTE 12 0:T*

J

/\\ <(, ~ 0 <t 9509D () 1/2"

1.

DE-...., 4050B N I 0 0 I -"' 0 I 8 9 SEE NOTE 11 111-7" 0 -- 4" SS 10 0 VE T N, NOTE 9 0 0 0 ROOF DOOR ~ 1" r.1 0 1 1 12 SAFETY CLASS 2, 3, OR -~**\\ j i~ SAFETY CLASS 1 ~:ilE 'AS MMN I 0 -- 1* "' 1 * "' 1* 0 DETAIL "A" TYPICAL SAfElY CLASS BREAK POINT FOR VENT, DRAIN AND TEST CONNECTIONS 0 00000000000000000000000000000000000 CD, I I 1

  • 0 0

0 0- 1%1 g 9501A I ~. i~ D ~ 4044 04* ~ J.i 1l! 7.-s 10"0 0 0 0 '---'..;;....+41-.....1i-------1 9501B 3 8" 4" PVC v ITT N ' TCD03 OUTSIDE CONDENSATE S10RAGE TANK <O 0 - TC 0 1%1 9501Q 4" 0 0 24" 2" 0 0 0 0 0 0 0 MANWAY 0 0 I ~.. [D 9501D 0 0 0 0 2" 3/4" 11/2" ~~D -"-----------"-----'"-----"-----------"------"-------t--lf--, 9502J EAST DI TRUCK r-----lllk.!Vll MIXED BED INLET + S;MPLE WES1 DI TRUCK '------lllk.fVllMIXED BED INLET 9502K SAMPLE G) ~,...... rri....... G') 0 CDl'.A I <D ~ I .:::. g N ~ 0 f'1 CD o I 0 0 0 0 y

  • ~*1~

2* f-"-.....


1 0 tn 0

0 I r-; I N, 9501L 3/4" F--'--l,.._:J D 9502A 2 1/2" 9529D "'v ~T CD () 9529A 3* 9501S 9501Z 3/8" <D CJ> 0 - ~----10t----1 3" 9501R 9501Y 3" CNDS1. DEMI~ BLDGJ TURB. BLDG. J, SEE NOTE 4 9501X 1* LCD05 2" SCD21 ,...------,3 I 4

  • t--t---)

3 4' y 9528B PCD05 OUTSIDE CST HEATER PUMP 1--_..,t-------j F 1-----.,...____J 9528D FCD01 9528E 9528A 9550V 3/4" I~ y <O CJ> b Iv 3/4" I E9502E 9502C YARD CNDST. DEMIN. BLDG. 9502W 9502Q 0 I 0 0 I 0 0 9513E v ~ 0 G) 0 0 <-; NOTES:

1. FOR GENERAL NOTES, SEE DWG.

0 2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543 33013-2241. 0 r-----r-' 0 3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TES1 CONNECTIONS SHALL 0 w BE AT THE ROOT VALVE IN ACCORD- °' "' ANGE WITH DETAIL "A". ~ ~

4. THIS WALL PENETRATION WAS PREVIOUSLY USED FOR A TEMPORARY CONDENSATE TRANSFER PUMP.

EHTRCD04 L!J D REF. TSR89-07

5. BLIND FLANGE INSTALLED BETWEEN V4051 AND CONDENSER THEREBY ISOLATING FLOW PATH.

11/4" I 9507F 3/4" ~---' TCD14 OUTSIDE CONDENSATE STORAGE TANK HEATER

6. LT 2022A AND LT 2022B PROVIDE REGULATORY GUIDE 1.97 CATE-GORY 1 VARIABLE INFORMATION.

PRESSURE BOUNDARY IS SAFETY SIGNIFICANT CLASS.

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 1 0328.

I I I L D l_J _I_ OUTSIDE CONDENSATE STORAGE TANK HEATER CONTROL PANEL

8. APPENDIX R LOCAL DISPLAY.
9. BLADDER WAS REPLACED UNDER TSR 95-085 WITH POLYPROPYLENE BALLS AND SCREENS.
10. NITROGEN GAS INSERTED INTO "A" & "B" CST'S BETWEEN SIDE WALLS OF TANK AND DIAPHRAGM.

THE NITROGEN GAS TAKES STRESS OFF THE DIAPHRAGM ALLOWING IT TO FLOAT AWAY FROM THE TANK WALLS DURING LEVEL FLUCTUATIONS (THERE IS NO LEVEL/WATER DISPLACEMENT DUE TO ADDmON OF NITROGEN). 33013-1233 405 4311 b "' !j;

11. REFER TO ECP-2008-0101 FOR REMOVAL OF 2" CONDENSATE DRAIN LINE. IT MUS1 BE REPLACED IF A BLADDER IS INSTALLED IN TCD03.

(G-9) 33013-1252 CONDENSATE PUMP SUCTION HEADER 1 3-CD-150-1 2 3 4 b ~* ,. I D 5 ~ (C-11) 2" 4* ,_-j.-:___:!:=;e~~~'---------L--11">-<"f-l."!.-j 33013-1908-2 4-CD-150-1 4"[~~~~~~:::>-;;r~~ 4048 4097 40498 0... <O 150-1 TUBING PCD04 <MO/CTP> CONDtNSATE TRANSFER PUMP 11/2" 6 1" X4833 ~O~ ~ t-'-14~0.49-D -fl;--.. b 4049F ~?~ 1* 9517P 9517R 1* ~----i~i-- 9517U l.!J <O ~t 9517X 9517V 7 8 9 10 /\\ 12. USED WHEN ALIGNING FIRE WATER TO FILL ~ CS1's USING CONDENSATE TRANSFER SYSTEM. 1 1 REFER TO ER-AFW.1. /\\ REVIS£D PER ~ 000849 RJM 8/28/14 CAD FILE NAME 33013-1234.1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. GINNA STA. NONE R.E. GINNA STATION ONTARIO, NEW YORK JOB NO, EWR 3391E CONDENSATE S10RAGE (CDST) P&ID DRAWING NO. 33013-1234 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 (E-1) 33013-1905 X3798 (E-5) ~ 33013-1923 X3359 (1-11) 33013-1911-1 CONDENSATE HEADER (D-12) 33013-1909 X5058B 1 Gi 0 (.}> co 0 0 -1 ~ ~ OJ 5 tD "' 5 " 3 8" 3/8 3 8" ~ 0 I I (() ~ 0 (() (() (J> - "' L!J D (J> 0 (J> (JJ (() (J> 0 1" (() g '1 (() (J> (() co I 0 0 I 8 I - 2 2 I 0 0 I "' v g I r.i 16" co I 0 0 I 0 )> 0 0 I _c--'J 0 "' "' 3/4" 16" <D g ()) OJ OJ Pl 4051 3 4" 16" <O (J> 0 0 v <D (J> -- 0 9506E 0 ~ ~ D rn z (;) }J z v 3/4" 9540A N ' 3 1/2" 3-CD-300-1 v N ' 9514C 9513G FCD04 4 1/2" Pl 4021 3/4" 3/4" ,-------t>Kl-'~,--J'--i><J~F IH/~r~-.____, 9536C ~ Pl L!J ~co TC g Pl 2529 L!J ' D (JJ '1 9513A Pl 2537 95138 3/4" 3/4" .------~-----"'c.c_----1<0 (.}> Pl 2528 (() (J> (JJ )> Pl 2530 14" <D (J> -' 9503A 3/4" N (;) ~-t-Pl 2532 Ci tD z (;) v v <O <D m m 0 0 '1 '1 <O (J> -- r <D (J> 0..

r:

N '<0 m 0 t: <O m 0 14" 'iJ z (;) 5 3923 3/4" 6 (B-10) ~ 33013-1896 >>---11//---#//- x15435 1~----~ AIR LOCKING VALVE \\~ ~-IH!f- ,--'(~C_-_10~)'--~~ co ' --i:><J-1 33013-1896 ~ x 1 5436 L---:..::..:_:_::____:_::..:...::._..-- 1 2-CD-300-1 "' -, SP-863 SP-5291 (J> 3950 NOTE AIR LOCKING o; N 0 LLl D (D-4) VALVE ~.,. .---~-~----- (() --J:><J-133013 -1894-1 )> X15491 15491B 14" 14-CD-300-1 1------+------------N-O_T_E_B-1142301 3/4" 4376 9512B BOOSTER PUMP TRIP 0 SP-863 SP-5291 PS 4027 11063 11065 (3 START 3/4" D


go* ~ ' 1:zc r=::======'.__:3~/~4"~-~~

(;)

J 0

_... D 0 <O ~ (.}> 0 0 co I 0 0 I "' g I 0 3/4" D E--- Tl 4064 ,_3~/_:_._*D--~~ " ---1 (;) Ci

) L!.J

"---A I ti ~ "' PCDO 1 B D 'j2 9504A b I N tD z (;) 0 N 7 3/4" 15436C 3949 15491C 1/2" l/P 2023 X9512K v ~1- -t, co... "; N I 0 0 I 0 0 I 16-CD-300-1 Pl 2054 N 8 1/2" 4375 14" 9 PIPING TUBING TUBING PIPING 4231B 11150 4232B DPT 2036 4231A 4232A ECD05 CONDENSATE COOLER ~ 18'~ (() 1--....:..:::.....__,;. __ __,~ 1 ' 10 1 1 12 18" 14" 12" D 12-CD-300-1 12" r-~~~~~~....:.0:..~~~-11....-1r-~~~~~~~~~---~~~~--=~--1 Tl 2027 SEE NOTE 4 TT 2023 t tD -f c OJ z (;) 3944 ECD01 C H2 co 1/4" COOLER 3940 (() N (JJ 11552B 3928 q SEE NOTE 5 KCD01 GENERATOR SEE NOTE 5 ECD02 ECD03 3/4" D--..--1 H2 COOLER 3939 3/4" D 3947 3946 (JJ }J " z Ci OJ z (;) 16-CD-300-1 16-CD-300-1 Tl Pl 2028 2055 C H2 H2 COOLER co COOLER ~ ~ Zl~.:i---, v ~ 1 /2" TI::c-:'J'=' 1--11>4--v 3941 H.. V 3938 Tl 2033 D 3/4" 3945 (JJ 16-CD-300-1 3937 (() N (() (JJ (D-7} Tl 2029 NOTES:

1. FOR GENERAL NOTES, SEE DWG: 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFElY CLASS.
4. MONITORS HYDROGEN TEMPERATURE AND PROVIDES CONTROL SIGNAL TO POSITION VALVES 4229 AND 4230.
5. THIS IS NOT AN HVAC COOLING COIL BUT REPRESENTS THE TUBE BUNDLE FOR THE HYDROGEN COOLER.
6. ELECTRIC MOTOR EJN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
7. 4229 FAILS TO 50% OPEN ON CONTROLLER FAILURE AND SIGNAL AIR FAILURE. 4229 FAILS AS IS ON SUPPLY AIR FAILURE.
8. 4230 FAILS OPEN ON CONTROLLER FAILURE AND SIGNAL AIR FAILURE. 4230 FAILS AS IS ON SUPPLY AIR FAILURE.

/\\ 9. tJ;t:,. THE GASKETS SPECIFIED IN ME-318 ATTACHMENT C FOR LINE SPEC 300-1 AND ECP-2009-0254. ARE SUITABLE FOR USE WITH ECD06 FLANGES. 1 0. SPACER RING USED BETWEEN ONE OF THE FLANGE FACES AND 3955. SEE ECP-13-000830 & DWG. 03021-1499. 18" 33013-1233 - g CONDENSATE o -:;:. [\\; BOOSTER (J> ~ 0 I u N 14" ECD06 TURBINE GLAND STEAM 14" N 14" l-'-------'--*---irJi--------1 CONDENSATE HEATERS 1A/2A & 1 B/2B Jj z G'l v <D g (.}>., <D (.}> 00 '1 L!J w ' PUMP B TC D <MO/AVP9B> Pl 2535 <O (.}> '1 N Pl 2536 <O <O " N c.o

(0

°' m (.}> 0 0 (J>

r:

~ PCD01 C ..::::. (1: CONDENSATE " "' -, BOOSTER w ' L!.J PUMP C TC D <MO/AVP9C> 18-CD-300-1 3 (() "' g " (.}> 0 Pl 4060 3/4" <D (J> - 14" <D (J> 4 9505A <D (J> 0 0 v Ci OJ z }J " z 5 6 12" 7 [><] 1-'--' ---'--I 3952 SEE NOTE CONDENSER LSEE NOTE 9 3953 12" 12" 1--------------------111111---------------------1 c OJ z (;) ()) I o Tl 0 l 2025 0 0 I 3951.. N N (J> N Pl 2052 10" N N N " N ' 3226 8 3954 1 O" ECD07B AIR ';;;:~' ~t 'l I CONDENSER ECD07A CONDENSER K; AIR ~ EJECTOR INNER COOLER -N N ' 1/2" 3230 1 o" y 9 Tl 2026 12" t---+-~~---1rJ1-----~ N (J> - Pl 2053 3955 g SEE NOTE 10 I Ci OJ z (;) 10 00 I 0 0 I 0 0 I N I 0 0 I 0 0 I 1 1 CMB CJW i1/s/1s Ji IP 1S CAD FllE NAME: 33013-1235,1 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES II ~// AS BUILT DATE RELEASED FOR ENGR. rACUTY GINNA STA. R.E. GJNNA STATION SCALE NONE CONDENSATE (CONDENSATE BOOSTER PUMPS TO HYDROGEN COOLERS & SLOWDOWN RECOVERY SYSTEM) P & ID JOB NO. DRAWING NO. REV. EWR 3391 E 33013-1235 CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H 1 i:=..- 3973C 2 0 I 3 (G-7) 33013-1905 / ~ ( l-D- )>l!J TC ~ X3810D 4 (1-11) r - --iL_3_3_0_13_-_1_25_2:__.> PS 2010 CONDENSATE BYPASS TO SOV 39595 TC lfil PFW01A<MO/FWP1A> 171 FEEDWATER PT 2017 5 ... ~ ~ 17 - rn"


I-_.

4261C 0 I 0 1/2" ? ~

J v 6

~ I 1---P 3973 3973B i" t~~~~Hr ~ PUMP A ~ "- / I 1 o" 14" - 3977 );!* L "'; f--'"---r-E f-..:..;-.,---1.*

  • -,---1 11-.,.-:-,-,-,---1--:))\\.-J M 4260A 1/2"

"--._/ r-.1 /2" ~.;~ 1/2" Cl ~ Y 4H - 1-FW-300-1 J ) b"'; 13975 ~ -; L..-r:- L!J ~1 L!J ~v o El i)1 *E]i)' r 0 D '° 4499E YL{ 1 1/2" 3977A J .... :J -::i 3973D I (.N 5 -1'>- cri.1 l _..j.. L_ = I NPSH ~-- ~-- \\_ 3/4" v E~'-' (H-11) -fLARM TT ~T--, 21--; 7 3977B < 33013-1252 f-2041 I... 8-FW-900-1 CONDENSATE BYPASS 4" ~ TO sov 3959S I ---v ~------------:------ ------== -------~-i '1 1

  • 1 1 /2-FW-900-1 4035 I _________________________ _J

~ ,, l149~~s,,cr:' I L 1/2" t----..... f-'3 v 4499D I '----l - M r:' ~ iTT' -~*L.._, IZ/4147 I I MANIFOLD I r -

  • 1 12" O

v L:.... 0 4099C l 0 A

  • 1 /2" ?

f---+-~-vr><~:1--+-_,_--"v'><'~J-!.l-=---I_ 12167L 4251 ~ -~ 11 rp ~ ~f!'S:\\¥'.,}------/1- ,,---'---f{-,,---','

-ff-Ii I

L FT 2004 I ~... °' I ......i _. ~ m TUBl_N~G-+-~30_0_-1 =~--@ 1 /2" v ~ 12167H 4250 (G-8) -txJ-1 33013-1895 >~----,,,_y-- X14522U '-------------------/ (J-5) 33013 1233 CONDENSATE HEATER 4A & 4B (F-8) ,~------'------'------~ 18" CXl y ~ I 33013-1905 ,>----_J X2900B GLAND SEAL Ii 1" 4373 1 " ~ 4371 1" - : :J D 4374 12-FW-300-1 1/2" 3v 4499C 1" * ~D 4499F OJ I ~ I '" 8 I 12-FW-300-1~ r I I I FT 2005 MANIFOLD I ~' r °' I UJ.i t. OJ ~ 12163H v~ 12163L 1". ~ . 1/2" 4372 4253 TT DE *

  • 1" 4499G N 8"

OJ ' 0 0 OJ'

  • L!J D

I I ------- II 2042

'

IZ/4148-;;J 3 v ~ ~~ f-- 2005


---- -I ---- ---- ---- ---- -


---- ---- ---- ---- ---- :--'T'- I I

I v E.. 1 /2" -~ v LJ ' * /;; I

  • ~

' I 14905S E NPSH 4099D

]

.. ~ I L ____ __ __ __ __ ALARM

r _. ME ,~' 8 I tt*., !fl ~ I o IS ~ .~ f----..,.1-':Jv I ti 4499K H

C:::

(G-8) X 1~ 33013-1895 > PT 2018 it;' 7 °' 00 I rn 4495"" IJ;Q] ~' 0 °' 0 v 171 ~ ' I I I I OJ 3/4"

  • 1-FW-300-1 CXl '

I (H-11) <~_3_30_1_3-_1_25_2__Jf- _J I I 1 1/2" 3976A CONDENSATE BYPASS TO SOV 3959S PT I ~ I "' 8 I I ~ I 0 0 I - 2016 i4*~ PFW01B<MO/FWP1B>

--V r;;-i FEEDWAIER C-_ 1:...J..,;::3:c:.0:0-1 l2J / PUMP B 10*

-=-[:: 12" 14" e_ I .\\7 ' f--.-'-----l M (1-11) 33013-1252 CONDENSATE BYPASS TO SOV 3959S (E-7) .. / I 33013 1905 I X3811D I - - _1/Z" ) '--L-l><f-rl-bo:'.1---1. - 1 42s8 3818 ~1% ~-; PS 2011 C-1 ~ " b ~b'""~b*r 4259 ~- ~.~~AL l.Qj bA L 3820 300-1 )> OA = Y ~--- ~-:_ o __ o-- 0 0 I


JO CJ>

0 I... D 1 1/2-FW-900-1 4034 13974 "' - ~976 ~"' ~.... L!.J D 1" D[ ;.._""" 3979D 8-FW-900-1 14" TT 2063 1" 1" 8-FW-900-1 -1" DE...... 3978D E---'--'---'--'---'-_,_---'----~ I FL 1 2 3 4 5 6 7 8 9 Pl 2D17 0 ' 1.. -i c m z " 0 0 I EFW05A FEEDWATER HEATER 5A 4363 1" ~ t;*, "' "' L!J D 1" \\ 1/2"

  • :J

...... :J v 3979V I ~ I 0 0 (B-5) ~-----------------------I: 33013 2711 3 PT 488 PT 501 ... --'] ~_c1_"_-1.!. NOTE 4 rn CXl - CXl ~... 1" 0 I FEEDWATER LEADING EDGE TRANSDUCER LFW15 <O -1'-.,, a OS, "° ~. ~ ~ !.-'-~--'-' 20-FW-900-1 I I (F-l) q*-71--'-----11 1-----,----'----------11 33013-1236-2 1 /2" ~* r NOTE 3 ~. ~-----+ I r 0 0 I I ~ I 0 0 I OJ L!J v Pl 2540 c1 OJ z -+----1-"' 0 0 I - 1" 4266 FT 488D L@NOTE 4 (H-11) I 33013-1233 FW CLEANUP RECIRC. LINE l" 1.. (E-1) --'--,--,:,--...------_,,,f-----'-----</33013-1236-2 ~ 4362 1" i.0~. ~**~r~*Q ~Al L!.J D 1" 1" L-... t---'------l NOTE 3 39828 14-FW-900-~ 1/2" .... --=i v 3978V t;* °' - (Oj (2J D 4365 (E-1) I 33013 1233 MAIN CONDENSER A L!.J TC EFW05B FEEDWATER HEATER 5B 7 I 8 9 v ~ X1406 PT 502 ... --'] g] ' '" "' °' 0 ~.. / v ~ X9507E v ~ X4361 10 10 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1236,REVISION 10.
3. IN ACCORDANCE WITH EWR 5114, 8", 14", AND 20" MAIN FEED-WATER PIPES ARE SAFETY SIG-NIFICANT CLASS FOR HIGH ENERGY LINE CONSIDEATIONS ONLY. CLASS BOUNDARY FOR ALL BRANCH LINES IS AT THE CONNECTION TO THE MAIN PIPING, 4, ALL 488 SERIES FLOW TRANSMITTERS (FT-488 A,B,C,D,E,F,G,AND H) ARE CLASSIFIED SAFETY SIGNIFICANT SINCE OPERABILITY IS REQUIRED BY TECH.SPEC. PRESSURE BOUNDARY IS NON-NUCLEAR SAFETY CLASS,
5. ELECT. MOTOR EIN'S FOR MECH. EQUIP, ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

DATE f\\ REVISED PER LlB, ADC-15-000876 AS BUILT RELEASED FOR i-;.;:REV::_,___-'R"°EVl'-'S::E::,D,:_F"'OR:.__--l DRAWN CHECKED RESP REVIEWER FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAO F'IL£NAME 3P123601 ONTARIO, NY JOB NUMBER WR 3391 FEEDWATER (FW) P & ID DRAWING NUMBER 33013-1236 SHEET REV 1g 1 1 i___=c=c D::::;__:0::._!1_,I '-"'C'-'-'N'-'-T'-"R L"'--"C,_,,O,_,_P-'-Y....!!..# __ --l A B c D E F G H

2 I 3 4 5 6 I 7 8 9 10 11 12 i A ~

t°..L..1.""iIT~~~
r-1i.,-~~~----_.!!,"-:!"'~-;!900!2;-:.:.'------*

~' *=-1 A 8 c D E F G H P404 11 f--C~N~~.!._ t ~ ~ -.~. J-11) 2 4 5 6 7 8 9 10 ~~~-* ..StLJH£ 'L~~~ a.GS {Q) DETAIL-A. nP.SAFOY CLASS BRE..VC POINT FOR 'iDiT, OfWtl ar TEST CONriCCT10f!S NOTES' !. FCR CE.NO'l'Jtl.. NOTES REfCR 10 ORAWI~ JJ013-1241.

2. PE\\'l".ilUN ~u* Gr nus O!l.r.W!NG SUP£RSEOES POR'llONS Of JJ01J-12J6, REVISK>N 10.

1 ~s~~J:lr E'~~grn1lti~A~ AHL FLOW COHIROL CONS;('V{.(llONS ONLY. 8 c D E F G

8. t8" El.ROWS CONNECTtNG ?l?E 10 S/G'S Wt.RE I H C.~Gf(J TO UAl'Effi""- S\\-2J4-WP11 (CHROME MOU) PtJI CWR 100J4.
9. REFER 10 33013-1236,l FOR INSIRUWEl'H AIR D£TAlLS.

11

1 A B c D E F G H I J 1 NOTE ~.,__ ____ _, 2 ~ ~ OJ NOTE ~ ll--------1 2 '.e ~ 2 ~ I OJ ~ ~ I 2 OP/3995 3 4* OP/3994 3 1 4" ~~ D-7) 33013-1893 INSTRUMENT AIR F-8) 33013-1893 INSTRUMENT AIR 3 1* .... g 1* 4 3995S 3995HH 3995CC "I 3995N 3994S 3994HH 3994N 4 <O <O <O <O 0

r COPPER "l.

"l. 399588 1 Z' <O "l. <O <O <O 5:: U) ~ U) U) <O <O 0

r COPPER "l.

"l. 399488 1/Z' <O <O "l. ~ <O <O 5 3995P 3995U 3994P 3994U 5 AIR AMPUFIER CFW3995A AIR AMPUFIER CFW3995B AIR AMPUFIER CFW3995C AIR AMPUFIER CFW3994A AIR AMPUFIER AIR AMPUFIER F 6 U) <O N <O <O <O <O

'(

<O N 6 L.:.J t.:J 7 1/4" 3/.f' 1> 3995EE "' 3995G [hQl <O <O "' ~ L!.J 1/4" 3994T4 E-_._-r::t:'.l_y_l '..fZ'c-J 39940 ~99400 3994R 3/4" 1> 3994EE "' 3994G [hQl

g
El L!.J 7

1* 1" 8 3995K ~ = r 3994K t.:J 0 D 8 TFW3995 AIR ACCUMULATOR 3 3 TFW3994 AIR ACCUMULATOR 3 3 9 10 11 9 10 11 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REFER TO 33013-1236,2 FOR VALVE PROCESS CONNECTIONS.

LIMrnD CONSIRUCllON: AS NOTED PREllMINAR'f NOT FOR CONSTRUC1ION BIDDING PURPOSES AS-Blm..T GINNA STA. R.E. GINNA STATION SCALE NONE FEEDWATER (FW) P & ID JOB NO. DRAWING NO. SHT. RE.v. EWR 3391E 33013-1236 3 & CCD 01 CONTROL COPY # 12 A B c D E F G H I J

A B c D E F G H J 1 4299H 112" w D 4-SW-125-1 I 301 ~~ (1-1) --1:><1-J 33013-1250..1 X4640 (E-1) 33013-1234 CONDENSATE STORAGE TANKS (F-4) 33013-2681 SUMP PUMP PWT35 4018 s !ill 2" 1/2-CD-300-1 (E-1) 33013-1234 CONDENSATE STORAGE TANKS 4"CS s 301 / 4016 <ill:> 4" 2 m z Q 125-1 --------- (1-1) 4" 1~1 33013-1250-1 4099 !ill 4024A 2 42938 w °' 00 0 (F-2) 33013-2681 3 4 5 J-6 33013-1250-1 X4091A 4" 1~ 4021 6 1----- @) I I I l 00 "' ---+ 2" 7 "' z 4488B Gl 4488A 3/4" (C-5) 33013-1893 !------~-- 3/4 900-1 1/2" C-2 2" 4343 "'30""1o-t-3"'occ1 4343F 301 125-1 3/4" 1/2"

t 1/2" 4343C J HOSE THREADS

+--~--:i 4342F 150-4 C-2 1/2" 1 1/2" 3-CD-150..1 1/2" 9521E 4325 1/2" 4091

~ ~ I 13256 NFW02 <MO/MAFP1A> PAF01A AUXILIARY FEEDWATER X15525 PUMP A NOTE4 2-FW-900-1 !§] 1/2" 1/2" -I c "' z Gl tc-+/- 2 m z Q X15466 3/8" ~ 4300 EAF02A w D (C-5) 33013-1893 AUXILIARY FEEDWATER PUMP A LUBE OIL COOLER 150-4 14371 :..:.s--1>.H~... -1 s ~ v~ 0 ~ 4342 4342C r ____ _,.C-.1--15_0_-4 __ ~~ ~~--~~---...._ v TC 11175 /4305 FLOOR DRAIN BETWEEN A& B PUMPS 4" ~-5) 4" 33013-1915 3" 1/2" SS TUBING r--~~J-~6~-----~ -!:XJ--1 33013-1250-1 X4090A 1-CD-150-1 4083 4" 4014 I( 0 1" (B-5) s 33013-1893 >-/f-C*., <MO/MAFP1 B> PAF01B AUXILIARY FEEDWATER X15523 14372S 2" y 3-CD-150..1 TUBING 150-4 9521G 1/2" ~,---"'----C!------'-.L.'..-1 f--0--, 4326B 112" TC 3/8" 1/2" 4090 NFW04 ~ 9521H -+---C-2 150-4 C-1 3/8" 2-FW-900..1 ~-- L'..J D EAF02B AUXILIARY FEEDWATER PUMPS LUBE OIL ~-~COOLER (l-11) 33013-1909 X5075A (C-4) 43~73 2-CD-150..1 ~ ,--'---{X}-"-'=-=-'---Y 33013-1234 ~ 4080 1I:QJ TO CNDST STORAGE TANKS (G-11) 33013-1238 '--------'X4294A SAFW CONDENSATE 3/4" CASING VENT .. r.i PAF03 til ID 0 TURBINE DRIVEN AUXILIARY FEEDWATER PUMP LFW30 42910 4291H 4291 150..~ING (D-3) MANIFOLD 318" ~~lf-n---11-----J'l---< ____ 33-0~1~3--1~8-93--, __::::-------'X4291S 8~ w 900-1 TUBING 1" Pl 2156 1/2" Pl ~ 1-f<til--- -- -- -- -- -- I TURBINE DRIVEN AUXILIARY FEEDWATER PUMP LUBE OIL COOLER ~-- EAF01 2" 4493 "' z Gl X15456 X15455 3/4" (J-11) 4492 33013-1909 ....___:_:..:_:.:._:.:_:cc_ __ JX507 4A 3-FW-900-1 4494 w 0 ~ 3/4 900..1 4295D TC ? 3 1/2".. c 0-1 ~ ~ 3" ~-~----i"l 1/2" i:~... ---j 4309 C-1 900-1 E 1---t::-:1-'-1 *_* __, I:; g 4308A (B-5) 33013-1893 3" X15524 4495 4295E w D 296D i!J 4295G 5:.,, 4296E 1/2" 1---.,...1-:Jv ~ 42968 3998 (1-11) 33013-1909 (D-3) 33013-1893 (D-3) 33013-1893 0 lo SUMP PUMP PWT36 Dt__.._, 11095 C-2'--o_..,T-"'UBING 11096 TUBIN~G"-f--'C-2 1/2" (D-9) 1" 3 L,,=1:::==:t:::::'.. __ _sc;_-2:2____Jr-----'--rJ-----,-J 33013-1231-2 1 X4087E,-~(_l-9~)----..._ 4087D 1,, 33013-1250-1 2 C-2 4087 3 4087A 4088A 40876 4 NFW03 1" 4085A TURBINE DRIVEN AUXILIARY 3/4" FEEDWATER PUMP 40888 40856 QUENCH TANK 5 6 7 8 4489A 4008 IBLCI ---+ -1 "' z Gl 4483 4351C 350D 4351E 4353E 4350E 9 /\\lo !ID 43530 4353C w 4352D 4352E 6 ~ 43536 '::l ~ OJ w D I ~ -~1 _____ 2_" __ --< I >----------~ 5-FW-900..1 ~ 1" r g X15454 X15453 -I c "' z Gl 4348 44908 (C-3) 33013-1893 (C-3) 33013-1893 3999 !ill C-1 4348A 3-FW-900..1 ~3/4" 4297 NOTE5 J-11 33013-1909 m TC 0 ~ 10 11 12 1" (B-3) 3" r-.. ---'--------'-----1::x:::r:'--I 33013-1236-2 ~ 4011 STEAM GENERATOR A 4000C t !ill m m z 4353F UJ 4352F 4352G w TC L'..J D

Jo 4012

!ill Pl 2794 (J-5) 33013-1235-2 STEAM GENERA TOR B ~ SAFETY CLASS SAME AS MAINLINE SAFETY CLASS 2,3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS v.....-- 43478 i-1 4001 !ill 4347C ~ ~ 3/4" 4003A (A-3) 33013-1236-2 STEAM GENERATOR A (J-5) 33013-1236-2 3"

J v

~ 4349C v r.i NOTES:

1. FOR GENERAL NOTES SEE DWG. 33013-2241
2. EXCEPT WHERE OTHERWISE INDICATED SAFETY CLASS BREAKS FOR ALL VENTS, DRAINS AND TEST CONNECTIONS SHALL BE ATTHE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIRINITROGEN VALVE.

REFER TO INTERFACING AIRINITROGEN DRAWING FOR SAFETY CLASS.

4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
5. VALVES ARE ADMINISTRATIVELY CONTROLLED OPEN.

APF \\.\\(~ 11/12/15 NUMBER CAD FILE NAME 33013-1237,1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIM!NARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR GINNASTA. R.E. GINNA STATION SCALE JOB NO. EWR 3391E NONE AUXILIARY FEEDWATER (FW) P&ID DRAWING NO. 33013-1237 REV. 4004 4006 CCD 01 CONTROL COPY# 8 9 10 11 12 A B c D E F G H J

A B c D E F G H J 1 2 3 4 5 6 7 8 9 10 1 1 12 1----_-.-.. -.---_-_, ~

ANIFOLD

~ 11123B - D-- L!J v ~ -----~ j ~ co U1 f---'V C-11 33013-1250-2 9709A1drlj y 4-SW-152S 9629A IBLCI 4" co 1 /2" FIRE HOSE D CONNECTION <D ~"'----! 0 00 U1 CJ) t * ~ 11124 ';J-1--rl*-.-.[TC D L!J 4-FW-152S f, NOTE 3 ~ co 0 I )> L!.J PSF01A(MO/SAFWP1C) STANDBY AUX. FW PUMP C t

  • co 0

CJ) 1 4" '-1~--<TC '° (B-9) ~

! HH~<

33013-1892 v );' -...__:.::..::..:..::._:.==-_J x 14256S NOTE 5 1/2" <~ wm_. 3 ~ "'- 300-1 152S 0 0 I -"' "' J, icl )>

fl,~

';J-I

fl

)>1~ c,.., x,;u v 9673 (/) (/) 1/2" v i:--1.---i 9674 1/2" vE:..... H 9720D 9720A 9721A ~ 0 CDI CD V 5 r 171 ,g (0 I ~ Ul [DI"' rr co i: ~1--<f-'"-h,-, 1 /2-CD-300-1 ~ O'l 9787A 1" D E-91---1.__'----I 9787 <D 0..... CD 0 00 [I) 33013-1230 (A-6) (G-9) 7 LFW05 3-AFW-151 33013-1908-3 ,__J.---1 I 9781 co 00 9831 r,., <D co 00 0 0 CD 0 ~ I ~ -----~- ~ 0 I 0 0 I '1 L!..J I () f--j~J-::::0--1 v I ' __ 98_3~_E - _J MANIFOLD~ co 00 9832 1 ** >--.!--mi-':J D 9834 ~** 9764 9793 ""'"~** 3"~ }-- 4 .:..." __ _J__:._L~: 0PS~~~ (MO/PS:03) 1 RECIRC. PUMP 9782 9776D ~-----~ I I 1 -CD-150-1 9665 (H-9) 9666 .......... 1-:J 9763G 33013-1908-3 I----~ 9763B'9763D ~~ ! ~ ~ I 9798 "' "' i: L!.J D v 2* 9763A ' 9763C ~L..!.J ~--~MANIFOLD v 00 <D 1/2"" r---- 1 I L r'";-l=::-1 9797 ______ RECIRC JV ~ NITROGEN EQUIPMENT NOTE 10 ~ I - U1 9776E 9776A N17 N10 2" Nl 1 N6 2" I SPARE 3" I SPARE HEATER

1i CONTROL PANEL

~ <D <D I i ~ 9785C i9785A '----'---@ TC TC TCD05 DI WATER STORAGE TANK NOTE 8 2" 1/2" I"' 3-AFW-151 Ol (\\.) Ol (\\.) N7**~S T' :~85D i 97858 CD

s )>
m 2*

'---n-=--11 N 12 j 9774B '-----1%" 9773 9773A 2* E*-+-.,-.--=iF~ 9660 ~ 2" SAFW BLDG. ANN EX


YARD ---

Ml 36" I MANWAY 2" 1 /2" N4 *o * * * *

  • 4" N9 m

~ ~ ~ MANIFOLD g L..!.J ~ 00 (D-9) v 33013-1230 w ~

fl f-N2 3"* *
  • 0 'ii" 2"

--"'---"'--__:1/_'----'-"'-f'-j ~*~llZIS'1~*:......:*:......:*:...i10,_*_*_*_*_,c---~----------~ z 4 0 e

  • N5 P

I NOTE 6 ~ 774 NOTE 6 9790 ~:~ 4" $lb

          • Or.1 N3 0 ~

~ ~ ~ ~co

fl ;fl ffi CD CD 55

)> z z ~ U1 )> L.!J

  • 4

~" 1----..::iv 9760 9780 0 NOTE 6 u D IH*t-:--:"4'-:":-:~N~B _________ ~N'.._'.l_r3'-j** 1*

  • j I *
  • I 0 f-'*:.....;;*e::*--=-*--=-*-'1::---_::3_-.:..:AFW...::...-.:..:1..:5.:..:1 _ _L ___ -1 f--....L---1 j/H--,.J'
  • 9772. *

)> ~ 1 NOTE 6 9770 ,z 9768 ~ ~ m ~ "'~ D J-IM-fJC 8-9 co co I~~ I - 9757 I 0 0 I c gi z L!.J v L.!J 11111A 11109 g ..... 14--':J TC "' Ul --f::><l-i.:3,::3..:,0.;,1 3.:..:-~1.:..:8:.:9..:2~_...- >-\\\\-~H g 'cjl X142575 NOTE 5 "'~ ~ 0 I - 0 v co 0 0 I ~ 0 I

fl I

~ DJ v '71 3* (B-11) "' "' t 33013-1250-2 96298 IBLCI <D CD 1 /2" FIRE HOSE D CONNECTION 0 -D "' t: 0 U1 Ul 11125 -,......,._,-.[TC L.!J L!.J t

  • 4-FW-152S SEE NOTE 3 L.!J 11 1/4" T

~ L!.J PSF018(MO/SAFWP1D) STANDBY AUX. FW PUMP D ~ ~ "'-f -+--+.~ c! ::: CD - -o z 00 <D CD L!.J D t ' 9701B l8LCI 0 "' ' v ID Vl Ill 0 -'---=---'-... D 11106 ~ tll 0 Ul 111D5 D 2"l I ~ ~ I D ~ u~ ~ ~ ~~ ~ L!.J D D 0 9704A ~ "' IBLCI ~. LlJ D ,.lo c::'O X'z . l;g rn z ~1~ Iv ! ~ ~ P1..!ill en 9702A

-:-Tl 9705A ILOlco

~ : I co [§]~ ~1 ~~ LlJ D FW-902S D TC )> ~ (A-5) 33013-1236-2 9706A STEAM GENERATOR A [j;QJ J-----'J D "'~ CD I 0 0 I 0 0 I - I 0 0 I 0 0 I 9746F

J D

~...... 9671 (E-l) 1-CD-300-1 I f-1 -~N'----11>::J---< 33013-1234 > LFW06 9667 ~C-O_N_D_E_N_SA_J_E-~ 9662 LFW42 I

t;

[I) L.!J ~ m 0 9672

t; 0

t

  • 9661 v

Q 1-CD-300-1 m ~... )> L.!J D 1-CD-300-1 t ' ',.lo c'o x'z . I ;g wz "'I z MAKE-UP (J-9) 33013-1252 (F-4) 33013-1915 HOUSE HTG STM (H-4) 33013-1237 MDAFW AND TDAFW PUMPS TC X4084 X7976 X4083 P,123 ! I ~ t (H-5) .:::...u 3"

  • r---'--"'--~-

--t SAFETY CLASS SAME AS MAIN LINE SAFETY CLASS 2, 3, OR SAFETY SIGNIFICANT (0) DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. EXCEPT WHERE OTHERWISE INDICATED.

SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

3. THE ~ SIGNALS TO STANDBY AUX. FW PUMPS C AND D CAUSE THE PUMPS TO BE TRIPPED FOLLOWING RECEIPT OF THE SIGNAL.
4. ELECT. MOTOR EIN"S FOR MECH. EQUIP.

ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

5. VALVE FAILS OPEN ON LOSS OF INSTRUMENT AIR AND FAILS CLOSED ON LOSS OF ELECTRIC POWER TO SOLENOID.
6. STAINLESS STEEL DOUBLE BRAIDED CORRUGATED HOSE.
7. VALVE 9728 SHALL REMAIN IN THE OPEN POSITION TO ISOLATE THE SAFW TEST TANK.
8. REFER TO CBI DWG. 175180-000-SP 000201 FOR DI WATER STORAGE TANK (TCD05)

NOZZLE AND MANWAY NUMBER DETAILS.

9. 3/4" PIPE DOWNSTREAM OF 9774 IS SCH. 80.
10. SEE DRAWING 33013-3167 REVISED PER MLS CA CJW CA AOC-16-000023 1/07/16 1/07/16 1/07/16 1/07/16 3 4*

9738 3 4* 97228 l-~6.J....-l33013-1236-2 ~ --n L 97o5B 9706B STEAM GENERATOR B [bQJ ~ ' i I ILOI ~ ~ LlJ I FW-902S CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES D D 1/07/16 DATE AS BUILT CJW RELE'SED FOR GINNA STA. R.E. GINNA STATION NONE STANDBY AUXILIARY FEEDWATER (FW) P&ID I !:'J 11107B !:'JI l_-=._ f-_-::._-::._*_""_~-=.-_-1~ MANIFOLD 33013-1238 DRAWING NO. JOB NO. REV. EWR 3391E CCD 01 CONTROL COPY # 1 2 3 4 5 6 7 8 9 10 1 1 12 A B c D E F G H J

A B c D E F G H J 1 2 1/2" 5923 ~+/- TC 1181 OB 3 4 TDG02A D/G A COOLING WATER EXPANSION TANK 5 6 r BOLTED ACCESS COVER 3 4" ,------"L:!--r 1" o o o o o 0 d I -i 125 301 o 5935 , I ~ 0 0 0 0 0 7 8 9 10 (C-6) 33013-1250-1 1 1 SAFETY CLASS 2, 3, OR SAFETY SIGNIFICANT (Q) 12 SAFETY CLASS SAME AS MAIN LINE '---11-~TC --i 11802 c J~ 3/4" lill P"-'-J 5939 "-'-o~-,---0---0--L--'o ~ 125-1 I ~ o w"-; 0 0 o o SEE NOTE 10 DETAIL A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN, AND TEST CONNECTIONS FDG02 PRIMARY FILTERS 5 L3/4" PDG04A :J-rv'f 5917 DIG A FUEL OIL PRIMING PUMP PDG05A D/G A FUEL OIL BOOSTER PUMP FDG04 SECONDARY FILTERS 3 8" ESW08A D/G A JACKET WATER HEAT EXCHANGER 5890F 3/8" ~ ...._---l[..,.-1------"L:-"---- 11/2" FUEL OIL BREATHER N 5890G 2 1/2" T~ I 5960A 11/4" 5989iil. I I~ ! ~~t ~ ~ TDG04A DIESEL GENERATOR A FUEL OIL DAY TANK Ci "' OJ 0 z c\\, G) D 12419 O"-rf--3~/_8_-_F0_-_1_5_3 __ ~ ~ 1/4-F0-153 01 1/4-F0-153.,, i:--..lf--1 i:-....11-1 12398N 12398M ~] 11/2-F0-150-6 T 11/2-F0-150-6 TC ~* 1" 5977D I I I I ~ ROOF v I NOTE 7 t b?l 3" TE 6622 ESW09A D/G A LUBE OIL COOLER 5907 lfil 1" 5937 ~ Y 3 I 4" r..l'-----'~ 1--<-><l--f" 90~ ~ ~~ 2" l ? !fol (F-9) ~ 3T t._5947B 2" 1---~--°'__.__._, 33013-1239-2 ~ " 5943A ~ I. ~ ". ~ -:;:-- -ii;QJ ILO I L.:= i 5911 p p ~! ~ )>I w 0 0 G)I G)

u J :u

""I~ ,, OJ A (F-9) 33013-1239-2 12398G X5967 X5975 5941A 5945 N I I <g 0.A.-:;;::_A ~ 150-4 TDG03A Ji. ~ D/G A 150 4 STARTING ~ 1~ ~mt~ REC~~ER ~ D A1 COG01A 5947C <M0/AMS1A> ~ D/G A STARTING ~ AIR ~ COMPRESSOR °' <O... ~ 2"1---' I:: b I -"' 0 I O> 2" 2" 5959i:l SEE 3/8-F0-1t NOTE 3 l I 12398A CJ 1/2" CJ-3/8" <O PIT 2052 TDG03B D/G A STARTING AIR RECEIVER A2 N E 3/8-F0-153 ~ 2 I:: 2" 2" <O O> <O,, D o<t 0 2 12398E <O OJ -t I O> 3" SEE NOTE 10 1 1 /2" <O SEE NOTE 10 ()) 0 L _ -4 '---------t-l ~ 0 ~ 0 r.l 0 0 0 o NDG01 2" 0 0 125-1 0 J 0 0 0 3/8" -D-ITUB-ING 21/2" l___~1815L N ' L!J KDG07A PRELOOP FLOW REG. 0 0 0 0 0 I FILL 0 0 0 ROOF TUBING 125-1 --~ SDG01A D/G EXHAUST MUFFLER 0 N 0 ' 0 0 150-4 f'l .250" ---- ~ WALL eo ~ Ill ~ '11 c-t-'--1-f--- -\\J- (- c _Q_ --+:::i ---" L-.--J 11 /2" Co-o KDG02A D/G A TURBO !--1_,.._~_.__~1-~-f--:-C-)H-A-RG_E_R __ (=-~ ]! 2" KDG03A ) D/G A TURBOCHARGER AFTER COOLER 20" ATM~ATM 150-4

5 "---.250" WALL 3

0'" OJ ~ 150-4 <O 0 0 D 0 0 0 ----------- 0 0 0 0 0 0 0 1" ,___ ___ ___,If--) l ~ l~ I "' 11--) L!.J~ ,__,._--j,

+-)

JI I) D ' V TDG06A AFTER COOLER OIL COLLECTION FLASK PDG01A TI 21~rJ -l ) <O 0 -u I D 5" --i c 9l _l 5" ) ~"---+--<f-- 21 /2" I ) D/G A 6 31/2" JACKET !jj '---"'-'----..L..J i-. ... --) 5" TUBING I FDG06 [£] SEE NOTE 6 jj ROOF D/G-BLDG. 3 4" J 3 4" J 3 4" J 3" I,. I I 0 I,. § m 1~ ~ I~ w I ~ I FDG07 [£] Pl 2854 11832 I ;uB1NG '--rlJ-w ) I PDG03A PS 2869 OJ 0 11831 PS 2870 OJ f--...,11-=lTC 11836 NOTES:

1. ANY NEW TUBING OR FITTINGS SHALL MEET LINE SPEC CLASS C-2: EXCEPT THE FUEL DELIVERY TUBES BETWEEN FUEL INJECTION PUMPS AND CYLINDER HEADS, REFER TO ECP-11-000932, FOR GENERAL NOTES, SEE DWG.:

33013-2241.

2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DWG.: 33013-1239, REV.4.
3. FUNNEL UPSTREAM OF VALVE 5915 CONTAINS SCREEN.
4. FOOT VALVE 5919 INSIDE FUEL OIL STORAGE TANK CONTAINS SCREEN.
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL DRAINS, VENTS AND TEST CONNECTIONS SHALL BE AT ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
6. THE EXHAUST MANIFOLD SHROUD VENT EXTENDS FROM THE EXHAUST MANIFOLD THROUGH THE ROOF OF THE DIESEL GENERATOR ROOM. ITS PURPOSE IS TO REMOVE EXCESS MANIFOLD HEAT AND EXHAUST GASES WHICH MAY LEAK FROM THE MANIFOLD JOINTS.
7. VALVE 5979 AT (B-3) HAS INTERNAL THERMOSTATS TO MAINTAIN 170T NOMINAL JACKET WATER TEMPERATURE. VALVE 5987 AT (C-3) HAS INTERNAL THERMOSTATS TO MAINTAIN 180T NOMINAL LUBE OIL TEMPERATURE.
8. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
9. VALVE 5961 INTERNALS REMOVED PER PCR 2001-0047.
10. LOCAL TEMPERATURE INDICATORS Tl-2646, Tl-2658, Tl-2661, AND Tl-2648, ARE LOCATED IN WELLS.
11. LUBE OIL FILTER HOUSING HAS INTERNAL RELIEF, WHICH BYPASSES FILTER ELEMENTS IF FILTER DP IS TOO HIGH.

KDG06A 3" (-~------~~ D/G A WOODWARD GOVERNOR ,Jt~l~{ ~-)----.., EXHAUST PDG03B 3" FAN # 1 .---'-:..:..:.::_~ D/G A CRANKCASE 3.. EXHAUST FAN #2 l--"--r-;r-;--,--,--,--,~J \\J \\J v v \\J v v \\J COOLING WATER DISCHARGE FROM ENGINE n r:-, r:-, r:-, n r,., r,., n 3" PDG08 J D/G A STARTING AIR MOTOR ~us-I L!.J ING KDG05A D/G A STARTING AIR MOTOR LUBRICATOR Ci 9l z G) _j_ (--+t----1~1/~2* ____ .i.__..,..__--I +:] v 5933D 2 CD ---j ) WATER z P_U_M_P _____ "'_ --L!.J-~-w~-:.:_. ___ r.I r.1--'--:;;:-*---~n 3/8" OJ <O 0 '- TS 2882 TS 2878 v n N EOG A ENGINE=KDG01A GENERATOR=EG1A L!.J TUB~ 5905A NDG06 5973 !ill Pl 2852 ()) N "' L!J 3/4" '----'2.3 C-"8_" -( 1 2" j-..rvf 11825 TUBI~ 5995 TUBING 3/8" 11822 E F0-150-6 F0-150-60 0 0 3" 0 5913 1/2" 0 5955 ° 0 NDG04 F0-150-60 OJ 5911AL!.J ~~~~~-1.....-s_. ____.J_..J_...f---J--D<l-2-"_J__, o 0 OPDG02A <MO/DTPlA> 2-F0-150-6 5961 5963 3/4" !:-'---' t 150-4 f\\ REVISED PER ~ ADC-15-000523 DG 7/16/15 0 ;;, OJ r 0 G) c z 0 Cl f'l I ~

u

~ g I z 0 1 <O <O,. <O 3/8-F0-153 Df:--1-----' D/G A FUEL OIL SEE NOTE 9 o 12398C TRANSFER PUMP 3 8-F0-153 o'--- 1-------.~-~o 0 0 3/8-F0-153 _ __,,.__Jo 0 0 'lZI 5919 5951 ROOF MAN WAY SEE NOTE 4 12398D 0 0 0 __j @I 2040

<>lro c

I TDG01A DG.A FUEL OIL STORAGE TANK 2 0 0 0 0 0 12398L 3/8-F0-153 N <O OJ OJ 12398H MANIFOLD (J-9) 5968 33013-1239-2 X5976 (J-9) ~-0--1--0-l 33013-1239-2 X5952 3 L!.J 2" 4 FAL2045/ FALL2046 3" J~ z G) F ~-----<1 NOTE 11 FDG05 5 SEE NOTE 10 3" 3/4" ~ l-<5~98.. 11-----l Ii l I~ JTC I 8 I 11806 3/4" I I OJ 0 °' OJ 11805L I MANIFOJ.Q___J '-l~-1TC 11807 6 TS 2883 7 PDG06A DIESEL GENERATOR A LUBE OIL PUMP 3/4" 1/2" I ,,;;i /,...., 1 3/4"L!:2.i j-..rvf l-5<:9*;9!-"'-?C.:!...--1 ~~ ~ 1 --i PDG07A to

N 65

<MO/LMS1A> ~ ~ z DIESEL GENERATOR A w L§1 ° PRE-LUBE OIL PUMP D 8 9 10 1 1 NUMBER CAD FILE NAME 33013-1239,1 CONSTRUCTION LIMITED CONSTRUCTION; PS NOTED PRELIMINARY NOT FUR CONSTRUCTION BIDDING PURPOSES

  • -1 AS BUILT DATE REl£ASED FOR

~ GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. DIESEL GENERATOR-A (DG) P & ID DRAWING NO. REV. EWR 3391E 33013-1239 SHEET OF 2 & CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 <D N N OJ v~ 59340 59068 2* I 2 KDG06B D/G B WOODWARD GOVERNOR s 5934B I LAS 2719 s 5934A I KDG05B D/G B STARTING AIR MOTOR LUBRICATOR 3 4 5 6 (E-6) BOLTED ACCESS COVER I 133013-1250-1 >>------ 12-5--- 1 -----:-i-----o-~1-o-~l>lbQJ<OJ-o---o-'-\\_0-/ I, 1 ;r 5936 o 0 , 0 "'+-C}-l I f--J 90 125-1 5940 3/4" 3/4" E o 7 0 ')_1" 0 o-TDG02B D/G B COOLING WATER EXPANSION 8 0 0 0 __j ______ r_A~N_K_~j___,,;------:~ 5904 0 0 0 0 MA~ SDG04 SURGE I ~Q~ DAMPENER LC TS 2897 0 0 0 o 0 r;;@E .......__1 1/2" ~ D 6621 0 .---1--------------1~0---------'0=------'-}"vi: 5" ,---------------'---'----J_-------------'--- 0 0 11915L 0 0 9 5924 1191 OB <D 10 ' *~ I~ '0 L MANIFOLD '° ---_:;-FDGos --I ~ E iii F L __ -u~ 5928 1 1 -l c OJ aJ ESWOBB D/G B JACKET SECONDARY FILTER PDG05B D/G B FUEL OIL BOOSTER PUMP PRIMARY FILTER 5891F 171 KDG04C t INLET AIR VALVE LUBRICATOR t---i:~---L.-___J TUBING 125-1 N 0 ATM SDG01B D/G.B EXHAUST MUFFLER 0 M6i'!IF0Ll) __ 1_1_§l15H __ o Ec.L-----i~~----~ --"'-l TUBI~ 0 0 0 0 C' OJ WATER HEAT EXCHANGER N m~ l~G 1~;-*~,J ~~*J___J D 5980A 5890V 5890W C' OJ 5_92.6..... :__l~ 5918 FUEL OIL BREATHER 1 1/2" 5960B 12 ~t SAFETY CLASS SAME PS MAIN UNE t ~SAFETY CLASS 2,3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. ANY NEW TUBING OR FITTINGS SHALL MEET LINE SPEC CLASS C-2; EXCEPT THE FUEL DELIVERY TUBES BETWEEN FUEL INJECTION PUMPS AND CYLINDER HEADS, REFER TO ECP-11-000932. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. EXCEPT WHERE OTHERWISE INDICATED.SAFETY CLASS BREAKS FOR ALL VENTS, DRAINS AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
3. FUNNEL UPSTREAM OF VALVE 5916 CONTAINS SCREEN.
4. FOOT VALVE 5920 INSIDE FUEL OIL STORAGE TANK CONTAINS SCREEN.

"'.(S),---------------------~ FDG13 [£] FDG14 0 ll 2 1/2" ~ '-~4-'-'--14 5990 1 1/4" ,f f 1

5. THE EXHAUST MANIFOLD SHROUD VENT EXTENDS FROM THE EXHAUST MANIFOLD THROUGH THE ROOF OF THE DIESEL GENERATOR ROOM. IT'S PURPOSE IS TO N

<D ~t '-'-' v N JV PS 2886 JV PS 2887 VE--+ 11931 SEE NOTE 5 "' D9 r ~ st%:~I

ij N g z

= ~ ~ M I f 0 I... i::-..---1 11936 1----------------\\.'..I----------------- ( -}..r\\:::r[ 3" PDG03C ~ r---1,-----) ~ ru~ EOG B ENGINE = KDG01 B GENERATOR = EG1 B PDG09 D/G B STARTING AIR MOTOR 1/2" N 3" 3" c +---l\\-) PDG03D D/G.B CRANKCASE EXHAUST FAN #1 3" c --i H---1\\-) DIG B CRANKCASE 3/~"~ 3/4" J J EXHAUST FAN #2 3.. E--~--~-~---.--<"1 COOLING WATER DISCHARGE FROM ENGINE !":),,., (;'\\ "' 17"\\ 17"\\ 17"\\ ""' 3" 150-4 OJ 0 OD KDG07B PRELOOP FLOW REG. FILL N TUBING I


-----t----- :r

'-+-S v v vC, (/),,,__,,_..... 0 Cl ~--~~ OJ c --i 1--I -... - - - -., - -, - - - -, .I.~ l~ ~... N = ~ 3 1/2" 1" '---+--) KDG02B (~'--- 1 1/2" D/G B >-+-~ .--:_-_T_u_;_B_O_-_C_H_A_R_GE_R _ __, ~ ~ (--l>-+-~-l=tJ-KDG03B ( ,2" D/G B TURBO-CHARGER AnER COOLER v (-1---j TDG06B AFTER COOLER OIL COLLECTION FLASK c-:- 1 N ~ LDG05 L--------T--1---) I r 5" D~ (-;.--i)-'--- m 1 ' ' L_ _____________ _ 2-SA-150-4 2 <D ~1 D N OJ <D ~ LDG06 - g; 3 1/2"

( .. I n c_ n n ~---** tt---~~~~*- 11922 PS 2990 TS 2901 11921 PDG01 B c --j -(-:_-:_::*==== D/G B JACKET I WATER C----)---1f-- PUMP n 3" MANIFOLD _ _ __J 3/4" ~-+--:J 5996 3,1' 4" lill3/4" ~ PDG06B DIESEL GENERATOR B LUBE OIL PUMP te' 3/4" r---..--,--t-..--D<J--+--1 Q;! 5982 I H><P-=--CJ-}..rvf 3/4" 1/2" l--=T--JJ*D---1 }.rvf 6000 5891B PDG07B <MO/LMS18> DIESEL GENERATOR B PRE-LUBE OIL PUMP 3 s 1~ z G) 4 Pl 2654 5 ~ ' .~ I i.1"' I ::: '<O ,o 11;; L!.J z Cl 3/4" 11905H : 11905L ' 6 10 FDG12 7 NDG02 1 2" 2 1/2" N I 0 0 _o_ 0 0 N I 0 0 0 N 0 0 <D -..J 3" SEE NOTE 9 1/2" C' 3" 3" N 5988 ~3"

)

TE 1/2 6624 ESW09B D/G.B LUBE OIL COOLER 1" 5938 12399G (F-3) 33013-1239-1 (F-3) 33013-1239-1 5908A [fQ] 12055 TDG04B DIESEL GENERATOR B FUEL OIL DAY TANK ~ D '----------~---~~"' N 12421 N [§] ~ ~ I d I


~3~8~-~F~0-_1~5~3-}.rv(

0 I 5967 1/4-F0-153 J-+.-J 12399M v g I.. ~ 0 I ROOF 2" l:i 5975 N 1/4-F0-153 J-+.-J 12399N 0 I 1 1/2-F0-150-6 T 1" 5978D [QI I 1 1/2-F0-150-6 Pl 2643 5948C~~ E 59428 2" 3~" 1 2"


r><l--i I 5944A UBING 5948 Pl 1bQJ 2542 2"

5944B 1; 4" 1UBll!G ~11/2" 2" 2" ~ ~ 'I' 5921B d J:'-;25"*----[__ _ _j 5946 1/4" 5942A r-.... 1--:J 5942C REMOVE EXCESS MANIFOLD HEAT AND EXHAUST GASES WHICH MAY LEAK FROM THE MANIFOLD JOINTS.

6. VALVE 5980 (B-8) HAS INTERNAL THERMOSTATS TO MAINTAIN APPROX. 170'F NOMINAL JACKET WATER TEMPERATURE.

VALVE 5988 (C-9) HAS INTERNAL THERMOSTATS TO MAINTAIN APPROX. 180'F NOMINAL LUBE OIL TEMPERATURE.

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHAICAL EQUIPMENT PER SFEWR 10328.
8. VALVE 5962 INTERNALS REMOVED PER PCR-2001-0047.
9. LOCAL TEMPERATURE INDICATORS Tl-2659, Tl-2660, Tl-2653, AND Tl-2655 ARE IN WELLS.
10. LUBE OIL FILTER HOUSING HAS INTERNAL RELIEF, WHICH BYPASSES FILTER ELEMENTS IF FILTER DP IS TOO HIGH.

_I.. //150-4 150-4 h 5960 2" ~{SEE NOTE 3/8-F0-153 I 3 12399A 2" "',I): od*~ ~ N 3/8" g TDG03C I D/G B '° ~ "' SYARTING AIR o RECEIVER ~ B1 5948B ~--r CDG01B -[><]--l I 5948A [bQJ 2" E--1 2" ~ <M0/AMS1B> ~ -"; D/G.B STARTING AIR COMPRESSOR {- F0-153 3/8" 12399E TDG05B D/G B 2" E---< TDG03D D/G B STARTING AIR RECEIVER B2 I <O "t" 0 D 2" 0 0 5914 ° 1 2" J FUEL OIL '° TRANSFER g; PUMP PRIMING TANK ~~3 2228 _, T s~D &i 0 0 0 0 z -+--+-G) 3/8-F0-153 1 2" F0-150-6 <D J, 2227 f--l5>9<1J-0---,orl F0-150-6a gLJ Pl ::-1 r2_"__,_2_" -l><J--1.-/'F---'---'-'-"--'-'"'--"--"'-'----I ~.. o o h--H-orll-'-2-"co 1--o -'-~"-L.-/'r-, F0-150-6 0 0 5964 5962 PDG02B NDG08 I 5956 SEE NOTE 8 <MO/DTP1 B> 3/8-F0-153 r.i ~t-!'J_IF_OLp_---i D/G B FUEL OIL .... JD I I TRANSFER PUMP 12399C 3/8-F0-153 12399L 'i 3/8-F0-153 ---<~~*+-=JD 12399D 0 0 0 0 0 0 0 CAD FILE NAME 33013-1239,2 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 5952 2 1/2"-150 ' I 0 ~ FACllll'I' GINNA STA. 0 R.E. GINNA STATION Cl SCALE NONE I------'-'"'-"~--'---------~ 0 0 (J-3) L-<::~3~3~0~13~-~12~3~9~-~1:=J X5968 N c z 0 f'1 DIESEL GENERATOR - B (DG) 0 (J-3) 0 0 0 0 33013-1239-1 24" MANWAY SEE ---i;gy NOTE 4 5920 / / i)l P & ID ~ 1---------~--------------------.----~ 0 JOB NO. DRAWJNG NO. REV. c 1------+-----------+----1 a EWR 3391E 33013-1239 SHEET 2 OF 2 ~ X5951 TDG01 B D/G.B FUE'.L OIL STORAGE TANK CONTROL COPY # CCD 01 8 9 10 1 1 12 A B c D E F G H J

A B c D E F G H I J 1 2 4 5 6 1" 1" 1 1/2" I I ANSUL AUTOMAN Il-C CUTTER HEAD (TYP. 2) SFS20 SFS21 NOZZLE H-1 PI Pl (TYP. 4) ~ N, HALON 1301 TURBINE BLDG. RELAY ROOM STORAGE TANKS 0 360 PSIG AT 70' F 18 LB. - NITROGEN PRESSURE ------- CARTRIDGE ~--- HALON LOCAL CONTROL PANEL S08 HLCP S07 AACR -- 91/i LB. HS PRESSURE SWITCH S08F -CR PUSHBUTTON ACTUATOR ON PANEL CONTROL BLDG. MULTIPLEXOR ROOM AUTOMATIC HALON SYSTEM S08 SEE NOTE 5 & ANSUL AUTOMATIC Il-C CUTTER HEAD ('W. ' '~"' \\ .c 90 LB. HALON 1301 TANKS (360 PSIG AT 70' F) (TYP.8) 1 SFS12 1/4" O.D. 2 . c SFS13 PI,__ _ S08F-RR 1 8 PRESSURE SWITCH ~ / HS 3 RELAY ROOM MULTIPLEXOR ROOM 1 1 /2" PIPE TYPICAL 8 PLACES i ~ SFS14 SFS15 SFS16 PI>--~ PI,__ _ SFS23 ~-~ --- 1/2"0.D. 4 5 REMOTE ACTUATOR N2 CARTRIDGE S08 6 7 NOZZLE H-1 (TYP

4)

~ ~ ~ ~ SFS17 PI r--- 1/2" O.D. CONTROL BLDG. RELAY ROOM AUTOMATIC HALON SYSTEM S08 7 ~ ~ ~ SFS18 PI r---1 8 ~ SFS19 8 9 10 TURBINE BLDG. RELAY ROOM ~ 1 1I4" ~ 340 LB. HALON TANK I'~ I /"' I r--l--i I I+ I

11 I

I t-t-i 1 SFS22 L /"-. /"-

I;
;~;-:;-

/ "-. / "-. /"-. /"-. /"-. /"-. NOZZLE H-4 (TYP. 31) PUSH BUTTON ACTUATOR ON PANEL


NITROGEN PRESSURE CARTRIDGE

~--~ ->---ANSUL AUTOMAN Il-C RELEASE ASSEMBLY 9 HALON LOCAL CONTROL PANEL S©S HLCP S08 10 1 1 12 - I NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. VALVE POSITIONS AT THIS TIME DO NOT REFLECT AUGNMENT FOR ANY MODE OF OPERATION; THEY ARE SHOWN ONLY TO REPRESENT THE SYSTEM AS-BUILT CONFIGURATION.
3. SEE DRAWING 33013-462, 0838 & 0839 FOR DETAILS OF THE ELECTRICAL INTERFACE I &

TO THE FIRE PROTECTION SYSTEMS DEPICTED ON THIS DRAWING. I £4. ALL PIPING IS SCHEDULE 4111, ASTM A-53 OR A-106. NOZZLE V

5.

FIRE SYSTEM S07 AND S08 WERE COMBINED INTO A SINGLE SYSTEM SUCH THAT ANY DETECTOR FROM EITHER OF THE SYSTEMS WOULD PUT THE SYSTEM INTO ALARM. _J REVISED PER OCR 2000-0018 PCR 96-125 AJV3 2/21/00 NUMBER RE\\l'.lS!ON CAD FILE NAME: 3P124201 CONSTRUCTION UMITED CONSTRUCDON: AS NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR.

  • ~

G!NNA STA. SCALE NONE FIRE PROTECTION RELAY AND MULTIPLEXOR ROOMS (FP) JOB NO. DRAWING NO. REV. EWR 10113 33013-1242 CCD 01 CONTROL COPY # 1 1 12 A B c D E F G H I J

A B c D E F G H J X14231S 1 (A-3) 33013-1892 (A-3) 33013-1261 2 1" 152 7321 ccw SURGE f1* I TANK CHEMICAL l ADDITION HOPPER 3 4 5 4-AC-152 2-AC-152 152 ~ .~I~~. ¥i0]~"7I:,------ ~ c:iiEti~~


+~-t---1 I~"'- t MANWAY ril 698A 698

'1. ril 1" 731C TAC02 CCW PUMP SEAL DRAIN TANK (E-6) 33013-1269 RMW (G-9) 33013-1908-3 NAC01 PAC01 CCW PUMP SEAL DRAIN TANK PUMP 2-AC-152 3/4" ~ TAC01 ccw SURGE TANK ~ I L!J D 713 250pl1p2 7300 1/2" 1" 730E 1" L!J L!J D 1" 2" 1" HHXJ---'T-1 J-'--IL><J------rl I 1-730A 730B [§] ~ J 31 J;i Ol T I 1" 2 .. t:9 § 1,s ~ i 2-AC-152 L-------------~ i5 2" ~ (1-11)


~~---+--< 4*

r--~--'---...... L--t-J 33013-1270-1 2* 3/4" 72~!1 152 TUBING S 3 PAC02A <MO/CCPlA> COMPONENT c_ _____ __c4_"-{ 1---"6-" ----, COOLING WATER PUMP A Pl [§] 2669 Tc~----1 12064A 3/8" O.D. v WASTE HOLD-UP TANK 1* 8* 8" 1 o* 6 7 8 v 733B t~ z G) Cll 0 ~ ,--------------------+-~ RM-17 COMPONENT COOLING WATER SYSTEM PROCESS MONITOR SKID R 12517B I A I v ril 12517A Q 10* 733A L--~C>> TE 6874 9 v 734B EAC01B COMPONENT COOLING WATER HEAT EXCHANGER B EAC01A COMPONENT COOLING WATER HEAT EXCHANGER A 10 0 Cll ' 735A ~ ~....__"' ;',, ~23 'tj -~ p 3 ~ ~ L__________________ --------~ L!J w*---~.._ 3-AC-152 s g *.------1 _________ ~""-'=--'-=-------------r><:~------' )> 772A D.I. WATER MAKEUP 14" 1---i,___, --11!~ I LL>::.:..1--,i-i 14" v (J-10) -C><l-J 33013-1246-1 X816 (A-1) ~33013-1246-1 X817 8" (J-10) [~~~~~=:>--~6-~A~C~-~1~5~2--i -l><H 33013-1246-2 X778 8-AC-152 14-AC-152 3/4" Sl-'--~4--------- 779A ~I"' <O 0 ~ )> "' 738A IBLCI 722A PAC02B <MO/CCP1B> COMPONENT COOLING WATER PUMP B [§] 7228 2-AC-152 14.. "\\ I 0 ' PUMP SKID 3/8" v PUMP SKID v t 723A 724A 8" 11~1 7238 7248 3" 772B 14-AC-152 3/4" 3/4" "' " 0 AUXILIARY BLDG. 1*-+---- SERVICE BLDG. £ o 3"'"' -...J -...J G) 0 .p.. 01 01 = 0 ""!(/) c fT1 <<; ;u c~ )> 0 ~!""' OJ CD!' ro OG) SERVICE BLDG. INTERMEDIATE BLDG. (/)I~ r'l r'l

u ;u fT1 Oo fT1 -

I~ l'1 fT1 olrn !" r g (G-5)


J'f--~===-----lf--<~3~3~0~13~-~1~8~9~9-~1]

'-:::=L=:--'l X1471 OS ~__,~ 747F 10048 747J 747G (G-5) 33013-1899-1 X14709S 747K 747D I 11 /2" 10020 I ~~ (F-10) 33013-1259 1 1 12 MANIFOLD 7358 12068L 12068D I ~I ~ OJ 1 2 D ~ 12068H 120691 ~---~ (A-4) 33013-1270-1 > ~5 3/4-AC-152 6-AC-152 3/4-AC-152 6-AC-152 (A-1) 33013-1246-2 B.A. EVAP WASTE EVAP. GAS COMPR. SW HEAT EXCHANGER (A-2) 33013-1270-1 (1-1) 33013-1246-2 CONTAINMENT SPRAY PUMPS & SAFETY INJECTION PUMPS & NON-REGENERATIVE HEAT EXCHANGER & SEAL WATER HEAT EXCHANGER X760A X773 ~I SAFETY CLASS SAME AS MAIN LINE

1' z

L SAFETY CLASS 2,3 OR SAFETY SIGNIFICANT CLASS (Q). DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS INTERMEDIATE BLDG. (E-6) -C><l-l 33013-1246-2 6" X760B 1 2" 2-AC-152 1--*---l'r:f 740A ~---~ v "I"' <O 0 2-AC-152 r:f 7408 ~---~ 10* 7388 IBLCI FIC 651 )>

I z

--+-~ 6 1-----11~-----1 r 0 0 120678 0 O> O> r I of'- °' "' o~ =- "' D 2-AC-152 L-----"'--'-'"'----'-"'"--------{:0-::}----------11 >-------~ 769 © 2 3 4 707A [Q] EAC06A RHR PUMP COOLER A 7078 [Q] EAC06B RHR PUMP COOLER B 7088 [Q] 2" 5 ) ) PAC01A <MO/RHRP1A> RESIDUAL HEAT REMOVAL PUMP A PAC01B <MO/RHRP1B> RESIDUAL HEAT REMOVAL PUMP B 6 7 1" 1* 1" 1" 1" EAC01 FAIL FUEL RAD. MONITOR HEAT EXCHANGER EAC05A PRESSURIZER LIQUID SPACE SAMPLE HEAT EXCHANGER EAC05C 1~ 901 1" 771E PRESSURIZER STEAM 1* SPACE SAMPLE HEAT '-----'-[><:J---j EXCHANGER EAC05B RC LOOP B HOT LEG SAMPLE HEAT EXCHANGER EAC04B S/G SLOWDOWN SAMPLE HEAT EXCHANGER B EAC04A S/G SLOWDOWN SAMPLE HEAT EXCHANGER A 771D 1* 771C 1* 771B 1* 771A 8 10049 9 ESS04B ESS04C SAMPLE COOLER RACK 10 SUMP NOTES: 1. FOR GENERAL NOTES SEE DWG. 33013-2241

2. THIS DRAWING SUPERSEDES PORTIONS OF 33013-435
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. THIS SECTION OF CLASS 3 PIPING ON TOP OF CCW SURGE TANK IS NOT SEISMICALLY SUPPORTED.
5. ELECT. MOTOR EIN'S FOR MECH. EQUIP.

ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328. CAD FILE NAME: 33013-1245,1 CONSTRUCTION LIMITED CONSTRUCTION: PS NOlEO PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES PS BUILT DATE RELEASED FOR ENGR. GINNA STA R.E. GINNA STATION 1 1 SCALE NONE JOB NO. AUXILIARY COOLANT COMPONENT COOLING WATER (AC) P & ID DRAWING NO.

  • SWR 3391E 33013-1245 CCD 01 CONTROL COPY #

12 REV. A B c D E F G H J

A B c D E F G H J 1 (E-1) ~-33_0_1_3_-_1_2_4_5~::::>- ccw HEAT EXCH. OUTLET 33013-1887 X 14138sL..:=c:::__:.::o::_~~ 1 2 3 2-AC-152 817 IBLOI 4 8-AC-152 5 6 6-AC-152 7 8 9 10 (E-3) 33013-1890 ti?:sc X14291S 1 1 12 NOTES:

1.

FOR GENERAL NOTES REFER TO DRAWING 33013-2241

2.

REVISION "O" OF THIS DRAWING SUPERSEDES PORTIONS OF 33013-1246 REV. 5.

3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

3-AC-152 4"

4.

EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING 4* 152 !TUBING 3/4" 1---*~TC 750D VI I /'; I OJ 3" 751B 15 SEE NOTE 152 1 TUBING 3/4" P'-'---.... 1--11-- D 2732 3/4" 152 l~UBING

JTC 2741

--:d b-P1 3" 750B 152 © © 152 4" PRC01B <MO/RCP1B> REACTOR COOLANT PUMP B ECHOBB RCP 8 UPPER BEARING COOLER SEE NOTE 6 N VI <D (:;j i~ D 1" 7 1" 3/4" 1----<f,J\\..n MOTOR 1-JVlr----------.-..-JID 3L8" 3/4" E-U '61... H>---< ~125~i.~1~-~:~~. ::::3 ~ 2738 PUMP ~i1---- 3/4" "' u SEE ~ 2" 761E ~ ~NOTE (:;j ~ "' ' 8rlf---11-~ 1 2 (JI ~ v D 12305H 12305L MANIFOLD ~


jti 758B 765B 1/2"

<Ill D 12307 4" 2" ~-----< 1" 2 VI ~ P125 (}> 4" __(FE\\

  • ~

v 11~2* Fl 615 8" 3 3" 7578 ~ I (}> 4 ~ I (}> 2-AC-152 u ~I 152 l\\UBING 3/4" °' !--'--.... 4--Jif--:J D 1521TUBING 3/4" ~ 2730 <$) ; 152 ITUBING 3/4" TUBIN~2 I 3/4" D Hf--l.... -1 2728 "'27~ ~ <$) ~ ' ~----H-~ (}> -:d 3L8" 3/4" E-l 761G !---'---...-1

J TC 2761 bP127 VI '

AUX. BLDG. CONTAINMENT 01El ~l P124 SEE NOTE 5 2-AC-152 ~ TUBINq 11 ;52 ~ 3/4" TCE ECH03 EXCESS LETDOWN HEAT EXCHANGER 1~BING 3/4"

J TC 750C

~ 751A H""H~---il SEE 2776 2" DI 152 © © 152 4" 3* ".:li~ (}> (}> D PRC01A <MO/RCP1A> REACTOR COOLANT PUMP A ECH08A RCP A UPPER BEARING COOLER v SEE NOTE 6 OM8 2756 NOTE IM B 7 1 * '-r---lk.f'vl H MOTOR f--il----~hJV-1:1-----~-l 152,,.J© .1.152 I- "'*VI 250~ I *~©-~~-©_. I ~so3

J ~

'-t:<<'.1--.---.--1*-l PUMP ,,_,>-----~-~ 761F (}> D D I /'; I (}> ?. 7441Jt--1=- 3/4" (H-10) 33013-1888 152 ITUBING 3/4" t--..... -Jr--:J D 2723 152 ITUBING t--....,-JI D 2724 -:db--- P131 3/4" 2733 15?,:-t-151 3.. 11----- ~ -I 2"--11 -~ ~ 152--1--151 O> 3/4" DI~ 2750 -/ -/ -I -I -I 4" 4" 151---i--- 152 ~ 3" !- ~_.if 2752 £1 ~ 2" /- ~ ~~1-1.-----1 151 152 /- I- /- /- /- /- I-I- I- /- /- I- /- 4" £1 3/4" 1----:J D 2751 SEE NOTE 8 "-------_Jx14132s 1/2" 1--+'4 D 12309 .---1,-.--f><:J---+..L..f 1--{::e:J-,~ 12308H 1765D i--.... t-:J D 12308D 152 2505~ ~I '------+---'----i>Q--+rl 12308L MANIFOLD ~


jti 758A 2"

765C 1/2" <Ill D 12310 3" 2503 1~>----~ 3" 757A I /'; I 4* LAC01 3/4" Dir--. 2748 1" 818 r-- 3/4" -I /- -I I- -I /- -I /- -I /- -I I- -I /- -/ I- -/ I- -/ I- -/ /- REACTOR SUPPORT COOLER B SAGOS 4" 4" 152--j---151 FOR SAFETY clAss.

5.

CHECK VALVE 743A INTERNALS PERMANENTLY REMOVED.

6.

RCP UPPER BEARING COOLERS ARE SUPPLIED WITH MOTORS. SHELL-SIDE PRESSURE BOUNDARY IS NON-CLASS, TUBE SIDE CLASS IS THE SAME AS CONNECTING PIPING.

7.

COMPONENT COOLING WATER FOR MOTORS: CLASS RATING EXTENDS THROUGHOUT CLOSED COOLING COIL.

8.

COMPONENT COOLING WATER FOR PUMPS: COOLING COIL AND THERMAL BARRIER ARE CLASS 1. CLASS BREAK FROM CLASS 1 TO CLASS 2 OCCURS AT CCW PIPE INTERFACE WITH COOLING COIL.

9.

ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328. 1-3"---l I ~l---l~-1~~ -I 151--J-152 13" /- D--4H_.o/ ,___2*-~*1----:__~~~-/ 152--1--151 2771 £1 ~ 2" 1- ::;;; - I 1,.e-,____, 2710 I 151-l-152 4" 3/4" DI----. 2769 4" LAC02 O>... O>..l I- - /- - -/ /- - I- - /- - /- - -/ -/ /- - -/ /- - -/ /- - -I /- - -I -/ /- -/ /- -/ /- -/ /- -I /- -/ /- -I /- -/ I- -/ /- -/ /- -I /- REACTOR SUPPORT COOLER A SAC07 !~ H 4" 3/4 ~. ID .J 2768 4" 1YP. 8 PLCS. 1" 1YP. 96 PLCS. ~-t-----11 D 2767 D VI ~ P126 3/4" v 11---t----I IP130 ~ 5 (}> CONTAINMENT AUX. BLDG. 6 7 1-3/4" O>, 8 816 3/4" D....,1----1 11259D 7368 1/2" DE~4---I 11261 1?~0' ST.STL.PIPE~ MANIFOLD 11259H 1YP. 11259L w 8-AC-152 9 ~~o=*~* AS MAIN LINE r Z tSAfETY CLASS 2 OR 3 DETAIL-A SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS 14" (E-1) 33013-1245 CCW PUMPS 10 1 1 RJM 5/13/1 CAD Fll£ NAME 33013-1246, 1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES I IV PS BUILT DAlE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. AUXILIARY COOLANT COMPONENT COOLING WATER (AC) DRAWING NO. REV. EWR 3391E 33013-1246 SHEET OF 2 L11 CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 (C-12) 33013-1245 ccw HEAT EXCHANGER DISCHARGE TT 2841 <MO/CSP1A> PSl02A CNMT SPRAY PUMP A [I] ) 1/2" EAC11A CNMT SPRAY PUMP A SEAL HEAT EXCHANGER 1 33013-1245 CCW HEAT EXCHANGER DISCHARGE 6" 3" I I fl I - 2 748A [ill 3 2" 3/4" 4 21/2" ~~pwvg-*~1 ~I N ' 3/4" 748D v 0 774C ECH01 BORIC ACID EVAPORATOR DISTILLATE COOLER ECH06 BORIC ACID EVAPORATOR AIR EJECTOR CONDENSER N ' 6" ~-----1!....e-lf-----11-----,----'----, I fl I 3/4" 3/4" 815B 727B 0 OJ

L 1-AC-152 1..

774B ~!--------....----------! 11278L 1.. 5 3/4" f---" '-,.. N ' (FE\\__ 1S2 250S '-----tt:J 77 4A ~I 3/4" I 727C D..... 11--1 11278D 11278H MANIFOLD Fl 642 L!J I fl I -'" N (FE\\__ ~. 11/2" 3/4" 2712 6 11 /2" (FE\\__ ~ 2-AC-1S2 ST.STL.PIPE 1 2505 1 /2" 8 1 D~ 11273 3/4" 727L ~ 152 2505 3/4" 1/2" D~ 112720 727K 11274 I ST.STL.PIP~ ~SOS 0 7 3/4" 11/2" 8 (F-1) 33013-1273 11/2" v 111--... c----; L_ __ __J _ __J 77SB sT.STL.PIP~ I ;sos 1/2" D~ 11276 3/4" 727H 152 3/4" 1/2" D~ 2505 1127SD 11277 I ST.STL.PIP~ ~S05 3/4" 11272L 11272H L!J MANIFOLD 1127SH 1127SL L!J 7740 l:if--~ 1" EWD01A WASTE GAS COMPRESSOR A SEAL WATER HEAT EXCHANGER EWD01B WASTE GAS COMPRESSOR 8 9 3" OJ 10 2-AC-1 S2 v 3/4" (J-1) 3 4" 33013-1273-1 SEAL WATER 1 1 X1032A 12 ~! SAFETY CLASS SAME AS MAIN LINE t SAFETY CLASS 2,3 OR SAFETY SIGNIFICANT (Q) ECH07 BORIC ACID EVAPORATOR HEAT EXCHANGER -~ 1-_ _::2_" -~---------------------------------------------_.__. 2" '::i DETAIL-A 1YP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS A SEE NOTE 6 1/2" 1/2" 3/4" 6" 2 2-AC-1S2 <MO/CSP1B> PSI02B CNMT SPRAY PUMP 8 [I] ) 1/2" EAC11B N 0 ';:) CNMT SPRAY PUMP B SEAL HEAT EXCHANGER 6-AC-1S2 1/2" FE 649 1/2" -.,J ~ ~ ~ Y-4...,,--+ __ 01_ I N 0 0 11263B r 4 7640 ITRL! L'-1 D 6" N 0 ~MANIFOLD I 3/4" EAC08A SI PUMP A SEAL HEAT EXCHANGER 777L !ill (1-1) 33013-1245 CCW PUMP 3/4" 2810A ~ 0 3/4" 777M 2 !ill t::::::::=J i:--H >----"---~------, 3/4" EAC08B 3/4" ) SI PUMP A F~~=l-ror:~.f; *.:(1==::;:=~_:__, SEAL HEAT L EXCHANGER 28108 3/4" 2 3/4" t----;1-- ---{;.(I----( 777F !ill 3/4" EAC10A SI PUMP. C SEAL HEAT EXCHANGER 777N !ill 3/4" 3/4" 2810F N 0 N g; 777E [ill 3/4" 777G [ill t:=:~ r:--.., f--L--__,.,.----, 3/4" ~c~~BMP C 3/ 4"I::::;-~;f;;jj::('f:=:;==::: SEAL HEAT i=::=i t EXCHANGER 28lOE ) 3/4" 2 3/4" 1--1-- --~Cf---{ 777H !ill EAC09A SI PUMP 8 SEAL.HEAT EXCHANGER 3/4" 777S !ill 3/4" 3/4" 2810D I: 2810C N 0 N 0 2 777P !ill 777K !ill ) 3/4" 3/4" 2" 6" ~

1.

N 3/4" N

  • 11-..... Kl~N PSI01A SAFETY INJECTION PUMP A

[fil <MO/SIP1A> 2716 (1-1) 33013-1270-1 PSI01 C SAFETY INJECTION PUMP C [fil <MO/SIP1C> PSl01B SAFETY INJECTION PUMP B [fil MANIFOLD <MO/SIP1B> I:: N I g; I ECH04 SEAL WATER HEAT EXCHANGER 3/4" 12719 ~ FIG 650 11266B N N g; ~oo N 1/2" 1/2" 6-AC-152

  • 3/4-AC-1S2 3/4" 766

~ I fl I N 2-AC-1S2 N (Xl L!J D N g; u 01 7648 NOTE 5 v ~!~152 ECH05 NON-REGENERATIVE HEAT EXCHANGER 3/4" 152 *I ;sos 1/2" 2718 D [C--c-i-- J--- 11270 1/2 D~ 727S 1S2 2505 D~ll--1 11269D 11271 I 1s2.~sos 776 3/4" 3/4" ~f---t-~1--cH D 2721 ~ I N 0 Tl 600 MANIFOLD 11269H 11269L OJ Fl 601 L!J (B-10) [__--f/-----11--~:::::=3~3~0~1~3~-~18~9~1==] (B-lO) X15906 1.* '-----f.__ _ 2-AC-152 2-AC-152 L'J 3/4" 2722 l/P 130 33013-1891 ~X15907 3/4" (F-1) 1-~1-- --t:a:'.1---{~--'------..-------- 11---------Dl(j-----------o--~ 777J [Q] N g; 3/4" 777R !ill 6-AC-152 ~. 764C ~ !TRLI 33013-1245 CCW PUMPS 5 7 8 9 10 1 1 NOTES:

1. FOR GENERAL NOTES SEE 33013-2241 DRAWING
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1246, REV.5
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE !N ACCORDANCE WITH DETAIL "A".
4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
5. THE WASTE EVAPORATOR HAS BEEN ABANDONED IN PLACE. VALVES 764A AND 764B ARE KEPT CLOSED AND LITTLE OR NO MAINTENANCE IS PERFORMED ON THE PIPING OR COMPONENTS WITHIN THE ISOLATED SECTION.
6. THE PIPING FROM THE CONTAINMENT SPRAY PUMP TO THE SEAL WATER HEAT EXCHANGER IS STAINLESS STEEL WITH 405 PIPING AND 150#
FLANGES, CAD FILE NAME 33013-1246,2 CONSTRUCTION LIMITED CONSTRUCTION; AS NOTED PRELIMINARY NOT FOR CONSTRUCTION B!ODING PURPOSES AS BUILT RELEASED FOR ENGR.

'~ GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. AUXILIARY COOLANT COMPONENT COOLING WATER (AC) P&ID DRAWING NO. REV. EWR 3391E 33013-1246 SHEET 2 OF 2 A CCD 01 CONTROL COPY # 12 A B c D E F G H J

N I 0 ID "02d..!.. -!!!!L ~~~~~~~~.-~-+-I ~~~~~~ ..... r I cncu~,.,. I ~, c!""I t& _ff;, I ..-J l( -.0 °:!:a1 l. I~ !111:11ru H1$1 .___1 __ -;-J:~~f-.;;~_!_'.::,.__;:i..:L~ () m N OJ )>

A B c D E F G H J 1 2 3 4 LT-310 3/4" v E---1M--I 799E CPB-AUXILIARY LC 0 y 5 PAC06 <MO/SFPSP> SPENT FUEL POOL SKIMMER PUMP fr z c __, ?< Sti CD CD 'r 00 6 7 (F-11) N -i 33013-1259 > 2-AC-151 "------'Hl-------~-=-='--'"-'-----'-----_J INTER. BLDG. NOTE 3 ( TEMPORARY SKID 8 9 NOTE 5 6-AC-151-SFP SFP FILTER ROOM (F-9) 133013-1908-3 > 2" 788E ~ N 1 0 SFP FILTER ROOM 811 788A [!£] R.R. 4" 6" / SEE NOTE 11 BLDG. 661


"SUMP

---cooc-------~ N 0 C-2 I 2~t# I. 301 ... I-- HOSE 1,, E--+--Nve:--~--- 1" -~ E Nvi::-~-- NAC03 STRAINER LJ z,.. g 2-AC-151 AUX. PUMP SKID (F-11) 33013-1259 ~ "'-"",,__,µ BLDG. CONTAINMENT INTER. BLDG. SACOG SUMP NV[ ~HOSE NORMAL WATER MIN. WATER LEVEL 257'0" LEVEL 276'11 3/4" TAC03 SPENT FUEL POOL ~------1--- SPENT FUEL POOL TRANSFER GATE FUEL TRANSFER CANAL NOTE 4 SAGOS \\_ LEAK DETECTION CHANNEL ~~~-1~~~~__J_~~ LEAKAGE COLLECTION CHANNEL TC °' 650P2 Pl 21 f-"---11-~ Tl 24 650X 3/4' v P~+------' 'T1 °'"" SEE NOTE9\\- r----'~"" "' 0 V ~ C'l ~ Pl 22 °' "' D }.\\ 650P PAC03 SKID MOUNTED SPENT FUEL TC POOL PUMP '] D 8671 1/2" SS TUBING EAC12 SPENT FUEL POOL STANDBY HEAT EXCHANGER Pl 23 1/4" c_~_J 650V 3/4" 6" Tl 26 (F-10) 4" 33013-1272-2 REACTOR COOLANT DRAIN TANK PUMPS (..; V> '0 I :r ~ l"1 ~-------------~"" 0 r f,, I /) I I V>

i J rz N

J (C-7) 33013-1264 NONREGENERATIVE HEAT EXCHANGER (B-7) 33013-1264 NONREGENERATIVE HEAT EXCHANGER v m co I,.. 0 I ~ Q LT-311 N SEE NOTE 6 X1722 Pl 652 501 I 151 2-AC-151 820 601 151 821 y 1/4" (0-1) 33013 1272 2 REACTOR COOLANT DRAIN TANK PUMP 824 0 "' 0,, 0 LAC07 r----.-4--JTC 86728 ~ 783E PAC07A <MO/SFPPA> SPENT FUEL ~ POOL RECIRCULATION PUMP A ~ ~ 0 ~--~ 4" -1'- NOTE 5 co O> N O> NOTE f-'--------,.--_J_--'--i-~ 6" --f:><l----0,-1---1>-"-+-)--=~ 86~4 ~ J 8655 3Q OL'.J 0 NOTE 3 Pl 8665 1/2" SAC01 OTE 3 Pl 8672 1~ 1-----~4--ITC 86666 AC-151-SFP 8658 N N I /) I D 806 8667 vE (C-3) 33013-1261 REFUELING WATER STORAGE TANK X808 PAC05 <MO/RWPP> REFUELING WATER PURIFICATION PUMP 33013-1230 (B-1) X9050 3/4" 7830 Tl 633 Vt-iH----1 783C v [-j!l--i--1 787 7798 11----1 ~ (C-6) 33013-1270-1 WHT g; 0 TUBl1NG 51 °' v Pl ~ 653 co LAC OS 810 3/4" 0 I /) I (J-7) 33013-1264 WHT TO QUICK CONNECT AT RESIN BATCH HOPPER ON DWG. 33013-1264 (H-4) 795 2-AC-151 0 Hll-i'*-r L-j__ce2c:-"'A"-C-=15;_;1<___J 790A TUB$ 4-AC-151 EAC14 SPENT FUEL POOL HEAT EXCHANGER A TAC04 SPENT FUEL POOL DEMINERALIZER Pl 632 786A 785 Pl 665 2-AC-151 8614 OTE 3 6" 1/2" 3/4" D 2" 798B 7968 N I /) I 794 RR ~ 2 RR Q TE 666 4" Pl 637 v DE CON' PIT MAKEUP ~t~ FAC02 0 ~SPENT FUEL 2" / POOL FILTER ,:::.._-._J_ ___ _j F 1--- 2-AC-151 6"

uCO
  • D i"N N

I /) I Pl 638 (B-6) 33013-1270-1 ::.:> WHT

u 0

0 (B-8) 33013-1261 REFUELING WATER STORAGE TANK co O> m O> I /) I I V>

i (J-5) 33013-1264 WHT (E-4) 33013-1269 REACTOR MAKE-UP WATER (1-5) 33013-1264 SPENT RESIN TANK tjO 8635G s

TBG~669A S, c ~~- 3 r----------~~ 1 " tjD 8710 (1-10) 33013-1272-2 AUX. BLDG. SUMP 1 3/4" 2 3 MANIFOLD 4 5 8667E FIT 8667 6 7 Pl 667 TBG~ c-2=1 1 2'" 3/4" o, 8670A 8 EAC13 SPENT FUEL POOL HEAT EXCHANGER B TE 668 6" 9 10 NOTE 3 1 1 +--J v 8635H vO =i tj 0 0 z 12 SAFETY CLASS SAME AS MAIN LINE LSAFETY CLASS 2,3 1 OR SAFETY SIGNIFICANT (Q) DETAIL A TYPICAL SAFETY CL-ASS BREAK POINT FOR VENT, DRAIN AND TEST CONNECTIONS NOTESo

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDES DRAWING 33013-0436.
3. THE PIPING DESIGNATED BY LINE SPECIFICATION 151 -SFP ~VAS INSTALLED UNDER EWR 1594B, WHICH HAD A SEPARATE LINE SPECIFICATION FROM SP5291, 151.
4. SAFETY CLASS CHANGE OCCURS AT PENETRATION 29.
5. THE TUBE SIDE OF THE SKID-MOUNTED SPENT FUEL POOL STANDBY HEAT EXCHANGER (EAC12) AND THE SKID-MOUNTED SPENT FUEL POOL PUMP (PAC03) CONNECTS TO THE SPENT FUEL POOL COOLING SYSTEM, UPSTREAM OF VALVE 8664, GRID COORD. (B-8)

AND DOWNSTREAM OF VALVE 8662, GRID COORO. (F-4) WHEN IN USE.

6. LEAKAGE COLLECTION TANK BODY CONSISTS OF A VERTICAL 10-INCH SCH. 40, 304 S.S. PIPE SECTION, 17 INCHES HIGH.

TOP AND BOTTOM COVERS ARE S.S. 3/8-INCH THICK FLAT PLATES.

7. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES ANO COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
8. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
9. BLIND FLANGE IS REMOVED FROM 8669 ANO 4"¢ HOSE IS CONNECTED TO FLANGE DOWN-STREAM OF 8670 WHEN SKID PUMP IS TO BE ALIGNED TO SFP HEAT EXCHANGER B.
10. THE PIPE IS IN A PENETRATION THAT IS 17' 4" LONG AND 20" IN DIAMETER. THE ENO AT THE OECON PIT HAS A PLATE WELDED AROUND PIPE ANO COMPLETELY COVERS PENETRATION TO PREVENT ANY LEAKAGE IN OECON PIT FROM GOING THROUGH PENETRATION.
11. HOSES ARE REMOVED WHEN NOT IN USE.

f\\ RE.VISED PER f.1..£.. ADC~l&-000051 NIJM8£R POL 1/25/16 CAD FILE NAME 33013~1248 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BU!LT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION 1 1 SCALE NONE JOB NO. AUXILIARY COOLING SPENT FUEL POOL COOLING (AC) P&ID DRAWING NO. EWR 3391E 33013-1248 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 FSW010 C-1 125-1 E-12 N N 0 N o D 2 TRAVELING SCREENS FSW01C FSW01 B C-1 125-1 PS 2664 C-1 125-1 3 N 0 " 2" OJ D C-1 FSW01A 125-1 N 0 N

J> D 4

5 6 7 - ----- ------- --- -- ------ - ---- -- 20:_~~~1* 125-1 I I I I ~ 3 8" TUBING ,,_ ~ s: I ,g I "'-' '-'L t 1~ ESW08A 11504C 11504L I D/G A

J OJ N

0 I (/) I JACKEf WATER ~ I ~ 6626 HEAT EXCHANGER I 2* 1 1/2" g I 11503A 11503C ilJ I I I 16" L ____ l TE 6081 8 9 ltt=~ :--19+---r:----l'f-12-5--1---r--I ,f: ~ h i>< () () N I~ ><W 125-1 152N ~,-- 1.. 4790 [bQ] 125-1 I 1,52N N 01 I .--...... D 12501E 11503H I ! I J~-~~INTER. BLDG. 1.. f----C><:Jl--'---1-. 4789 lLOl I f---D f----l ~ 1 0 3/4" ) 4794 [bQ] w w PSI01 B SAFETY INJECTION PUMP B <MO/SIP1 B> 3/4" 4794A [bQ] 3/4" 1 1 12 1-10 1" ';::,.--~(G_-_1~)--, 1.. 1" 33013-1989 ~ 12501~ f' ~ 2"<t 1/2" ~ NOTE!(/) l.2JN 15 (/) I I N w 4795A [bQ] H-~ ..... t-'-~-1 33013-1250-2 '---.~-H 4739B 4795 [bQ) w PSIO 1 C X5250C 12501C ~ () (/)(/) I D ~"-SW-125 12501 B ESW09A D/G A 11503D I BRASS OJ I LUBE OIL COOLER '--~--'-==-~~~~~~---[;:.::J-}Vv[:-t:::-::J--L----' N I (/) I ~ I SAFETY INJECTION PUMP C <MO/SIP1 C> 1 1/2"-301 125-1 I I:t Pl (F-4)1501D 11501H 1" 3 2102 33013-1896 '"'° i~ N I 47913 4" ) 152N 125-1 125-1 125-12 8" I I 3 4" I __ _, ..._ D 12501A 4667A l-l't/;o2('" 1-----cc__j 4598F ~ SAFETY-DE_.. __ __, ~ E 1/2"SS 4525 3" 2 1/2" OPl4598G RELATED 125-1 [ 150-4 8" ,......----..---~I ~~ t;; I I ~ ~! I r-11--D I 0 4612E I D 12500Z 4667F [Q] f-----l~ ~IH)-H-Gl OP/4598H 01 00 I (A-8) 4501E 4501F )> N ' 4666 Pl 2098 PSW01A SERVICE WATER PUMP A <MO/SWP1A> II] SSW02 NOTE 13 f-------"12._*-1r-1101~114* 4601 4605 NSW20A E=-..i---f-1 4502E Pl 2099 Y450:~ ~x~* I o N i::5 f--'-TC"-{:>>Qf--J../'lf-- 0 - N 45028 4502C ' SSW03 PSW01B SERVICE WATER 1---------'"'12--i" 101~114" NOTE 12 4602 4606 PUMP B <MO/SWP1B> m El~ N 0 ' 2" I 8; 1" I ~ 33013 1239 1 N I

~

LO X5939 o '-"1 L__ 1---~ D/G A COOLING WATER ECD13 SAMPLE COOLER I I I I/NOTE 9 (F-4) EXPANSION TANK II ~21o2**r111125-l DIESEL GEN.RM.A V 45981 33013-1896 1/2" SS SAFETY RELATED DIESEL GEN.RM.B 16" 14" ~ ~ j - 14" M (G-4) I g 4665 C:J<c~1'-'0"i"~--1--1 H 33013-1251-1 > rT1 flr\\l O'l 6" 0 -I I z r ~ :;i:,. -I'-- r;:J rv ~

  • 1:::0 fS1 0

1 -..J ~ )>

01!'.D ~

'---!>Q-'2~"-p2"-J D I c ~ ibQi t~ -;, 4670 ;;5 o c 46~13 150-~ 1 153 I w f'.lw.i.. 0 I £1~ D 1l1 LU~~15 3 J-r-l ' * "'? \\W ' 0 0

  • m 0 4612C I

0 OJ (J-2) 4612A 3/4" SEE NOTE 4 125-1, 1 125-9 'if : 33013-1896 >>--tt//-1 __ 1/2" SS 20" ~ SAFETY RELATED l-*~-,"--.-u--o+1(f) <fl-11,_o(f)--l,~1L:_.J 4668B rJ ~ob ~ .. l 17;. 17;JQP/4599H -":,: i '~EE NOTE ~ i:1 'w',~ : ~Il----jll;i/.. "F' ~l'i 'f ~T Ht---- v1 /2 - >------<[><Jr-I ~----~---- g m 0 E 4599E PT 2027

J G'J 4799A 11 (A-4)

SEE t~~1*~;y;;::_::---------~~~~~~~::>:~:'.8;- 5 0 rn NOTE 14 (\\; 33013-1239-2 °' ~ X594D Fl 0 ~ D/G B COOLING WATER IQ] EXPANSION TANK 301-r--\\Jc-'3L"---~--=2~1/~2~"i Pl .T 1/ 2"\\ 4668F (J-2) 33013-1896 1 /2"SS SAFETY RELATED Pl 20000 4754 4769 0 - z 0 [bQ] w M SS ~-=-+---cs m NOTE iO I (/) 4768 --(:J------1 f 4768A 0 - 4752 301 I 125-1

  • 1

.301 4579 11T1 4579A 45798 4579C 1 (A-1) T 3""'3"'0,..13-=-.,.1=-8=-6_6~1----' ~ ~577 TC 5133 1/2" Pl 2247 w PSI01A SAFETY INJECTION PUMP A <MO/SIP1A> NOTE 5 1" 2 1/2" -~- ~ c ~ AAA01A 2 1" c 2 1/2 ACA05 cw N 2 1/2" AAA01B 2 1/2" N ' ~ 4564 I~ r v.f I 00 1" 1/4" 4770U [bQ] l 1" (/) I 0 - 4770W [bQ] 4" N I 0 N O> I {J~ r-c~="'=-----' NOTES:

1. FOR GENERAL NOTES REFER TO DWG. 33013-2241
2. REV. 0 OF THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1250, REV. 8 Pl 2000 AK
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN

& TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

4. THE ACCEPTABILITY OF VALVES 4611A & 4612A BEING NORMALLY OPEN HAS BEEN EVALUATED BY EWR 5168
5. SERVICE WATER PROVIDES COOLING TO THE OUTBOARD BEARING HOUSING OF THE SAFETY INJECTION PUMPS.
6. CARBON STEEL PLATES HAVE BEEN INSTALLED IN THE INLET AND OUTLET FLANGES OF AAA03A, AAA03B, NSW20B AND AAA03C BY TSR 92-158.

L...j)-*lf--1'-'1.L-"'2_" --1--,..---.......,--4...,7{5]J 5

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS 2104~26 1" :JD 4669A 3 I 3 8" TUBING 1/2" 4503A 4503B 0

3143A = I,, ADJACENT TO MECHANICAL EQUIPMENT 3 4 PER SFEWR 10328. }Vv[-l)<J--,--, 115020 11502H E4503D f503E t () ESW09B D/G B LUBE OIL COOLER 2"~ Ol I (/) I

8. 20"¢ STAINLESS STEEL SPOOL PIECE

~ FOR CONTROLOTRON SITE INSTALLED PER SSW04 t ~. PCR 98-107. PSW01C SERVICE WATER PUMP C <MO/SWP1C> II] 4504E PSW01D SERVICE WATER NSW20C PUMP D <MO/SWP1D> ~ NSW20D 12" I l~I 14" 0 ' XIT-5403 CHLORINE MONITOR OJ 0 ~ NOTE 13 20" w D 125-1 I _,,. j----{)l(}--j/ N 0 0 - 0 _,,.' N ' 4504A 4504B TC SSW05 12" 101~1 NOTE I 4604 12_) 4608 PT 2028 I N 0 -<o II c, (/) ill "' I :< 'Z;o I!, ~)0 N OJ o I '(' 'I"" 8rn ftO 1/ " 11503F I ~RASS 11503G 01 0 N OJ Pl 6081 j '--~~~~~~~~-i;:.:~}Vv[-j,xJ--~~ 11503B rn ESW08B D/G B JACKEf WATER HEAT EXCHANGER 112* I 1/2" ti ' r--- 30l 4718A - 13/4" 00 4llf!B lbQJ 11502C 11502L 3/8" TUBING '-'-~~~-[Xr}Vv[:-i:::-:::i,--, 11505D 11505H 2" 1 1/2" 115~ I eyRASS 01 0 01 OJ 1" f--125-1 DIESEL GENERATOR ROOM A DIESEL GENERATOR ROOM B . I II 10" 6-SW-125-1 5" 4" 1--~~___,Dr~-+~~~~~~~~~~~~~~~~~~~-1-~~~~~~-----"'--1 ~~~~.-'--~~-~-~-~-~~~~ (G-1) 33013-1251-1 I (1-1) II N I USE SPOOL PIECE AT THIS LOCATION FOR SYSTEM BACK FLUSH 16" 301 C-2 1" 125-11150-4 r:______;..-i__ NOTE 6 t.: l._.J I 2" 2 1 I 2 "..---::::::: c SAFETY INJECTION PUMP COOLER B AAA03B NOTE 17 4770E ~.,..=..CW~ NOTE 6 2 1/2" SAFETY lNJECT!ON PUMP COOLER C AAA03C 1-, 125-11150-4 ~NOTE6 NOTE 17 cw 2 1/2" 4770D NOTE 6 2 1 /2"-.--~- SAFETY C INJECTION 1-, PUMP COOLER A "--r:.CW:.:.J ~~ 3 ~ 7 4~70C 2 112.. NOTE 6 2" j 150-41125-1 (J-2) 33013-1237 4087E c__ _____ X4087D (G-1) 4-SW-125-1 4" ,_3~3~0_1~3----12~3~7 _ _J--------------------------------- 1------------------,.._ _____________________ ___,_~c~s-~::_--i..... ------'-~----------------; TURBINE DRIVEN I NOT~S 8 33013-1250-3 47701 [QI 1 4" 1" 477~ 578

\\ 9. CONTROLOTRON TRANSDUCERS, FE-120A i

i'j~ AND FE-1208, MOUNTED ON SS SPOOL PIECE, PROVIDES SIGNAL TO j' CONTROLOTRON FLOW METER, FM-120 ~ "' 10. 3/ 4"¢ STAINLESS STEEL PIPING FOR "C CONTROLOTRON SITE, INSTALLED PER MDCN 2358, TYPICAL FOR ALL SIP'S.

11. TUBING MATERIAL (316SS, 1 1/2" O.D.

X 0.065" WALL) PER PCR 2004-0045.

12. DOWNSTREAM FLANGE OF SWP DISCHARGE REDUCER FLAT FACED PER PCR 96-080.
13. UPSTREAM FLANGE OF SWP DISCHARGE CHECK VALVE FLAT FACED PER TE 2008-0028.
\\ 14. CONTROLOTRON TRANSDUCERS, FE-125A

~ AND FE-125B, MOUNTED ON SS SPOOL PIECE. PROVIDES SIGNAL TO CONTROLOTRON FLOW METER, FM-125

15. VALVE 4623 AND 4624A REPLACED WITH SS EQUIVALENT UNDER ECP-10-000103.
16. THE FOLLOWING LINE SPEC DEVIATIONS ARE JUSTIFIED PER ECP-11-000539.

VALVES 4754A, 4755A, 4769A & ADJACENT PIPE FLANGES ARE 150# CLASS. PIPING LESS THAN 1" DIAMETER IS SCHEDULE 80, NOT SCHEDULE 40. THREADED FITTINGS/CONNECTIONS ARE USED FOR THE RUPTURE DISK ASSEMBLY AND RELIEF VALVES. BUTT WELDED CONNECTIONS SHALL BE USED FOR THE TRANSITION FITTINGS BETWEEN PIPE SIZES GREATER THAN 2" AND PIPE SIZES LESS THAN OR EQUAL TO 2".

17. SAFETY INJECTION PUMP COOLERS AAA03A, AAA03B & AAA03C CUT, CAPPED AND ABANDONED IN PLACE PER ECP-11-000539.

RE.VISED PER j\\ AOC-1-4-000250 ~ CONSTRUCTION UMITED CONSTRUCTION: AS NOTED ~~P~P I SS (D-1) I 4-SW-125-1 4" cs ,_3_3_0_13_-_1_2_3_7__Jf--------------------------------i-----------------...... -'-----------------------="---I 301~--< AUX. FW. PUMP A & B I N 0 ' 1" I ~ I ~~ ~ 1" C~~D~t-t~:"'~ 3" 4738 [Q] ii --t SAFETY CLASS SAME AS MAIN LINE

1----~'--z-S7A-FETY--J!CLASS 2,3,0R SAFETY SIGNIFICANT (Q)

DETAIL-A ? I DATE PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE 1 2 3 33013-1237 u* -(,_L 4090A X4090 -+-------~ D 301 I C-2 J, INTER._JlLDG.m ~ ~ ~ ~ 1., 1/2" (A-3) OJ 3 33013-1237 r Pl 2569 125-9 1 125-1 !"'o ~~ _ I 4091A X4091 I 8 L _______ ~o-sw:..:.25-9 _______ -- _______________________.L _ +-+-----lf-----"----'---- 4 5 6 7 8 9 TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS 20" (A-11) 33013-1250-2 4615 II] X4779 10 1 1 JOB NO. STATION SERVICE COOLING WATER SAFETY RELATED (SW) P&ID DRAWING NO. REV. EWR 3391E 33013-1250 SHEET OF 3 M CCD 01 CONTROL COPY# 12 A B c D E F G H J

2.

3 4 5 7 8 A 3 u~'1rr-~~~~--~~~~~~~~---. 671J c

t.

G

2.

3 4 5 6 7 8 9 g 10 l-A t ~ s..AffTY CLASS S..-.ME I AS UAlf'l LINE ?SAf.CTY CtA~S :::..:!. Off SAFETY SIGN!F1CA.">iT (Q) !:£TJJl.-A TY?. SAf'tT'( ctASinf.;"tN{"""ii°oiNT FOR \\'E.Hi, o~ ct. itST cONN::cnms 10 11 11 12 J. fOP. ClNllilU.. NO'l1.~ HLF[H TO DAAW!HC JJD1J-2241. ~. ~~fl~ 1WSuft.~G SL.i?~SECES Jl013-!.250. REV. 8. Sl'"UON UIMC( t:OOUt.:G Vl!1llR SAFE!YRS.ArrD i2. B E F G H

A B c D E F G H J 1 2 (C-12) 33013-1250-1 (H-9) < 33013-1908-3 1 " I Ill I I ~ 21/2" [_ ,rn rnj'8 oz r r;; 1(g z'F ~!8 f'1 1Ul 10 gi 11'1 (/) Ill f'1 )>

<: IUJ I'.) fl1 1f'T1

'-~ liii N z I I 21/2-S~ O> N (1-10) 33013-1250-1 D-9 33013-1251-2 1 v ~r.i N 0 0 " 16-SW-125-1 4614 ~ 4664 ~ <f 8" 3Ql_\\ .1~ t-91-'---1 "' NOTE 7 47990 1--s-1 4642 [ill 0~~ t;,~ ~ Q § 1* 47~~T l__ U)1z SJ 1' Pi < ;u o* f'1 OJ 'r tll1 0 r\\"'

o.

2 3 NOTE 7 3/4" C----19--Q-j D 12500K 4 D 5 4" l 12540 3" CONTAINMENT 1 RECIRCULATION 153 C 'i FAN D COOLERS TC 4 3 8" ~ D E-'-J~-'4'-"---'j I ~---'4~ I I P312 ...LJ 8" 4" 12542 3" 6" °' ~ lii ' D 4649 T1 Pl 2148 c Ill ~~ 1: \\o/ s ~ t~ co l I I I I I I P--t---------1---. I 2 1/2" SCI03A AIR CONDITIONING WATER CHILLER A 2 1/2" 6 I I ~--~<<i I .-:!;;~_,1, TE 6876 I 4794K I~ ~ 10 q I !)l I 'ii' I I 2*U 2" ---+' Pi09 !,- NOTE! ~ e! 6 ~ {)) 2" Cl ~-=c.J P201 I I E <O w D 2147 4519 2054 TUBING;Jg-1 301 7 4655 TIA 2010 § '1~~ ~ ~ ~ --{ c Ill D ' z " RR Pl 2000C 8" 0 ' 8 301 C-2 v 1/2" 1--=--t----M----::J v 12500R I IJl I I 9 CFRC A B c D SHAFT \\ COOLING COIL ACA10 ACA07 ACA08 ACA09 INBOARD END OF MOTOR " I I MzCJ Xtll '-0 g?Q zo 3141B 10 4580A 4582A 4584A 4586A 1¥p~I DRAIN VALVES 4580B 4580C 4582B 4582C 4584B 4584C 4586B 4586C CRFC MOTOR (TYPICAL) AIR FLOW t [:,_, c A r:*-* B 4580D 4582D 4584D 4586D I 1 1'-2" r:*-* 1 1/2" c [:,_, cw D AIR FLOW.. I.. AIR FLOW DETAIL B CFRC MOTOR COOLING COIL, DRAIN VALVE, AND FLEX JOINT CONFIGURATION (TYPICAL 4) 1 1 INBOARD FLEX JOINT SCS190 SCS192 SCS194 SCS196 OUTBOARD END OF MOTOR I D OUTBOARD FLEX JOINT SCS191 SCS193 SCS195 SCS197 12 fl ~ SAFETY CLASS SAME AS MAIN LINE ZAF~ CLASS 2,3,0R SAFETY SIGNIFICANT (Q) DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS y 2 1/2" 2 1/2" 4592B... c <O CD N z )> 0 0 4659 4659A Pl 2000G 4659B ~ 3 [QI 8" f--~---+-"'---1l....e--J1---~-1 ~ 4643 [@] 5 TIA RR 2012 NOTE 7 4660A 4660B ~ [QI I r-~----+-"'--11....e-- 11-----~ ~ TIA 2013 3/8" y.'--"-,1 i-..+:J D ~ 12502U 4644 [ill RR NOTE 7 4" C-1 0 12516C 3 4" --~ r----:J D 12516F I I I I RM-16

~~ i

,- CONTAINMENT RECIRCULATING TUBING RE 16 H A 1 FAN COOLER PROCESS MONITOR SKID ~301 N ~ <O <O N TURBINE I I 12516J 12516B _J BLDG.BSMT. N ' D f----301 /1/2" 18 CLEAN SIDE BSMT. (G-3) 33013-1893 ~ N... G) '-'-' 4" 15531 D [:'--9"-"1 12516M IB CONTROLLED SIDE BASEMENT II I (G-3) Yf{f----<< 33013-1893 [_,.,__,..,___ ~----~lx'154'6o IB CLEAN SIDE BASEMENT 1" N N I (/) N 0 0

>' D

~ VE-f--'-1 4799X (}) 4624C I N I 4 v E-1 .l.._~ \\."-! 125-1 1 125-9 4 799V '-[;:<<}--! v~ ! 301 125-1 [;~ ! 3" (H-3) 33013-1893 (1-9) 33013-1908-3 (E-12) 33013-1885-1 > 301 12~516H ~4"------trnt-E------~

E C) :;o l 4799W I

Q 3 I (B-3) .-----lf-------11-<:'----:;3~3mo~13~-~18~9~3~1 I (C-6) PC


H----12679 )----------<

.....__3_3_0_13_-_19_2_0 _ _,


Im N

(C-3) X14400 X15451 X5839F N .---j/-------f1---<..._._:3~3~0~13~-~18~9~35___j I X15452 X15461 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1250, REV.8
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTION SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. ALL SAFETY CLASS LINES ARE SEISMIC CATEGORY I.
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASE ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO INTERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
6. 2" AND 2 1 /2" SOCKET WELD FITIINGS WERE INSTALLED ON REACTOR COMPARTMENT COOLER SUPPLY LINES NEAR P201 AND P209 UNDER TE 2008-0037.

7, STAINLESS STEEL BUTIERFLY VALVES AND ASSOCIATED SPACERS INSTALLED UNDER ECP-2008-0064. CAD FILE NAME: 33013-1250,3 A CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE 4652C.---tr-~-- HOSE I C-1 1/4" -*H-:J--,.rV{-~---H~---- (F-3) PC f-----------<::::::~~~~~=:l-:;J;;,;;Q;;; 2680 33013-1920 STATION SERVICE COOLING WATER SAFETY RELATED X5839G 4" 1" 4652B 3" 4" J--"---C}-jf----------+-~--J....--..__, (SW) P&ID 4650 3 4 SCl03B AIR CONDITIONING WATER CHILLER B 5 ,,, 4520 3/ 4" TUBING~-1 6 Tl 2053 4652AI 7 JOB NO. DRAWING NO. REV. EWR 3391E 33013-1250 SHEET 3 OF 3 M CCD 01 CONTROL COPY # 8 9 10 1 1 12 A B c D E F G H J

A B c 0 E F G H J 1 -.~_ 4553 Pl 2200 1/2" PCD02A<MO/CP1A> CONDENSATE PUMP A n I 2 1" I 3 I 4 (H-3) ~------------------;: 33013 1232 ~ Pl 2201 4798K 4798L PCD02B<MO/CP1 B> CONDENSATE PUMP B AIR EJECTOR SAMPLE COOLER v rn °' 3/4" I 4798J Pl 2202 N I ~'t' -s ~ = LC! D PCD02C<MO/CP1 C> CONDENSATE PUMP C I 5 2386A 11/2" I 6 7 I 8 I 9 I 10 I 1 1 I (A 1) 10-SW-125-1 12 v X4693 ~-r::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::;::::::::::::::::::::::::::::::::::;--------t, 33013 1251 2 4682'.J~ I 10" 4675 (A-1) I 33013-1894-2 X14500S Pl 2108 3" 3" 2" 2"., 21/2" ESW04 GENERATOR AIR SIDE SEAL OIL COOLER ESW03 GENERATOR HYDROGEN SIDE SEAL OIL COOLER Pl '----1"~125-1 10" (A-1) ~----------<'1 33013-1251-2 ~ [ill 4682A ' _;;: I _Y'I. ITT DISCHARGE ~14682B 1iJ 3,, HEADER f--.---11---------1 9 2109 1 ~ ~ N 4676 Pl 2110 4677 T '------C><Jf--~----1; l;f------[;x::J---_J 4677A 46778 ATE01A GENERATOR BUS DUCT COOLER A tt A 21/2" 4674A r---125-1 4681B*JJ~ j "' ~ 4681C Pl 2107 )~ 3/4"

JD 4530A 3"

Di:-..r:. 4799K GENERATOR BUS "' ~'.l Tl "' 4674C 'f'~ DUCT COOLER B o o .p.T ~ NOTES:

1.

FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2.

REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1251, REV. 5. I r-i n I r-i ATE01B E0;3 ,,_ 9 V ~I

f---l><!-~2~1~/~2*-1 __

~_,~E~~l@--..-~---"L-';:'.~,--20~4-0-~-'.L[~;:.::}.L,iJ'--~-~_i-'-t~r*;~/_2_"-l

3.

ALL PIPING/COMPONENTS ON THIS DRAWING ARE NON-NUCLEAR SAFElY CLASS. FOR AKP03, AKP04, AKP05, SAFElY CLASS IS SHOWN FOR SERVICE WATER SIDE ONLY. I LJ D (J-11) ~ - 33013-1925 X4785 IL.. _____ _,, 1/2" N 1/2" 1-l I c--'-- Tl '-f--- 2059 1/2" 4555 T Pl 2203 1/2" 2" I LJ D 1/2" Tl '-1---j 2060 1/2"..n 4556 ., = ~ l rnj 1" Pl 2204 8 (1-2) -..rl.-1 33013 1232 X2386B 1 11/2" N LJ x5325 X47BiB 1/2" ~ J 1/2" 1-l I >--'--- )> Tl ';; 1--...J 2061 D 1/2"-"' 3/4" (C-1) 33013 1925 IA COMPRESSOR A (A-1) 33013 1925 IA COMPRESSOR C I "'j N I - Pl 2205 v 11/4" 4" 0 ' T TURB. BLDG. N g~ ~CV? 46748 4674 CONTROL BLDG. AKP05 L'* NSW06 Y 1

  • .I I
  • I i------..,...--1_,* i * - -

>----1,~ v+-,-------~-:..,... T _ __,. ~.,_ _ _, .,,.i T. 4674H (\\; 12502V °' 4674M ~,_1 ~r1 BATIERY ROOM AIR CONDITIONING 1" D UNIT D ~--------------~---~~-1:*~*1--11.1---------------~ 4674G Pl 2111 2 ro z N 125-1+1 ,4: 4684 ,,_V ~J84Aw ~*r~ o Pl 2112 i--:J (';; 7 ~ ~ 2 ro z Tl 2043 11/2" 46741: 1 1 /2" 1 1 /2" 46798 I ~ !""~ CX>ro~ G1 1 ~7 ~lO N~7-~ ~ N I - f--L~-~--------1----~----:f--l il/\\ /\\ /\\ /'J f--J:f----L-----'------~__JL_ _ __l_--1~~--~--'-~---J 4678 v

  • ~

i I v v v I io~; .4679' ~'Ir-;:::_ 4l98G EXg~~~R-gg~LER r1 AEP04 ~g~~u~~~R~61{'J ~ t. r-; Nswq1 12so ... i? _ *c~.,_,,_ L1_2_5_,oo..,sc_A_/_c UNIT 4l98E ~ 479BF ~ 301 ! i4761W 4761T~ 1 /2" 1 /2" 9 3/4" 4fas'A(Pi\\ ~ AKP03 TCV ---v-~~, ... r'_-,-4-;c:6.. :i-1v-'---.---4-1;c:61-:1 P---JN~@~8:1---4-7r..:~.l-1-Q~'---l J-i ::i*---J .._,, 7 RELAY ROOM 4l61E NOTE 6 TC rn ~4761G ~ 7 ~l.J. 9 2 ",9 ~!" ;;i0 DJ §125o2w '-4~-'D\\D T.S.C. BLDG. - I ro TCV 12505 TURB. BLDG. ~ '1 ~ 12504 .;:,*--¥---' 1/2~ N, 7 v ~ 47980 1" ()li.l. 12502x -+-- 1" 476fN '-.l ~,.;. ro ~ 4761 R AIR CONDITIONING '---li761A rr-t:_~ @ P~ U::p:4 I LOI -1>,p I l.CJ 4 6454 ~ I FLUSHING 0, TEE WITH TC rn TCV PLUG I )4761X F301 112* 112* 4---.L_-. _ _L_Y--cf-----J,ftrif---t,__,_1-r)--I~ :: 3/ 4

  • I 1"

4761J NSW09 ~18 "z 12545H 4761M 1/2" 301 £1T f 4761F 4761L 4761K ---... 1"

4. ELECT. MOTOR EIN'S FOR MECH. EQUIP.

ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

5. SPOOL PIECE WITH THREAOOLET FOR FS-2090 INSTALLED UNDER ECP-11-000174.
6.

TCV LOCATED INSIDE THE UNIT HOUSING.

7. GENERATOR EXCITER AIR COOLER SUPPLY AND RETURN PIPING REMOVABLE SPOOL PIECES HAVE VICTAULIC COUPLINGS AT EACH END.
8. TUBING MATERIAL (316 SS SWAGELOK TUBING AND FITIINGS) PER ECP-14-000770.

6" 1/2" Pl 46868 &i' 7 00

?),

,, 'L..--ll.-...J 6 1~*, -, 4686 4686F "' °' "' 0 SS (1-1) 2" h~,---------1: 33013 1251 2 125-1 SS TUBING NOTE 8 X45J7A (1-10) 11/2" - -,r--------.. 33013-1925 >--------.;._----i------, (D-6) 10-SW-125-1 tt A I 33013-1250-1 ~>--------------! ro,-1 "125 "' r 4761S RELAY ROOM NOTE 6 AIR CONDITIONING UNIT B @ JTELEPHONE EQUIPMENT! ~ (til ROOM jcrl ~ ro ATP03 ro 3". - ::J 46B6A x47a6 i._ _____ (1-1) I 33013 1250 1 DIESEL GENERATORS HEAT EXCHANGERS (E-12) I 33013 2286 1 9S37G I 10 SW 125 1 x4s 13 'L.::..::..:.;:__:_: __ x47a7 (F-1) 33013 1925 IA COMPRESSOR B I 21/2" ro ro rr 810 I~ I 12545,TC N ,1 1, (JI 01

  • 10 NSW14

(';;,-' "'I t:;> D 4i:~,+1-25{4}5iG~~"-L--t-112C5k4-15-E-l_ __ ~-:( '-'-'""'~----'-..,'/ D l 12545D 10-SW-125-1 °' 00 0, 11 /2" -SW-125-1 Tl 6450 1 1/2" (J-1) L--r---------------r-----..1.E:~".=.~:=.!.---------~~---------------------------121~0~*------<:::;:~~~~~ 10 SW 125 1 I 33013 1251 2 I. X4693 N, Pl 2208 ~ I I 4781 ~j _1c__1_2*-cf-~-:c.Lt-_s_~_-{ 3/ 4" 1----' I I N 0 - 4707 1/2" ~+--:] v 4799H N I (/) I 0 I N 1/2" ~.- 4799G 1/2" *-* Pl 2209 i--:1 8:' l 0 4-j(js v NSW04 l__J 1/2" 3/4" NSW05 PCD03A<MO/HDP1A> HEATER DRAIN TANK PUMP A C2 125-1 "'-.n I I Tl 6451 125-1 C2 w N 0 N N -,, o-0> 4709 4710 I ~ I 0 I N I I w~ ~ _ 112" ~., ~ PCD03B<M0/HDP1 B>

3 g

l!..l HEATER DRAIN g; N _U ... ~28's-'--=---1

  • ... -:l-C,.1-c ~ -

~*~ "',..,~ 1 1 TANK PUMP B 11 /2" -SW-125-1 '--------------!-------------------------~-------~ 2 I 3 I 4 I 5 I 6 1".... t--1-.c--:J D 12SOOD ~** 0 0'" r'1 D -' 7 I 8 I 9 I 10 I 1 1 /\\ AMID F£R /.ffi AOC-16-CID126 CMB W\\.\\ IL ~./11 P., w H~ 2/17/16 Z/1(\\1i. <.119//t. t}1qf1£. CAD FILE NAME: 33013-1251,1 CONSTRUCTION LIMITED CONSTRUCTION: /JS NOTED PRa.JMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 7 lft/16 /JS-BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE STATION SERVICE COOLING WATER NON-SAFElY RELATED (SW) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1251 SHEET 1 OF 2 CCD 01 CONTROL COPY # I 12 REV. A B c 0 E F G H J

A B c D E F G H J 1 (A-12) 33013-1251-1 (A-11) 33013-1251-1 DISCHARGE HEADER (B-3) 33013-1895 X15303'--.::..::_::.c_:c_:.::..::_=-_,-- (B-3) 33013-1895 X15302 '-------~ 0 I Ul I I 2 3/4" VINYL TUBING 1 /2"15=3'---<-+-_J 4719 3140K TSW03 ~ SW BACKEND BIO-BOX 3/4"PVC 1 2" PSW04 SAMPLE 2.. PUMP 1/4" 0 G) 3140E "' ~ 3140A ~ 4795C 11/2" 4696 1/4" XIT-5400 CHLORINE MONITOR l/P 4538 0 0 'l 3 ~125-1 Tl 2047 10-SW-125-1 4---,:J 4600A 4 (B-1) 2" 33013-2711-1 1/2"-153 TSW02 SW FRONT END f.¥/4" BIO-BOX I PVC 2131D 2131 t 125-1 4721A 1'! ~ N I N ~. 6" n~ ~ Pl 1" '] v <O 2124 ~--------~---- 125-1 301 11/2" 2" 4694B 4723 1" 125-1---l 4723B 4723A lbQJ 1 1 2" 3/4" 1" 4724 125~ 2" I 6" 2" 5 6" v ESW05A TURBINE LUBE OIL COOLER A __/ 3/4" I 1'! L-W--':J D 4692A i ~,3_/_4...

  • -::J v

~ 4690A ESW05B TURBINE LUBE OIL COOLER B --.,-/ 3/4" l ~ c_46*9M-1 A-::J D 3/4" ~-~4597 EEH01A EH CONTROL SYSTEM OIL COOLER A '---_J SEE NOTE 4 '---_J --~ SEE NOTE 4 ~-- EEH01B EH CONTROL SYSTEM OIL COOLER B 3/4" 4698 Pl 2121 8; <O 6 4539A 4539 TUBING 125-1 -I... c )>~ z G) Pl 2125 N * ~-----------------;!rl


<tx::Jr-----11!r---~-=-'---'

4700A N

  • 2" 125-1 SS TUBING NOTE 5 v

v rn... rn 4704 (F-12) o ~ 1t5~: I 4726 Pl 4726A ~ 2" -SS TUBING NOTE 5 zoo ow 0 - '-----!~ 0 - ~ Ol 1" 2" 4703A 11/2" 3/4"

JD

)> L3~3~0~13~-~1~2~5~1-~1~.::r----:---~-.;-1?:;;.--'--"----~:,---'-------11~-----Jf-8--1r---~~ 4537A 4701 NSW12 §1-1 oc "' ;u

u ~

G) '"' gi~ 0 0 6L __ 1 N I 2" v ~ 11" y 4725 125-,.___j 4703 0 ~ (1-10) EH q < 33013-1885-1 ~ - 125-1 SS TUBING NOTE 5 ~ 3,, --14~7~0*6--=----~ (G-3) 125-9 125-1 [~~~~~~~:::::::::____:_1~/~2:.J" v.::::__ 33013-1882 ... 'T' "' X7469 (H-12) ~ 33013-1251-1 X4680 1 2 3 0 'l 1" 4720 Pl 2130 rn... N * "' 1/2" TW '-H--V 2051 ,., 4720A 11/2" 11/2" 10-SW-125-1 4 EFW02B FEEDWATER PUMP B LUBE OIL COOLER EFW02A FEEOWATER PUMP A LUBE OIL COOLER ESW07 CNMT. AIR TEST AFTERCOOLER 5 11/2" 0 N 3" A 1" 3/4" .---*--j

J D 4704A NSW11 8;

<O 4705 6 (C-1) 33013-2711-1 2" Pl 2127 N

  • 4702 7

2" 4687 6" 4690 6" 4689 2" v ~ ' ~ 0 N [!!::,,_ ~ = 7 SS TUBING 125-1 NOTE 5 3" 0 I I N I 0 * ~ ~1 D 8 9

'!! 1"'

CJ r G) CJ . i (H-1) 33013-1250-3 _J X4614 2 1/2-SW-125-1 2" (E-1) 33013 1990 1 1"-125-1 3/4"-301 . I. N

  • X5187 1"

1----t><'.l--'---I 1-----'--W-::J D 4799N 2130 11/2" (A-11) 33013-1921 4799 VACUUM PRIMING PUMPS 8 9 10 10 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1251, REV. 5.
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. EEH01A HAS 503 OF ITS TUBES PLUGGED PER MDCN 3436.

EEHO 1 B HAS 503 OF ITS TUBES PLUGGED PER MDCN 3619. A 5. TUBING MATERIAL (316 SS SWAGELOK TUBING AND FITTINGS) PER ECP-14-000770. 1 1 REVISED PER A -1s-oooa35 [!!::,,_ CAD FlLE NAME GMB 10/30/1 33013-1251,2 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES I 1'S BUILT DATE RELEASED FOR ~ GINNA STA. R.E. GINNA STATION SCALE NONE STATION SERVICE COOLING WATER NON-SAFETY RELATED (SW) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1251 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 I I [~~(A~-~ 3~)~==:>,_21~0~H~D~6~~=; x'41391 33013 1924 10" (G-1) 2 24" MANWAY I 3 KMS01A LP TURBINE A ECD06A MAIN CONDENSER A I x - U>' (]> 'i'.' -~ 0 -~ I (Xl 00 <O ~ I II l/P 4025 4 "' ~ I I co co <D ~ I I NOTE 5 -JVVf ~. 7 U> 0 II II I 0 D t-1.-C--, 9512D II 5 I 12-CD-300-1 SCH.SO 6" 0 ~ G) CA I I 0 <D ~ 0 U> NW~ <O U> 0 ro r'l ' 9591F 6 I I I I I I 8" 4" 7 II 3958 0 ~ 0 u I I 0 <D ~ 0 U> 1 I 300-1 8 0 1'

c 0

I 600-2 g) -~ 0 I m 0 0 I g I (Xl I 0 - );' I I '° - ~ <D -}VVf NOTE 5 0 I 0 0 I m 0 0 I 9 12" 95098 SP-863 20-CD-150-1 I 14" KMS01B LP TURBINE B ECD06B MAIN CONDENSER B 10 I 1 1 f 6-BD-150-2 (H-7) ~-~-~----.,. 1---* ..... 1-~L-<, 33013-1277-2 5744C S/G SLOWDOWN FLASH 24" MANWAY TANK DRAIN 3-CD-150-1 3-CD-150-1 3-CD-150-1 8" 6" X5744B I 12 ~ 6" I I I I ~1T 1-1/-,," -<~CA~-1~0) ~* -:J 6' 33013 1896 I X15433 ~ X6838 l/P 2006A (B-1) I I I I I f-- 1 I 43~. T 3/4" I '-r--f"><l---1 ' I ~. 4'_341A 1" - v ~ 4201 300-! 1 .TUBING 1/2"

J TC 11042 1;2*

1.. .---:J TC f-'--f:x:1'_J 11045 4203 300-1 TUBING 42\\).5 1" \\ *

J D 9512E 3/4"
J v 9534G E-rn (H-1)

~--'---"--~, - - L_ __ -< 33013-1921 '--------'1x321s 1 ~"1;7 U>o (J-1) 6-CD-150-1 __.,t---~1~/4~*---'--f~ I_ I I '-I"" - 33013 1232 '-----------! ------'1"-/_._4" __ _:_1-!C}- ( LI \\ ~~ ~


{jt'--'-1-------------------'-------~

L-cJ-1/4" I ~001 g 6" <O U> 0 00 rn I I ~ I ~ 10" 21 /2"

  • 11 /2" 1

LT 2006 v 4208 4204 4206 LG 2016 ~* T 11 '2"

  • 3/4" I

3/4" g I 15 ~ I s" r-,}---1.t><:t-=2_" -1 ,----v 4336A 1" .,.... :J 11;2* I f 0 I v I 4202 3/4" 1---'="'---=-'--...c+-----J~TC

33013-2711-2 I

I~ ~~ ~ ~, 3/4" 300-1 1-3-'-/_4_-_30_0_-_1 _ __L__:J I 434~ 20.. i.L '----___ _.1H......... ID 14.. 4207 I I I I 4:z1ii 11041 11/2" ~ DC:--..-- 300-1 TUBING ) TC~~ n 2051 4336E r---;--...,---------'~----:-;===I 1 1 1 4336J ____,_, I IL __ 4:2~*=- 1-1-14* __ -- 1_ .. _ -- 1: ""; __ 1:_ 1" 11/4"

    • ,,--"'-'CB:...-_;1..<.) __

1/2" ~-.=:iv 4336L ro I 20-CD-150-1 ...L ...L ~~--1 .. ><~"H1 33013-2711-2 4215 x6s39 1/2" vc-...- q 4336K L 12-CD-300-1 n 2052 ____ U I 20"-CD-150-1 28-CD-150-1 11/4" !:e---------11~/_2_" _________ ~----------------------- ' 1/2" ~ :J D 3900A "' I I 36-CD-150-1 4336C ...., 1/2" '----ti-.---:J D 3901A TUBING 150-1 (A-9) I I 33013 1905 ~ -~ L___ GLAND SEALING WATER 1" 1 /2" D~.--->; 3902A 150- -~1-+--~TU~BING I (J-1) I I I x'6a41 43368 L-,,,-~-~-,.....120" 1.. (B-10 l.!..I ,_;.;;.;;~~_JI IL__!='==l . --r::* ><1*-----11 I - 1 I --~-- .. --i~ ~ 4214 I 33013-2711-2 20" 1 1/ 4" - 4212 (B-10) 33013 2711 2 X6s4o (D-1) 1/2",.--L-.~---.... 33013-2286 -x9s16r SP-5291 SP-863 (.()

.... ~ J v

~ ~ 9512J g !(b-..,-11 --~~I: 3726A~ 1/4"~~.1~1 33013 1234 X4045 I Xl SP-863 (A-1) 18"

  • ~

.--~~~~;-~~~~-,.~~,,_._~___,: 33013-1911-1 0 0 I c rn z G) ~ 1/4" ~ TUBIN~.rr:~-1~~---1cJ 1" U> 0 I (f) §0 ~I 2" -- 4216 112 300 1 DC:--...; ~..; 3914 1/2"

l ----
!

Pl 2037 3903A :JV n I I 2" I,,______, i--..4-" . ~ 3903 L_1 /2" 'T' 1" I 0 0 I (]> 0 I 0 0 I 21/2" 1/2" 4312 U> 0 I (f) 80 '° I 2" Di:* ' 3915 g ~ I <D t -"',. ~ v ~* ~.., 1,/2" 2"

  • '~

3904 1(2" 4218

  • ':iv n 3904A I I

f--,-~J v 14" ~ '....__f--- 1/2" 3918 v 42238 I I 1..:::11, '-r-,,-~J4=>-... N (...I ~~~ ~¢_',~@ I 1" Pl 2948 l!J "'?: ~ PCD02B(MO/CP1 B) D ' Q;l CONDENSATE i5 PUMP B I 0 0 I 0 0 I 1" 0 0 I 21/2" ....__ 1/2" 4313 t* 3721 U> 0 I ~O I 2" 1_/2n 2" 2". ~ DE-1.... ~11----+...---4.i.'41~1---'----1, I' 3916 1/2" 4220 3905 _1--*....:iv n

== 3905A I I Pl '---~J 11H 1116" 14".I. I L---1 I I..::: II L ~LJ.... "' "' 1/2" 3919 ~*"

  • t
  • 1~ " '.;,;, '

ot.1~ D -t>-_.1~ D

  • ., 4=>-

-1 c "' c PCD02C(MO/CP1 C) rn 'o CONDENSATE i\\'5 0 ~I 0.!.L_I <D 0 0 I 0 0 I I I I I I I I I ~ 112" I 12" (Xl ""--N~~ 4314 L . t (f) 0 0 3" I ~~ i~-76.. MIXED RESIN VESSEL (F-7) 300-1 JUBING 1/2" l--'---41:2><2::::61+-----------1, 33013-2251-4 ~ (A-1) X67IB 300-1 I TUBING 1/2" 'I' 4225 4225A 3" -. - 4086 2" 3924 2" .---~--i: 33013-1905 PT 2014 I-I "' 61 I g[ I -r I I 3959S ~~ v GLAND SEALING WATER (B-3) 33013 1236 1 I NPSH (PFW01A) (1-3) 33013 123s 1 I NPSH (PFW01 B) (A-4) 33013-1236-1 I PS 2010 (1-3) 33013-1236-1 I PS 2011 (E-1) ~-~-~--., - 33013-1896 '------__JX76o1o NOTES:

1. FOR GENERAL NOTES SEE DWG. 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-543.
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. ELECT. MOTOR EIN'S FOR MECH.

EQUIP. ARE DEPICTED IN BRACKETS ADJACENT TO MECH. EQUIP. PER SFEWR 10328.

5. FLEXIBLE PIPING CONNECTION CAD FILE NAME 33013-1252,1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATI' RELEASED FOR ENGR.

D (.,.! -- N ~£ 2949 ~ 0,_-_ _J~,. -{8--cJ.-6....,---., 6 PUMP C 0 I I I ll~. I I~I g*.--~(~IH_-~7~)-~ GINNA STA. R.E. GINNA STATION 1 I 2 I Pl 2040 3 SCD18 PS 11036 2055 14" I 4 18-CD-300-1 I 5 Pl 2041 I 6 7 I Pl 2042 NONE CONDENSATE P & ID ..e-f-,--J ..e-33013-1233 & 13501't:: T"', 3959 3502 HEATER DRAIN /;; 4 ~ FO PUMP DISCH. )> t.1 ; D JOB NO. DRAWING NO. REV. EWR 3391E 33013-1252 (E-11) 1" - 1" I L'..--l.,"><_'.l----'---1, 33013 1238 4084 ~. x9661 CCD 01 CONTROL COPY # 8 1 9 I 10 I 1 1 I 12 A B 1--- c D E F G H J

A B c 0 E F G H J 1 (B-3) 33013-1990-2 36" x BIRD _/ J '-----. SCREEN r OUTSIDE AIR 2 3 PROBE LOCATED IN THE TSC MECHANICAL EQUIPMENT ROOM FOR TSC A P. OPEN END FT 5262 4 5 AEP02 TSC TRANE A/C SUPPLY AIR UNIT NOTE 9 AED02 \\ Q !ADI M AEA01 \\ AEA02 6 7 TT 5264 8 SMOKE DETECTOR DSD S33DA F YARD v.,-----,SCS161--1~--1 i SCS161-2------i >-+--) TSC NORTH 1------l p l E N u M ) TSCMR60 36" x 66" EXHAUST TO OUTDOORS 9907V 9906W -i> CD ' x ~ ' WALL Iii g~ <O )> 8 m AEU01 (Tc\\________rfH ~ L!6J AED33 I I@ TC 5266 l00IS L Iii 1' 1' -i> ---~LJ AEP07 SAS/PPCS A/C UNIT A CONDENSING Iii UNIT Tj ~ 28" x 28" RAIN HOOD 9907S 9906R <O 0 " oo AED18 AEF01 AEP01 TECHNICAL SUPPORT CENTER CHARCOAL FILTER SYSTEM MECHANICAL EQUIPMENT ROOM F <O <O 0 " 9907F f"'l 120" x 74" OUTSIDE _ A___ AIR -y~ (C-6) AER01A -i:><t-i 33013-1897-1 X15728 10" x 10" --0--- TSCMR165 o I lcolg Iii 1' 1' "' ~LJ 28" x 28" RAIN HOOD <O <O 0 Ol <O <O 0 9907U 9906L TSCMR90 F ___£ AEP08 {~Qm*, SAS/PPCS A/C UNIT B CONDENSING UNIT COMMON PLENUM RETURN 9907T 9906 0 Tj -i> o- <O zl N Zr~ SCS165 AEZ01 SPARE A~ REFRIGERANT C_J COMPRESSOR AEP03 TSC TRANE A/C CONDENSING UNIT AEF03 36" x 66" TO OUTSIDE l6QI ) SCS167 RECEIVER AET05 <O <O 0 " 0 )> f"'l 0 Ol m m E-~--~-----+-------------~ i8\\ ' ' I l 8"¢ (TYP) ADMINISTRATIVE OFFICE AEP04 ADMINISTRATIVE COMPUTER ROOM A/C UNIT AEA05 AEM03 AEF04 Lr-;;;';;=;;'oo 9906S L---'=4 AEA09

o RECEIVER 9906M AET03

'--'='-l AEA08 ROOF -Hf--- ROOF COMPRESSOR AND CONDENSER AEL07 AEA04 24"X24" :J UNDERFLOOR (TYP.8 PLACES) ADMINISTRATIVE COMPUTER ROOM r+----~R.OOF _ 29"X70" 9906Pl--Y'--- E I r--~~~~~-~~-~-~~---~ 24"X24" l29"X70" [ =i==ll_ (TYP.10 1---Y'--- ) I PLACES) E9906Z I DX DX E I 9906U:J AEL08 AEA 10 AEA 11 AEMO 1 AEF06 AEP06 SAS/PPCS A/C 9906Y 9906T 9906N c___ __ UNIT A --- ROOF INTAKE t~ CD ,,I. ~~Tl ROOF FAN EXHAUST £1~ I I I F CORRIDOR TSCl21 ROOF INTAKE t~ ___ SAS/PPCS COMPUTER ROO_M __ ROOF FAN EXHAUST (1-8) IN 33013-1894-1 I~ X15013S'-------' ROOF INTAKE -i> ' x 0 AEA07 AEA06 AEM02 AEP05 SAS/PPCS A/C UNIT B ) AEF05 16" x 16" I I 16" x 16" l--t--4,..---1 F 16" x 16" F 12" x 12" --0-- TSCl13 116" x 16" 14" X 14" F -- 1-*--l 8 1-----l TSCD24 1-- A --0-- 16.. V.fC. 8 l------l"<'F_-114" X 14" ~: L J TSCl12AE~ A TIER"._ ROOM Q UPS 14"X14" TSC DIESEL GEN. RM. 1 (Tc\\_ ~ 2 f---<t-F ___, !:H/ -..,__,-' TSCl1 AED29 AEF29 3 CORRIDOR HEATING 4 _J A DIESEL GENERATOR -ENGINE COOLING FAN EXHAUST AIR 5 l9907M I 'I 24"X24" (TYP.8 PLACES) 9907L NOTES:

1. FOR GENERAL NOTES, SEE DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DRAWING D-381-432
3. VALVE POSITIONS AT THIS TIME DO NOT REFLECT ALIGNMENT FOR ANY MODE OF OPER-ATION; THEY ARE SHOWN ONLY TO REPRESENT THE SYSTEM AS-BUILT CONFIGURATION.
4. EXCEPT WHERE OTHERWISE INDICATED, COMPONENTS, PIPING, AND DUCTWORK ON THIS DRAWING ARE NON-NUCLEAR SAFETY CLASS.
5. THE TSC HVAC SYSTEM OPERATES ON ONE OF TWO NORMAL MODES DETAILED ON THIS DRAWING:

A) NORMAL BUILDING USE WITH COOLING. B) NORMAL BUILDING USE WITH HEATING.

6. THE EMERGENCY MODE OF OPERATION IS ACTIVATED WHEN THE WALL-MOUNTED EMERGENCY /NORMAL SWITCH IS MOVED TO THE EMERGENCY POSITION.
7. AEV05 AND AEV08 ARE NORMALLY CLOSED AND OPERATE AUTOMATICALLY IF THE COMPUTER ROOM SPACE TEMPERATURE RISES ABOVE 78T.

Q l 37" X 1" (TYP) L

8. INTERFACE WITH SAS/PPCS HALON SYSTEM (SEE DWG. 33013-2350).

ISOLATE THE SAS/PPCS COMPUTER ROOM BY CLOSING DAMPERS AES15, AED45, (THROUGH AEV05), AND AED48 (THROUGH AEV08) AFTER ALARM BY ONE SMOKE DETECTOR. AIR CONDITIONING UNITS AEP05 AND AEP06 WILL ALSO SHUT DOWN IN ORDER TO MINIMIZE AIR CIRCULATION. REFER TO EWR 4378 FOR MORE INFORMATION.

9. REFER TO THE PROPOSED OPERATING DESCRIPTION FROM EWR 4075 FOR FURTHER DETAILS ON THE HVAC SYSTEM.
10. THE INTEGRITY OF THE PRESSURE BOUNDARY FOR AEP02 IS SAFETY SIGNIFICANT CLASS, HOWEVER THE COOLING AND HEATING COILS AEA01 AND AEA02 ARE NON-NUCLEAR SAFETY RELATED.
11. WALL MOUNTED THERMOSTAT WHICH IS ADJACENT TO TC 5246 AND INTERFACES ELECTRICALLY WITH THE DOC CONTROL SYSTEM.

6 7 AEA15 H KITCHEN 8 AED52 Q 9 47" X 1" (TYP) NRC SECRETARY 10 Q 36" x 10" AED53 COMPUTER ROOM UNDER FLOOR w AEV08 COMPUTER DISPLAY AREA r.1 AED63 AED62 r:--..~--.~--.,..-.-'L--~~~~......... ~~'J Q )> f"'l 0 " 0 II ii I Iii 0 Ol ID )> f"'l 0 m CD )> f"'l 0 Ol " Iii 0 Ol Ol 47" X 1" (TYP) DATA DISPLAY AREA TC 5242 AED74 47" x 1" WESTINGHOUSE OFFICE II II AED84 ~------+- II "f:i II Iii 0 0 CD 0 "~ ) ~ I ~ I MEN'S LAVATORY 1fl ~ I WOMEN'S LAVATORY )> f"'l 0 m j E AEA14 TC 5244 )> f"'l 0 m AEV01 AED41 AED44 AED90 f ... H ~ AED91 Iii r_J--;===:'..-~w' l------'li---11 -~- ~, l ' 11----A-E.:.Dti,.9-2-ll g I AED93 8 'I L!J <O 0 x 1 1 12 24" x 48" ~HH-AES15 !Ha )> f"'l 0 -i> Ol (Tc\\ SEE ~ NOTE 11 47" X 1" (TYP) DATA DISPLAY AREA s FV37 Q TC 5247 AED47 j AED71 47" x 1" E w AED72 NRC OFFICE LOCAL PANEL OPEN END /ii LOCAL PANEL IS LOCATED o IN TSC MECHANICAL t, EQUIPMENT ROOM. i 47" X 1" (TYP) DATA DISPLAY AREA Q AED42 AED87 AEDBB 1---------j - w AED89 CAD FILE NAME: 33013-1256 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES /-? AS BUILT DATE RELEASED FOR ENGR. s ~ I '~ GINNA STA. R.E. GINNA STATION 9 SCS168 Fl6Qj TSCD19 I I AEF08 SCS169 OPERATIONAL L SUPPORT~ CENTER F SAS192 12" x 14" -~-THROUGH TSC DIESEL GENERATOR ROOM TO GOOSENECK EXHAUST ON ROOF 10 1 1 SCALE NONE TECHNICAL SUPPORT CENTER JOB NO. EWR 3391E HVAC P & ID DRAWING NO. 33013-1256 CCD 01 CONTROL COPY # 12 REV. A B c 0 E F G H J

A B c D E F G H I J VI O> 1 v r:---1..... 1-+----111M--, 577 549C 2 3 4 4-RC-2501 4-RC-2501 4-RC-2501 3-RC-2501 3 fj' H 01 537 577B 2~01 ~ 12240 v E---i~-~t-11--1... ~*----.,,, 577A~i~536 at $ t~ 12237 12425 L!J 3/8" SRC14 l ~ CONDENSING e 1; '~u 01 ~ 3 L!J D 3 4" 533 3/4" 510 3/4" 3 4" TRC01 PRESSURIZER I N ------ ~ M~NIFOLDI ~ r N N I I N ~ 2505 2501 I (N. N I I (...I I ~ ~ I I ~ ~I "' I ' I I I f-----1-J-----I I I f-----l*~J-----1 I I I 12231B I I L ______ _J L 12232B X952 X297 (D-6) 33013-1278-1 (H-4) 33013-1260 REACTOR COOLANT LOOP 8 HOT LEG (C-10) 33013-1265-1 (C-6) (SCH.140) 10-RC-25017 _J 3/4-RC-2501 2-RC-2501 PRESSURIZER SURGE LINE ~ 33013-1888 >~-------Hu~---------~u-------- x1'5J531~----- (D-6) l~33~0~1~3~-~1~8~88~_;.>---/f--j X15155 (H-6) 33013-1260 REACTOR COOLANT LOOP A COLD LEG (C-6) 3-RC-2501 ---t><H 33013-1888 >>------l.#f----------J'f----------,,11-~ - X15154 (E-6) 33013-1888 X15156 (D-4) 33013-1260 REACTOR COOLANT LOOP B COLD LEG 1 2 01~

<
: I ro ro 3-RC-2501 3

01 SRC13 CONDENSING POT 01 ~ 01 01 511A G I N I VI I ~ 71 N I ~I ~1 VI ID I f-----1-J-----I I I 12233B I L 3/8-RC-2501 3/8-RC-2501 4 _J 518 RR IMB 517 RR IMB 431A IMS [9 4318 IMB [ill 5 LOOP SEAL VI 00 G ------ --;;-i I N ~ I I VI (;J I I ~ ~ I I f-----1-J-----I o I 12234B I L ------ _J 441A 441B 6 G I N I VI I ~ N I ;<:: /\\.) '.-..)> VI 1 ::;! Z 01 ' " 'Tl r .:...,..o f-----1-J-----I

5 I

L _J 12235B (D-3) 33013-1890 X14286S'-------_,.- WD-2505 (F-10) 33013-2280 X1600E (D-4) 33013-1274 Xl 662.__ _____ _,.- (C-3) Xl~ 33013-1890 > VI I

u 0

I 01 441 7 ~

u 0

I 01 ~ H 3/4" 8 v I (E-6) I


'~----f-~~-----...~.-c><f-L __

~ 33013-1278-1 / VI " ~

u 0

I 01 547 A ~ C-2 151 3-RC-2501 3-RC-2501 4-RC-2501 43~ l[Q] 1 43~C [9 1 Q X950 (G-11) I I 2501 L __ 33013-1887 X14145S (E-10) 33013-1272-1 VENT HEADER rn !<f 2: TUBING l..J ~ RC-2505 Tl P120 TC i:'---1_.----. 495 3/4-RC-151 .---1..._ t---_.-4----'::J TC -l c z G) 01 9 10 1 1 12 6-RC-602

s2-RC-602

=/?EE NOTE 9 __ JNOTE 8 L-t.... --...oe------i"' 513 563 -~>---602 H 2501 I ;; <!F _ ~ 3/4" 514 5641 <119> 2* 527 l[Q] 151 v .j> I

u 0

I O> 3/4-RC-151 538 <fl9> .j> 12" 3/~ TC 545 -l c z G) 01 (C-10) --!hi-'---<< 33013-1263 00 I

u 0

I O> 3-RC-602 (G-10) --,ff-~----<< 33013-1263 6-RC-602 3/4' 3/4" OMB IMB O> O> E 3-RC-601 01 VI -l c z G) 3-RC-601 1-RC-601 01 00 I

u 0

VI I (A-12) 33013-1264 (B-4) 33013-1265-1 (H-10) 33013-1262-2 ~ (H-8) ~B ~ SAFETY CLASS SAME AS MAIN LINE \\__SAFEIY CLASS 2, 3, OR SAFElY SIGNIFICANT (Q) DETAIL-A 1YP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS ~


iv---<'°-:;;~~;;--i~~~~

0 33013-1887 I 01 (A-1) A B c D E 3/4" 3/4" TUBI~ r:----1 (E-9) T1 ~ I 2-CH-151 I ~~ ~ 5671 576 ~~ 2" 151 3/4" 33013-1260 550B 5 33013-1269 RMW PUMP DISCHARGE I 508 VI I iITJ[g ~ ! ~ I I


~--~

(G-11) 33013-1887 X14146S'---------- TUBING PRC01A SEE NOTE 4 <MO/RCP1A> REACTOR COOLANT PUMP A 6 TUBING SEE NOTE 4 3/4" 7 PRC01B <MO/RCPlB> REACTOR COOLANT PUMP B 151 8 L!J D (G-10) 33013-1272-1 REACTOR COOLANT DRAIN TANK 2-RC-151 \\_ 531 IMB 2-RC-151 3/4" 2" 9 1709A 526 IMS [ill 3 4* 3/4" SRC52 TRC02 PRESSURIZER RELIEF TANK 01 (H-1) r---U--<"~3~3~0~1~3-~18~8~7'.___j I X14139S F 3/4" 550A s (I-8) 33013-1260 ~ ,-------~ (D-4) NOTES:

1. FOR GENERAL NOTES, SEE DWG.:33013-2241.
2. THIS DRAWING SUPERSEDES DWG:33013-424.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. SEAL PURGE WATER LINE FOR FLUSHING #3 SEALS (DISCHARGES INTO #3 SEAL ASSEMBLY WHEN UTILIZED).
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
6. PRESSURIZER HEATERS' EIN'S:

EHTRRC01A EHTRRC01B EHTRRC02A EHTRRC02B G

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-H MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
8. LOOP SEAL INSULATION FOR SAFETY VALVES 434 AND 435 IS SS CLASS AND SEISMIC

--.,,.H---<< 33013-1888 ~ CATEGORY 1. X14103S

9. RCS VACUUM REFILL PUMP (CRC01) IS CONNECTED AT THIS FITTING WHEN USED.

10 11 CAD FILE NAME: 3P125801 CONSTRUCTION llMITED CONSTRUCTION: AS NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCJ\\1.£ NONE JOB NO. EWR 3391E REACTOR COOLANT PRESSURIZER (RC) P&ID DRAWING NO. 33013-1258 CCD 01 CONTROL COPY # 12 REV. I J

<~~:!*~~I ~-*-** ~-i><J-X1:l101

A B c D E F G H J X550B [Jl 0 1 2 (F-11) 3/4" 33013-1258 >-'3':.l.-4'--..:..R:.::Cc_-...:.1..::c5_:_1 --.-1.... 1--::J D L_ _____ RMW PUMP DISCHARGE 2" 2" LRC03 v 1" 1 * [Jl [Jl 00 rn 151 v 556A [Jl 0 [Jl rn 0J I

u 0

I [Jl SEE NOTE 10 PRC01B <MO/RCP1B> REACTOR COOLANT PUMP B NOTES 6 & 7 3 (VIEWED 4 (B-10) 33013-1272-1 R.C.DRAIN TANK 27.5"1.D.-RC-2501 5 3-RC-151 ---i c rn z G) 2" IMS OMB 0J 'ro-1

u 0

I [Jl 0 [Jl 523 524 541 503 7 8 2" 2-RC-2501 2" (C-12) 33013-1264 EXCESS LETDOWN X310 HEAT EXCHANGER (1-8) 33013-1888 X14131S (VIEWED OUTSIDE OF LOOP) I 29" l.D.-RC-2501 6 ()1 ()1 tO SEE NOTE 4 (VIEWED INSIJE OF LOOP) (H-1) ,,,-----------, 3-RC-2501 (VIEWED INSIDE OF LOOP) 10-RC-2501 (C-6) X14143S (C-10) 33013-1272-1 R.C.DRAIN TANK (C-10) 33013-1272-1 R.C.DRAIN TANK 1-11 33013-1887 (E-12) 33013-1264 REGENERATIVE HEAT EXCHANGER 1 -~-2-RC-2501 1~501 \\ 540 507 427 ITllFOI ~ ~ 2 506C ~ Tj I 01~ rj~ 0 0J .~ 11435B 0J [Jl ~+-----! L __ T~ _ _J 2501 TUBING 3/8" 2501 TUBING ~ Tj I 01~ r,~ 0 8"1~ 114~ D 11440B 0 I L __ T ___ _J 114~ D 0 ;u 0 ~ 2501 TUBING ~

u

'U 'ii fT1 0J ~

  • 0 l ;u 0

I N ()1 0 EMS01B STEAM GEN. B 3 -i:><t--<. 33013-1258 X431B PRZR SPRAY D-10 10-RC-2 01 33013-1262-2 X86 7 A '-----:S::-:A-=F=ETY=-=-""'1N'""JE=:C:=Tc-:IOc:-N. X721 PUMP DISCHARGE & ACCUMULATOR TANK 1-1 33013-1247 RH (B-10) --t::><.t-J 33013-1265-1 X295 eves CHARGING (H-1) 33013-1247 RHR 33013-1247 RHR (B-6) SCH.140 2-RC-2501 853A TC 3 4-RC-2501 33013-1278-1 X954 NUCLEAR SAMPLING E-1 33013-1262-2 X877A SAFETY INJECTION PUMP DISCHARGE X393 A-10 33013-1265-1 eves CHARGING E-1 33013-1258 PRESSURIZER SURGE LINE 2-RC-2501 2-RC-2501 1 -RC-2501 (SCH.140) OUTER INNER LEAKOFF

-\\

/ 3/8-RC-2505 \\ LEAKOFF 3/8-RC-2505 4-RC-2501 0J I

u 0

I [Jl 0 [Jl 0 tO rn [Jl 0 L __ _J


1-- REACTOR SHROUD z (/) VESSEL

~f:i RRC01 X431A ~ [Jl 0 0 G-1 fT1 33013-1258 PRZR SPRAY (F-1) 33013-1265-1 X383A eves CHARGING H-11 3-RC-2501 I (f) I "i5 10 ,§ I I I SCH. 140 r-3_3_0_1_3 ___ 1_2-78---1-..._ '>-~"'--/'- 2-RC-2501 SAMPLE ROOM (G-1) 33013-1247 RESIDUAL HEAT REMOVAL 1-11 33013-1262-2 SAFETY INJECTION PUMP DISCHARGE 2501 TUBING ~ v I I 3/4-RC-2501 LRCOS,I ~ '-C:s:::t--=-'---'-'-"--='-"-'---j I SEAL CHAMBER SEE NOTE 1~~ TRC06 1 2 NOTE 6 I J500B t SEE !LOI NOTE 15 MANIFOLD 1~ 11445L 1~ I~ I 6 596 33013-1262-2 SAFETY INJ. 10-RC-2501 SCH.140 (VIEWED INSIDE LOOP) 29" l.D.-RC-2501 I (VIEWED OUTSIDE OF LOOP) 4 X867B ~ <ill> Jil~! 590 592 592A LRC0 1 [fil [fQ] !J;Q] ~1"~ - Jil~I,~ 591 593 593A LRC02 _ i!5 1 [ill [E9 ~~ ~~ 2 J1E: _ _r-g.._ NOTES 12 r ~Lii AND 14 TC 5 PUMPS 6 7 27.5" l.D.-RC-2501 I (TE\\ ~ (VIEWED OUTSIDE LOOP) (F-11) 33013-1258 X550A '--------- RMW PUMP DISCHARGE (A-10) 33013-1272-1 R.C.DRAIN TANK 8 OMB 551 9 EMS01A STEAM GEN.A TUBING 2501 )>I ~I ~I I I )>I Z1 ~I o, 11441B 11442B ~D 114420 11443D NOTE 6 OMB 552 tO 2-RC-151 9 o-rn rn o-OJ OJ (1-4) 33013-2278 10 0 ;u 0 (/) (/) ~ fT1

u

'U 'ii fTl 0J ~ !='

u 0

I ()1 0 2* X11585 10 SEE NOTE 10 SEE NOTE 4 3 4-RC-151 1 1 12 NOTES:

1. FOR GENERAL NOTES, REFER TO DRAWING: 33013-2241.
2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-424.
3. LINE CLASS 2505, EXCEPTION TO SPEC.: 1" O.D. TUBE X

.220" MIN.WALL; MATERIAL IS A269, TP 316.

4. #2 SEAL LEAKOFF LINE (AT PUMP SHAFT). CLASS 2 ACTUALLY ENDS AT #2 SEAL, NON-CLASS BEYOND.
5. #3 SEAL LEAKOFF LINE (AT PUMP SHAFT). SEAL SYSTEM IS NON-CLASS BEYOND #2 SEAL, INCLUDING
  1. 3 SEAL, HOUSING, AND LEAKOFF.
6. THE 7 TEMPERATURE ELEMENTS WITH DUAL ID NUMBERS IN AREAS (D-9),

(G-8), (H-8), (D-3), (1-4), & (1-9) REPRESENT DUAL ELEMENT RTD'S.

7. TEMPERATURE ELEMENT TE-410B-2 IS SPARED. SEE DWG.: 21489-0504 FOR DETAILS.
8. FLOW ORIFICE LRC06 IS 1/4". SEE DRAWINGS:

21489-0501 AND 33013-1626 FOR DETAILS.

9. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 1 0328.
10. REFER TO DRAWING 33013-1265, SHEET 1, FOR eves CHARGING AND LEAKOFF CONNECTIONS.
11. MOV'S 852A AND 852B HAVE BONNET PRESSURE RELIEVING VENT HOLES IN VALVE FLEXIBLE WEDGES ON DOWNSTREAM SIDE AS INDICATED BY POSITION OF ASTERISK (*).
12. RCS VACUUM REFILL PUMP (CRC01) IS CONNECTED AT THIS FITIING WHEN USED. (OPTIONAL USE)
13. CONTROL ROD DRIVE MECHANISMS (CROM) ARE LOCATED ON THE REACTOR HEAD AND ARE A REACTOR COOLANT PRESSURE BOUNDARY.
14. ORIFICES LRC05 AND LRCD7 ARE 1/4". SEE RGE DRAWING: 03021-1419 FOR DETAILS.
15. LINE CLASS 2501, EXCEPTION TO SPEC.: SCH. 80.

1 1 [Jl ()1 0J OJ 1* v LRC04 2" 554 2* [Jl ()1 [Jl CAO ALE NAME 3P126001 CONSTRUCTION LIMITED CONSTRUCTION: /JS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR F"'-'lY GINNA STA. RocHESTER G>.s & El£crRlc CORP. t------------j NONE REACTOR COOLANT (RC) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1260 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 LOOP SEAL LT 921 11626 2505 894A 8948 (C-6) 33013-1270-1 (B-11) SEE NOTE 8 33013-1247 X857C._ _____ (1-1) < 33013-1270-1 (D-11) 33013-1891 X14369SL-_____ (D-11) 4" 2" 893A 151 2" 3" 8" ~=3~3~0~1~3-~18~9~1==::>-- X1437oc! 1 m ' 2 6" TSI01 REFUELING WATER STORAGE TANK 0 ' 6-Sl-301 357 2" 8938 I 11625 1~05 2" 2-Sl-151 3 (l-9) 33013-1870 AUX. BLDG. EXHAUST FAN 1 G ~ (F-5) 33013-1248 1 o" 8~ 8 REFUELING WATER CIRC. PUMP (G-5) 33013-1247 4 6-Sl-1501 X856 m 0 m OJ 916E ~ - 1/2" m 0 ri; 1 2" 5 6 7 2-Sl-151 1801 v 3-Sl-151 1733 2-Sl-151 (D-1) 10" 10-Sl-151 (F-1) 33013-1262-1 -C><t-1 33013-1262-1 x 1 817 l:'.::'.'.:'..'..:'.=.'..::':'.'.'=.'__./'"I I X8258 SEE NOTE 11 1------1.:::::<r-6-_;S;;_l-...;1..:.5.;...1 -( r---8-" ----,--i r-1 L )d-1 4" 858A ~ m ' C! OJ z 0 0 - [];QI PSl02A,<MO/CSP1A> LT 932 11623 25051301 3/4" 863A v 0 - CONTAINMENT SPRAY PUMP A SEE NOTE 7 1~-0>~ ~ v E---1-t--, l[1 _I._ ~ + 'f ,~ ~ 1802 ~ ~ TUBING~49E "' 1" "_I- ~ 2 ~ 3 4" 301 2" 8498 MANWAY TSI02 SPRAY ADDITIVE TANK 849C ---, 849D ~ (/) T 0 - 836A 2" D 3/4" _r-~~IS 6-Sl-301 863B 2" CONTAINMENT SPRAY EDUCTOR A SSI01 8734 IEQI 845A ~ 2" l-8-C7*3:}B-,--__.J'---I s7o f---8{;7*3AJ--=----1 881B Ol [bQJ ~ -":, 2" [QJ NOTE.JQ_I [QJ 2-Sl-151 ~T ~ 1: D ITE 10 15~1 87~C ~73D u:;g u:;g 2 2 0 - 2-Sl-301 Ol .... g;i s 881C !ill SEE NOTE 11 v ~ OJ 6-Sl-151 6" 8" I M) 4" '--"-=-T=-r:::<1--....:.....--c1--.....:...--'--I+- 3 43* 858B [];QI PSI02B,<MO/CSP1 B> ~ I Ul T CONTAINMENT SPRAY PUMP B SEE NOTE 7 2-Sl-301 6-Sl-301 3/4" 8737 )-.::.!-'------IV SSI02 CONTAINMENT SPRAY EDUCTOR B 2" ~ 831B [bQJ 2" 8~ 0 1" 859G [fil 860A IBLCI 2" 860B [fil IBLCI 6" E 2822A ~D 116 __ ~ 0 - c 21 z TC M 860D IBLCI ~ [§] 2 OJ z 0 860C IBLcl ~ Pl 0 6" L'-J D 6" t§ 933D 2823A ~ t:i~8_s_1 ____________ 1_-_s_1-_3_0_1 _____________________________________________________ ~ 2 3 4 5 6 7 (/) T 0 0 - 6" 8 (1-7) 33013-1266 BORIC ACID BLENDER (F-10) 33013-1272-2 R.C. DRAIN TANK PUMPS (E-10) 33013-1248 1/2" m I ~ I 0 - 862A 1/2" ~.-,:i 869F 862B 8 m I (/) T 0 - m I (/) T ~ - 1/2" ~ ~ 910B 1501 - 910A 9 (C-1) 33013-1262-1 SI PUMP DISCH. & ACCUM. TEST LINE PT 950 MANIFOLD ro SSl10 910D 0 910C Pl 933A (D-9) 33013-1262-1 SI PUMP DISCH. FULL FLOW TEST LINE Pl 2780 "' ~ ro OJ ~ 868A [QJ Pl 933B ro ~r, ~m I o I Ol O> O> OJ t~ 6" 6" D 3/4" >---.---:J TC 2861 3/4" f--... 1---:J TC I Ul -I 0 - 2862 mt 875B JBLOJ 8768 IBLOI ~ 876A !BLO! 2863 lbQJ 3/4" 2864 1" I 3/4" 6.. 6" h----'-----';__-1 ,,.10 co xz . );! OJ z r;;:: 0 "' 0z 9 ro -"' OJ ro OJ 10 CJ PT 944 ro - <O 0 ro 0 ro - <O 1 1 12 2505 2506 n 2505 2506 ro )> 4" 2505 UPPER CONTAINMENT SPRAY RING (90 SPRAY NOZZLES) SSI07 3" 4" F-2 33013-1863 POST ACCIDENT CHARCOAL FILTER (E-2) UNIT A C-10 33013-1863 POST ACCIDENT CHARCOAL FILTER UNIT A B-4 33013-1864 CONTAINMENT AUXILIARY CHARCOAL FILTER A 33013-1863 POST ACCIDENT CHARCOAL FILTER UNIT B (C-11) 33013-1863 Tl NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DRAWING 33013-425
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. CLASS BREAK OCCURS AT PIPE TO NOZZLE WELD. REFERENCE DRAWING:

PITTSBURGH-DES MOINES STEEL CO. DWG.: ES-56063-02-D REV. 1.

5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR NITROGEN LINES AND COMPONENTS IS BASED ON UP-STREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO INTERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
6. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
7. THE START SIGNAL FOR THE CONTAINMENT SPRAY PUMPS IS HIGH CONTAINMENT PRESSURE.
8. DC CONTROL POWER REMOVED BY KEY SWITCH.

~

9. REMOVED
10. EXISTING SCH. 10, 2" PIPE LABELED 2-Sl-301 NEAR SPRAY ADDITIVE TANK AND REPORTED IN CR-2007-000729 HAS BEEN EVALUATED TO SATISFY REQUIREMENTS OF SEISMIC UPGRADE PROGRAM DESIGN CRITERIA AND LINE SPEC.

CLASS 301 "DESIGN LOADS".

11. CONFIGURATION OF THE CONTAINMENT SPRAY PUMPS MECHANICAL SEAL WATER PIPING TO THE SEAL WATER HEAT EXCHANGER IS SHOWN ON DRAWING 33013-1246,2.

POST ACCIDENT CHARCOAL FILTER UNIT B 2863R A-4 33013-1864 CONTAINMENT AUXILIARY CHARCOAL FILTER B 1/~ ii ~ SAFETY CLASS SAME AS MAIN LINE ZSAF~ CLASS 2,3,0R SAFETY SIGNIFICANT (Q) 4* LOWER CONTAINMENT SPRAY RING (89 SPRAY NOZZLES) SSIOS 4" 10 DETAIL-A TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS CAO FlLE NAME 33013-1261,1 3" CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES '2.- -15' AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION 1 1 SCAt£ NONE JOB NO. EWR 3391E CONTAINMENT SPRAY (SI) P & ID DRAWING NO. 33013-1261 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H J 1 2 3 (H-10) - -,,_~~~~-......... ~ " I 33013-1887 (H-1 O} 4 5 (J-10) .,_~~~---.......~ --C>< _:::l_-1, 33013-1887 >--,.. If-----, X14137S I X15064 '~ _;:- I 33013-1887 >-If- .. ----lf- .. ----1 .. 'f-----, l/P X15065L.._ _____ I v L....r-1* 945 " V-{-><l'f---"-(*'"'r--..~---'-,--r-------1~--'S~l--~90~3:._ _____ _..,.. ___ ---, ~ - ~* I ~

  • 945A 945 I FP120 ~ *~~

(F-6) Im _lJ 0 I 33013-1212-1 f---- I

  • I

~ - I 33013-1262-1 >---------------'---'_f',J--r l--C-:J---.-----1-------' X846 11 8623 n 8624 ~ (A-10) I t/) I 0 PT 941 903 902 I CJ) T ~ 6 v? = 830A ~r-J~152 ~ 1-Sl-902 PT 940 t-.J s:l'\\ 7 2 >* l 7 8 9 10 1 1 ~ SAFElY CL.ASS SAME AS MAIN LINE SAFElY CL.ASS 2,3, OR SAFElY SIGNIFICANT (Q) DETAIL-A 12 I \\..1...... I I ~ I ~ N= J, ~ 8" 0 TYP. SAFElY CL.ASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS 0 L!J TC (D-1) 1* <::~3_3_0_13_-_1_2_63 _ _;1-----------~-------~ L I I (C-10) 1J113 4-Sl-1501 2-Sl-902 TC f--r-.L_-I>(]-':......::"-""""--, 1-Sl-903 LT 939 833A TSI03A SAFElY INJECTION r--l ACCUM~LATOR <O ~ '-.---i;s~-:;i-2~--S~l_-~9~02=--~ -+--l-833B Y ff:' r i ~J~ G'l w D 3/4* DI, i84S I 33013-1262-1 >-------------r-----------------, X88BA -i--1 ~ t-- ~-+-*-*-+-~ > (') cl~ x [lJ I z r.::: Q p z _J ~-~ ~' 2505 1501 ml.....------ FT 924 E- ... 2** I I 124ozH Bz8A 12402L 8288 ~ 2505 501 {1-5) 33013 1888 sov 14123S ~---~- ~ 150~1-...,2~501 = 2" 1¥1 --t. 8788 IBLOI I CJ) ~,.. ~ N*il-

== 835~ [f9 1501 902 <t 878G 1" oo,' ~ I:: C)J. z 2-Sl-2501 w G'l s 2-Sl-902 2"

J TC 832A LJ LT 938 (H-5) r---jf--;------;{f---------,;{f---------,;{f-----~<==3~3~0~1~3~18~8~8~]1 V.....::i X14118S 2-Sl-902 2"

0 832B ~ ~,, ~

~

2 10iSl-902(SCH.140) 'f;~ ~ ~ 1" (B-10) _"_o~~o ~~::;:::---~-~-f----.-J:--lt---l.... _t----'----------------------------1: 33013-1272-1 892A _"'l. ~44A REACTOR COOL.ANT -~ [ill DRAIN TANK ~- tJ1 0 @) ~ ~ ~" D 90 51 (J_-_5_) __, 1 - !). L-"'.J ,.-------jf--,,------jf--,.--------H-33013-1888 ~ - ~ SCH. 1'!2_ 2501 1150\\ '" X~;, 2~s LSI01 ,~ 3F4-Sl-2501 ' I ' $H.140 ~ "'... - 11' I'----~ I 11------a-t3w9.,.A1----, Im ~ _ SCH. 140 D 1: (1-5) 2845 3/4" LSI02 ,r:-


</11-' -------</i1-' -----,,,.','------<< 33013-1888 f-txl-1

'I ------.. -*'r'..---t-~ X14122S D II I I I 2844 '------, IFcl ~39Bl 3/4" v I, ~ ~ 2843 SCH. l 4Q_ 2501 11501 I I (G-4) 2501~01 ~ I ~ ~~ J MANIFOLD D ~ I CJ) (H-1) 1:1f--<:::==3~3~0~1~3::2:18~8~7~],r-C><:::t-_ 867A I 10-Sl-2501 (SCH.140) I I (D-4) 33013-1260 LOOP B COLD LEG L 33013-1260 ,r------------------~8~ 7 7 ~A--1....-~~...... r---t..,.t--' LOOP B 878F "'m" ~ 878A G °' IBLDI HOT LE ~ T ~ 0 ~ PT 937 co l'!i1 CJ) JI o Bv.i *... " ~ ---:J X14136S ~8308 v ~1-i.

;

/ SI-~ ~ 1 rri. * ~ ffi~ 1-Sl-902 ~ = -+--+"'

g Sl-902 PT 936

<O 3/8... "' 9. - ~ 2-Sl-902 TC 837A TSI03B SAFElY INJECTION r--l ACCUM~LATOR n' 2 ,.::2~-~S~l-~9~0~2'---{;:8::J-'2~"-"r'.i..,"1, _3/ 8" LJ 838A ---,_.r-:l TC (H-11} LT 934 2" 2-Sl-902 I 33013-1888 >-If-.,---, X14164S 0 6 8378 -t--<-:---="'c:J' 1:-. c CD (]ljl z G")UJ D LSI05 l../1-3/4" - 1" DI, 2836 DJ ~ ~ I CJ) ,--1_-_S_l-_1_5_0_1 ___ ~,lf-- L_ ____ _.9,.._ _____ __J I I [E£J 83~8 <O ~ ~.: ~ c I T 0 ~ 1---~:i FT 925 MANIFOLD ,--+ - - -- - - -+-r I I 124058 I ~'17 o I ~~ l I TC . ~ :J 12404 co ,.. > 3/4" 3/4"~ 0 - 1501 902 01 0 ~101 ~.,,-------....... _j_J 4-Sl-1501 4" 9 _ I 33013-1262-1


;-;-:-.._----i-----t I t-------------------...,

u; (F-10) X888B T 150+--3 ~ ~~ I /\\

  • -f----l,_:::l-.*--,

\\§) 0 [@ ~, " it)1 ll~ " FCJ', ,.~ 2 601 ~ 150 I II.JI~=~ ~ ~ ~ "'mi** ' m-,i ~- 890 £-lr-1-i & 3/4" Pl 10 (G-10) I

_,-c3::-:3::-:o-1"'3--12::-:6::-:2::-:_-1--,}-'----------=i:~_J x819 I

1 2 ~, *.fl.*..

== D ~ T I -D 25~1 3 4 5 o~* Z w G'l s <t I " I a18t1 I 01~ ~I aJ 2-Sl-902 8388 10-Sl-902(SCH.140) 2" LT 935 SCH.140 2".. 6118 6 I <O 0 ~ 1'l: 7 I 8678 I 8 I 111 I 0 ~ v = 15~1 (H-11) 33013-1888 f-tx:J-X14165S T (E-11) (1-6) 10-Sl-2501 (SCH.140)


<! 33013-1260 >

LOOP A COLD LEG (G-11) ~---,:~1-------ff1-------ffH-----~:~1---<< 33013-1888 ~ X14162S (E-8) ~~~~~~~~~~~~~~~~~~~~___,,_! _3_3_0_13_-_1_26_0~)> LOOP A HOT LEG 9 10 1 1 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1262, REV.10
3. EXCEPT WHERE OTHERWISE INDICATED, SAFElY CL.ASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE NOTED, SAFElY CL.ASS FOR INSTRUMENT AIR AND NITROGEN LINES/COM-PONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE.

REFER TO INTERFACING AIR/NITRO-GEN DRAWING FOR SAFElY CL.ASS. RE'llSED PER ECP-I 5-CXJOM5-CN-001 MLS MZ MLS MZ 2/17/16 2/17/16 2/17/16 2/17/16 CAD FILE NAME 3P126208 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 2/17/16 ~ BUILT MLS DATE RELEASED FOR ENGR. ~ GINNA STA. R.E. GINNA STATION SCALE NONE JOB NO. SAFElY INJECTION AND ACCUMULATORS (SI) P & ID DRAl>lNG NO. REV. EWR 3391E 33013-1262 SHEET 2 OF 2 & CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 2 3 4 5 "' 2 1/2" 8621,i:Jf-- ATM 6 1-_1_-~S~l-~9~03"-------- ~----;~ ~ ~ 8627 N Q 7 8 9 10 (A-3) ---IHI I H i 944A ff-N ~ 1/2~ H; ! 1827 ~ ~ OO ~ ~ VI (J-4) ~ _, -? 621C ~ ~ ~ ~ (A-J) L3~3~01~3=-~12~7~4=>----__!1::_-~si::_-2~5~0~ 3 ------~~ I~ I l--f:><1--'--'---11,._ __ L __ _:_( ____,, _ _..,...,._--1*-*-<f-..i.--rJc-1'-"--L------J__-_,...t-~1"'-""s1"'-""90"-"3'---------------------------JI 33013-12s2-2 >.N- _lf44D NITROGEN 1827A ZWDOl 18278 8628~*44 8529 ~ 846 X8623 SUPPLY 2503 903 ~ [jJ IITJ (H 1) SEE NOTE 5 2" ~-----------------1----------------------------.. ----f 33013-1272-2 > SSl13 SSl14 (B-9) 33013-1261 X898 1 TS I 2-Sl-1501 2505 918A N ' 1501 '---'----'-.. ~ ~-----~~ 9188 ~ 3/4" g,_...._~_, 898A (C-12) -"-,-c.J , 4-Sl-301 0 0 .* ~ J 33013-1247 _,.,...,..~*-~---~-~-;~~*--~--~-~ Xl 816A ~-R-H_R_P_U_M_P~ DISCHARGE (D-7) 1-Sl-301 1 2" 1820A [!)) 891A 2* LS!08 1""- 1 /2"¢ II! 1501 1 151 1 2" 3/4" TSI01A 12406 i T ~F 'I ~ j~so5 TUBING I 1501 8741. 2 7 8750 J 1 v_ ~ /\\ l5, 3/4" '*1" ~ 1/2"¢ ~ v'P"O ~ ~ ~ ~ ~ X9081 33;~~~;230 Lill. (C-1) TC '5'~TUBING 3" ""'1

i:

~ 4-Sl-1501 0 0 0 0 0 0 f.'--.--=-------f::k1---------...::.----,-----r::x::-1--l--Q-----r--.W'-------------L-----'--......:-i 33013-1262-2 ' r--i_)k:::r----1t--'-+--) 1 888C SEE NOTE 4 1 " 0 I !ll I 0 0 0 890A [Q] TUSING 0 1817 "-~~-----::.-:::.-:::./ _____ 8_8_9A~I ~... ~ ~ 8[@ ~ [8 !".) FE924 PS!01A ~ o g 2" N

Q co iU SAFF.:TY INJECTION PUMP A TC

<M0/SIP1A> 2" 150~05 r!TUBING 34"~ SSI04 1/4" 1/4" 2" (H-1)


!133013-1272-2 >

AUX. BLDG. SUMP ~ ~ ~ I" ' (C-9) .. ~3-Sl-1501 I oo_t_ 1 L 33013-1261

i:'t' 898C FE910 >

1 1 12 < 33013-1261 J---~'4---LM<!f--'=:J TC 8748 N2" 914A 914C o SEE NOTE 4 0 t.... ~ _3/?"_ W ~TC ---.::O;f~:ING 1/2"¢ VE ~TV61NG 1/2"¢ 187560' TSI01C 8757 (D-3) 33013-1261 RV/ST j§ r, ¥' 0 I (fl , T 0 10-Sl-151 TUB~ v --j-11----...-.>4--* 2815 0 825A @!]I [fil °' ' § 0 TCJ-C}-3: "' T TC 0 3/4" 0 0 1~1r01 8-51-301 8258 IBLOI [fil 0 DI 3/ 4'~ TUB~ 0 0 0 0 0 0 0 0 SEE NOTE 4 ,, 890B I [Qj 0 0 0 0 0 0 1" 3/4" PSI01 C SAFF.:TY INJECTION PUMP C <MO/SIP1C> "-~l]J_s ____ ~/ PSI018 SAFETY INJECTION PUMP 8 <MO/SIP18> 0 0 0 ¢ 0 0 0 0 0 881 s 1* 1" 2"

oJf, z

C~ 1:1 884 l 879C ~ 1'\\ "' ~ "'.... * ( <_3_3_0_;3----~-'2-6-1 --,,_ __ s_/_4_-__ s1_-_1_5_1 ___________ I ______________,_J ' 2" RV/ST (G-3) 33013-1266 BORIC ACID STORAGE TANK A 827A [:@] 1" 8-Sl-301 0 0 0 0 0 2817H PSI01D SI ACCUMULATOR MAKEUP PUMP <MO/SIP1D> 2" COLLECTION RECEPTACLE 5/8" ~ - 2817F 3-51-1501 2849 ~505 1 2" TUBING LI

-1/2"¢ TUBING 4

101C ~ ~--------------------~3~ T ~D 8-Sl-301 0 0 0 0 3/4" i:;; 6-() I TUBING 2" 1/4" SSI05 3 4" j 2505 TUBING I 1501 (H-1)


1133013-1272-2 >

AUX. BLDG. SUMP 12407 915A ~ ~ 915C TC ~TC 114.. 913C o:i tu rn TC 87:l 3 4* 't 1/2" v 874C 6 ~ ~ ~ (H-i) 4-Sl-1501 i-,;:....;.;,._;.;..:.;__--f'::k:'.1--l.--~--{><]-.l...(~~-...,---l.~~~~~-_;_...;_:....;...:..;_-1._-1 33013-1262-2 Q ~ 8898 8888 888D FE925 I~ 8742 ~----<Or------- [!)) -! 33013-1230 X9082 (F-1) 0 0 0 0 0 0 0 3/8" t----t-,:J TC 28178 0 0 879 rill 2505 ~TUBING j 2505 -TUBING 3 8" 3TC 28170 ~ 3/8" --jD s "' "' "' ~ D~ 1/2"*) TUBING 3/4-Sl-1501 TSI018 8~ f----,----:)-'::Jv 8753 """- 1/2"¢ TUBING 8754 y (J-1) 33013-1262-2 ~ 'X872A SEE NOTE 0 8755 826A filQ1 ~ SAFETY CLASS AS MAIN LINE SAME [fil 0 0 0 C> 0 0 0 ~ TUBIN~ : L SAFETY CLASS 2,3,0R SAFETY SIGNIFICANT (Q) NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DWG: 33013-1262, REVISION 10.

3, EXCEPT WHERE OTHERWISE INDICATED, SAFF.:TY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A". 4, WELD PREPS ON BOTH SIDES OF VALVES 890A, 8908, 1815A, AND 1815B ARE SCH. 10S. WELD PREPS ON DOWNSTREAM SlDE OF VALVE 826A AND UPSTREAM SIDE OF VALVE 826C ARE SCH, 10S. ALL COUNTERBORING IAW EWR-3092.

5. V-8628, V-621C, V-944, AND V-8629 ARE ABANDONED IN PLACE. PRESSURE CONTROL IS NOW PROV!OEO BY VALVES SHOWN ON 33013-1274.
6. MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO

~ECHANICAL EQUIPMENT PER SFEWR 10328. 7, UNLOADER, Pl-928A & Tl-918 WERE PERMANENTLY REMOVED FROM THE SI MAKEUP PUMP SKID IN ACCORDANCE WITH ECP-13-000426. POL 10/24/15 CAD FILE NAME 33013-1262,1 CONSTRUCTION UMJTED CONSTRUCTION: AS NOTED ?REWMINARY NOT FOR CONSTRUCTION 1----+--'

  • ----;~

BlDDING i>U~PO&S 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 8" 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1822Aw o o DETAIL-A A_S 8UILT (G-7) 33013-1266 BORIC ACID STORAGE TANK 8 1 8278 [Q] 0 i 0 8-Sl-301 000000 Q 0 0 0 2 0 3 4 5 !o o 1 VJ,, 0 SEE NOTE 4 ~ 826C IBLOI [fil 0 6 7 8 9 TYP, SAFETY CLASS BREAK POINT FOR VENT, DRA!N & TEST CONNECTIONS 10 1 1 J REl.fASEO FOR GINNA STA. R,E. GINNA STATION NONE SAFETY INJECTION AND ACCUMULATORS (SI) P & ID JOB NO, DRAWING NO, EWR 3391E 33013-1262 SHEET OF 2 CCD 01 jCONTROL COPY# 12 A B c D E F G H J

A B c D E F G H J 1 I 2 I 3 (H-8) ,r--------- 17---J l 33013-1887 >-------h,,'------------1/-,,--, X8604A (B-1) I 33013 1262 2 SAFETY INJECTION ACCUMULATORS A & B (G-8) 1 " OJ ° 0 0 )>' ~ ~ 7 0 0 l' OJ ~ 33013-1887 >~--,11--'/ X8604B 1 I 2 --j c OJ I~ I PS 457 1/2" r--*...

  • -r--:i v 8602'A PS 458 3
  • <:> _ 1 /2" 86038 I

I PT 455 TC 4 TUB!~ ° '"'-- 3 I I 1 " ~ 8608A'

  • TC I

OJ ° 7 0 };1 ~ s;, * "' N N_ O> J>'

  • L!J D

5 TRC03A OVERPRESSURE PROTECTION ACCUMULATOR A I TC - OJ 01,

  • N '

6

' 1 1/2"

/' 1 1/2" '.- 8615B OJ ~ 0 N r-7~ ~** 1'.. ~ ~CR02 l~I 1" r-------t. I 8606B I r--.,--...---t,~-,,-1-1,,"°* 8612B 1-_,_ __..._-'---1 co PT 456 1 " 8608B'. TC OJ OJ O> 7 0 " OJ' TUB~NG (J> N 0 m*.. .f:..:: \\-------,--('~ l 86o9s 4 v D I 0 0> \\) TRC03B OVERPRESSURE PROTECTION ACCUMULATOR B 5 I 6 7 3/4" 7 I 8 TRC04A OVERPRESSURE PROTECTION NITROGEN SURGE TANK A 1" 1,_ I 8619A Isl I f----fv~*f--""1, I t-----1 8618A ~~~- g;1 r_. ~*.. N= L!J D 9 I .1.---r 8630A SEE NOTE 3 1 0 I 1 1 (B-11) 0t--:::-1 I~ 33013-1258 AOV-430 (B-7) 3/4",, ~ L---11,,"--J r--~-11-,,_,: I r-1 __,1.,_: -----<C1!"'iiill*--J111--<< 3301 3-1888 ~ 8620A X7067L TRC04B OVERPRESSURE PROTECTION NITROGEN SURGE TANK B I 8 I 3/4" t-~:~ A (C-11) J--"--:JV"v-C_,1~~3-30_1_3_-1_2_58~> I :r----c 8630B SEE NOTE 3 3/4""

11 rJ SAFETY CLASS 2 OR 3 DETAIL "A" AOV-431C (C-7) u

~""'i.*--11-u-~< 33013-1888 8620B SAFETY CLASS SAME AS MAINLINE TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN, AND TEST CONNECTIONS. 9 I 10 I 1 1 I 1 2 NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. THIS DRAWING SUPERSEDES CATALYTIC DRAWING A-202.
3. CHECK VALVES 8630A AND 8630B ARE PROVIDED WITH ORIFICES IN THEIR DISKS TO ALLOW CONTROLLED CLOSURE OF THE PORV'S, REFERENCE EWR 1660.
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

REVISED PER jJ /) /) A OCR 2DOD-0194 AJV3 NJ'l J Hf/J!t -:;i;;:.p PCR 96-079 i--:.=-f!...Uf<L./--IC--'-'---1---1 MDCN 1963 10/11/DC /o//ljN"' fo*-/t;,-d) l*/)b/._,, NUMBE!\\: R£VISlON CRAWN BY CHECKED SY RESP. ENG, RE:VIEWER CAD FILE NAME: 3P126301 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PREUM!NARY NOT FOR CONSTRUCTION BIDDING PURPOSES A B c D E F G H Pho/;._, AS BUILT

p; r-~-"-t-~--~--------r~~-1..____

DATE RELEASED FOR ENGR. rACiurv GINNA STA. ROCHESTER GAs & ELECTRIC CORP. SCALE NONE ROCH£:Sl£R, N£W YORk RCS OVERPRESSURE PROTECTION NITROGEN ACCUMULATOR SYSTEM P & ID JOB NO. DRAWING NO. EWR 3391 E 33013-1263 CCD 01 CONTRQL COPY # I 1 2 REV. J

A B c D E F c H J I 1 I 2 I 3 I 4 I 5 I 6 7 I 8 I 9 I 10 I 1 1 I 12 (E-10) .,,.--~-~--..... >-

  • I 33013-1891 X14207s'-------_,..-

X9B7 (FT\\ 3* (D-11) X1 -590-8[~~~~-~1~~~=>*~~d~-- ---~ 2" W-1) ~ ~ r--~========================~-----~-----4!=1~1~> 33013 1891 ~.....-+--- _:_~ ----11-1;::


1*------<: 33013-1270-1 trn ;:,

.<210 I PRESSURIZER RELIEF TANK (G-3) 33013-1278-2 I-I 0 I I -"' ~ I () I I v 2* -D-4.- 7 239B Pl 136 --1 c OJ z 0 12159B ~" iljo PT 6Dl-+----'-~l.S-i 3/4" AUX. BLDG. SUMP TANK f ~ ~ <j ~©I ,;* 'I' -*-----iht-' --1©/P r----1t1-)~< 3301(~=~~88 L,____...,_ (C-10) en r 5' ! L-' J (A-9) '.l> "' 6;.J>-I --~ 6249 133 -* -----~ 1 X'1°51'61 ~u o 135 y ~-- ~ ~ ';;;, c 203

S" (F-4) v 33013-1891 33013-1890

' =i ~ x1s9Q9'-------~~ L!J x14'204s-------~~ " I

r--:r>

__... f----------#-,,--------,,11-------""-,,-- ----------ff,,-----< 33013~1sas I 0 I I 3/ 4-CH-151 ------... l;> 145 z39A ~NoTE 4 Pl 142 I 2-CH-151 "' 7 ~ A ~---l-'><~:1----1-'><~:1----I F t<:"7 2so8 i5oc Y-. z500 I ()

r I

0 ~ Pl I '\\._ FCH07A LEfDOWN DEMIN FILTER "A" 137 ~' ) COARSE MEDIA --1 ~ 250 RR v N

uz IMB
  • Xl5162

--,fl--;'+J ' "~ " ~ ~:: ~, 0 _fl_'-~-" OMB j33' IFcl '50-';:'. E---13_4_*__ TUBING


i

.. ------------11 3301;~~:;2-1 > ,,,, + " ~

  • - §

~ ~,~ i~ " 8 ', ff 'f<_"------~-~--()- _________ 1 2 CONTAIN~J~)SUMP A ff ~!~ ~ 1/ 2" 1/ 2" r1 ';;; );! "' ~------!::! ~ P112 = 1~. --~-----~< __ 3~3~0~1~3~-~1~2~4_7_JI ~ 2" ""T ' L-J

: 2-cf:i:!601 2*?

D !Loi 2-CH-601 1 1,1--'~::.;__.:;;;:..:.._ __ .,---.1......<---.1-i)"::i--t-:~ r--'--r-i::-:J-.--T-:-::.:.:......::..:..:..,----t:<<J----.....,1---'-----------------------.l---.,--------=-..:.:.:,:;.:..:..--------, RHR LOOP 204B 7"',, 204A J,~ 371 --n ,----~3,,,J~4~"--1'1' ---~3,,_;/~.4~*__, ';' 314* (F-7) TUBING 151 204E 1135 204C 2" . ~ o '< r tiJ I. 2 ~ ----1hr-' -~< 33013-1888 ~ TE I z lQJ ~ - ""; ~ !Fcl I CJJ ~

0)

~

~

I -* ------~ 1 x14°168S 151, l~ 0 sifi 130 8 ~ iii ~ I A s S ,.,, A s S (F-7)

u t\\..)

0 Q:! L ~ \\->-/ ~ r-!110 ::5 -..; )-!ff/--, ~ \\~I N Piil ~...,,_.,,_,ff "' ~-3-3-0~1-3---1~8-8_8_, - ~---2_-_C_H_-_1_5_1 __ ~ VOLUMECONTROL ~~§ r-.> 6 NJ_ v Qi£1tv VII v ~LQJg v II gj_ 1g~~ _JlX-14169S TANK [-~1---._J ! m 8 (H-l) -1 ~ ~a ~ ~ B ~ ~ ~a 348 ~ 3/4" is1D -I c crJ 3/4 ~ I ~

o ~

~-----<: 33013-1248 I I REFUELING WATER X820 I g g 0 I I 0 TE 127 Pl 138 1--... ---1.:: N.., 1i173E N,., ~ ~ ~.., 0 ~~~,,...... :- A ~ : b ~ --~TUBING I I N CO VJ fTll.) ()1 z........, f\\. N 14201S c:l ,, 1t I L 14201S1 (A-12) (lYP) !l 'r~@-c:.~¥<6h~-.;1f-l/,'-P-\\@-=::-<:,,,--3-3-:B-1 ~-~-:-~8-9-,: f15S08 LH.::c::<::::=~3~30~1~3~1~8~8~9~ 112A I ff 1X15807 PURIFICATION PUMP ~ ,b SUCTION I t)_ '- 5- - 5- -- CG-1 J 8 T**L* __ :~~~~:;_-_*_-_-__ B_J*.... --~~~~~~~~~~~~~~s_:i:_J-....._-.-~ (F-12 ff


11U--<< 33013-1888 H?<;J:::

33013 1248 '~ - I


~X14167S REFUELING-*WATER X821 PURIFICATION PUMP I

I (B-8) DISCHARGE I


*-*------------------------f __

3/~4_"-~<~-3-3-0~1-3---1~2-6-0--,~ ~-----~ X544 r---~---------.._~CH-2501 El u TC

~.,~~

ro I )> ~ -~--te @:1: g'~ m~ ~~ ~ 6 ~ I ~ I "'3/4"

  • 1
  • NOTE 4 Pl 6248 I

~I ~ Q.-;v>----rl-ff---; ECH02A REGENERATIVE HEAT EXCHANCER -'--.L.----'-----r:><l-41 298c ~ 151 301 ~') I "" 301 1151 (A-1) ~~..1--,---'----------'-!:><l--l:x~(J--J F rC:>I 249-249A ~ 2s3P. 248B .c/ / 2-CH-151 \\" '~ ~.. ~- 2-CH-151 2214 I 33013-1265 2

.(256 3/4-CH-2501 ------.,

3/4"

  • .Iv 2210 CH-2501 (1-1)

RR "', ) FCH07 u 253 RR °' LETDOWN ~----------1' DEMIN (F-3) --j 33013-1278-2 3/4-CH-151 X974 A (A-9) 2" 3/4" 33013-1270-1 :1------l l---"----' WASTE HOLDUP TANK (F-3) FILTER FINE MEDIA _,,..-~-~---.2-AC-601 -i-X~J---<, 33013-1247 ,r---------~ X822A (E-10) /,,,..--~-~-.,. - 2-CH-151 r-~.. 11--<~_:3~3~0~13~~18~9~1!._J I X14208S (E-4) 33013 1907 2" - - 245 I 0 I I I 0 I I RR 228 RR 2* I 0 I I

o ~' ~
o ~J JN I

0 I I 227C RR " J-

o N

!___ Al );!

  • 2"

{~-~-

229 RR 1: 230 RR 395 RR N I 0 :r I RESIN FILL THIS DWG. (H-10) L~ I 0 I I fCH01B LEfDOWN DEBORATING DEMINERALIZER B 1------ -- m (;:;;:;\\ n MANIFOLD "" .....-+~- ~o~ I (J-10) I 33013-1267 I I 2" Ll L 237C RR 2" 3* I 0 I I 236 RR i3a8 RR 2" 226C RR ~~~ 396 RR N I 0 I I -"' ~ I 0 I I ~ c-:. 238C RR RESIN FILL THIS DWG. (H-10)~ RESIN FILL THIS DWG. (H-10) L -' 1 r N (A I J L () I I TCH01A LETDOWN CATION/DEBORATING DEMINERALIZER A NOTE 6 3* 2-CH-151 I 0 I I ~ 0 0 0 0 (A-7) 0 '----,----1: 33013-1267 ~' )~ eves HOLDUP TANKS ~ I rn* o I T D en 2-CH-151 RESIN FILL THIS DWG. (H-10) ~ ~ u ~ rr=l N

  • rl£?.J I

fj=} N 7Jtt.i ) ~ lQ.I ~J.. ;uO>J ~ I ¥,__ __,_-_,\\[: 1-CH-151 --- 378 N I () I I E N I () I I TCH02 LETDOWN CATION DEMINERAUZER BED x 7 u 0 ~ I vi I I 0 N ~ 00 RR N I 0 I I 0 I () I I Ol - 2" 0 0 I 0 :r: I (B-4) ---~~~----,,. - f--1.,.1--< 33013-1891 1 x14312s 0 2" (J-9) -= 0 r-~* <~~=:J 33013 1266 2276 1'1oc IFCj BORIC ACID BLENDER rn ~ rn MANIFOLD ~I ~+- ECH03 EXCESS LETDOWN HEAT EXCHANGER '~ ~E ~~ 122 3/4" 311A ~3/4" I 12276 PT 121 '~


,lf'/---------11//----<< 33013-1887 ~

~----~ 1 XW40S ECH02B REGENERATIVE HEAT EXCHANGER CH-25011 (]-- ECH02C REGENERATIVE HEAT EXCHANGER iJ I ~1 01- "'I

~

'---,,,ft-------~,,1---, ~:~ ~11 I (E-1) L+/-2=1CHs:2~5~0~1-+--_J_-<:::::~~~~~]" 33013 1260 I - I X427 ~ -ri' ~ () -~- 1,'~ 2 i

F:

/j D G') II Ljf-ff------t,,f--<, " il;P\\ ~--11--l 1---~,'f-- ,:. ~ ff ff 3/4" ---~=.'IL i

  • 33013-1888 I X15l87 (F-9)

,,,,-----~~~.,, - L._-,,,/f-----.. lf--< 33013-1888 1x15188 (F-9) L----fl"L.----fl- "--<::=~~~~~=}* -- L _3_1_1_G_ ------------ I 0 LJf I 0 :r I ~ 2-CH-151 ~ __r-., 1 -CH-151.--.. 1---+-1 214 E RR TCH03B LETDOWN I I 0 I I MIXED BED DEMINERALIZER B /\\ 2" 2" N I () I I Ol I __['"- 1" - t--Y---'---,_._.,_ 1---1-1 222 E RR TCH03A LETDOWN MIXED BED DEMINERALIZER I ()

r I **'

Ol ~ A

== 1 <O

  • D ff 33013 1888

'xHllOs (D-10) I 33013-1272-1 REACTOR COOLANT DRAIN TANK TCH16 RESIN BATCH HOPPER ~---~3/_4_-_C_H-_1_5_1 _________ 1 (C-1) 33013-1265-1 (D-10) > I I I I '--------------------{, 33013-1272-1 (1-9) 33013 1269 218 201 0 QUICK CONNECTION COUPLER FOR RESIN FILL ON THIS DWG., AND DWGS. 33013-1267 33013-1248 33013-1276 r~~,'~ DETAIL-A c SA~ETY CLASS 2,3, OR SAFETY SIGNIFICANT (Q) RMW SAME CONTAINMENT AUXILIARY BLDG. NOTES: REACTOR COOLANT DRAIN TANK 1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2. THIS DRAWING SUPERSEDES PORTIONS OF 33013-426 & 433.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DEfAIL "A".
4. VALVE 145 AND 112A FAIL WITH FLOW TO THE VOLUME CONTROL TANK.
5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES IS BASED ON UP-STREAM INSTRUMENT AIR/NITROGEN VAL VE. REFER TO INTERFACING AIR I NITROGEN DRAWING FOR SAFETY clAss.
6. LETDOWN DEBDRATING DEMINERALIZER A (TCH01A) IS BEING USED AS A CATION DEMINERALIZER. RE

F. PROCEDURE

S-4.5.10. RJM /'fl Afl. C'.gA. 5/12/14 ')*12-1'1 <;*f2*(1f. &:1>-ILJ 33013-1264,1 CONSTRUCTION LJMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION lYP. SAFElY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NONE CHEMICAL & VOLUME CONTROL LEfDOWN (CVCS) P & ID JOB NO. DRAWING NO. REV. WASTE HOLDUP TANK (J-10) <~_33_0_13_-_1_26_7~1-SPENT RESIN [~(~G~-~*10~)~==>-2~"'__J

.. ;;
33013 1248 (E-8) 33013-1248

~;; X794 -*--*---*-*---1 X791 EWR 3391E 33013-1264 TANKS CCD 01 CONTROL COPY # 1 I 2 I 3 I 4 I 5 6 7 8 9 10 I 1 1 I 12 A B c D E F G H ~ J

A B c D E F G H I J 1 (E-11) ~ x 0 ~ 0 s;; I Z

o

-<IF-< ~1~ 0 z 0 I I 2 JJ00 3 t' 4 N I 0 :r: I N 01 s N 5 ECH02A ECH02B ECH02C L3~3~0~1~3=-~12~6~5~-~2~,;>~--::::::-~~~r.:;;;t-~r;:---:;r:!?-~.l.----:;~;!-~~~~... ~i-~~-::-J X384B II 370B ~ 370A 362C S (D-11) 33013-1258 v s* 314 I PRESSURIZER f ~


~ RELIEF N

-I', 151 2501 TANK ~ E-4 33013-1888 REGENERATIVE HEAT EXCHANGER 6 7 2-CH-2501 I P108 L!J TC 3/4' ' ~ 1" 01 3/4-CH-2501 l--------~=---'---::_:_:_-=:...::...:------------------------------ (D-11) _J_J 33013-1265-2 ~~ - - - _ _=J I (F-12) s* PIPING !UBING 2213 TUBING PIPING MANIFOLD 3/8" N <D f'l 293F 293D 293G 293C 2505 2501 MANIFOLD --33.. co ~ 3/4' 385F 385G 3/4-CH-2501 3/8" 385D 385C 38 6 3-CH-151 IFcl 0 s:: l'l, llJ OMB IMB 3/4' t--l~-11 D 2214 2" Ol N )> N I 0 :r: NOTE 6 ~ PT (I-1) I -J><J-j 33013-1887

>:.-----HH-------,1~1-----HH------1/~1--

I X14141S=-------~ I N 01 s I I IX14133S (H-10) 33013-1888 (H-6) 33013-1260 COLD LEG LOOP A

t 2501 N,

2501 v-12194D 2505 N 01 s 01 00 co )> I 0 :r: I N 01 s ~ 2" X14142S t' N N llJ 3/4' lt--..14--'-----t 'I 318B 0 :r: I N ~ ~{ s (I-10) 33013-1887 f'l I ()) f'l I 00 N I 0 :r: 3/fS' 3/4-CH-2501 3/8" 2501 306B I MANIFOLD 293M 293L 2~3H 2~3-!._ 2505 2501 MANIFOLD 3 8" - 385M 385H 2505 385L 385J co 01 A NOTE 6 ~ PT 174 12195D 01 s 01 00 00 llJ 8 NOTE 8 D D N N s 00 D t' 9 OMB IMB 392A 9315 IFcl N ~ -...... 01 -I', OM.a..,JMil I <21 I 2" I 294 9314 [ill t' 296 9313 IFC I N N ~I s °' J_ 'I DOMB I IMB 297 <D ~~D 250*BING (TYP. 3 PLCS.) 10 (G-3) 33013-1888 (H-4) 33013-1260 HOT LEG LOOP B (H-3) 33013-1888 (E-4) 33013-1260 COLD LEG LOOP B G-3 33013-1888 (F-1) 33013-1258 t~~~'~"~' AS MAIN LINE

ZETY CLASS 2,3 OR SAFETY SIGNIFICANT (Q)

DETAIL A - TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS CONTAINMENT X14108S X14109S X14107S L ________ I 3/4" v 11---....._-f v 1 2501N.1-: VI VI E sl'-. s OTE ~1~~ ~~ N 01 s 3/4" l----tie------11 v 2221A I N 01 s IMB, i,OMB "'-""H:v) NOTE 5 N s Ol (D v N (J1 s - -- - ----;UXILIARY BLDG.- -- - v 1 N N N 00 v N 01 s N c gi z G) 2" 2" TC I I J_j102 383B N 305A 3/4-CH-2501 1----Jr-~-+---~---~~---~ 3/4" 2219 ID l-3-t/,.4._*-l~~ING 2218 3/4" 3/4' 9306 v 11---....._-f 2502 1 2" 302A TUBING SEE NOTE 4 IMS OMS 3/4' .-.t4-1IV 2222 1 1/2" __/ 3/4" ~ 250jl-~~l---~~-IHXl-t---'-r2=2,.2*3--ll V N 01 s ~ PVcJ01A 30~A -+------+--+--_,-<--> ~REAC OR COOLANT IMB OMS

i H

_rl s <MO RCP1A> 12193D ai N PUMP A 2501 ~ D i!i 2217 ~SEE NOTE 11 i---..-i-==-= - _I_ -N. I ~)> "' 3/4' 1 1/4" 3/4' I § I~ l-~*--11 D I <D I ~ M I~ ~ 16 v~ 3/4" 1/2" L --- _J 5 12193B TUBIN~02

J TC TUBING

--i-- 9304 ~2502 SEE NOTE 7 SEE NOTE 4 3/4" 3028 N 01 s 3/4' 2216 305B 3/4' I IM~ i ?MB 1 1/2" 3 4" 309B 2501 TUBING 3/4' ---- 12196D ~REAC~U~PC~OLANT IMS OMB 3088 I PRC01B * <M?J;;RCP1 B> - _L_D - t~-SEE NOTE 11 I ;::; N I ~ N::O I~ co I~ s::

0) rn (V)---1----2501 I

~

r:

I 0 L r---.*--J _J 5 121968 3/4'

J TC SEE NOTE 7 9302

~ 2502 TUBING L ___________ ~ ~0~------- - AUX~~;~NB:~~~ -- ---- --------~ ~.--- --- --- --- --- -_ _J 2 N, FT I 1-----1 :2.1-4:5;s_----1 l ~ I 1-----1-l2-1:4:7:B_----1 l ~ l ~ N I~ l N N I~ N I ~ ~ ID I ~ ~ 10 ~ I ~ ~ _J5 I ;::!

! _J5

~ 3/4' DHl---.... H 2225 g; "',-----t:-::i:r--_l__:_ ___ _ (FE\\___ N '.;\\ 2988+ ~ D ~- "' 2502 2505 12146D -!>; '----c:.c1 3 4 5 2224 N I 0 :r: I 01 s N (FE\\___ ~- 6 I 1----_12:1:4:9:s_----I I ~ I 1-----1 __,2-.1-4:8;s_----I I ~ rr I ~ I~ I ~ I~ fll N -ri N T'.~i

r*~

10 I ~ 10 1:~ ~ ~ _J5 I ~ ---~ _J5 1- --- 3/4' ~D 3018+ 2502 2505 3/4' 12149D 2-CH-2502 7 8 2" t' 303A RR v 303C RR 2502 299C 2502 c gi z G) N 01 s N 3038 N RR ~ ~ SEAL INJECTION rn J_ -!>; FILTER A N <!) <!) 0 D D c gi z G) N 01 s N 303D FCH09 RR ~ SEAL INJECTION FILTER 8 1 12161B 3-CH-2502 275 [ill 9 t' t' (F-11) 33013-1265-2 X289 10 1 1 1 1 12 NOTES: 1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2. REVISION "r/J' OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1265, REV. 8.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "1'.'.
4. SEAL WATER INJECTION, BELOW MAIN FLANGE. CLASS 1 RATING EXTENDS THROUGHOUT #1 SEAL HOUSING AND INCLUDES THE
  1. 1 SEAL.
5. #1 SEAL LEAKOFF LINE (FROM PUMP SHAFT). CLASS 2 ACTUALLY BEGINS AT UPPER FACE OF #1 SEAL, AND INCLUDES THE #2 SEAL AND ITS HOUSING.
6. DIFFERENTIAL PRESSURE MEASUREMENT FOR #1 SEAL, ASSEMBLY IS CLASS 1 TO THE LOW SIDE OF THE INSTRUMENT.
7. DIFFERENTIAL PRESSURE MEASUREMENT FOR THERMAL BARRIER, ENTIRE ASSEMBLY IS CLASS 2.
8. VALVE 392A FUNCTIONS AS BOTH ISOLATION AND RELIEF (250 PSID RELIEF SET POINT).
9. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
10. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
11. REFER TO DRAWING 33013-1260 FOR RCP CONNECTIONS TO REACTTOR COOLANT SYSTEM.

CONSTRUCTION LIMITED CONSTRUCTION: l>S NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES l>S BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCALE NONE CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING (eves) p & ID JOB NO. DRAWING NO. REV. EWR 3391 E 33013-1265 SHEET OF 2 A CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 3 (D-6) 2-CH-151 L-3~3~D~1~3=-~12~6~4:____;;.>-------:::-~~:;;---:;:;-;;;;;:;;;--;---;-~--------1 X2274 151 TUBING TUBIN'-"G-;..,_ (A-1 D) 33013-1274 X1673HYDROGEN SUPPLY MANIFOLD 1" 3/4" >------l 15l1~-2 -,~,H[~~(IB~-~ 7)~~:>~___:1~*--{J---1CL..:::.2'_'_-c*'.l------c 33013-1274 X1657 NITROGEN SUPPLY MANIFOLD -X*9'6~9-A,_;-3-3_0_1~::-~-;2-~-~---2---->------------'-1'_' _____ 1_8_"~M~ I TCHD4 VOLUME CONTROL TANK X209 (B-4) 33013-1264 (B-11) 33013-1270-1 WHT (A-9) 33013-1267 HOLDING TANKS 3-CH-151 1-CH-151 1-CH-151 3" 1" 3/4" 264B 3-CH-151 1" 264A (C-4) 33013-1891 X142D6S (1-6) 2-CH-151 L~3~3~0~13~-~1~2~6~6 _ _;;.>--':__::;..:_...:..::...:__-j X368 X271 (D-9) 33013-1266 (1-9) 33013-1266 1-CH-151 1-CH-151 0 0 0 4 1 " 1~1NG 3 4" - I ---"!--"'--I><~ ~259 I 3 4" 2" 255A 2" 1275D 2* 2" j 255B ~---!Ir-'"-:---~ 255D 1 "

0.

267 ~ 2" ECH04 SEAL WATER HEAT EXCHANGER 321 5 193A 3-CH-151 265 3" 6 2D5A 9!.5 I ~"' 1~5 7 8 (B-8) 33D13-1267 > HOLDUP TANKS (H-9) }-t><l-r~ r-----fl------<:::::~3~3D~1~3~-~18~8~9~~-i;;;;i;;--

J X15819 4D7F 151 v

'-"' 319B ~ (E-1) 33D13-1273-1 WASTE GAS 152 COMPRESSORS (G-3) 33013-1278-2 (C-10) 33013-2280 X16DOB f---'-----'--l F 1----1 315B RR FCH03 SEAL RETURN FILTER 315A RR (1-3) ~ .... *---133013-1270-1 319A RR SUMP TANK (l-1) ....-"-'--*~-----~-----------! 33013-1270-1 3/4" SUMP TANK J-1 33013-1270-1 SUMP TANK 3/4" 2-CH-2502 12153 313 ITl 9 10 3-CH-151 MANIFOLD 12154B -~4D D 3/4" N 384A 142 384B ~,; ~ ~"'-*...---~[fQJ"o~--[Q]~~~--__, 2 384C r----r.::<<:::r----1..... ----..:.....-------lli----------~ "1. 8" 281A 287 1> (G-7) 2 Q c! 286 3/::f J.... 112BT1 ~ 33D13-1891 X14307S (B-3) -.--.1

i 33013-1261 X357.___ _____

112B 4" ~ ~ 4;1 I r---2-£7>9('Bf"3'.L2--f/ 1 " 2244 1" 1" '-----------------'----'-----! 33013-1270-1 NOTE 8 <$><$> SCH16B l I 1"-CH-151 ~ t-'--,---~fV'Vi~I----,----------, 00 I 0 ::r: I N {)l 0 N ~ I 0 ::r: I N 01 0 N 8 281B 3" l.!.J D N 01 0 N -I c OJ z G) 1 1 12 NOTES: 1. FOR GENERAL NOTES, REFER TO DRAWING: 33013-2241.

2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33D13-1265, REV. 8.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
5. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
6. CHARGING PUMP CLASSIFICATION SC/2 BOUNDARY INCLUDES DISCHARGE FLANGE, MANIFOLD, DISCHARGE CHECK VALVE, AND VALVE SEAT. REAMINING PUMP SECTIONS ARE SS CLASS.
7. PIPING AT NOZZLE MODIFIED PER PCR 2005-D015.
8. PER TE 2D08-D019, EPDM OR CORRUGATED STAINLESS STEEL FLEX HOSE MAY BE USED. PER TE 2008-D019, EPDM FLEX HOSE END FITTINGS ARE TWO PIECE, BUTT WELDED, SEAMED CONSTRUCTION.

C-1 33013-1265-1 REACTOR COOLANT PUMPS (B-9) 33013-1890 --._..::..::...:.....:.......c..::..::..:....__J x 1 5954 (B-9) 33013-1890 '--------' X15955 X370B 3-CH-2502 (J-1 O) l....---{:;:e::}-..:..... _____ ~33013-1265-1 [IQ] 1" I (B-1) 11 a: 2502 33013-1870 ~1:1284 358 (E-11) 33013-1266 X348B L---------- (A-1) ~ X2253 AUX. BLDG. EXHAUST (F-1) 33013-1273-1 2251 1" OVERFLOW (H-3) 33D13-1270-1 SUMP TANK 1 N N 01 0 1" 0 2-CH-151 0 0 1-CH-151 0 0 I 0 ::c I ~ 01 ~ 1-CH-151 1----11~1 ------------------~ 1-CH-151 3/4" TCH05 CHARGING PUMP SEALS LEAKOFF TANK 151 TUBING '--De(l--'-:J CONN. FOR NITROGEN PURGE W/ PORT. TANK 0 ~-.-"'---~-------~ 22~7 ~ Q 1-CH-151 2 3 269 1" ~ 0 OJ 3-CH-2502 N 01 0 ~ 2 288 8" '~Q SEE~ (H-1) 2245 1" L_E:.~-----=~:=:_:.:..:.::___:i.~I._l.2.___j 33013-1270-1 8-CH-2502 1"-CH-151 399 1/2" D E--iJi> 407H "PCH01C CHARGING 3-CH-151 PUMP C ffiJ 1/2" ~ ~ g I~ ~1 1" G) s ~I 2246 (E-1D) 33D13-1891 '-------_J X1 5915 4 1" 5 3-CH-25D2 ~ N -;:,.p01 N 2 c..,.i_..ll _..Q 01 ~ 291 8" N c,, (H-1) t-: ~ ,-----'----..C 00 1----'---I 33D13-1270-1 ~ 1" 6

r: J_

226D 2261 <MO/CPLRP1 B> PCH02B CHARGING PUMP SEALS LEAKOFF TANK RETURN PUMP B 00 I 0 ::r: I N 01 0 N 6" 3" SCH11 N <O 0 3/4" 24" CHARGING PUMP PULSE DAMPENER 289 3/4" (H-1) ~--------'----'--~----'-------'---133013-1270-1 <MO/CPLRP1A> PCH02A CHARGING PUMP SEALS LEAKOFF TANK RETURN PUMP A 7 2263 8 3/4" (A-2) 33013-1267 9 ~-ow*~" Afi MAIN LINE / ( t SAFETY CLASS 2, 3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT DRAIN & TEST CONNECTIONS X2267 10 SEAL INJECTION FILTERS 1 1 REVISED PER ECP-11-000789 -PCN-02-036 CAO FILE NAME 33013-1265 2 CONSTRUCTION LIMITED CONSTRUCTION: Afl NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 3 i '13 Afl BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCALE NONE ONTA.'UO, t£W YORK AUXILIARY BUILDING CHEMICAL VOLUME CONTROL SYSTEM CHARGING (CVCS) P & ID JOB NO. DRAWING NO. REV. EWR 3391E 33013-1265 SHEET 2 OF 2 ~ CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 3 4 151 TUBING 1" 0 (H-3) D [o o o o 406 ° 405 33013-1274 SCHED. 40 0 0 0 0 0 0 0 0 1-CH-151 ° 0 0 0 0 5 6 (B-12) o --<o ~~~;\\H><J-33013-1268 X1132 0 Q 0 0 (F-3) 33013-1274 7 X1656L 8 9 10 3/4" (H-9) .__3_3_0~13~-~1_2_69 __ >~----11R**------l/ I 1 1 12 ~*~~* r z ~SAFETY ClASS 2,3, OR SAFElY SIGNIFICANT (Q) DETAIL-A 0 0 0 ) O ~------l----+--- 400 402 RMW 359A LCH07 401 403 0 0 o N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PCH01 <MO/BABTP> BORIC ACID BATCH TANK TRANSFER PUMP (G-3) L_..:3~3~0~13~-~1~2~7~4'.___,;.>--'--- X1656K 1 2" v E--t~--.!L;~--1 421 TUBING 151 E 1/2" y 1" LCJ 1/2" LOOP SEAL (J-9) j;i f---1=2:0.2~-.2-B_-_----1 "'1 bl N r o 01 ~ N 0 N N r -I ~022D-D N N 0 0 (l) (l) cl [JJ z 0 N 0 (l) [JJ N 0 (l) 0 FF I 0 I I 0 0 at 0 0 0 w D ol_____j"'~~~ 3" E E ~;::====:':j::l!__ __ L 1------~3C"j------jil MANWAY 0 ~i EHTRCH02A BORIC ACID STOARGE TANK A HEATER TCH07A BORIC ACID STORAGE TANK A x OJ ~ 0 2" 0 ~i-1~1~2~"--j--------1 \\ 1.s1 ~ ~112" 0 0 0 (l) 0 0 0 0 I () I I 0 <.n N N... N 0 D 0 0 1-CH-151 ° 0 0 (G-3) (H-3) 33013-1892 .--~-~--xX15844'--------' 33013-1892 (G-3) 33013-1892 X15843'--------" 0 2" 0 0 0 I () I I ~ H-3 0 0 [al ~ ___.._._, J 0 0 0 3/4-CH-151 1--~

  • .--;r-- s 0

330A 0 0 0 2-CH-151 ° 398B 0 r-t---~---i-12019B FF 171L 0 0 N 0 (l) 0 0 0 0 105 3.i'.4-CH-151 IIT:i f-11---l/-- s o33ogoo 2-CH-151 0 0 0 398A 0 0 0 0 0 ~ 0 0 0 0 2" 0 0 33013-1269 0 I 0 I I X15841 X15840 0 0 (H-6) 33013-1892 (H-6) 33013-1892 0 0 (F-6) -CX::l-J 33013-1916-2 X6305 '--------' 0 LOOP SEAL 3" N I I Ul I 0 I 100 0 RMW TIC 100 ~ 375B 18" HATCH 397 MIXER 0 N I 0 I I 0 ("1 1/2" >-----+---! 0 ~cl 322 3/4" TCH06 BORIC ACID BATCH TANK ECH10 --~ BORIC ACID BATCH TANK HEATER N 0 0 2" 0 0 0 0 0 0 0 0 2-CH-151 (1-1) 33013-1262-1 X827A s 0 0 0 0 0 0 0 0 0 h I-O m 0 0 0 2-CH-151 ° 0 0 2-CH-151 0 o I 0 I I 0 330D (H-6) 33013-1892 ~------~x 0 0 0 <.n (l) <O 8-CH-301 0 0 0 0 0 3/4" 0 0 I 346A TUBING e ,. 151 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N I 0 I I <.n ~ 0 0 N 0 0 0 0 0 341 \\LO/ ~ 0 00 I 0 2-CH-151 ° 0 0 0 0 0 0 o 2-CH-151 ° 0 342 0 !ill 2-CH-151 o 0 0 0 J_~ 0 -I (l) 330C (J-9) 33013-1269 c__:::::.::_:_:::__:_:='--/ 0 RMW 0 0 0 0 0 0 0 0 N o I 0 I I 0 0


~o 0

0 0 0 0 2-CH-151 0 0 0 0 TCH07B BORIC ACID STORAGE TANK B PT 108 0 0 0 0 ... 0 );I t---~--I-z 12020B

==r;I OJ N 0 01 ~ N 0 N 0 r -1 ~200 - D LOOP 1" (G-3) 1/2" r--"-~,._-----,::1 v 421A 3"

I 1 /2" SEAL w

1/2" 0 1 1 2" v f7l 0 0 0 EHTRCH02B ,__ __ BORIC ACID STORAGE TANK 8 HEATER 0 0 0 0 0 TYP.SAFEIY CLASS BREAK POINT FOR VENT DRAIN & TEST CONNECTIONS 3/4" 1/2" l--__.~f--D'.--3 359B CHEMICAL ADDITION SCOOP (D-3) 33013-1265-2 CHARGING PUMPS 1" 327 TCH08 eves CHEMICAL ADDITION TANK I 0 I Q ~ 12201 I 0 I I LG 2680 12202 (B-1) 1" 3/4" f----L/'l'-'----l*~f---'----ll---':LC'----__J'-tl*4--133013-1270-1 271 272 273 WASTE HOLD-UP TANK 0 0 0 0 2-CH-151 ..f>.-'1-IFl--~-l--f'>.d-~-l-~~~~~_.~~~~~~~~~~~~~~~~~~~~.....-~~'4---'I-. 0 0 0 0 0 0 0 0 0 0 0 2-CH-151 (H-1) 0 0 0 33013-1265-2 3 ° 348B 347 \\_ 348A 0 0 0 0 (l) I 0 I o I 0 0 0 0 0 0 0 ~ FCH02 BOfrLfE~CID 3 4" .__...._-IHD 349A Pl 154 t-> t----\\ N2 GAS!:i f'1 z t ~ co TCH53 HYDROPAD

i Q

ACCUMULATOR f71~ t----\\ ~ 2240 (J-1) 0 8-CH-301 °.-------, 33013-1262-1 151 TUBING 8-CH-151 TCH54 X827B NITROGEN TRAP (8"¢-3.5 FT. LONG) I 0 I I ~ SEE NOTE 4 1 /2" E--'-'-"'--1_ SC~. 401 "' "' '" 0 0 0 0 0 -' 350 w 351 Pl 6243 s 14300S1 348C l/P 110A 3/4" 0 N 0 CHARGING PUMPS (1-9) 33013-1269 353 [ill RMW (H-3) 33013-1892 ~-------'X15846 (H-3) -ir---r-<'--~3~3~0~1~3-=..1.118~9~2~ X15845 s 14300S2 NOTES:

1. FOR GENERAL NOTES, SEE DRAWING: 33013-2241.
2. REVISION O OF THIS DRAWING SUPERCEDED DRAWING 33013-433
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".

I I Ul I 0 I... 0 0 PCH03A <MO/BATP1A> BORIC ACID TRANSFER PUMP A N I 0 I PCH03B <MO/BATP1 B> BORIC ACID TRANSFER PUMP B ~--~~3/f'+/-4'.'._" -J1--i1 0 346B s x ~ 0

4. VALVE 110A CLOSES WHEN BOTH BA TRANSFER PUMPS ARE NOT OPERATING, AS REFERENCED IN EWR 4375.

X6366 (1-1) 33013-1916-2 3/4-CH-151 0 0 0 0 0 s ----1..... f-----l (G-5) 2 1/2" [s~K~3~3~0~13~1~9~1~6,~2~>i:ii:~~~f---{ 15 PSIG PROCESS 6343 STEAM SUPPLY (G-5) SK33013-1916,2 CONDENSATE RETURN 1 ZHS191 1" 6318 324 z I Ul m N 0 0 0 2-CH-151 ° 375A 3" 1 1/2" 2" 1 2" 360B ~o 375C ECH011 N z I Ul 360A N ' 0 0 0 0 2" 0 0 0 0 I () 0 I I 0 0 o I ~o 336 2-CH-151 337 rr;g [QI 0 0 3-CH-151 ° 335 0 I 0 :r: o I 0 0 0 0 X1801 (B-4) 33013-1891 X14313S,__ _____ _,,. (D-3) 33013-1265-2 CHARGING PUMPS 2-CH-151 368 0 0 o N I 0 I I 0 (A-8) 33013-1261 0 0 l__-..~-11-- s 0 367 0 7 B-11 33013-1267 v X1103B Pl 6241 111 s (A-4) 33013-1891 (B-4) 33013-1891 x <O N <O 0 0 0

5. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.

"' "' °' 0 363A 2-CH-151 2@' 2" (G-9) --1 FT t-n;.;;;:--1-i;;,;:1--<::.___~3i:l3>Q0.1.:13~-=.!:12~6~9~ 111 360 359

6. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
7. NOTE DELETED.

M 2-CH-151 0 1108 ° [IT] 0 0 0 0 o RMW 3/4" 0 2238 0 BORIC ACID BLENDER 1-CH-151 -;;~--7E----7E-'--l----'-....::.-'-.:..;:..:...._~-t:x::J~~-j 0 SCH01 (ENLARGED PIPE) o~---------~o 0 0 0 0 2-CH-151 0 0 0 0 0 109 ° 1-CH-151 ~ (D-3) 1 °' 33013-1265-2 I 0 I 0 CHARGING PUMPS (D-6) 33013-1264 X110C 0 0 :; N '

8. VALVE 2243 IS A PERMANENTLY MOUNTED TANK VALVE FOR NITROGEN GAS FILL/

BLEED. CAD FILE NAME 3P126601 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. '~ GINNA STA. R.E. GINNA STATION SCALE NONE AUXILIARY BUILDING CHEMICAL VOLUME CONTROL SYSTEM BORIC ACID (eves) P&ID JOB NO. DRAWING NO. EWR 3391E 33013-1266 CCD 01 CONTROL COPY # REV. A B c D E F G H J

A B c D E F G H J 1 1121D 1122D 1 " 2 F-10 33013-1272-2 REACTOR COOLANT DRAIN TANK PUMPS (E -11) 33013-2275-2 1-CH-151 3 1100A X1281W 1121 c 1103C D 4 AUX. BLDG. WASTE DISPOSAL PANEL 1-CH-151 1122C 5 4-CH-151 (F-9) 33013-2289 P/1 3126 3-CH-151 6 7 8 9 10 1 1 12 (C-1) 1-CH-151 -J:><t-t 33013-1265-2 X264A.__ _____ 4" 2" (B-9) 33013-1269 4-CH-151 1122A 1121A X1247A 1103A (D-5) 2" 0 ~~ ~zf~ D ~ 33013-1264 >>- 0--- 0--- 0--- 0--- 0--- 0--- 0 X254 (D-12) I 0 2"


...-----11 °

~L 3/4" (J-9) (F-7) (F-10) 33013-1265-2 <D °' 00 I () I I (JI TUBING 2268 2267 ABANDONED AIN PLACE (D-9) 33013-2289 P/I 3126 0 )> _c.--- en x -u. 0 III en r )> 0 r0 -u )> ::;: Z)> fTI en r---< fTI X1656J (E-4) 33013-1274 NOTE 9A (A-3)

o fTI "'

33013-2289 >--fl--~ :;:: "' __) ~ ~ P/I 3100 fTI 0 (1-7) 33013-1890 ~-----~ X7381 AUX. BLDG. WASTE DISPOSAL PANEL 14233J 1100B [!;Q] '--------' X2265 33013-1889 33013-1890 X15800 '----------- 3" C-4 33013-1273-1 ~ 33013-1268 >>------------- X1133 ° 0 ~V 0 0 3-CH-151 0 1133A" 3" 0 0 0 (;J 0 -1>- <D 33013-1890 1732B 1049 1661 c 1.. 1100C [ill X12018 ~ ~ 33013-1274 (A-8) -c><t-i 33013-1265-2 3" X257 1100D [1QJ 010 '::1----=--='--'=-- ~ 2-CH-152 NOTE 8 ~::::j:::::::-~~::::::::::t~ - -1 12016B ABANDONED IN PLACE D I I I I I I 00 z G) X15969 151 1101C NITROGEN 2-CH-152 (G-7) 33013-1890 (E-10) 33013-2280 X1600G (E-4) 33013-1274 NOTE 8 ABANDONED IN PLACE D (JI

r:

12015B 0 Ul r 1101 B 2-CH-152 (F-7) 33013-1890 (E-10) 33013-2280 (D-4) 33013-1274 X1656G NOTE 9 /\\ X1600H ABANDONED IN PLACE 12014B D -1>- r o 2" X1656H (D-1) 33013-1870 NOTE 9 A McI 2-CH-151 (E-1) ~ 33013-1870 ~ l--2_*_... t-~2_-~C~H_-~1~51.:__ __ 3-CH-151 TCH09A eves HOLDUP TANK A 1123C [ill AUX. BLDG. EXHAUST (F-8) 33013-2289 P/I 3125


~

___,..,..~_: I I 1266 zs~1---~~~~~---+I y 3-CH-151 A _____________ _] TCH09B eves HOLDUP TANK B 1123B !ill AUX. BLDG. EXHAUST (D-8) 33013-2289 P/I 3125


~

fil 11655 I I A _____________ _] -1>-, TCH09C eves HOLDUP TANK C 1123A 0£] TUBING 151 3/4" 2-CH-151 24* I MANWAY AUX. BLDG. WASTE DISPOSAL PANEL 2-CH-151 1125 24* I MAN WAY AUX. BLDG. WASTE DISPOSAL PANEL 2-CH-151 24" ..----------t~l---1--------:---~IMANWAY 1129 1114 2-CH-151-~-1 2-CH-151~~~~! -1>-, I I tl ~ ~~ ).. I tl .1. I SUMP TANK r " ~ :1 _ --- -- -- -- -- -~ --_r_ 3 _:u_ 1 ~~-_ 1 1 _ -- -- --~~l_ - - _i __ (E-3) 33013-1270-1 I (D-3) c5 I I 33013-1270-1 I I I (B-8) SU_M_P_T_A_N_K _____________ 3-_C_H_-_15_1 ______________ ~- ----------------------------------------~ --~I 33013_ 1270_ 1 > L _2-c_H-15_1 _______ 1 v J_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _J C-12 33013-1889 1 X15811 l E-12 33013-1889 v X15816 <O °' 1 1 2" PCH04B <MO/SFP1B> GAS STRIPPER FEED PUMP B s c III z G) WASTE HOLDUP TANK N 0 NOTE 7 361 RR PCH05 <MO/RP> eves HOLDUP TANKS RECIRCULATION PUMP 4" D 1/2" 2" (H-8)


<< 33013-1266-1 h?:::t-X365B (A-1)


JI 33013-1273-1 >

VENT HEADER (D-10) 33013-2280 >-M-- ~------ X1600J (F-1)


;~_33_0_1_3_-_1_8_70 __ >

I 0 :r: I (JI AUX. BLDG. EXHAUST TEMPORARY CONNECTION TO FUEL TRANSFER CANAL 1.. NOTES: C-11 12011 B 1-CH-151 33013-2275-2 PCH04A <MO/SFP1A> GAS STRIPPER FEED PUMP A 3/4" SAFETY CLASS 2,3,0R SAFETY SIGNIFICANT {Q) \\~~~~Ase~~ LINE I

1.

FOR GENERAL NOTES REFER TO DRAWING 33013-2241.

2.

REV. "O" OF THIS DRAWING SUPERSEDES PORTIONS OF 33013-427 AND 33013-434.

3.

EXCEPT WHERE OTHERWISE INDICATED.SAFETY CLASS BREAKS FOR ALL VENT.DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A". 0 0

r:

o D 0 1105 159 1107 _(FE\\ ~ VE~.--..__-~~-;;><f~-'------' 12013 1152 (C-4) 33013-1268 CONCENTRATES FILTER FCH10 151 (A-11) 1180 RR 33013-1270-1 WASTE HOLDUP TANK 1 1" I () I I 01 1" FCH04 ION EXCHR. --;, FILTER 3/4" 1708J 2

o ;;;
o (JI

(;J X1281P 1164 RESIN FILL CONNECTION ON DWG. 33013-1264 (H-10) 1163 RR ~ _;_..--cH-151 (D-1) 33013-1270-2 SPENT RESIN STORAGE TANKS 3

o-
o"'

co ~ f\\.) I 0 :r: N I 01 1167 RR TCH10B CATION ION EXCHANGER B 1173 RR 2" 4 (H-4) 33013-1269 RMW 1170 RR 5 1" N I 0 :r: I 01 1172 1176 RR 1146 1147 +-::1 1144A RESIN FILL CONNECTION ON DWG. 33013-1264 (H-10) CH-151 TCH1 OA CATION ION EXCHANGER A 1171 RR 2" 2" 3" 6 (H-4) 33013-1269 RMW

o -
o ~

01 CXl )> I 0 :r: I 01 1-CH-151 1182 I I RR I 0 :r: I 01

o
o 1183 RR 3"

<D (JI 3/4" s RESIN FILL 3" CONNECTION ON DWG. 1184 33013-1264 (H-10) ~ CH-151 I 0 :r: I TCH11 B BASE REMOVAL ION EXCHANGER B 1188 RR 2" 1-CH-151 1-CH-151 1" I 0 :r: I 01 1186 RR I () I I DETAIL A TYPICAL SAFElY CLASS BREAK POINT FOR VENT.DRAIN, AND TEST CONNECTIONS

o-
o <O 0

1" N I 0 :r: I (;J 1189 RESIN FILL CONNECTION ON DWG. 33013-1264 (H-10) CH-151 TCH11A BASE REMOVAL ION EXCHANGER A 1187 RR 2" (1-4) 01 Y~--~c 33013-1269 1192 RR RMW (J-2) 3"


<< 33013-1264 DEMINERALIZERS R

-~~~~~~-.-~;r:;-~-L-~~~~---=-----<~~(J~-1~) ~ 2" 33013-1264 DEMINERALIZERS 7 8 9 10

4.

EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR LINES AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/ NITROGEN VALVE. REFER TO INTERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.

5.

ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 1 0328.

6. 3/8" SPACER ADDED TO ALLOW VALVE REPLACEMENT V-1127 ONLY.
7.

PER TSR 2007-0187, eves HOLDUP TANKS RECIRCULATION PUMP (PCH05) SPOOL PIECE IS SCHEDULE 40 WITH SLIP-ON FLANGES AT BOTH ENDS.

8. LT-156/154/153 AND ASSOCIATED INSTRUMENT AIR AND CONTROLLER EQUIPMENT IS ABANDONED IN PLACE.
9.

N2 BUBBLER AND FF-156/154/153 H/L USED TO PURGE o, & H, FROM eves HUTS. RJM t1'f CAD FILE NAME 33013-1267,1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES IS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION 1 1 SCALE NONE AUXILIARY BLDG. CHEMICAL VOLUME & CONTROL HOLDUP TANKS TO GAS STRIPPERS {CVCS) P & ID JOB NO. DRAWING NO. EWR 3391E 33013-1267 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

A B c D E F G H I J 1 2 3 4 5 6 (B-1 :J) 33013-1889 X15810 '-------------- 1-CH-151 0 0 0 X1650 1116 0 0 0 7 LT 151 E 'l ,---121328 ---1 I t;; t;; I I'-" 0::1 L'J L_~_ ---- -~-J ~D i----.....-::i v 12134 12132D 8 9 AUX. BLDG. WASTE DISPOSAL PANEL ~--_J -~---7~-~ 33013-1274 1-l>/'I- '------___JX1656E 10 1 1 1 2 2" (F-7) 33013-2289 P/I 3124 rn ~ 0 0 0 0 ~ 0 0 FF 151H 1-CH-151 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 ~ ~-------~ llJ (J> PI 148 0 0 ~ 0 ° CH-151 v 0 1 0 0 0 0 rn 0 I +- ~ (J> 0 ()) rn v 0 (J> O> 0 0 I 0 OI I 0 0 (B-12) 0 s (1-8) (l-1) 1157 0 FCH05 1 BORIC ACID 1124C -{XJ-~I X15809 (E-12) 33013-2274 BORIC ACID EVAPORATOR DISTILLATE COOLER N <D (J> --f><)- 33013-2274 X1128Bc_ _____ _,, v -l><J-- 33013-1267 X1296 ~-------' EVAPORATOR CONCENTRATES FILTER 3/4-CH-151 (D-7) 33013-2289 P/I 3124 D AUX. BLDG. WASTE DISPOSAL PANEL PI 165 1" ~ 1-CH-151 1-CH-151 '--~12~8~~,B--1{2>2~6B,_..:.--,-~....L..--,.-!_,,' ~ ,l------.-----'--""'--'-"'..'..--------1~2~2~6~A--------'--"-'-'--'-':'...'---------....-~1~29~4.fD....L..-..1...--f1>29<~0}-,/--1 F FCH06 _./ ~ CN t;; -f BORIC ACID w~ N

-,~~ ;t;;

Q v* EVAPORATOR

i>

DISTILLATE Q 1-CH-151 1" 2" FILTER (C-9) c rn PI z 163 ° 33013-1269 RMW N I 2" 0 ,-----------------**--*~---------i 'f (1-4) 33013-1907 CAUSTIC MIXING TEE (E-6) 33013-1269 RMW (J-4) 33013-1907 X4887 '----------- 1215 2" 2" 2-CH-151 2" 1207 2-CH-151 N N 223 1222 ~ N N (J> (J> 1" TCH12B BORIC ACID EVAPORATOR DISTILLATE DEMINERAUZER B N N N.,,. s 2-CH-151 TCH17B RESIN FILL HOPPER B ~~ -~--- 1228 I 0 I I (J1 1273 CH-151 I 0 I I (J> (B-5) A (D-1) 33013-1270-1 WASTE HOLDUP TANK (B-3) 33013-1270-1 WASTE HOLDUP TANK 2" (B-5) 2,, N N G N N 'f 33013-1270-2 U> SPENT RESIN TANKS 1205 TCH17A RESIN FILL HOPPER A 1229 1274 CH-151 v N N '-1 TCH12A BORIC ACID EVAPORATOR DISTILLATE DEMINERAUZER A N G 1204 < 33013-1270-1 i-l---- WASTE HOLDUP TANK 2" 1-CH-151 ~------~-; (B-5) 33013-1270-1 WASTE HOLDUP TANK (B-3) 33013-1270-1 WASTE HOLDUP TANK B-3 33013-1270-1 WASTE HOLDUP TANK 1 1" 2" 1201 1200 2 .3 4 5 I 0 I I (J> s 2" (B-1) 33013-1271 X9137 '-------_,... 3/ ~-CH-151 (A-4) < 33013-1269 RMW PUMP SUCTION (A-3) 33013-1270-1 WASTE HOLDUP TANK 6 2" 2" 1239 [9 (N I 0 I I <D <O TGH13 BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK 0 0 0 0 CH-151 1210 3-CH-151 MANWAY EHTRCH03 BORIC ACID EVAPORATOR ~--- CONCENTRATES HOLDING TANK HEATER (G-9) 33013-1269 >>-------- RMW 2-CH-151 0 0 0 0 0 0 (G-9) 33013-1908-3 MIXED BED DEMINERAUZER 3-CH-151 1-CH-151 1" 1255 1 9144 N ~ I -~; ~ 'i! AUX. BLDG. tv N, WASTE DISPOSAL DISCHARGE FROM CHEM NUC SKID SEE NOTE 3 20" MANWA~ PANEL (D-10) 33013-2289 PI 3127 O> I 0 I I (J> N v I 0 I I (J> PCH07A <MO/HTP1A> BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK PUMP A ~~o --i-) 0 111 7 0 0 N I 0 I I (J> 0 1141A ~ PCH07B 1-CH-151 <M0/HTP1B> BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK PUMP B L__o--f><l---1-o-+----) 1143 1-CH-151 0 0 0 1132 0 3/4-CH-151 o 3/4--CH-151 l--Ml-----11 s 1131A 0 0 0 0 0 (A-6) 33013--1266 Pl 186 1-CH-151 2-CH-151 (A-8) 33013-1267 HOLDUP TANKS (D-6) X404 0 1------+1-------------1~'l-------~h~ 1 ----~< 33013-1892 20" MANWA~ AUX. BLDG. WASTE DISPOSAL PANEL (F-10) 33013-2289 Pl 3127 1.--~ l~1 I N I I I L@;)_cn_11_~ 01 I 0 I I v (C-6) 33013-1892 ___JX15836 0 0 0 0 0 0 3-CH-151 3-CH-151 N ()) 20" H--- MANWAY N I 0 I I (J> 7 3" 3" 3" TCH14B MONITOR TANK B SEE NOTE 5 N 01 3/4" 1276 ~----~---------~151 TUBING 1" 1238 3-CH-151 (B-5) 33013-1270-1 1" 2-CH-151 SUPPLY TO _ CHEM-NUC SKID SEE NOTE 3 WASTE HOLDUP TANK 8 PCH06 <MO/MTDP> MONITOR TANK PUMP 9 20"1 MANWAY TCH14A MONITOR TANK A f SEE NOTE 5 1278 ~----~---------~1s1.1 JUBING ~ N _J ~ 12281 (l-6) 1 1/2"


~-~<

33013-1270-1~ X1762A ~ (E-11) -R--j 33013-1271 > 1249 WASTE DISCHARGE ~ UNE (C-4) 33013-1269 1252 [9 ~-~CH-151 (B-9) X1250 NOTES:

1. FOR GENERAL NOTES SEE DWG. 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDES 33013-427, 33013-428 & 33013-434.
3. CHEM-NUC SKID EVALUATED UNDER EWR 4999A, SAFETY ANALYSIS, "CHEM-NUCLEAR UQUID RADWASTE DEMINERAL -

!ZING SYSTEM".

4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICETD IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.
5. SEISMIC CAPABIUTY OF MONITOR TANKS "P:,' AND "B" UPGRADED UNDER PCR 2005-0037.

CAD FILE NAME 3P126801 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PREUMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. '~ GINNA STA. R.E. GINNA STATION SCALE JOB NO. NONE AUXIUARY BLDG. CHE~HCAL VOLUME & CONTROL BORIC ACID EVAPORATOR TO MONITOR TANKS (CVCS) P & ID DRAWING NO. REV. .__,..__ __ ~... --=2: ___ M*--I 33013-1259 > 1256A ~-----~ EWR 3391 E 33013-1268 [QJ CCD 01 CONTROL COPY # 10 1 1 1 2 A B c D E F G H I J

1 A B v c D E F G H I J 1 20" MANWAY 20" MANWAY I 2-CH-151 1283 4" I 2 v q TCH15 REACTOR MAKEUP WATER TANK (SEE NOTE 5) Al SEE NOTE 6 1284A 2 s 1 2" 1--'-~=-:i 1/2" >--~-:i 3 1286 1-CH-151 3 4 5 (J-6) 3" ~ 33013-1268 >>----------~ X1239 1285 N I 0 I I X372 X381 X792 X374 X376 X4881 (J-11) 33013-1268 (I-7) 33013-1264 (J-4) 33013-1264 (H-1©) 33013-1248 (J-6) 33013-1264 (I-7) 33013-1264 (E-1) 33013-1911l7 (G-1) 33(1)13-1264 DEBORATING DEMINER. B 1261 X1252 2" 1 1/2" 3-CH-151 2" 2" 2" 2" '1' 2" I 0 :r: I (ft 3" X1214 X823 6 (C-5) 3311l13-12711l-1 WHT PCHlll8B <MO/RMWP1B> REACTOR MAKEUP WATER PUMP B 3/4" PCHlll8A <MO/RMWP1A> REACTOR MAKEUP WATER PUMP A N (C-5)

j

~ 3/4" 0

< 33013-1270-11,__ __ -l c m ~ z 0 <.n WHT (G-1) 33013-1268 (C-1) 33013-1245 N.... OJ 0 7 1-CH-151 2" 2" 2" 1241 8 N I 0 I I 1--~F-x"l-~..l.-...-.... ---1 <.n 1257 2-CH-151 1-CH-151 2" X11 lll3A X1245 2-CH-151 X1248 X1124D X5©8 X1683A X1682 X36Ql X1141A 9 10 2-CH-151 (J-10) 33013-1268 .:....:___, X1256A (A-12) 3311l13-1267 (E-1) 33013-1268 (J-1) 33(1)13-2275-2 (D-1) 33013-2274 (I-1) 33013-2274 (F-6) 33(1)13-1258 (B-11) 33013-1270-2 (H-1) 33013-1270-2 (H-11) 3311l13-1266 (C-8) 33(1)13-1268 2" 1246 I 0 I I <.n 1-CH-151 2-CH-151 1-CH-151 2-CH-151 2-CH-151 Tq,1--..,e--, 1141 1" 0 0 0 0 0 0 0 N (J) N N I 0 I I <.n N I 0 I I (I-8) 2-CH-151 © i-------------------+----------J -~-----'c__[__,_ ___ _, 144 i------3~8~71f-------------------------e----~-J 391 J Hlll1 (H-3) ~ 33013-1267 X1191 (I-6) 33©13-1267 X1176 (I-4) 33013-1267 X1167 (I-10) 33013-1267 4 2" N I 0 :r: I 2" 1------------1 <.n t' t' 5 X9134 X359A X353 X201 X3758 X217 6 7 8 33013-1276 (A-9) 33013-1266 (E -11) 33013-1266 (G-1 Ill) 33©13-1264 (D-2) 33013-1266 (F-5) 33013-1266 9 3/4" 10 2" [lJ 2" 2" '[ 2" 2" I 0 I I <.n 2" 1 1 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 3311l13-2241.

12

2. REVISION "Ill" OF THIS DRAWING SUPERSEDED DRAWING 331/l 13-428.
3. ALL PIPING ON THIS DRAWING rs NON-NUCLEAR SAFETY CLASS.
4. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

A B c D E F G

5. RMW TANK (TCH15) HAD DIAPHRAGM AND H

ASSOCIATED SUPPORTING HARDWARE REMOVED /\\ 6. 00 1 1 PER PCR 2004-0003. SEISMIC CAPABILITY OF REACTOR MAKEUP WATER TANK UPGRADED UNDER PCR 2©©5-0©37. CONSTRUCTION UMITED CONSTRUCTION: AS NOTE:D PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BU!LT DATE RELEASED FOR FN:nnY GINNA STA. R.E. G!NNA STATION SCALE NONE JOB NO. EWR 3391E CCD 01 AUXILIARY BLDG. REACTOR MAKEUP WATER eves p & ID DRAWING NO. 33013-1269 CONTROL COPY # 12 REV. J

A B c D E F G H J 1 EQUIP. DRAIN FOR BORIC ACID STORAGE TANK B EQUIP. DRAIN FOR BORIC ACID STORAGE TANK A EQUIP. DRAIN FOR BORIC ACID FILTER (G-4) 33013-1276 X9121 '---P-OL-IS-H-IN-G-~ X273 DEMINERAUZERS D-12 33013-1266 (1-8) 33013-1276 X9127 '--:..::.__ ___ ...../ (E-1) 33013-1870 AUX. BLDG. CHARCOAL FILTER (J-1) < 33013-1272-2 AUX. BLDG. SUMP 2" c:l OJ ~ 2 3 4 (G-1) "' EQUIP. DRAIN FOR ,,_C ~ ~ ~ CCW PUMP A ~1-i:J " --C><l-l 33013-1250-2 X806D 5 EQUIP. DRAIN FOR CCW PUMP B 6 EQUIP. DRAIN FOR AUX. BLDG. EXHAUST FAN A I~ I (H-11) ~ (C-12) 3 4" I 33013-1259 ~. 33013-1245 I ~ X737c t 314:;--r 1-301 (E-5) X1749 EQUIP. DRAIN FOR ~I (D-12) I 33013-1245 I X806C CONDENSATE RETURN PUMP r-:;;~E~-;:5;-;;:;::::;-""-.;,3if4'~' :::::J--y >--'-------! I 33013-1250-2 -c><1--1 33013-1250-2 I ~ X737D J-6 301 I 3/4~ (G-1) ,.,.,-,~I ~I y EQUIP. DRAIN X737B 3/4" 2" I ~ FOR BORIC ACID I 1 TRANSFER PUMP A ~3".J I J-o EQUIP. DRAIN ~.. L_ W-L FOR BORIC ACID I TRANSFER PUMP B 3} 3~ BORIC ACID I _j I--' uBATCHING TANK 3" EQUIP. DRAIN FOR REACTOR MAKEUP WATER TANK 2" !--'-----! I 33013-1250-2 H><J-33013-1268 ~ I X806B J-1 1~301 J-1 2" 33013-1268 >--"-.i_---, I 33013-1268 X1204 I -...__:_::.:_:;:__ _____ _, X1273 X1203 3.. J-1) 1-1 2" f- - 2".----~~-'-i><J-33013-1268 33013-1268 '----==.:.::.._:_:=__J x 1201 X1216 1-11 33013-1271 x 1 7 84 L_.:_:_:c:.::___:_::.:_:__....... (J-1) 33013-1268 X1274 '--==_:_=:___.... H-1 2" 33013-1271 X2613,__ _____ X2614 (J-1) 33013-1271 3" 3/4" 1-1 2".-----"---'-'-----,-, 33013-1268 1-r'><'I>- -...__:_::.:_:;:__::_:;:__, x 1207 311*. (1-8) < 33013-1268 r,_,,2_" l-~I 1 1 MONITOR TANKS & PUMP I I s-5 I I I 33013-1259 11 '-.-. ----~x1277B --1_1 r-.. I 1r11/2 13"1..-11 3/,:.4-~C~-~6~-, L - 33013-1269 K><J-2" 3" X1277C X799A X783D (F-7) 33013-1870 HEPA FILTER UNIT G (D-10) 33013-1248 (H-6) 33013-1248 4-WD-151


t-- -1 I

A-5 33013-1890 (D-9)

tJ~~~~~=>-=~

3/8" 33013-1247 ~ X686K&L (D-1) 3* - '----<:......_~3~30~1i_.:3:-:_i1!_2~61~_J

-------~B-5~-------r-----------t l~t----:-- t l~t R~~~~~ ftJ~R I

33013-1890 (F-8) CLEAN X15984 CLEAN ~-..JI-~- C-10 33013-1247 OUT OUT --=--. I 33013-2289 RESIDUAL HEAT REMOVAL 2" C-8 33013-1247 c:l OJ- .--1---~ I HEAT EXCHANGER A :r-3.. P/I 3117 I ~ ~ ~ 1---,--------------~--T- ---- "'..+------f--1--~""'i ~ ~ z "' t;) 12191 w I 3" I + \\-<;+ + I + ~ I~ ~ ~* II~ F-2 Q RESIDUAL HEAT REMOVAL HEAT EXCHANGER B I ~ ~ TWD09 AUX. BLDG. SUMP TANK 2" CLEAN I 33013-1267 OUT I w X1070 I CLEAN eves HOLDUP TANK A I OUT F-6 L 2" -J----<:..._~33~0~1~3=-~12~6~7_J I X1271 '-------~ I eves HOLDUP TANK B 7 2" 3" 2" 3" 1791 (G-10) {~~;!~~:::::::>---!4'~'--1 --J.x.1-, 33013-1272-2 X1001 WASTE DISPOSAL I E-9 ,. y PANEL L2" 33013_ 1267 1 _1___ EQUIP. DRAIN FOR GAS 2" I X 1270 I STRIPPER FEED PUMP A ~----6(1---'L...L:..' --Yx!---J----i I eves HOLDUP TANK c I 1119 1120 I I g PWD06B 1-1 _;r*_ -,- - - - - - - - - - - - - --- - L-D--y EQUIP. DRAIN FOR eves <MO/STP1 B> + j + HOLDUP TANKS RECIRC. PUMP ~ AUX. BLDG. 1 1 . T EQUIP. DRAIN FOR GAS BWD03 G-10 33013-1272-2 X1073 0 1" ~] 1074 I SUMP TANK I STRIPPER FEED PUMP B ~ PUMP B I~ 11uB1NG I.!. ~~ ~ I~ 1018F I ~~3" r-1 I B-2 33013-2274 ~3"]--o GAS STRIPPER CLEAN EI OUT EL_i ~3"-------------3--D-- ~ 4 ::"J..n EQUIP. DRAIN FOR WASTE CLEAN H _j v HOLDUP TANK OUT El_ ---JI -INSIDE SPENT RESINROOM 3* r - --0 EQUIP. DRAIN FOR SPENT 4" RESIN TANK B EQUIP. DRAIN FOR SPENT (]- - --1 RESIN TANK A I 3" ,---0 EQUIP. DRAIN FOR SPENT RESIN TANK A (G-6) 1" --i:><t-1{~33~0~1~3~-~12~6~5~-~2:::::::>---------2...--( INSIDE SPENT RESIN R.:.O.:.OM::.:_ __ X280B (F-6) 1 * --C><l-l 33013-1265-2 X280A 1-6 1" --i:><l-l 33013-1265-2 X280C --C><l-1 33013-1265-2 X281H (G-1) _____ _j L__ 4" I 1" I I 3/4" E~c-r <::~_3_3_~-~--.:.-~_2_89 _ __:---~ 1

~

15-4 G-f P/I 3118 (J-1) 33013-1265-2 X2256 1-WD-151 (A-7) 33013-1870 AUX. BLDG. CHARCOAL FILTER 3/4" 1734 1737 NOTE 6 1" 1762 2" r.l 1792A 3/4" 1" 2602 1610A 2-WD-151 PWD12 <MO/WEFP> WASTE HOLDUP TANK PUMP ~ Y 2 ~*792 1/4" _.__ 122:0 I (A-1) 33013-1271 D X1782 ~ 33013-1261 X881A 2" 3" 2" I 1---IllillNG >~~~~~d~~---+-[-D---i 4~* 3 ~ 1-11 L'. 1 -"-f>.<l----t 11 /2"r-~33;0~1~3=-~12~6;8;---':;>--t><lf- ~~t[~~(~D~-7~)~~>--'--~31Li: 4":____--i r1 - 33013-1265-2 X282B I I 2" I


1 I 2*

3/4" 1-- c5ec,.N E---t-[-- _3~ - ~ (H-7) 3/4" 2" --C><.J--1 33013-1246-2 X2719 (E-7) -{;><f-j 33013-1265-2 X282A f-19> (A-6) 2" E 4" I L..:3:.:.3.::..01:.:.3-_1...;c2_64~>>------_;__-----t- '--(]- - _J NON-REGENERATIVE HEAT EXCHANGER 1 2 (D-7) 3 4 SEE NOTE 5 FWD03 ULTRA FILTRATION SYSTEM 1762AL f----. WD-301 0 0 0 1650 0 0 0 0 0 0 0 1769 1653 1654A 5 0 0 X12281 (A-5) -...__3:_:3..:_0_13_-_1_2_6_8__. x 1116 6 (J-1) 33013-1270-2 k 0 I 7 4" I ~ I N 3/4" 1 1 2" 4* 3" 8 (F-10) 33013-1273-1 J-10 33013-1273-1 (F-9) 33013-1267 eves HOLDUP TANK X1610C X1610D 9 10 1 1 4" 3" I~- -r-0--,- t (J-1) )_L::-*-~ 2*~*<::.==3~3~0~13~-~1~2~6~7:::J I I I I I ll'.~ (D-2) 2,, I _j v 33013-1264 >>---- 1--;:::+.-, I I 2..

':J..n 2"

2" (C-12) 33013-1273-2 GAS DECAY TANKS A & B (F-12) 33013-1273-2 ~ GAS DECAY TANKS C & D 4" I t j t I u __ ~ v I I I L3.'._ ____ :J-o 2" 1" ~----i <i-----:J 3" 2" 2" EQUIP. DRAIN FOR BORIC ACID EVAPORATOR CONCENTRATES FILTER EQUIP. DRAIN FOR ION EXCHANGER FILTER EQUIP. DRAIN FOR BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK EQUIP. DRAIN FOR BORIC ACID EVAPORATOR CONCENTRATES HOLDING TANK TRANSFER PUMPS C-1) 33013-1265-2 (J-1) 33013-1270-2 (1-8) 33013-1992 12 X1610B X264B FIRE PROTECTION X9239 (F-1) NEW G:Jrn I I N ' 1/2" 2" 33013-1.866 --...__:::::=::.....:=:;:__J X6320H (F-1) 33013-1866 -..._=.:.:_:c___:_o__~ X9980 FLOOR DRAINS LOCATED ON EL. 271 '0" SAFETY CLASS SAME AS MAIN LINE l SAFETY CLASS 2,3 OR SAF£TY SIGNIFICANT (Q) DETAIL-A ~w DRAIN, WHEN NEEDED, / TO HAVE HOSE. RUN TO N _J TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES: AB SUMP TANK TWD10 WASTE HOLDUP TANK FLOOR DRAINS LOCATED ON EL. 271 '0" 4"

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1270 REV. 4.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO INTERFACING AIR/

NITROGEN DRAWING FOR SAFETY clAss.

5. THE ULTRA FILTRATION SYSTEM IS rnrnrn~R~N;sA~~~;N;r;~rnrnrn 1-<;

I-<; I"""' 1-<; 1"""* I ' 1"""* 1-t; I-<; I-<; NOT AN OPERATING PACKAGE AND ALL SKID ISOLATION VALVES ARE CLOSED.

6. Fl-1007 IS NON-SAFETY CLASS AND WAS REMOVED FROM SERVICE BY TSR 93-024.

L __ l __ _l_

7. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

I----~---------~' CLEAN

i OUT 4" CLEAN

~------'--:J OUT 4" ~-'----'-'-:J CLEAN OUT

8. 4" SURESEAL INLINE FLOOR DRAIN TRAP SEALER EXISTS IN GAS DECAY TANK ROOM FLOOR DRAIN.

CLEAN OUT r.l 4" 3/4" 8 (D-10) 33013-2289 P/I 3117 3* CLEAN OUT r.l (F-7) ---<< 33013-1870 CHARCOAL FILTER G aJ ~1 re, ox, 0* ~ SAFW RM 10:;: ~ r-I ~"' r6 r6 FLOOR TRENCH 1 0. A........,-;::-' r4_"_+- - --_J"; - _J"; - _J "'; 4-AC-152 9 12198 WASTE DISPOSAL PANEL LI 1001 10 (C-6) 33013-1245 "------~ X732 (B-1) 33013-1891 REVISED PER RJM AJ c. AJ'C \\ 1 F ADC-14-001038 <-=--+--.--,--+-~~+--~---i 11/5/14 11/JI ti.{ II JI llf. tdn l"J l1llAWl\\I BY CHECKED BY RESP. ENO. CAD FILE NAME 33013-1270 1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED (8-1) PRELIMINARY NOT FOR CONSTRUCTION 33013-1891 BIDDING PURPOSES "------~ X15946 1-'/'.11 :'!" c.:'~Ll-------"AS'-"'su,,,1Lr,____ ____ +'--"'-'""'-l 1 1 DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE WASTE DISPOSAL-LIQUID WASTE DRAINS, HOLDUP TANK, SPENT RESIN TANKS (WD) P & ID JOB NO. DRAWING NO. REV. EWR 3391E 33013-1270 SHEET OF 2 ~ CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 3 4 5 (G-4) (H-4) r A[ i~~~~~===::>---lf-"----------i"'/-------------/f"'---- Q ~ I 33013 1891 11 11 II X14319S


Ii"'--<~~' - -

C-- 33013 1891 1x14:31ls (A-4) I 33013-1274 NITROGEN (C-4) -l><f1 33013-1891 H X15934 (C-7) < 33013-2289 I H P/1 3114 (E-3) A 2" L...:3:.:3:.:0..:.1.:.3_-.:..1 2::.7...:6c__,.->--_:::..-, X9133 I (1-3) A ,.--~~------.. 2" , I 33013-1268 >--.....::_-l X9143.__ _____ / (J-3) I 33013-1267 ION EXCHANGERS (H-1) '>--'3'-"-'-- 33013-1273-1 11----- (H-10) X 1~ 33013-1892 >>---11//-- (H-10) f697 -ff - -/f - -ff-2" 2-WD-301 2-WD-301 MANIFOLD . ~ 122278 D .. 12227D LT 1005 I 1684 16~ ~ 151 I C-2 I 3/4" .,...-, 3/4" ,-0 '~. *Ooo 0-1; '" 0 "' '" 1; FF 1005L WASTE DISPOSAL PANEL !(Cc - -LI~ LI 10058 1005 1005 I FF 1009L WASTE DISPOSAL PANEL ~I - -L2\\l MANIFOLD r-+-- - --+~ 12228s 1009 1009 I I LI 10098 122280 ~. ~" r---; 1 009 r---1 "~ l

  • .--~(*~--~7)_...

L....j 33013-2289 3-WD-151 P/I 3114 3-WD-151 ~..., 2" -/f - -ff- ~C[S:J __.. ___ -,,-- "'-*------.~---~ '1---~2~*--4:41689 N, 2" 1699 1698 -l><l-1 33013-1892 >>---ll//-- -/f - -ff-7 7 r---t - X14277S r--t- -- (H-4) - -,.------~,>- I TWD05A SPENT RESIN TANK A 33013-1891 X1432 JS-----'-----~/ (G-4) ~ 33013-1891 H " X14318s>--------~ (A-4) I 33013-1274 [---- [=---- (F-9) _Q zc ~,Vl 0-f'l 0,.,, 00 ~,~ 0-rO ,.,, r,.,, 1700 l -If-I 0 I ~ 1641 15112505 -;/4" ~

/8",

1~59() i6s6 (C-6) _.----~(D_-_4~)--,X15936 I* PT 1006 33013-1891 E-4) I 33013-1891 X15S3i 1'------~ PT 1008 ~ L:::-Jt. ..=~ -~-f---1~ 1642 I 2505 151 - 3/8"'...-... 3/4" 1691A 1691 (D-6) 33013-2289 \\._ o~,~ Pl rl 33013-2289 P/I 3113 ,~ 10068 --D3/4"~ iss4v ~ 151 2505 12299 " 10088,., P/1 3113 )1650 ....... rri PC Pl ,, "1z29~@ 1008 WASTE DISPOSAL PANEL --i ~ 3/ 4 ::..-c_ Ok -..J....- l...J 2655 2505 151 -:. 7 0 ~LJ 1-WD-152 152 ---,-151 1" . ~ 1658 r-------~' I '>-----------~ 1/2" :

1/2"

_6 6 I 33013-1269 r~ ~ 7~ 10F6E8

  • ,,,, r T.F.. -:~ **;* :

2" c-::.i


11~-----...----- -

1682 PRIMARY MAKE-UP WATER (G-4) N I 0 I z G) 1---1.Hi,!----( 122296 )> z N

  • 7 N

z G) ~ ~ '~ 1702 TWD058 SPENT RESIN TANK 8 1-- N i 0 I 6 _o zc (/)I_, (/) 0 ,.,, 0,.,, 00 CIC Q1 rn 0-rO ,.,, r,.,, I x :;:17 ~l :i 0 (/) N i 0 I 0 7 8 9 10 1 1 12 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1-WD-151 0 0 0 0 NWD04 .---4'.--1'--- ... j65 'ij J 2657 0 r\\/ II ~ 1799A 2660 r-1 2661 r ~ ! 3/4" 17998 ~ 2678 2662 1.~r -D "3/4" 17980 I~ 1]99(: 2664 r-1 2665 2666 rl.-- 7 2667 .._ 1"Y"' / II [..J 1798~ ' 112". ~ 2676 - 2668 r-1 2669 17990 2670 1..,,,r., -D 1 f9is 1---:J.. v 2672 -1~1"'!'

  • .,.__1-rl.--_. 7

\\ v 2673 0 0 0 0 0 0 0 0 0

J 1654!J

.J 1" - ~J---la---1 s 2651 ~tT' 'T -_.2~"-,.__-l~-------j',.,-~*.._ _ _,__~1-_W"-"D_-~1~5~1 _ _,_l __ ~~t--i-----~<::==~~~~~~ 33013-1269 1797 1683A 3/8" O.D. TYP. Ill rn -/f -


11.:*~ ---*--t-3 1798CUS 1799CDS

~ - ---;+-,;' - -/f 1798CDS 1799CUS --ff - -ff- - * - fl-- -:r = -ff- =-If .,"-----11-.. "----H-- ~ ~____,..._;~ 1799DUS 1798DDS 1 = = = = = --ff - * - * - 71#--,+r'/ - * -

  • 1799DDS 1798DUS
  • -
  • _.,,.,"-----,If-;' - * --II,,"~-------t~l--+3 17988US 1799BDS

~ - ~ -


1,~1-------#-,," -

-ff- -11"-----11-"----7"1--- 1798BDS 17998US 1799EUS 1798EDS -.-------+3 1799EDS 1798EUS PRIMARY MAKE-UP WATER (G-9) 33013-1892 "'---------' X 14268S (G-9) 33013-1892 '-------'X14269S (F-9) 33013-1892 '-------~x14266S (F-9) 33013-1892 '-------~x14267S (F-9) 33013-1892 '------~X14265S (E-9) 33013-1892 '-------'x14264S (D-9) 33013-1892 -._ _____ __,X14262S (E-9) 33013-1892 X14263S (D-9) o o:,::""'1;------,"'1-----~"'---- _,~.... ~.... 33013-1892 "_::_::.::...:.::__..:..==--' x 14261 s 0 0 0 0 0 N, 1l99E -D 179sl\\ 2674 1798AUS 1799ADS 1798ADS 1799AUS (D-9) 33013-1892 '------~X14260S ~rnc-~c PS MAIN LINE / t -t_ SAFEfY CLASS 2, 3, OR SAFETY SIGNIFICANT (0) DETAIL-A TYP.SAFElY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1270 REV. 4.
3. EXCEPT WHERE OTHERWISE INDICATED, SAFElY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. EXCEPT WHERE OTHERWISE INDICATED, SAFElY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO AIR/NITROGEN IN-TERFACING DRAWING FOR SAFElY CLASS.

~ 33013-1891 >>---lil/~-- ~ r 0 X14316S I (E-4)

-N-1 33013-1891

>>---ll-#--- X15939 (E-4) ~ 33013-1891 >>---lf//---1------j"f---o 1t X15938 I (1-10) Lu..... -*"--" I > " I 1 FC ~ 33013-1892 >-,,,.,~1 v68o' X1069AH1 0 ') 1069A 10698 ~ ~ D 122~9D L r#r-\\ w~__, .. ~r---<w 2-WD-151 '°'"""~ ~ STATION) I: ,~ ~ 12293 (C-4) -:--/---<< 33013-1891 f-rxi-- X15932 " I FC (8-11) 1 ...o1111i;;--..Q ~ 2-WD-151 33013-1270-1 11------~---------------------~------------------='----------' TO WASTE HOLD-UP TANK (J-6) 0 0 0 0 0 0 0 0 0 1" 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0


~-~----,, 0

~, 33013-1270-1 1f----------------------------~*-.--------------------------------------' X1654A 1 2 3 4 5 6 0 0 0 0 (1-10) ---11-#--<< 33013-1892 1--i><r: ~-----~X10698H1 0 0 0 7 8 9 10 1 1 /\\ EVlSEO PER RJM AJ"C. AJ'C crp~ M c-13-000390 l--'*/~2~6/~1-31-~~3"'0~/"l3+/-'i'!-i"J~o'°13+/-'1=;o~,,-1 CAD FILE NAME 33013-1270,2 CONSTRUC110N LIMITED CONSTRUCTION: "5 NOTED PRELIMINARY NOT FOR CONSTRUC110N BIDDING PURPOSES '-1.30 i3 AS BUILT AJC.. DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE WASTE DISPOSAL-LIQUID WASTE DRAINS, HOLDUP TANK, SPENT RESIN TANKS (WD) P & ID JOB NO. DRAWING NO. REV. EWR 3391E 33013-1270 SHEET 2 OF 2 Ah CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c 0 E F G H J 1 2 3 r c1-6) ~ I 33013 1270 1 i1762 I a 1 WO 151 A X9144 L NOTE 4 NOTE 4 (E-6) _r 33013-1268 '---~M~o-cN1=cTo'"'R~TA-,.,N"'"'Ks=-' 1 9137 L lNOTE 4.--~(_l-_3)~----. 1782 2" 1" 9105 --1'C:>l 2"...._1',.:1_*.---1-~<iif- ~ 9105 1644 A I x'§104, 33013-1276 / 1" r (C-6) ~ 33013-1892

>~-----~h'I-' --~

X7036G '------~ LNOTE 4 I CJ I 4 1765 I 1-WD-151 1764 I CJ I -"' - r (B-6) ~ 33013-1892 X7036H

>~---*H---

2-WD-151 2-WD-151 LNOTE 4 NOTE 4 (C-8) 33013-2289 '--'-'-'--'-----'-__J' P/I 3115 (B-6)

33013-1a92 X15835 fD-6)

A I I 33013-1 392 v X15837 ~v vf' 1" LK_r-..,_l-+-... '--- 1 (.._..! 82s8G -(}- --:J 1--1'-"--' 8259G 1" 151 TUB-TUB-151 I.. 3/4" ING, ' ~ ~.--'----. J-L 'I 1768 i-r_-~ ING 3/4" 112"v--~ -~1~~? ~ f-------1 TWD11A WASTE CONDENSATE TANK A ~J,l.--- - LI LI 1012 1013 N' 0',l TWD11B WASTE CONDENSATE TANK B

  • r------J

~IT ~.?~ ~:~T LIV' ~SJ t t ~~" t~-11-" -=::.J - __ __,,"~---~'* (LC\\_:" 'w I~ ~I'°' I (10~~B~' '~1o~~A i ~NOTE_3 WASTE DISPOSAL PANEL,,


,,11---

3f4" k L (D-8) 33013-2289 L_ '-----~,--- P/1 3115 v 2611 1712 Tl 11000 Pl~ 1 /2" 1018G SWD20 2" 0 I f--t-_,oM--S 2607 151 C-1 ~,) 5 1" 9138 1-WD-151 2" 1" 6 I FWD01 ACTIVATED CHARCOAL FILTER I 1 1 --.i.+T.....-- s 2640 7 8 DISPOSABLE MIXED BED DEMINERAUZERS B -}--- O> DWD01 t:'

  • A

-}-- i---..--i_~- 2636 DWD02 f-_....__s 2637 9 EWD11 WASTE EVAPORATOR DISTILLATE -COOLER r---- 10 NOTE 3 3/4" D u 3/4" l.J'-,J--"---'-------'-ll><l-_1,__ _____ _,__~-~*x::i---------'-----'-~--'~-.._,~---:3 i- -t.--' 2641 2632 263 i L!.J (H-10) I 1 " 2-WD-151 f---~,.-/~,'--.-----fr------------------------=-_:;_=--_:_::_;___ ___________________ -<, 33013-1259 I., 1781 X1743 I ~ I - 2-WD-151 (1-11) /,.----'---"-----, - - ,-----------------~---------~------------------<, 33013-1268 I, - ( I WASTE DISPOSAL PANEL (D-5) 1"- '-t i6oo .JR\\__, -

  • '~-" isoi 1

.~ -'\\ r'.. ) - --------i I I I RM-18 I ~ I LIQUID WASTE DISPOSAL ~ MONITOR SKID I " I 1 1/2" ~l

r: -'

FILL E~----J u t;)i I~ H 0,l.J A D RE 18* r:1 1 1/2" I I

Jt'-:::'..

I g~ t-; ~. --- - 301 12518F v "'- ~, ~ 3/ 4" fT1 Fl 7 ~I ~I MONITOR X1249 TANK PUMPS 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED DRAWING 33013-420 AND 33013-423.
3. EXCEPT.AS NOTED BELOW, ALL PIPING AND COMPONENTS ON THIS DRAWING ARE SAFETY SIGNIFICANT CLASS. THE EX-CEPTIONS ARE:

ALL INSTRUMENT AIR AND NITROGEN LINES (NON-SAFETY CLASS) LC-1012A/B, LC-1013A/B, Fl-1064, Pl-1018G/H (NON-SAFETY CLASS) THE SAFETY CLASSIFICATION OF EWD11 IS FOR THE SHELL SIDE ONLY 2"- 1713 ABANDONED IN PLACE A 4. THE WASTE CONDENSATE TANKS ARE ABANDONED IN PLACE. BOTH WASTE J,-11.. -_~J ..r - 1

  • I 1774

~---~ 2 ,I 3 3/4" .:::--:. 3 I 4" '\\. *" v 3/4-151 I

  • CONDENSATE TANK PUMPS & MOTORS HAVE BEEN REMOVED FROM THE PLANT. MAINTENANCE ON ALL EQUIPMENT WITHIN THE NOTE 4 FLAGGED BOUNDARY IS NO LONGER REQUIRED.

Pl~ 1/2" )--:.!....'.:..-(::]-- 2610 / 2~ ~ - 1\\2-WD-151t, NOTE 6,;* 330;:-~)895 I....- (D-10) 1Xl4i20S

5. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS AD-JACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

1018H s SWD21 2608 151 TUBING

J,O"'

0 (Xl.

I:.

1" 1" __..., 2" i7s3 ABANDONED l IN PLACE FT 1 064,,.) J i6o5 1785A 1" __.., 2" 1" - 2" 1785 [@ !H-8) E-. "1 I 33013-1259 >- -; X l795KL-,~::..:.:c__:_:=.:.___..,. (784 (B-6) L-1,~1---~<~3~3~01~3~1~8~9~2=]: ::...: X15833 . le-:>

~ 12"1 I 33013-1885-2 1 ]958

> VJ 18 L... 18A 1L.:.:=~...:..::=--=-_/" [@ f' ~ J DISCH. CANAL f; f; NOTE 7 p P (B-3) I 33013-1270-1 WHT T t f*)1~ ~~ 1" 1" 1".J:>. 2" __.:.__ 2" 2" 1:>---1~-~w~D~--"15~1'----'----~*r---._~'--'--__1.-'-__.,.. _ __,_:_-{f-1c~~l--_.,~-'---.--'-'--------------------------~-----------~*------------------l: 33013-1276 1 1716 1.. 118 91o7 POLISHING DEMIN. (1-10) =i 1 - 33013-1259 2" '---------------~---------~------------------------=---<, J v NOTE 4 :::J 9146 4 5 6 7 8 9 10

6. THE LINE DOWNSTREAM OF 18 FITS THE LINE SPEC. 2-DW-151, EXCEPT IT JS SCHEDULE 40, NOT SCHEDULE 1 OS.
7. VALVE 18A IS BURIED AND SECURED IN OPEN POSITION.

CAD FILE NAME 33013-1271 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTEO PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES (5 AS BUILT A 1 1 DATE RELEASED FOR

ENGR, GINNA STA.

R.E. GINNA STATION SCALE NONE OHll\\RIO, NEW 'lQiK WASTE DISPOSAL-LIQUID LIQUID WASTE EVAPORATOR SYSTEM & WASTE CONDENSATE TANKS (WD) P&ID JOB NO. DRAWING NO. EWR 3391E 33013-1271 CCD 01 CONTROL COPY # 12 REV. A B c 0 E F G H J

A B c D E F G H J 1 (D-6) 33013-1864 1A AUX. FILTER KIDNEY PLENUM FLOOR DRAIN EL. 235'-8" (A-4) 33013 1863 CNMT. RECIRC. FAN B (1-1) 33013-1863 CNMT. RECIRC, FAN D (H-10) 33013-2278 z ~ FLOOR DRAIN EL. 235'-8" 2 FLOOR DRAIN EL. 278'-4" FLOOR DRAIN EL. 253'-3" ~---J 4" z FLOOR DRAIN EL. 253'-3" ~ ~----+ L------, I 4" FLOOR DRAIN EL. 278'-4" I I I I FLOOR DRAIN EL. 253'-3" I l I I "' I I 3 FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 274'-6" 2" FLOOR DRAIN EL. 235'-8" 151 4 FLOOR DRAIN EL. 278'-4" FLOOR DRAIN EL. 23$'-8" FLOOR DRAIN EL. 253'-3" 5 2" FLOOR DRAIN EL.278'4" FLOOR DRAIN EL. 293'-4" z 0 ;;: ~-+- 2" 151 ~--------! ' FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 274'-6" 3 8" FLOOR DRAIN EL. 253'-3" FLOOR 6 (8-6) 33013-1864 18 AUX. FILTER B KIDNEY PLENUM DRAIN EL. z 253'-3" s 4" N ' f'l (B-1) <~-3~3~0~13=-~1=8=63_~ CNMT. RECIRC. FAN A (A-12) 33013-1264 STEM LEAK-OFF FROM VALVE 0133 (8-6) 4" _,.c_ ______ ~-~< 33013-1863 CNMT. RECIRC. FAN C 3/8" [---< I ~ ~---_J L_.,._ __ 1 ____ :.::_j L - _!:l?T£_3 -


1.,..,__ -- -- -- -- -- -- -- I FLOOR DRAIN EL.

274'-6" 4" FLOOR DRAIN EL. 253'-3" FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 235'-8" FLOOR DRAIN EL. 235'-8" 3/8" FLOOR DRAIN EL. 274'-6" 4" ~ ~ _s.:.,._ !_y_' - - -4:'.'._ - ~ L I 6" FLOOR DRAIN EL. 253'-3" (A-3) 33013-1262-2 STEM LEAK-OFF FROM VALVE 945 z 0 ;;: I I I I I I I I I FLOOR I DRAIN EL. 235'-8" I~ i - - - - - -- - L - -1 ,__6_" I ~ 1 I Q T I I 3/4" ..--__.,..-=-3*_* --+- - - - I 2-WD-151 >~-- -~~~--- --~~---------, ~~ t.... I I I I I I I I I~ I PWD19A z ~ FLOOR DRAIN FOR REACTOR f'l FLOOR I COOLING FANS I '-" DRAIN EL. EL. 235' -8" 235' -8" PWD198 <MO/VSP18> CONTAINMENT SUMP PUMP 8 N. <MO/VSP1A> CONTAINMENT SUMP PUMP A FLOOR DRAIN EL. 235'-8" I I I I L __ _ ITl ITJ LT 2039 3/8" 1:---1 I I N ' 7 3/8" [---1 u ' 8 2" 3" 3/8" t-'--:J 3/8" t-'--:J I I I L ___ J_ ___ _J I CLEAN OUT I I- - J L ___ J I 0 N 3/8" r--:J I I I I I I 3/8" i:---j (.N c 2" -i ~-+---!- I I ~ 1" 1" 2" 2" 9 3/4" 3/4" 1 0 (J-8) 33013-1260 A RCP #2 SEAL LEAKOFF X554 (8-4) 33013-1260 REACTOR VESSEL FLANGE LEAKOFF (C-10) 33013-1262-2 A SI ACCUMULATOR DRAIN X544A (E-1) 33013-1260 8'-RC_S_L_O_O_P_D_R_A_IN___, X540 (E-1) 33013-1260 B RCP #2 SEAL LEAKOFF X559 (F-12) 33013-1264 EXCESS LETDOWN (DIVERTf312 (G-12) 33013-1264 EXCESS LETDOWN (DRAIN) X3 l l G CLEAN OUT . _J C--J_ __ I_ f----. _J_ ___ _J FUEL TRANSFER CANAL DRAIN CONTAINMENT EL. 235' 8" _I - L - ~ CLEAN OUT I ?11 4" I (/) - () I I

r: (/)
,. T o_

(/)~ 10 I M I I NOTE I f-2.:_ _L6~ 1 1/2" 1" 151 _t ,-----'--'-=-------'!~ 1712 N 1716 OJ v Ol 0 <O v () D 1 " 1" (G-10) 33013-1262-2 10 8 SI ACCUMULATOR DRAIN X844B N

  • 2" (D-8) 33013-1258 PRESSURIZER RELIEF TANK 151 X527 3/8-WD-2505 1717 (1-8)

~ 2" 151 --- ' ----=------'-'-'----<< 33013-1258 ~ ~----~ X526 PRESSURIZER RELIEF TANK ~~ ,.)-,--~-~-~--~--.-~ LT 1003 I 151 I 1715 1714 2" TT 1058 TWD01A REACTOR COOLANT DRAIN TANK -i c ~ z TC f-~ 8429 [QJ OJ 0 4-WD-151 4" 8431 3" 1002 ~ ~ L_ s I 0 I O> - _J FL. EL. 210'-0" -+--10 J I __ _ 6s- - - - - - - - _J L - ~"- - _[_ - 6" 1 2 3 6" CONTAINMENT SUMP A 4 5 6 7 8 9 1 0 (/) ()

r:

0 1 1 ()I,, 0 c z x ". z I °' r f'l I o z 0 -l ~129 P123 12 3/8-WD-2505 ~~- (B-1) 33013-1272-2 GAS ANALYZER P143 4" 3" (D-1) 33013-1272-2 REACTOR COOLANT DRAIN TANK PUMPS (G-1) 33013-1279 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1272 REV.6.

3, ALL PIPE EXCEPT WHERE NOTED SHALL BE SCHEDULE 10S STAINLESS STEEL SEAMLESS OR WELDED ASTM SPEC.A312 TYPE 304 WITH SCHEDULE 1 OS STAINLESS STEEL SEAMLESS BUTT WELD FITTINGS ASTM SPEC.A403 WP 304.

4. ALL PIPE, DESIGNATED BY NOTE 4, SHALL BE SCHEDULE 40S STAINLESS STEEL SEAMLESS OR WELDED ASTM SPEC. A312, TYPE 304 WITH SCHEDULE 40S STAINLESS STEEL SEAMLESS OR WELDED, BUTT WELD FITTING ASTM SPEC. A403 TYPE 304.

X1716A X1655 X1721 X1728

5. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIP-MENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT AS PER SFEWR 10328.
6. ORIGINAL 3" SCH. 1 OS DRAIN PIPING FOR THE B SI ACCUMULATOR IS BURIED, SEALED, AND

/\\ ABANDONED IN PLACE. SEE ECP-2008-0044 AND ~ DRAWING 33013-2954 FOR DETAILS. 1 1 j\\ REVISED PER M ADC-12-001180 CAO FILE NAME 33013-1272, 1 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES AS BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCA!£ JOB NO. NONE WASTE DISPOSAL-LIQUID RC DRAIN TANK (WO) P & ID DRAWING NO. REV. EWR 3391£ 33013-1272 SHEET OF 2 ht CCD 01 CONTROL COPY # 12 A B c D E F G H J

A B c D E F G H J 1 2 (B-3) v 33013-1890 X15986 >-----..,'/-------.., N / X1608 (D-4) 33013-1274 (A-12) -C><t---1 33013-1272-1 X1716 (B-12) -J~><t--1 33013-1272-1 3 4" 152 1" 1716A 8 Pl 11023 PC-i~__Jl,.:-;:{Xh 1016 1014 2* 152 ~ u; N L!.J TC ~ z 2505 3 c ID z " 1713 1793 [ill X1717 1655 2505, 151 X1810A (D-3) 33013-1247 (C-5) 33013-1890 X14282S.__ _____ / 6" 151 (C-5) [~33~0~1~3~-21~89~0~=::>--------!f-------i X14284S D 3" (B-12) 4" 3" 4" ~3~3~0~13~-~1~2~7~2~-~1=::>--~---l~---[1-----l'><'l----i~-------L_, X8431 1721 (E-4) 33013-1248 FUEL TRANSFER CANAL DRAIN (D-5) -1><1-j 33013-1890 X14281S [jJ [E9 3-WD-151 1722 [ill r~ D

>=~----------~u----------------ffn-I 0

I 3/4" 4 1787 [E9 ITl 3" NWD07 SEE NOTE 5 s 5 17AAI ~~ v T 17~1 [Eg~ PWD10A <MO/CDP1A> REACTOR COOLANT DRAIN TANK PUMP A 6 (C-3) 33013-1890 B-3 33013-1890 D-3 33013-1890 151, 1.2505 BWD05 Pl 1018A X14289S X14285S X14290S 2" 151 f-----llf-----l'-..J-----'"----.--'"'-'-~~-_.L_--t*'.l~-, s w D NOTE 11 1724 1725B 1726 N ' 1724B 2" 2* 7 8 152 1675 3 8"-2505 1020 151 601 1811A 151 601 1811B 9 (G-1) 33013-1273-1 (G-10) 33013-2280 10 X980A L-. _____ _,- X1600A (A-7) 33013-1247 >-tx:J--- ~----- X1812A (E-7) >-tx:J--- ~----- X1812B 33013-1247 ~ (C-4) 6"


___ ------------~6_-~W=D_-~1=5~1-----------t------l>------<<:: 33013-1247 151 f-c><r X1810B (D-5)

~ 33013-1890 X14283S >~----,~Y---------~-----+rH------~--- (A-7) X14295S [~33~0~1~3:-21~89~0~=::>----H---------------,!f--------------i EX.FLOOR - DRAIN BOX SEE NOTE 6 S.S. BOX ~ I tWA~tlNG PUMP ROOM SUMP PUMP PUMP LOCATED IN FLOOR DRAIN I *- 1;2* x 11;4* ~ SCREWED '--'--:;=l)~:'_-S.S.REDUCER (E-3) 11/4" PVC-I.__ ____ 11; 4* PE ~ 33013-1279 >>--------------t X1723 (E-10) 2-WD-151 NOTE 3 33013-1262-1 >~-----------------~ SAFETY INJECTION PUMP B (C-10) 33013-1262-1 SAFETY INJECTION PUMP C 2-WD-151 NOTE 3 1001 N I 0 I ~ v T NWD06_/ SEE NOTE 5 10~ 2" 6" 4" 1/2" s PWD10B <MO/CDP1B> REACTOR COOLANT DRAIN TANK PUMP B N 1725 3/4" l~I~ 151 J1016A 3-WD-151 2" 2" 2" 2" N ~1708':.l "; ~ 1727 B-10 33013-1262-1 SAFETY INJECTION 2-WD-151 NOTE 3 EQUIPMENT DRAIN 1" 6" 11/2" (/):;'. ;;E (/)'.;::

  • NOTE 9 PUMP A PWD20 CONTAMINATED STORAGE BLDG. SUMP PUMP 151 151 NOTE 3 ID(/)o I r-io g~z ~

(C-6) . i!) ~ I EJ [~~~~~:=::>----t-_:2r" ____ -l"' z -t:><J--l 33013-1247

i:;

X711B X711C RHR PUMP B o (F-6) 33013-1247 RHR PUMP A 2* E 2" (C-1) ~-- SUMP TANK 1 3" 2 RESERVOIR FOR 151 (NOTE 3) CONTAINMENT SPRAY PUMP B EQUIPMENT DRAIN RESERVOIR FOR CONTAINMENT SPRAY ~PUMP A 1" 2" 151 NOTE 3 I

ii 0

I ~~-----~--~---'----!~ 4" T p 2" 2" TRENCH J-lct--=---------------------~~-. DRAIN 1780 NOTE 10 ~ el ID 5 WATERBOX----~I AUX. SUB. BASEMENT EL. 219'-o" 4-WD-151 3 EL 232'-3" ~~ o SEE g* NOTE 9 3" 4" 4" 6" ---3 4 5 1" SEE NOTE 9 ~I~ ~ 1 LWD03 1 D 6 2"151 11 4" N 2* SEE NOTE 6 7 3* ~x :r 0 r N LS 2043 3-WD-151 2-WD-151 2" 1" 1073 4-WD-151 (B-8) 33013-1261 (D-8) 33013-1248 (A-2) 33013-1267 HOLDUP TANK (F-1) 33013-1270-1 (E-6) X1733 X798B X1100A X1707 151 '------------------133013-1270-1 PWD05A <MO/ASP1A> AUX. BLDG. SUMP PUMP A PWD05B <MO/ASP1B> AUX. BLDG. SUMP PUMP B 0 L 3 4" N WASTE HOLDUP TANK (J-1) 33013-1248 SPENT FUEL POOL PUMPS FLOOR EL. 219'-0" AUX. BLDG. SUMP 8 9 10 1 1 12 ~=- AS MAIN LINE ~ l ~ SAFET CLASS 2, 3, OR SAFETY SIGNIFICANT (Q) DETAIL-A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF THIS DRAWING SUPERSEDED PORTIONS OF DRAWING 33013-1272, REV. 6.
3. WHERE NOTED, PIPE FITTINGS FOR SMALL BORE PIPING SHALL BE SCH. 1 OS SEAMLESS, BUTT-WELD PER ASTM A403 TP304.
4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN

& TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCOR-DANCE WITH DETAIL "A".

5. NWD06 AND NWD07 ARE A "WAFER-TYPE" STRAINER WITH 1 /16" NOM.DIA.

RODS WELDED TO IT AND USED TO SUPPORT A SCREEN.

6. SUMP PUMP IS INSTALLED IN CHARGING PUMP ROOM FLOOR DRAIN BOX AND DIS-CHARGES ANY OIL SPILLAGE THRU A 11/4" DIA. POLYETHYLENE PIPE THAT IS LOCATED IN THE INSIDE OF THE FLOOR DRAIN PIPING SYSTEM. THE PIPING EXITS THE EXISTING DRAIN SYSTEM AT DRAIN BOX #2 AND TRAVELS OVER THE FLOOR TO THE HATCHWAY OF THE RHR PIT AND EVENTUALLY TO THE AUXILIARY BLDG.SUMP, LOCATED IN THE RHR PIT.
7. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED UPON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
8. ELECTRIC MOTOR EIN'S FOR MECHANICAL EQUIPMENT ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT AS PER SFEWR 10328.
9. THESE DEVICES ARE SAFETY SIGNIFICANT FOR FLOW RESTRICTION AND BACKFLOW PREVENTION QUALITY REQUIREMENTS.
10. CONFIGURATION CONTROLLED PER SAFETY ANALYSIS OF EWR 4764.
11. 1 1I4" STAINLESS STEEL RESTRICTION ORIFICE TACK WELDED INSIDE PUMP CASING DISCHARGE FLANGE.

1 1 M REVISED PER RJM AJ c. A TC

  • 1 t-OC-15-000242 1--'~___,ec...."--T-+--T"-T-c-t-"7-~-t 3/31/15 3 "

15 3 31 )5 3/., '" CAD FILE NAME' 33013-1272 2 CONSTRUCTION LIMITED CONSTRUCTION: PS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 5 31 /5 AS BUILT DATE RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION JOB NO. EWR 3391E NONE WASTE DISPOSAL-LIQUID RC DRAIN TANK (WD) P & ID ORAWING NO. 33013-1272 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

.A. B c D E F G H 2 (!J-::} I J~1J-12~1 ):.-~~~~~ eves t!Oi..DUP TNC;.;s {E-!} ~i.!:.~~~-i/>-~~~~~~ SFEUTRES!N ~JOH<\\G( !.Al':KS 2 3 3 4 5 ti 8 9 10

    • t-------***-u***--*-*--*-**---ff*-**---**--**--r----*---G~~~:J;;~5 1--~*-**~~~~~~~~~~----;J~1J~~;J-2 ;~

4 5 6 7 8 9 10 12 NO:IZ5: 1 na 1;Et.;£FAL NOlru m:n:R ro n:tAwitm !1!1013-1241.

2. nus ~R.t.Wlt:G Sl!P£R'..ilOCS P..::1?t10t-S Of 3301l-12"1J RtV.B
l. fOR MATERW. SP[C. IN iHIS MEA SEE J:1,lft'I~ 0-JSJ-525 P.E'W.1.

'4. OcurlWti[fif:D'!liOM'l.'ii::tf.lli:AT(D'SN"ElY Cl,.ASS UiH:i'Jfl.Al EXctWICffi 'SNETY Cl>S5 INDICATU'l f"C.ISC Si-'EU.SIDEG<<l..'f.

6. OCEPI WHERL omOM15[ ttmr:.-.m>. WETY Cl.ASS F'OR iN5TRllJIOfl A:R MID Nr.TiOGE.'l UNt'S/COMPONIJlT'S IS 6'SCO 0!4 UPSl:IEAM 1Nh"TNUME.NI IJH/NITHOrn'.N \\'...,,.\\'E. Rffffl TO

!lfl'f.RfAQt-.'G Ai>>iW!RL>Gf.N ORAW!t4G H>P ~~U'fO.~ J. WCiHIC' uororc flf\\I~ FOO MECl"\\Ah:CH..

QUIF-lilENT AR( [)tp;c
ra> !t4 8FiAO:Ka5 AA:J.CENT TO ~ECHAN:CAL EC1.;IFM£.'t"i PER SfF.Vrli 103.28.

~--1/'4 CL-300# FF f'l..JJlCE IHL£T/iJun.£f OE\\~TES FR0'4 UHE SPEC. kt. ""1TTYCV.OS...., ll!irl1NE 2~~'~ a>U(~ lW.sr.sETY ctAss~W"K:~r F~ vwr DIWN A TEST CONlfECTIONS 11 WASlf. OOiPO!W.. - GAS (1(J)

-~~~r~~~;~!--~*;;-1-1 GCO 01 i CONiROL CoPY ii 12 B

c D E F G H

A B c D E F G H J 1 (F-10) 33013-1871 (F-5) -t><J-1 33013-1889 X14244S (G-7) I I 2 /J REUSE 3 2-W0-152 1" 1618 [ill 1" 1630 X 1~ 33013-1889 (D-10) -t><J-1 33013-1889 X15814 (G-5)

>~--~n,_ ____ _

-t><J-1L._3_3_0_1_3-_18~8~9 __ :>>--~h~'----- X14248S (D-10) ~ 33013-1889 X15815 (F-5) >>---11-"---- It -t><J-1L_3_3_0_1_3_-_18_8_9 __ >>-----"H------ x14243s (G-10) I.33013 1273 1 1" (8-10) < 33013-1273-1 '-I ~3~1~4--~w""'D--~ 1 -"' 52"-- (G-5) -ff -ff - -ff - -t><J-1L_3_3_0_1_3-_18_8_9 __ :>>--~h~' ---- - if- - X14246S (D-10) I-- x~ 33013-1889 > H if- - (H-5) -t><J-1L_3_3_0_13_-_18_s_9 __ >>--~n~--- x14249s if-(H-5) -t><J-1 33013-1889 >>----i>//'------ X14250S (D-10) ~ 33013-1889 >>----1/,1-' ------ X15813 (G-5) -t><J-1L_3_3_0_1_3-_18_8_9 __ >>--__,/~/------ X14247S ~-9) 171 ~ 33013-1889 >>-----Jh+-' ___ __,,fl'- X15821 ,ie _r-PC 0 (!)' v II 16068 II ~ 1037A II V'J 1629 1606A 1036A 1620 [ill 1632 JJ JJ ~ 1" n_


i..x-J

~ 1606D 1039A I C---' 1626 II I ~ 1625 1-WD-152 1" II I ~ 1628 ,--., 1-WD-152 1619 [ill II REUSE I' 1631 II JJ 1" y 1606C 1038A 1" II I ~ 1627 t-----:L~ 3/4" 1022B .. JsL,<§~ ~~ JJ o'~ 16'oio~~"~"' ~ ..p..: Ul <µ, N O>> --j ~ c O' 7 Q:! 0 z "':. ~ G")

>---3 1039 4

II JJ ,,~T 1711 I " ~~Q+--#--11-+---11--,,- 1607c 0 "' ~:o"~~ ~ --j 017 c 0 -1':1 > z z "'--:1 G") ---11--1 P°T\\ ~038) 0 11.. T ~ 1048

..,_Jr+----1~1------~11-----

r::- t.:: lf __ 711 1048A (F-9) ~ 014' t ~ 33013-1889 >>-------11n--------Jh"-' ------ X15820 l!.l 2-WD-152 .J ~ .----!../;.....- ,--f1,.XJ-- 1659C 1656C ITRLI .J ~ v I v """1 16590 1656D jTRLI CD Z r --l om G") ;u 1-WD-152 SWD08 ~ 3/4-WD-152 -cJ-5 CD )> 'c ox

p.

1624 ?1*jL--=2~*__, JJ 1-WD-152 I H II 6 (F-3) ---,11-r _JI 33013-2289 > P/1 3120 JJ PC 1037 A/8 E-+----fl"~--l Pl II 1037 WASTE DISPOSAL PNL ~ SWD09 ~ 3/4-WD-152 <}-- ,,"1------1-- if- - 1-WD-152 I (D-3) r--1111"~----1: 33013-2289 P/I 3120 PC --fl- ,,---'----IH,,---,----/, ,,"1----l 1 03 6 E--'----1,~1--,--1 A/B Pl 1036 WASTE DISPOSAL PNL SWD10 Ji 3/4-WD-15<r-1622 l1'i'---=2~*----' II 1-WD-152 if- - I I I 0 0 0 I I I ~ ~ ~ N N N SWD11 ~ ~ I 0 I ~ N JJ N (F-4) 71 l 33013-2289 L_ _____ _/ P/1 3121 PC --1,;1--*~--ll-lii-~---111"/-----I 1 039 A/8 H L II Pl c:--'-----1,,1----1 1 039 WASTE DISPOSAL PNL (D-4) I 33013-2289 > P/I 3121 PC


~,,"f-----L-~,,"i--.J.---~---11-~---J 1038 A/B Pl E--'-----1,,1----1 1038 WASTE DISPOSAL PNL 7

8 1 WD 152 1-WD-152 SEE NOTE 3 SEE NOTE 3 SEE NOTE 3 SEE NOTE 3 (1-7) I 0 I N 0 0 rn 0 ~

u 0 0 ;;
:

0 0 ~

u 0

0 ;;:: GAS DECAY TANKA TWD14A 1-WD-152 9 3/4" 3/4" 3/4" I I 0 0 I I N N 0 0 3/4" GAS DECAY TANK 8 TWD148 1-WD-152 1-WD-152 10 ~ 1" 1638 ~ _J 1" 1637 1646A 1646B 1 II c--(J--~ . ~ 1645A 164SB 1" 1640 1 " 1639 I 0 I N 1 1 12 2* (B-9) -~--------1133013-1270-1 > (8-4) 33013-1274 I 1685 NITROGEN GAS DECAY TANK C TWD14C GAS DECAY TANK D TWD14D II JJ 10398 // 103sB II 1-WD-152 1" 1648A 1648B (B-9) 2.. 2" E---t---=---------1: 33013-1270-1 1-WD-152 1" 1647A 16478 I I 0 0 I I N N 0 0 (A-7) H < 33013-1889 ~BS (8-7)


i/11-' -~< 33013-1889 ~

~-----__J X14240S (B-7)


,~1--~<:"~_3_3_0_13_-_18_8_9_~~

X14241S NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241
2. REVISION "o" OF THIS DRAWING SUPERSEDED PORTIONS OF 33013-1273 REVISION 8
3. PC-1036 A/B CONTROLS VALVES PCV-1036A AND B IF WASTE GAS TANK A IS SELECTED FOR PRESSURIZING. TANKS B, C, AND D HAVE SIMILIAR PRESSURE CONTROLS.

A SECOND TANK CAN BE SELECTED FOR STANDBY.

4. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN LINES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
5. DEAD LEG TEE INSTALLED.

II if- -ff ___,/11-/ ____ ____:__ij! ~ ~ I 014H1 15961 14233K I < 33013-1890 H?:9:- ~-----1X7381 ~ r------**----~ - 103l8 L __ _J WASTE DISPOSAL PNL (B-7)


!hf-' ---<< 33013-1889 H><r-X14239S 10368

" '~ 1025 - _Q .97/'7 3/8"-2505 F f---t.>1<'.~f-----.::!l.-"'--~~'--------l: 33013-2280 FWD10 1022A GAS ANAL yzER (F-10) ~'>--tx:., ~ X1047A DATt CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED ----1---1 PRELIMINARY NOT FOR CONSTRUCTION ----1---1 BIDDING PURPOSES />S BUILT RELEASED FOR ENGR. GINNA STA. R.E. GINNA STATION SCALE NONE ~ -

1~------.J WASTE DISPOSAL -

GAS (WD) 1659A 1656A lTRLI (1-l) 3/4" 33013-1273-1

i------------------'-------------ll...---!~/l!--'"-t~'x~a--------_J 16568 lTRLI 1659B 1

2 3 4 5 6 7 P&ID JOB NO. DRAWING NO. REV. EWR 3391 E 33013-1273 SHEET 2 OF 2 ~ CCD 01 CONTROL COPY # 8 9 10 1 1 12 A B c D E F G H J

A B c D E F G H 2 2 3 (A-7} fT 17UU. <*-*) < JJOt:l-1206 FF1D41i.l 3 4 5 [C-B) --l!=.!L itM8 --~13-IZ7l-*1-*

  • p,df;i~

(C-1 33013-1275-! 1* X1831tMll:ICDI~ 1174C ~ fEJEr~~ L. 1"-1~2 3301~~~72-2 J/.. t----'--..:....:::~---]*** X1014 ArAClOR COOi.NiT 1608 DfWtfTNf( ~ TtJll"Y' 4 (C-8) 33013-1287 FF 1SJH,1. (C-1) JJQ13-1267 FF t56H,L I 34* 5 6 7 8 9 10 11 12 A B IGS? JlOtl-126.~ 1/llUJOICCOlf!ROt. - 1* c

  • ----r--~

,-----1881~---I----------~ X1~18 D u--*----- ~--- E F ~ I. rem ClNl"RM... NOTES RrrEA Ta CIRAW~C lJOJJ-2241. 2* ~~~ ~~~ ~~~4:50. J.OEl.tT!ll H

4. =-~oi:'~~~m.rs W>.Stt OISPGSAl.-tJ.S 1"

,....... ~"r:m~' 1804 !EOG FlU 6 7 8 g 10 11 12

A B c D E F G H J 1 F-2 33013-1899-1 '.'::'-------~ O> O> 0 (/) r'l z ~.. (C-4) 33013-1274 NITROGEN SUPPLY AUX. BLDG. 2 Pl 11A 1836A 0 0 ~ t 3 4 H-2 --j;><J--j 33013~ 1899-1 X15653 (F-2) 33013-1899-1 ---.:=:..:.::_.:.=:._:........i x 15658 3/4" v i:,...----n 1-'-'-_'.__j 10202v 0 0 x 1,0202W 10202Y 1 2" 1" 0 0 rn O> Ow 1" (/) 0 :r: c. 0 0

u

~ 0 0 " " "'

u

'jj "' 0 z "' 5]:;;: (/) 0 :r: 0 0 x (/) 0 0 " " "' "' " " "' (/) - 0 - r:::;io; "' '--" (/) z OUTSIDE 1830B AUX. BLDG. C-1 r-r-.-:i 1079 ADJ. MANIFOLD REG. 2 STAGE PRESS. CONT. (A-2) H~r--1 33013-1275-2 1080A lill 0 N 0 0 Pl 12B )> 1830A 3" DIA. 'o / GUARD PIPES~ ~ NOTES5&6 X8423 C-1 V 1" 3/4" 3/4" 1830D C-1 PT~ 1830E 2971 1* OXYGEN L..:...-L,-'f----4-+:J TRUCK 1830F 1830G rn )> r-c ox 0 0 N :r: 0 CONN. c ul 0 1" 1" 10202N ~TC FWD02 10203T 10204B (B-3) --11-H--<< 33013-1892 L.-.._,.,__


'x'i58'.l2 H-2.

-[><..I_, 33013-1899-1 NITROGEN BOTTLE (F-2) X15654 33013-1899-1 ~-----~x15559 (G-2) --=3~3~0~1~3_-~1~8~9~9--'-1-'X 15655 1" v i:--t* ~---,--i 10203J 1/4" 0 0 0 i------11~--+-----11>1-3v ~ 1 0203G ~ 1 0203E ~ 0 4>; v 0 0

r:

~ "Tl 1 2" 1 2" ~---.HHf--.l._ __ ~.._---'---L.....jHlt---lXJ--'--l l-'~--1 (H-2) -C><.J--t 33013-1899-1 X15657 (C-10) 33013-1889 X15817 '------~ (C-5) l/P~ 5 ~ 33013-1899-1 >>---------#ff----- X14401 K'------- D-5 10202T II.. H II 11409 H r I H

  • H if II II 0

0 r-H H H w v FE 1B s 10200S 0 0 0 L!J~ v 5 .if if 6 7 D-2 33013-1899-1 x 563>6'--------_.,. (C-1) 33013-1275-2 X8435 10205S1 x~ 1

  • if (C-5) 33013-1899-1

~------~ X14401 L (D-11) -+--~_Jil 0 c ~1 ~ TC TC r.1 1084A 10209S1 lill Ill (F-1) 10209S 33013-1275-2 X8427 0 0 (/) 0 ~ (/) - (G-1) 2" _,,--'----~----, 33013-1275-2 X8425 33013-1899-1 >>-----1>H'---- .. // D-11 H 33013-1899-1 x 14426-"-'-'-'-'---'-'-""----~ --=====:::;-i (D-5) 33013-1899-1 X 14401 H 3301 ~~~;99-1 01J HRACP ."-::~:--+------11-------j/'-----<.._;3~31Q0.!_:13~-::_11~8~99~-::_11_J X14 01 G HYDROGEN RECOMBINER A *coNTROL PANEL 1 2 3 4 5 6 7 N 0 0 - rn 8 Pl 14A 0 ~ 0 ;u "' 0 .. 0 =o ~ II 9 v -r.i 0 0 v 8 10 1 1 12 D-2) 33013-1899-1 X15639 3/4* ~ 3 4 1 l--'---l~~-'--t-----11...-3v Pl 2937 Pl 2716 0 0 0 0 0 "' 0 r-0 0 ~ ~ ~ = = 0 0 0.,, 1

  • 10200E 0

0 0 0 1/2" 1/2" ~ \\V ~ 10200B v ' - r.lf ~ 0 ~ 0 1 1/2" ~.. w 2" 10200A 0 0 0 0 -~~~~~~~~~f (C-2) 0 0 0 A 1 1/2" --ttH--~<33013-1899-1 ~ X15635 3/4" 0 N 0 - 3/4" v l:~-4----1 f----lf----1 i----....-3 v 10201D 10201C 0 0 - 3/4" r----l~~i-----t-...... ~3v 10201H 10201F 1 2" 2" 1" 0 "' g (B-10) r-;-'-,_~3~3~0~13~-~1~2~7~4:____ X1878 HYDROGEN 4" DIA. GUARD PIPE SUPPLY 1" 1" (D-2) --lh'I-' ---<< 33013-1899-1 ~7 (C-8) ---ll#--<<33013-1899-1 ~ ~------X15644 v ROOF 10211S1 10211 s 10210S .-+--.--Ill 0 c ~1 ~ 0 ~ w ------~-1~*------- (f) i:-~---r 1-.------------- H t 10213S 10201P 10201S wt; O> HRBCP N ' 1* 3 4" 1" ,----------j--------'---( ~---l rv w (E-8) H 33013-1899-1 ~ /---,; \\_ SAFETY CLASS 2,3, OR ~ SAFETY SIGNIFICANT (0) (D-8)


h~'---~<33013-1899-1 f--txJ--

DETAIL-A Pl 7B (C-11) 33013-1899-1 X15648 TYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "O" OF. THIS DRAWING SUPERSEDED PORTIONS OF 33013-1275, REVISION 3.
3. EXCEPT WHERE OTHERWISE INDICATED SAFETY CLASS BREAKS FOR ALL VENT, DRAIN & TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. SOLENOID VALVES 10214S AND 10215S RECEIVE CONTAINMENT ISOLATION SIGNALS, BUT ARE NOT REQUIRED TO ACHIEVE CONTAINMENT ISOLATION AS DEFINED IN UFSAR TABLE 6.2-15, THEREFORE THESE 2 VALVES ARE NOT INCLUDED WITHIN THE SAFETY CLASS 2 BOUNDARY.
5. TWO SECTIONS OF THE OXYGEN SUPPLY LINE GUARD PIPE ARE MISSING AND THE GUARD PIPE FUNCTION IS NOT MAINTAINED.
6. DEAD LEG TEE INSTALLED.
7. PLANT ORIGINAL THREADED CONNECTIONS ON VENDOR SUPPLIED PIPING AND VALVES FOR THE HYDROGEN RECOMBINERS DEVIATES FROM THE 152 & 152N LINE SPECIFICATIONS. REFERENCE VENDOR DRAWING SERIES D10881 & D10882 (FABRICATING ENGINEERING) FOR CLARIFICATION.

(\\ REVISED PER RJM

5 I- <.i)

M ADC-13-000784f-::-71"'1"'1;':-,1"°3 ~"1:,11, "-3.-P.:;r.,/r./~h9-"°"1*"1!." CAD FILE NAME; 3?127501 CONSTRUCTION LIMITED CONSTRUCTION: AS NOlED ~------4'14426C PRELIMINARY NOT FOR CONSTRUCTION 711/ I (C-11) DATE BIDDING PURPOSES AS BUILT RELEASED FOR ENGR. 33013-1899-1 X 14426~,_*-___ G_IN_N_A_S_T_A_. _ ___, R.E. GINNA STATION (D-11) 33013-1899-1 ~------X14401 SCAlE NONE JOB NO. WASTE DISPOSAL GAS HYDROGEN RECOMBINER (WD) P & ID DRAWING NO. REV. HYDROGEN RECOMBINER B CONTROL PANEL EWR 3391E 33013-1275 SHEET 1 OF 2 & CCD 01 CONTROL COPY # 8 9 10 1 1 12 A B c D E F G H J

1 A B c D E F G H I J 1 2 3 4 5 (E-1) __l_j p 210 1* SCH.80 OR XS COPPER PIPE ~ 33013-1215-1 >>---------------------11 I r-----.-------r::><J----j X1080A -n 8423 I I ~ !LOI 8423A (B-6) -J:><l-i 33013-1275-1 X1076A (D-6) -J:><l-i 33013-1275-1 X1084A (E-7) -C><l-i 33013-1275-1 X1076B (G-7) -[:><f-i 33013-1275-1 X1084B 2 3 I~ t~' I NOTE 4 z w 0 TC c! I NOTE 4 I~ JJ P304 T~ I NOTE 4 3/4" t (lJ gi z TC r.i -i c TC gJ r.1 _f 8435 [Q] 8433 [Q] -i c gi L E--+---' 3 4" E--'-'"-'----1 ~ z n1

u 0

0 fTl z 0

g
s z fTl
r:

fTl ro I z c -J ~ 10" x 23" ~I G) I NOTE 4 ~ I ',,,, __l_j 3/4" t' NOTE 4

r:

TUBING PIPING H l----T-14-* --il~I w~ ~w" CWD01A HYDROGEN RECOMBINER A BLOWER DUCT PIPING 10200V 1" 3/4" -152N -i c gi TC z r.1 _r cu... N ffiABANDONECT; IN PLACE ~ 8427 8427A [Q] 2" 152N 8425 8425A [Q] E--+--~ (lJ E--+--~ TUBING PIPING 0 c ~ 3/4" E-~~---< ~,I~ 3/4" 2B ~~---f~-::i 10" x 23" 1/4" H~r-14*--'---!~l~lt-----1 4 CWD018 HYDROGEN RECOMBINER B BLOWER 5 6 1" 152N \\/rGNITERS SWD03A HYDROGEN RECOMBINER A \\/rGNITERS SWD03B HYDROGEN RECOMBINER B 6 7 SIGHTGLASS 2501 3/4" SIGHT GLASS 2500 7 8 9 8 9 10 (J-5) 33013-1863 t'-~CDY °~ ' AS MAIN UNE ~wm '~"*"' SAFETY SIGNIFICANT (Q) DETAIL A TYP.SAFETY CLASS BREAK POINT FOR VENT, DRAIN AND TEST CONNECTIONS 10 1 1 1 1 12 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1275 REV. 3
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORD-ANCE WITH DETAIL "A".
4. THE PIPING SAFETY CLASS CHANGE INSIDE THE CONTAINMENT IS AFTER THE PIPE SEAL WELDS AT THE PENE-TRATIONS.

CONSTRUCTION LIMITED CONSTRUCllON: PS NOTED PREUMlNARY NOT FOR CONSTRUCTION Bl001NG PURPOSES AS BUILT DATE RE!.£ASED FOR ENGR. GINNA STA. R.E. GINNA STATION JOB NO. EWR 3391E NONE WASTE DISPOSAL - GAS HYDROGEN RECOMBINER (WD) p & ID DRAWING NO. 33013-1275 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 RE.V. A B c D E F G H J

2 .3 B c D E F G H 2 3 <J;01~10-2} SPENT flE'SlN STOfWiC fNiil< 4 JJ01.l-t264 (H-10} Rf:S!N Fll.L CONNECTION 5 6 ~ O\\Jr310l SHl[U>;t-1~ W>U w.sm~WN:L t------1 3-*0-l!Sl -L--*-*--- 9100... z* 7 OEWlt<£AAUZ£R ~ 9101 8 <=*~~~,.._, 1--~~i*~~.__-+-.-~~..-i-~ W.H.T. i J {B-t) 00~;;;-* W.4STE CONDfJ&lE TN<'<'1---+...,--l 33013-1278-2 TUBING P206 ! LL 1 600-1 5733 600-1 ---+1--*

  • ~N"""'o"'T=E""""5 5749~

TIJBING~ STEAM GENERATOR SLOWDOWN SAMPLE HEAT EXCHANGER A ~ I -

5' -MS-600-1 I :5' -MS-600-1 s
  • I 33013-1893 I :5' -MS-600-1 1 I :5' -MS-600-1

~:~ P321 I u

5'-MS-600-1

-...__ _____ _. X5738S I L!.J (JI _-3/4" ~ (JI (JI t;l - Ol s s I L!.J D

5'-MS-600-1 L!.J Li},

NOTE 8 L_ NOTE 8 UJ D I I I I NOTE 5 5701 3* [Q]l738 ~ ~ 'c! ~ t. ~:~ L!.J

o !D D

OJ OJ Zgi 5 5 G'l G'l G'l

  • I.

~ I ~ I L!.J LJ[p--Ol--~-m-'---De:::J-Y1--i NOTE 9 I () PSB02A 5777A 5776A 5779A ~ -Ii tJ 5778A IP DI [ WATER --~l::.;.._-0-----'I' 5751A 5780A 5776C (JI Ul s > L!.J I 1TUBING 600-1 I-3 ....==tki-~h~ 33013-1278-2 (G-10) 33013-1899-1 X5736S Li}, 1> N_:>_T_E~8..._E_:__::*::.::_:=l::......:..~---l<-=====~ 5777D )- 1-MS-600-1 lEQ) T LU SLOWDOWN SAMPLE P2Ll 573~ STEAM GENERATOR 3/F!' HEAT EXCHANGER B .--1---~~~~~~+-0...:J-~-1....!1---~~-Mf--j 1 57541 3/4"--- D 1 ~ ISl I c! gi z G'l EMS01B STEAM GENERATOR B 2" - MS-600-1 57806 2 2" -MS-600-1

1~

al I CD P322 (JI ~ m J L!.J Li}, NOTE 8 ia-=MS-60.~-~--i---.---i I 2" -MS-600-1 NOTE 8 600-1 TUBING ~ 3" -MS-600-1 NOTE 5

5' -MS-600-1 5702 NOTE 5 L

O-TE 5 ~-- -1 ~U 5776D (JI Ul s all..!..I D 57786 3 4 ~ s I

5' -MS-600-1 NOTE 5 "I ;"-MS-600-1 G-5 33013-1893

-...___;:_:;..;:..:..:.._.:..:..::.,::_--' X5737S 5737 [Q][l) UJ 5 D 5728 5727 6 7 NOTE 7 I t'--~.-----;- 5730 5729 6 122036 MANIFOLD- - (JI


;;:J s

OJ 3 4* 3 4" NOTE 7 MANIFOLD- -


~ -

al 4" ~ '5741D "l. L!.J v 7 8 9 (C-3) .------------------=------1 33013-2711-4

5' -MS-600-1 SGBCP SSB02 I oE12391 I

5 I I'-) I VJ L_co s NOTE 7 L!.J (C-6) .-------------------==---i33013-2711-4 SSB03 D !;-..--; ~ DE-..--; 12395 ~ 12, 389 I 5 ~ ~ L_co L_oo c! "'" '------,---""00_, ~ G'l Ol s s I - 3" -MS-600-1 SGBCP (JI Ol co al 8 L!.J NOTE 7 Ol s s I - TO SECONDARY SAM PUNG 9 X1406C X1406D 10 G-1 (C-1) 33013-1277-2 10 X5768A 11 -i_ SAFETY CLASS SAME AS MAIN UNE DETAIL-A SAFETY CLASS 2 OR 3 12 IYP. SAFETY CLASS BREAK POINT FOR VENT, DRAIN & TEST CONNECTIONS X5767A NOTES:

1. FOR GENERAL NOTES, SEE DRAWING:

33013-2241.

2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING: 33013-1277, REV.8 *
3. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS BREAKS FOR ALL VENT, DRAIN, AND TEST CONNECTIONS SHALL BE AT THE ROOT VALVE IN ACCORDANCE WITH DETAIL "A".
4. ALL SAFETY CLASS UNES ARE SEISMIC CATEGORY 1.
5. MS-600-1 UNE SPEC. APPUES, BUT SEAMLESS 2 1/4" CR-1MO, ASME SPEC. SA335, GRADE P22 PIPE IS SUBSlITUTED.
6. EXCEPT WHERE OTHERWISE INDICATED, SAFETY CLASS FOR INSTRUMENT AIR AND NITROGEN UNES AND COMPONENTS IS BASED ON UPSTREAM INSTRUMENT AIR/NITROGEN VALVE. REFER TO IN-TERFACING AIR/NITROGEN DRAWING FOR SAFETY CLASS.
7. ELECTRICAL SIGNAL IS SAFETY SIG-NIFICANT, PRESSURE BOUNDARY IS NON-NUCLEAR SAFETY.
8. WET LAY-UP SYSTEM HOSES TO S/G'S ARE INSTALLED CONNECTED AND OP-ERATED ONLY WHEN PLANT IS IN MODES A

B c D E F G 5, 6, OR NO MODE OF OPERATION. H LOWER DRAIN VALVE IS CAPPED AND UP-11 PER CONNECTION IS A SUND FLANGE,

9. WET LAY-UP PUMPS, PIPING, AND VALVES AS IDENTIFIED AS SEISMIC ARE PERMANENTLY MOUNTED IN THE CON-TAINMENT.

CONSTRUcnON LIMITED CONSTRUcnON: />S NOTED PREllMINARY NOT FOR CONSIRUcnON BIDOING PURPOSES />S BU!Lt DATE RELE:ASEO FOR 1-"'""'---=G.::;.IN"'"N""A'-S;:;..;T..;..;A~. ----l ~ G\\s., ELEl:nm: O>RP. SCAt£ NONE JOB NO. STEAM GENERATOR SLOWDOWN (SGB} P & ID DRAWING NO. REV. EWR 3391E 33013-1277 SHEET 1 OF 2 ~ CCD 01 CONTROL COPY # 12 J

A B c D E F G H J X14541S 1 (D-7) 33013-1894-2 (B-7) --i;><:.f-l 33013-1894-2 X14527D (A-12) --1:><f-l 33013-1894-2 X5743BH1 (D-7) 3/4" D E-.....---1"' 5796A I (/) 3/4" I v E-c~t--i,~ 5794C 0 I 2 I TSB02B MIXING CHAMBER 57756 3 Pl 4114 DE:i12~3-<118t-3-J--i--{ J ! 5775D ~ ~ OJ 3" 4" -CD-300-1 ~ 33013-1235 ~>------ ---,-----------------____, X9512B~-----~ 3/4" TC 4 TC >---+------1 I i---~-----J 5 TC 6 (D-1) 33013-1233 LSB01 \\ LSB02 \\..+/-:MS-600-2 LSB03 5767 DRAIN HEADER (D-10) 33013-1894-2 (E-2) 33013-1924 L.P. HEATER 3A X5767B MAIN CONDENSER A HOTWELL 6-ES-150-1 5722 2" v [--l I l--IM--=--J 5722F 6" -MV-150-4 2" 7 ATMOSPHERE ~L!J L'...I 5791 B 8 5791A 1" DE--lMi-1 5796S (H-1) 3/4" 1" 2" 1" 600-1 150-4 E 1---c<<J------'-------------'--------1 (H-10) -t:><l-l 33013-1277-1 X5741D (C-11) 3/4" vE-..4---l 5775E -l><l-1 33013-1894-2 >>------ih'I-' -- X14527 3-MS-600-1 5767A ~ 0 OL!.J D 5710 II Pl 4112 33013-1904 ZGS07 (B-12) ~ 33013-1894-2 >>------11//--- X5725BH1


11-J-------l#r'--~t 5~7~0*L-H-.--t D E_,12~3...

81-7+-~--_, J I TC (C-7) --C><l:i~33~0~1~3:-21~89~4~-~2~;>---/f---1 X14542SL (C-7) --[:><f-j 33013-1894-2 X14542S (C-10) ~ 33013-1894-2 X14527A (B-12) 5770P >>-----"H-- ~ 33013-1894-2 >>------11H--- -~'l-x5725AH1 (C-10) 3-MS-600-1 33013-1277-1 X5741Cc_ _____ __.. 3" -MS-600-1 (S-7) --1?.:Sl::i 33013-1894-2 >>---ll-H-X14527C 3/4" DE..... 4-l 57976 5770T 3/4" v E_.,.4-1 5795C II ii 5768A 0 '° 0 L!.J D II Ii OJ LSB04 r--..,..-_ _._ __ --11 Hf--1.---l 5725v 1 I 5790 f--- SEE NOTE 5 4-MS-600-2 ~I 5770M t 5725A LSB05 OJ v t-:------to--'-----; I Hl---'----i I I 5789


l f--- SEE NOTE 5 4-MS-600-2 8-MS-600-2 (E-10)

--,tt-~----th1-' --<< 33013-1894-2 ~ X5768B 5723A 5740A c' SSB01 OJ CONDENSING 1'5 POT~ a> 5724A 1/2" 5739A 1" TUBING 0 v y ~[~ ~ ~ CJ °' t-+-.4--=:J D b 12379 i--__ ~112205 ,,-----.../ "' "' '° "' L!J TC 0 r LT 4108 122086 MANIFOLD ~[~- ~ a> H--.4--JD 0 12377 PT 4104 TSB01 S/G SLOWDOWN FLASH TANK 8-MD-150-2 1"-150-1 2" (B-11) NOTE 4"'"' 33013-1252 ~ ~ SGSCP 5745 Pl 2686 57408 6" 0 I TC i--.-1-J 12397 1" 3/4" DE........, 5797A X5744C MAIN CONDENSER S 57446 5744 5740 3" c_ __ (B-12) (E-10) '° "' "' "' 5742 ~ 33013-1894-2 >~------1/,1-1 - X5743AH1 TC TC TC 33013-1885-1 150-2 150-2 X3678 (F-12) 33013-1231-1 MS HEADER (E-1) 2" 4" TS802A MIXING CHAMBER LSB06 OJ LSS07 4-MD-600-2 LSB08 "' '° 0 5768 CIRCULATING WATER (1-11) 33013-1259 \\_4"-150-2 SEE NOTE 7 NOTE 7 PSB01 <MO/STP> S/G SLOWDOWN FLASH TANK PUMP v I 0 0 I 0 I 9 I 0 I 0 I 33013-1233 X1738V 5716 5717 C 2" --11----+----Mf---'---"---->4-__J DRAIN HEADER MAIN CONDENSER A HOTWELL 1 2 3 4 5 5715 5714A 6 7 8 9 1" I 0 I 0 I... 10 1 1 12 S/G SLOWDOWN CONTROL PANEL (C-11) H < 33013-1894-2 i----+------<C><J-- X 15854 (D-4) ---~1~1----<< 33013-1895 ~ X15301 I 0 I 0 I... (J-8)


<< 33013-1278-2 (D-7) 1"


<< 33013-1235 4"

8" (H-8) 33013-1231-2 (J-7) 33013-1922 J-10 8" NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241
2. REVISION Q" OF THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1277, REV.8
3. ALL PIPING ON THIS DRAWING IS NON-NUCLEAR SAFETY CLASS.
4. FLANGES ARE CARBON STEEL.
5. LINE 600-2 WITH EXCEPTION FOR MATERIAL.

PIPE AND PIPE COMPONENTS MATERIAL SHALL BE STAINLESS STEEL A312 TP304L. ,___ ___________ __, 33013-1885-1

6. ELECTRIC MOTOR EIN'S ARE DEPICTED IN BRACKETS ADJACENT TO MECHANICAL EQUIPMENT PER SFEWR 10328.

DISCHARGE CANAL 10 1 1

7. PRESSURE/TEMPERATURE RATING LINE IS 150-2 WllH EXCEPTION FOR PIPE MATERIAL. MATERIAL IS CrMo P22.

CAD FILE NAME 33013-1277,2 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES 11//S AS BUILT DATE RELEASED FOR GINNA STA. R.E. GINNA STATION SCALE JOB NO. NONE STEAM GENERATOR SLOWDOWN (SGB) P & ID DRAWING NO. EWR 3391E 33013-1277 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

5 10 11 12 A ©----3~*" i:-i-L--~ *. A s.:,i J/:l-SL-4~0:.

  • l.?.~.!~;~~1~.:'.~.. ::~~

B B JiO-t'AS-.i~' D [J t-t-------11---~(;;;~:~~=~*-rx~ J(~<4-4ili'S E E t G t H H t i;-.:~<} **------------------- fl.O* 4 8 lO 11 12

1 A B c D E F G H I J 1 2 3 (B-11) ,..._.,.,__, 33013-1278-1 X927C (8-11) 33013-1890 SOV 14304S (J-5) 9568 tO OJ 3/ff 33013-1247 e..::.3<-8:c..-....:S:..:L'--""-2"-50:..:5'-l!M--:J [-1------~ c___ _____

b8 959 I

RHR LOOP IFcl )> ~ 601 2505 c [Tl II] ?< I i" (D-11) l><'.t---133013-1278-1 X9278 (E-11) 1><:1--; 33013-1278-1 X927A (SEE NOTE 4) aJ I aJ I r r g 01 0 3 8-SL-2505 3 8-SL-2505 960 3/ff' 956A EAC05C PRESSURIZER STEAM SPACE SAMPLE HEAT EXCHANGER 956C 151 ---.-i-o-- (C-2) 33013-1264 LETDOWN 974 ,._. I rn)=o. ~ DEMINERAUZER rc1 fTI I ox ;o OUTLET~ 0* I. 15 3/ff 0 TC E-911~--...--------, 9878 987A 4 3/ff' EAC058 REACTOR COOLANT LOOP 8 HOT LEG SAMPLE HEAT EXCHANGER 3/ff' EAC05A PRESSURIZER UQUID SPACE SAMPLE HEAT EXCHANGER 3/ff 989 151~505 (A-2) I 3/8-SL-2505 33013-1264 >--Did--4-.--'-------11... ----' 2 987 ,._. I LETDOWN

'.S DEMINERAUZER INLET m

I ::o ~ )> 5c I rn 0?<1r 0 0 r-_(_B_-7_) __,3/ 4" ~ -t:><l--133013-1265-2

J E-...,__,..-1---~

)> z X975 VOLUME CONTROL TANK c ;;i ?< I i" rn I rn 3/8-SL-2505 ~ ~I~ I (A-4) 3/4~ 33013-1277-1 X5735 '---------,... STEAM GENERATOR SLOWDOWN 1A 3/8-SL-2505 (F-4) --;:><l--133013-1277-1 X5736 STEAM GENERATOR BLOWDOWN 1B 3 992A w 992C w L 4 988 2505 EAC04A S/G SLOWDOWN SAMPLE HEAT EXCHANGER A EAC04B S/G SLOWDOWN SAMPLE HEAT EXCHANGER B 5 964C 9648 964A 963C 9638 963A 6 RC LOOP 8 HOT LEG SAMPLE PRESSURE VESSEL TSS20

i-vvf __... ----'

962C 965A PRESSURIZER UQUID SPACE SAMPLE PRESSURE VESSEL 961C TSS21 Nvt----1... ----' 9628 9618 9658 PRESSURIZER STEAM SPACE SAMPLE PRESSURE VESSEL TSS22

i-vvf-11... ----'

962A 965C 961A r----- 994A 7 8 9 (B-1) AUX. BLDG. 1" -I-N-TER-. BLD-G. 969A l/2" E-t~--------'---------'-L-=----, 33013-1265-2 VOLUME CONTROL TANK I OJ CS> OJ 983 982 3/ff 986 9998 CX> 968 3/ff tO CX>.... I I I Ul Ul Ul r r r I I I OJ OJ OJ CS> CS> CS> OJ OJ OJ 3/ff SAMPLE l ROOM -HOO~ 985 971 972 3/ff t 3/8" 1" 969 I _ TUB~ 3 4" 1/2" (H-4) 33013-1279 OUTSIDE SAMPLE ROOM INSIDE SAMPLE. ROOM 3/4" w I rn 51 5 G"l G"l (C-1) 33013-1259 CHEMICAL DRAIN TANK (F-10)


11----c 33013-1908-3 10 X4268

"----------' X5030P UNES FOR PERIODIC SAM PUNG (A-6) 33013-1259 SAMPLE SINK LAUNDRY AND HOT SHOWER TANK A TSS23 VOLUME CONTROL TANK SAMPLE PRESSURE VESSEL OJ 9948 tO ~--+----< "?, )> 151 9738 TUBING '-"-"'>+--- 990 (B-1) 33013-1259 RADIO CHEMISTRY LABORATORY DRAIN TANK (G-1) ---,-__.,..__J_..ie----< J-----1------E 3/4" .. 11-----; 33013-1273-1 3/ff' 9928 992D J 5 977 978 ~--~ 979 992E NOTE 5 992F NOTE 5 <O <D ~ I (/) r I OJ CS> OJ OJ <O G"l 3 ff 976 co I (/) r I OJ CS> OJ 995A 996A 9958 9968 S/G 1A CONDUCTIVITY CELL & TEMPERATURE COMPENSATOR S/G 18 E~------< 6 3/ff 3/4" 3/ff 7 INSIDE SAMPLE ROOM OUTSIDE SAMPLE ROOM S.S. 301 WDG (E-9) 33013-1908-3 DEMINERAUZED WATER 12519A c.s. 301 RM-19 STEAM GENERATOR SLOWDOWN PROCESS MONITOR SKID NOTE 3 OJ [Tl FILL f7l v f7l 1/2" 1-'--"--V-r-----'--t---Cl---t--_,,,,.-__ _._ ___ _L__..,,.l-3S 6798A 1" 6796 ~ 125198 (E-10) 33013-1277-2 S/G SLOWDOWN FLASH TANK 8 12519C X5763 9 10 11 1 1 12 NOTES:

1. FOR GENERAL NOTES SEE DRAWING 33013-2241.
2. THIS DRAWING SUPERSEDES PORTIONS OF DRAWING 33013-1278 REV. 9.
3. RM-19 AND RE-19 COMBINE TO PERFORM A SAFETY SIGNIFICANT DETECTION FUNCTION.
4. AOV 959 IS NORMALLY DE-ENERGIZED (FUSES PULLED) AT POWER.
5. VALVES 992E AND 992F ARE THROTTLED TO MAINTAIN PRESSURE LESS THAN OR EQUAL TO 150 PSIG TO MAINTAIN OPERATING PRESSURE AND PROTECT THE FLOW INDICATORS AND RADIATION MONITOR.

CONSTRUCTION UMilED CONSTRUCTION: />S NOTED PREl1MINARY NOT FOR CONSTRUCTION BIDDING PURPOSES />S BUILT RE1£ASEO FOR G_IN_N_A_S_l_A_. _ __, R.E. GINNA STATION SCA1.E NONE JOB NO. NUCLEAR SAMPUNG (SS) P&ID DRAWING NO. EWR 3391E 33013-1278 SHEET 2 OF 2 CCD 01 CONTROL COPY # 12 RE.V. A B c D E F G H J

A B c D E F G H I J 1 2 3 4 5 6 7 8 9 10 1 1 12 (J-10) 10102B

cl

--i><1-j 33013-1899-1 :>~---*ff-------11-H---------ilH----------ti\\~' ----,l X14413S (J-10) u: PIPING TUBING X14412S 10015 __ __iI_-::1_1 ) ___ _ I 33013-1278-1=::>r----- (H-10) 3 8-SS-153 TUB~ I~,, --[:::tj-C]-----* 10025 10097E I~ l0097F z G) TUBING T-211-58 T-211-5A ARGON BOTTLED GAS (A-1) 33013-1899-1


1/--------fl--------H-------~---

1/4-SS-153 33013-2281-1 X14416S X10102J (H-10) 3/8-SS-153 33013-1899-1 3/8-SS-2505 10001 X14417S (C-11) 33013-1278-1 TUBING TUBING ~ ESS04B t:==., -[XJJQ~,u8"lpvvvj~~I-112" 10026 10056 10030 L'J (I -10) 33013-1899-1 >----//---------------//*---*--**-* --- -*-*//-*--*-*---------!'!----- N I (/) (/) I N °' G> X14414S (H-10) 33013-1899-1 X14415S (B-11) 33013-1278-1 10002 (B-7) 33013-1890 X14296S (B-7) 33013-1890 X14294S 10003 3" (G-1) ~-~-~--; 33013-1272-2 (C-7) -£><f-1~_3_3_0_1_3_-_18_9_0 __

>r----I~--+

X14293S 10040 X14292S X1002 X10024 (B-5) 33013-1890 (C-12) 33013-1272-1 CONTAINMENT SUMP PUMP DISCHARGE (F -11) 33013-1888 1 D ['------1 1<ll72 P107 I. BUILDING LCONTAINMENT e e N I (/) (/) I (.}; N I (/) (/) I (.}; iJ) IT] IT] z 0 -j IT] (~ PSS01 CNMT. SUMP A SAMPLE PUMP 11/2-SS-151 10036 [ill 1-SS-151 (I-10) 33013-2252 I~ (/) N I (/) (/) I (.}; CONTAINMENT SUMP A 2 l 3/8-SS-153 10013 3/8-SS-2505 1 2-SS-153 10012 L'J 1/2-SS-153 L'J (D-11) °' TUBING TUBING TE 302 10095 FT 303 10096 10016 // (H-5) 33013-1899-1 X15673 (F-5) 33013-1899-1 '--------' X 14 719S (H-5) < 33013-1899-1 ~s 2" < 33013-1259 3/8'~ I ~-- - - -- -- - -- - - -- - - -- - - -- - - ---D---~0~ 1 ;-cJ-- -J~l-1 1 3301~~;;81-2 POST ACCIDENT SAMPLE COOLER RACK 1/2-SS-2505 X1001 10039A (A-1) 1/2-SS-153 1---------i 33013-2281-1 ---lr-----t><l-Jvvt--1 ><I--~ 10039B 10038 1 /2 COPPER 1 /2-SS-155 AUX. BLDG. INTERM. BLDG. (F-8) 33013-1893 X14429S (E-11) Al 33013-2281-2 (E -11)

  • -1><.l--< 33013-1865-2 I--------~-------~--------~

X1598 10010 1/2-SS-2505 (J-5) 10089 10100 --l'><f--1 33013-1899-1 X14401S (A-10) 33013-1278-2 1/2-SS-2505 4268 426 426A L'J L'J L'.J L'J (1-5) --J:><f--1 33013--1899-1 X14406S (J-5) --t><t-{~~~~-=_1899-~r--~n~-------11-#-------~Jr/-------~H~-------11-fi X14404S (I-5) -*C><]-f 33013-1899-1 X14403S 10052 (I-5) X14402S ,..c..--8 5> <D (E -11) 33013-2281-2 (I-1) 33013-2281-2 j 1/2-SS-153 33013-1899-1 ~ '-------~><f----'-------'- f----1><~ 10006 10044 1/2-SS-151 4 5 6 PSS02 PASS WASTE TRANSFER PUMP 10045 7 10004 8 LE 301 (/) iJ) iJ) G> TSS19 PASS WASTE HOLDUP TANK N I (/) (J) I (.}; 2" (A-1) 33013-2281-2 (I-8) 33013-1875 (F -11)


<< 33013-2281 -2 INTERMEDIATE BUILDING RETURN DUCT 1/2-SS-153 N

I (/) (/) I (.}; 10008 ~~T\\ 10047 r*L2J--~ BSS02 9 1 2-SS-153 10059 1 2-SS-153 PSS03 PASS WASTE HOLDUP EVACUATING PUMP 10 10034 TANK N I (/) (/) I (.}; 1 1 1/4-SS-153 1/2-SS-153 (E-5) 33013-1899-1 X14718S 10011 10042 10018 10041 1/2" l 10043 NOTES:

1. FOR GENERAL NOTES REFER TO DRAWING 33013-2241.
2. REVISION "0" OF THIS DRAWING SUPERSEDED DRAWING 33013-1141.
3. AIR DIFFUSER WHICH DISTRIBUTES AIR MOTOR EXHAUST AND PREVENTS DEBRIS FROM ENTERING EXHAUST.

CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION >-----+----*-~-*--"- BIDDING PURPOSES AS BUILT RELEASED FOR '~ GINNA STA. R.E. GINNA STATION SCALE NONE 01/TAAOO. NEW YORK POST ACCIDENT SAMPLING SYSTEM (SS) P&ID JOB NO. DRAWING NO. EWR 3391 E 33013-1279 CCD 01 CONTROL COPY # 12 REV. A B c D E F G H J

LOG IC SYMBOLS (REF: NEMA STANDARD IC!-1959) SYMBOL t r>a.. *. r' L R LOGIC FUNCTION ANO NOT OR OFF RETURN MEMORY RETENTIVE MEMORY TIME DELAY ENERGIZING TIME DELAY

    • ~ DE-ENERGIZING COINCIDENCE (2 OUT OF 3 SHOWN)

RE TENT IVE MEMORY WITH MANUAL RESET DESCRIPTION R DEVICE WHICH PRODUCES AN OUTPUT ONLY WHEN EVERY INPUT EXISTS. i!ii:l)-,.~*;c.*. *.*,_,,_,.. i*Y' A DEVICE \\IHICH 'PRODUCES RN OUTPUT ONLY WHEN THE INPUT DOES NOT EXIST. A DEVICE \\IHICH PRODUCES RN OUTPUT WHEN ONE (QR MOREi INPUT EXISTS. A DEVICE WHICH RETAINS THE CONDITION OF OUTPUT CORRESPONDING TO THE LAST ENERGIZED INPUT, EXCEPT UPON INTERRUPT ION OF POWER IT RETURNS TO THE OFF CONDITION. A DEVICE WHICH RETAINS THE CONDITION OF OUTPUT CORRESPONDING TO THE LAST ENERGIZED INPUT. R DEV ICE WHICH PRODUCES AN OUT PUT FOLLOWING DEFINITE INTENTIONAL TIME DELAY AFTER RECEIVING RN INPUT. A DEVICE WHICH CONTINUES TO PRODUCE AN OUTPUT FOR A DEFINITE INTENTIONAL PERIOD OF TIME AFTER THE INPUT HAS BEEN REMOVED. A DEV ICE WHICH PRODUCES RN OUT PUT WHEN THE PRESCRIBED NUMBER OF INPUTS EXIST HoXAMPLE: 2 INPUTS MUST EXIST FOR AN OUTPUTl A DEVICE HAVING THE LOGICAL FUNCTION RS INDICATED BY THE DIAGRAM BELOW. RCTURT ING SIGNAL I MANUAL RESET (MOMENTARY P.B.l 212 x ADDITIONAL SYMBOLS /PC'~ 'Y'<s l_ LJ INSTRUMENT CHANNEL (SEE SPEC. G6751G4 FOR CODE LETTER EXPLRNATIONl INDICATES THAT THE DEV ICE OR INSTRUMENT CHANNEL HAS A BISTABLE LOGIC OUTPUT WHEN: - PARAMETER MEASURED IS GREATER THAN A PRESET VALUE - PARAMETER MEASURED IS LESS THAN A PRESET VALUE - PARAMETER MEASURED DEVIATES FROM A PRESET VALUE BY MORE THAN A PRESET AMOUNT -, J#-oR VoR "']...- SAME AS ABOVE EXCEPT WITH AN AUTOMRTICALL y ....t::::J

J

.--L SET VARIABLE VALUE ALARM ANNUNCIATOR (ALARMS ON THE SAME SHEET WITH THE SAME SUBSCRIPT SHARE A COMMON ANNUNCIATOR WINDOW) REACTOR TRIP "FIRST OUT" ANNUNCIATOR TURBINE TRIP "FIRST OUT" ANNUNCIRTOR DEV ICE FUNCTION NUMBER 52 I Pl?- CONTROL CIRCUIT, CHANNEL OR COMPONENT ITEM NUMBER LOGIC INFORMATION TRANSMISSION ~-- ACTION CALLED FOR BY LOGIC INPUT ~ COMPONENT CONTROL CIRCUIT / INDICATES THAT THE INSTRUMENT CHANNEL HRS RN OUTPUT RS FOLLOWS: P - PROPORTIONAL TO THE MAGNITUDE OF THE PARAMETER MEASURED p R - PROPORTIONAL TO THE RATE OF CHANGE OF THE PARAMETER MEASURED I l_ ~tSV~~~LE.l:::f oR roR -:Jc INDICATE SAME AS EXPLAINED ABOVE I ac, tc bo, ta 00 be a 10/. b 10/. INDICATOR LAMP T - TRIP STATUS LIGHTS P - PERMISSIVE STATUS LIGHT B - BYPASS STATUS LIGHTS POSITION SWITCH DEVELOPMENT 0 FULL TRAVEL - I I I I I I I I I I I I I I I I (VAL VE CLOSEOl (VAL VE OPENl DETAIL "A" TITLE REACTOR JRIP SIGNALS TURBINE TRIP SIGNALS DEV ICE FUNCTION NUMBERS ANO LETTERS (REF ASA STANDARD 372-1956 ANO NEMR STANDARD SG5-1959, SEE O\\IG. 10905-7) 1 - MASTER ELEMENT (CONTROL SWITCH) 20 - ELECTRIC OPERATED VAL VE 33 - POST ION SW ITCH SUFFIX LETTER } oc, oo, be, bo - LIMIT SWITCH SEE DETAIL "A" to, tc - TORQUE SWITCH FOR OPERATION 4 3 - MANUAL SELECTOR SW ITCH 52 - AC CIRCUIT BREAKER OR CONTACTOR SUFFIX LETTER o - AUXILIARY CONTACT - OPEN WHEN MAIN CONTACTS ARE OPEN b - AUXIL IRRY CONTACT - CLOSED WHEN MAIN CONTACTS ARE OPEN (c) - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO CLOSE VALVE lo) - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO OPEN VALVE (eel - BREAKER CLOSING COIL (tel - BREAKER TRIP COIL (uvl - BREAKER UNDERVOL TRGE TRIP COIL 63 - LIQUID OR GAS PRESSURE, LEVEL, OR FLOW RELAY 69 - PERMISSIVE SWITCH 72 - DC CIRCUIT BREAKER OR CONTACTOR SUFFIX LETTER a - RUXIL IARY CONTACT - OPEN WHEN MAIN CONTACTS ARE OPEN b - AUXILIARY CONTACT - CLOSED WHEN MAIN CONTACTS ARE OPEN (cl - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO CLOSE VALVE (ol - REVERSING CONTACTOR OPERATING COIL - ENERGIZE TO OPEN VALVE (eel - BREAKER CLOSING COIL Itel - BREAKER TRIP COIL (uvl - BREAKER UNDERVOL TRGE TRIP COIL 86 - LOCK-OUT RELAY SUFFIX LETTER P - PRIMARY BU - BACK-UP INDEX SHEET NO 02 03 SUB 3 2 4160V BUS AUTO TRANSFER 04 3 EMERGENCY GENERATOR START ING 05 3 SAFEGUARDS RCTURT ION SIGNALS 06, 07 5, 3 SAFEGUARDS SEQUENCE 08 5 FEED ISOLRT ION, AUX. FEED PUMP 09 5 NUCLEAR INSTRUMENT TRIP SIGNALS 10 2 NUCLEAR INSTRUMENT PERMISSIVES & BLOCKS 11 4 PRESSURIZER TRIP SIGNALS 12 3 STEAM GENERATOR TRIP SIGNALS 13 2 REACTOR COOLANT SYSTEM TRIP SIGNALS 14 5 ROD ST OPS & TURBINE RUNBACKS 15 4 NOTES: PROTECTION CHANNELS 1 & 3 ARE CONNECTED TO INVERTER SUSSES. AS BUil T REDRAWN PER EWR 4777R ORIGINAL ND. REVISION INITIAL DATE CAD F ILENRME 3Gl3530! M~W l/3191 BR 12116182 DRAWN BY CONSTRUCT ION §JO l*I0-91 JCL 12/16/82 CHKD LIMITED CONSTRUCT ION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION B IOO ING PURPOSE$

e(.

.C.._ /~I'd*'!/ GG 12/1£/82 RESP. ENG. T111'1 1-11-~1 GWD 12117182 ENG. MANG'R RS BUILT TH IS DRAW ING INCLUDES PORT JONS 'o 11.AS UEJ OF CLASS IE ELECTRICAL SYSTEMS. RELEASED FOR ENGR. REFER TO NOTES AND SPECIFICATIONS FACILITY GINNA TO DETERMINE SPECIFIC QR If------*------' ROCHESTER GAS & ELECTRIC CORP. PROGRAM APPL !CAB ILITY. SCALE NONE ROCHESTER, NEW YORK THIS DWG SUPERSEDES Ji DWG 8820612 JOB NO. CCD 4 LOGIC DIAGRAM INDEX & SYMBOLS DRAWING NO. 33013-1353 SHEET REV. 01 /1\\

0 8 2/3 TURBINE AUTO STOP OIL (SHT. 03) 2/2 TURBINE STOP VALVES CLOSED (SHT. 03) PERMISSIVE P-9 (SHT. 11) PERMISSIVE P-7 (SHT. 11) (SEE DWG. 33013-2095 SHTS. 3 & 34) R D24 ~----13/31---~ll-----' R D32 1 /2 + 1 /2 UNDERFREQUENCY (BOTH 4KV BUSSES) -----i. RT11 ~ACK 3 ~---i RT12' (SHT. 04) L 2/2 r---.--, 1/2 + 1/2 UNDERVOLTAGE (BOTH 4KV BUSSES)


i-___J I

RACK 3 (SHT 04) 1/2 I RT11 I R D16 1-----~-i RT12 +-, ~ THOT < 500°F (REF. 10904-204,205) ZIRCONIUM GUIDE TUBE INTERLOCK 1/2 HIGH FLUX SOURCE RANGE (SHT. 10) 1/2 HIGH FLUX INTERMEDIATE RANGE (SHT. 10) 2/4 HIGH FLUX (LOW & HIGH) POWER (SHT. 10) 2/ 4 PRESSURIZER LOW PRESSURE (SHT. 12) 2/3 PRESSURIZER HIGH PRESSURE (SHT. 12) 2/3 PRESSURIZER HIGH WATER LEVEL (SHT. 12) 2/3 STEAM GENERATOR LO-LO WATER (SHT. 13) EITHER LOOP DELETED PER EWR 4773 1 /2 MANUAL TRIP (SHT. 14) 2/4 OVERTEMPERATURE ?T (SHT. 14) 2/4 OVERPOWER ?T (SHT. 14) RANGE LEVEL 2/3 REACTOR COOLANT LOW FLOW BOTH LOOPS (SHT. 14) 2/3 REACTOR COOLANT LOW FLOW EITHER LOOP (SHT. 14) SAFETY INJECTION (SHT. 06 & 07) I - 2/2 r---.--_J R D8 NOTE 1 R D30 TRIP LOGIC TRAIN A ~ TRIP 0 LOGIC TRAIN B (SAME INPUT AS FOR LOGIC TRAIN A) TRIP TRIP 260V A.C. BUS 52 (UV)/BYB 52 (UV)/RTA 52 (UV)/BYA 52 (UV)/RTB 0 52/BYA ) 0 52/BYB O) 0 ) 52/RTA ) 52/RTB ROD DRIVE SUPPLY BUS TRIP 52/BYB EACTOR TRI BREAKER TRIP 52/RTA TRIP 52/BYA EACTOR TRI BREAKER TRIP 52/RTB THIS DWG SUPERSEDES DWG 882D612 ./ / ) M-G SET ROD DRIVE / /

0) 0 M-G SET POWER SUPPLY
I 2121 2/2 THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS.

REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. TO TURBINE TRIP BATTERY 1 B VIA 20/ET (SHT. 3) TO TURBINE TRIP BATTERY 1A VIA 20/AST (SHT. 3) 0 NOTE 1: ZIRCONIUM GUIDE TUBE INTERLOCK UNDERVOLTAGE TRIP BELOW 8% POWER AND 500° F. Jo/z/1$ AS BUILT DATE RELEASED FOR ENGINEER f\\ REVISED PER ill ADC-13-000669 RJM /511;' l?nf J/<6 10/1/13 1*!)1! 10/1/r?: 1o/t/13 REV REVISED FOR 1--~----------4 DRAWN CHECKED RESP REVIEWER FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 33013-1353,2 ONTARIO, NEW YORK LOGIC DIAGRAM REACTOR TRIP SIGNALS ELECTRICAL JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 2 ~ CCD 4 i ICNTRL COPY#

v v VA.. -... . v v v (11P1/1G)~~.J--N--il--O~FF~L=IN~E _________________

  • _v_v v_-_v_v __

v ~* v v v v GENERATOR MULTIFUNCTION

  • , ____ TRIP DISABLED

?:J-ON LINE > GENERATOR MULTIFUNCTION (11P2/1G)--.____) A A A A A A A A A A A A v AT RELAYS A A A A A A A A "'-<"-,_-"--..A/'-~--A~,A, GENERATOR TRIP LO~IC INPUT SIGNALS ( \\ r GEN. DIFF. (87 /G) MCB ' l ) ) } 0... MCB 0.. GEN. GRD. (59/N) --------:~~-=-"*'-"'"!*-~ PIPE CABLE FAULT ~ r-- -;;,.. 1--~ll---~ co (87P /PC PLUS 50 FD/87P-PC) UNIT AUX. TRANSF. DIFF. (87T/11T)-----~ LOSS OF ELECTRICAL LOAD (STA. 13A) ~ [L~ 3 I /T\\ K26 N N N -... P-9 (SHT. 11)------.---l-_l 1-----i-;;rr---------1-_ _J (J) r LOSS OF ELECTRICAL LOAD (STA.13A) UNIT DIFF. (87 /GT) NEG. SEQ. (46) MCB _____________ __,.-i DISTANCE (21) MCB ~~----i DIRECTION POWER (32) --------~ 0 --1------' MCB 3 1G13A72 OR 9X13A72 CLOSED '---.j/~ 4KV BUS , -;---. ;1-------<119-------- AUTO TRANSFER .----l'-'--_./ (SHT. 4) LOSS OF FIELD (40) =M=CB~-------~ UNIT AUX. TRANSF. OVERCURRENT (51/11T) ----~ /T\\ K26


i[>(f-------------0.,.1-~---,r---~

SEE DWG. SEE DWG. LLi LLi (/) UNIT AUX. TRANSF. GRD. OVERCURRENT (51N/11T) ---~ UNIT GRD OVERCURRENT (51G/1T)-------- GEN/UNIT GRD (59G/1GT) ------------' STA. 13A PIPE CABLE FAULT----.-*1 S- ~------ OUTPUT BREAKER FAILURE TO TRIP---. TURBINE TRIP LOGIC INPUT SIGNALS ( r CIRC. WATER PUMP 1A BREAKER OPEN 52/CWP1A (UNIT 3) 'T D CIRC. WATER PUMP 1 B BREAKER OPEN §l ~ 52/CWP1 B (UNIT 28) 0 ~ - Tl STM GEN. FDWTR PUMP 1 A BREAKER OPEN ~ > 52/FP1A (UNIT 7) LLi w (/) STM GEN. FDWTR PUMP 1 B BREAKER OPEN -... 52/FP1 B (UNIT 25) N 1G13A72 OR 9X13A72 CLOSED N [L i--~x ,____I N LL. N A K18 ~ IX>--~ 0 I "' 0 O> 0

z

~~-~ 03021-1011{AMSAC -------------------------@-------------------------I~/ <e ~


------------1---- -------.!- -;---./1------0~;::;-N 10905_0115 { MANUAL TRIP

'--__./ (AT CONT. BD.) /T\\ s REACTOR TRIP K3 (SHT. 2) @ ______________._ _________ _ REACTOR TRIP /\\ ~ COLJ~ N (SHT. 2) @ '~ \\ ............. ~ '.:::- ;1------0~ 0 0 i---- ~'-..__/ N ~ LOW COND VACUUM 63/LV l_ /T\\ K2 TURBINE BRG LOW OIL PRESSURE 63/LBO I '-------------i v (63XT2)LOW AUTO STOP OIL PRESSURE----- (N-T/5501 S3) TEST SW TURB. AUX. GOV.-------i I 1 I I I I I N l_ I -=-r-:= - - - TRusT BRG FAILURE 63/TB - ---= - =F -,---- = __,... ~ OVERSPEED OS -- -- -- -- -- -- J ,~ _r ~- -- _J llll


B----_J L MECHANICAL -HYDRAULIC SIGNAL HAND TRIP (AT TURBINE)

K17 K9 K1 K25 W. DWG. 461 B820 SHT. 6 I I r I l ___ J I 0 N CD 0

r:

(_) N '-.. 1-----~ I '"' (/) <D 0... O>

r:

(_) /A\\ 1 129 v 0 N I <"? v (/) <D 0... <D N <"? 0

c

(_)

A\\ 1 129

---i ~ ;;:;. !-------------~ (/) = 0... /A\\ 1 129 /A\\2 130 ~ ~-------------- §~ G L:S(/) u N N N N ~ N N v 0 0 I "' 0 O> 0 NU1 <D <( ""~ 0,_ ~ ~°". 8 ,___ _____________ u>- N L:SU'i et::~ 0,_ I THIS DRAWING INCLUDES PORTIONS I i OF CLASS 1 E ELECTRICAL SYSTEMS. I REFER TO NOTES AND SPECIFICATIONS I . TO DETERMINE SPECIFIC QA I PROGRAM APPLICABILITY. THIS DWG SUPERSEDES@DWG 882D612 Kif..,,,,,,

14{"{13 AS BUILT DATE RELEASED FOR ENGINEER f\\ REVISED PER

~ ADC-13-001146 RJ M }(R{ -r'R{ f'(/\\ 10/15/13 lrJ/ts-/t3,,fr.;-1!3 10/,,/13 ,__R_EV~ ___ R_EV_IS_ED_FO_R __ ___, DRAWN CHECKED RESP REVIEWER FACILITY GINNA BY BY ENGR SCALE NONE CAD FILENAME 33013-1353,3 R.E. GINNA STATION ONTARIO, NY TURBINE TRIP SIGNALS LOGIC DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 CCD 4 I ICNTRL COPY#

i TRIP

  • 52/AVP-98 UNIT 29 TRIP 52/FPlB.

UNIT 25 ~160V BUS llB 7 VOLTAGE SEE OWG. 10905~16 2 -l/llB 4160\\i :SWGR 1_---UNIT 21 _ __,.,.. 212 MCB AGA S2/27 l11B \\.. '.,/ LO; ON PICK-UP 15 SEC. 52b/BJPl*B 52b/12B . ~ 112) 52/12AX 52/12BX ~ 112) y SYNCH CHECK 25BX *

i.

212 FROM SHEET 3. 4160V BUS llB

  • FAULT 86/HB MCB SEE DWG~

10905-44 4160V BUS llA FAULT 86/llA MCB . SYNCH CHECK 25AX 212 52/12AY 52/12BY 52b/BIA-8 52b/11A f l/2' ' --- --- -I 86XI

  • l 112 I TRIP TRIP 52/RCPlB

... 52/HDP!B UNIT 24 UNIT 27 TRIP 52/CPIB UNIT 26 81-1/llB 4160V BUS llB FREQUENCY 4160V SWGR TRIP 52/CWP!B UNIT 28 81-2/llB i--- UNIT 21 ---t. 1.. 1--+......,.1---e BUS DIFFERENT IRL 868/128 x 12B BUS FAULT 86/12B x '~--...,..-.----. TRIP

  • TRIP 6/6

~ 112) ~ --- CLOSE TRIP . 52/EFlB. 52/15SS

  • UNIT 30 52/8TB-B UNIT 20 52/118 UNIT 23 81-1/l!A 4160V BUS llA FREQUENCY 4160V SWGR 81-2/llA i--- UNIT 11 ---i UNIT 22 SEE OWGS.

10905-15 t. 37 112) .TRIP 52/l!A UNIT 10 .. iX 6/6 CLOSE 52/8TA-A UNIT 12 12A BUS FAULT 86/l2A x BUS DIFFERENTIAL 86B/l2A.* l 112 I TRIP TRIP 52/FP!A UNIT 7 52/RCPlA UNIT B 4160V BUS !IB. VOLTAGE 4160V SWGR 27-3/l!B 27-4/llB TRIP 52/HOP!A UNIT 4 27-3/llA TRIP 52/CPIA UNIT 6 1160V BUS llA VOLTAGE 1160V SWGR 4160V BUS llA 27"'1/llA VOLTAGE 'I.. 4160V SWGR L--- UNIT 10 --...i 27-2/llA 2/2 MCB AGA. 52127 /llA \\. J T.O. ON PICK-UP 15 SEC. ~ l/2 I TRIP 52/CP!C UNIT 5 27-4/llA TRIP 52/EF!A UNIT 9 TRIP 52/CWPIA UNIT 3 SEE OWG. 10905-15 TRIP 52/!3SS UNIT 1 TRIP 52/AVP-9C .UNIT 2 NOTES: 4525. l 4160V SWGR ~l_.{ t THE UNDERFREQUENCY RELAYS ARE SET TO TRIP AT 57.7 HERTZ. THE TIME DELAY BETWEEN REACHING THE s.r.R. ~IN. I VALUE ANO PASSING ON THE SIGNfll TO THE RCP TRJt!.., 'UITS IS APPROX. 0.5 SEC. ~**, =*.,.*

2. 27-'l/llA <Bl ANO 27-2/llA (8) ARE SET AT 82 VOL TS,

<'1200-120 PTl l TIME LEVER. ...,__UNIT 22 ---i SEE DWG 10905-48 t. 317 i--- UNIT 10 _ __, 27-3/!lA <Bl ANO 27-4/llA <Bl ARE SET flT 90 VOLTS M 200-120 PTl; RACK 2 ' S!Xl \\. \\JJB I T -~ RACK 4J SlX2\\ ., 11B.' ~-T~ <NOTE n .I 112) "( ~-------. RACK 1 J SIX! ' 1 llA 1 T 212 REACTOR TRIP LOGIC <SEE SHT. 2) RACK 3 {S!X2' , l!A J T I 112 > I RACK 2 27X3/11B AGA .2 SEC T.D. DROP OUT

1.
1.

RACK 4 /\\. 27X 4 /118 /\\ ~ RGA ~ ,,__>r-.,,, .--;i-- \\ I J.2 SEC T.D. \\ , l -.., V DROP OUT, "- :,.." j 112 RACK l 27X3/llA /\\ AGA ~ .....-4~ .2 SEC T.l). ~.I DROP OUT -., ~ (NOTE 2,3) 212 REACTOR TRIP LOGIC <SEE SHT. 2)

1.

RACK 3 . 27X4/11A /\\. RGA ~ .,..._,r.-, .2 SEC T.ll. \\ . J DROP OUT.* "'- V l/2)

3.

THE UNDERVOLTAGE CONDITION GENERATES A LOGICAL CONDITION OF 'TRUE" (VALUE OF 1), WHICH IS DELAYED BY 27X3/11A(B) & 27X4/11A(B). THIS DRAWING INCLUDES PORTIONS OF CLASS IE ELECTRICAL SYSTEMS.. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. THIS DWG SUPERSEDES 11. DWG 8820612 1~~1 ctlANGE PENDING REVISED PER ADC-13-000890 ORIGINAL RJM 8/5/13 INITIAL BR JC:L GG GWO ORTE 12116/82 1Vl6/82 *J2/16/82 12117182 NO. REV.IS ION. DRAWN CHKO RESP. ENG. i-C~AO~FIL-E-NA_M_E-~36=!=35=3~04~.~_, BY ENG. MANG'R CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED.. pREUMINRRY NOT FOR CONSTRUCTION 81DO'IN6 PURPOSES AS BUil T

  • ffe?

ATE RELEASED' FOR ,. ENGR * . FACILITY GINNA IR.E. GINNA STATION! ONTARIO, NY j SCALE NONE LOGIC DIAGRAM ELECTRICAL PROTECTION LOGIC JOB NO. DRAWING NO. ,~ SHEET. REV. 33013-1353 04 4

  • ccn 4 I I

27 /17 27D/17 480V BUS 17 UNIT 25A UNDERVOL TAGE 27-B/17 27D-B/17 l_ ~ ~---~ 2/2 SI SIGNAL <SHT. 6) TRAIN B


----- ---------- --- 27 /16 27D/16 480V BUS 16 UNIT !!A UNDERVOL TAGE 2/2 27-B/16 27D-B/16 480V BUS 18 UNIT 31A UNDERVDL T AGE

~- ---- ----- -


~

e-- -- -- --1-------1------1--e----1--- ----@t----1----@>----------------1-----~ T TRIP 480V 52/*

  • S\\JGR l_ 52/S\\JPI~ ~NIT 27C 52/S\\JPID UNIT 27D SEE D\\JG, 10905-82A & B A

{ (/) Q_

0 Q_

°" w f- <[ w u ~ °" w (/') I 1/2 TRIP l_ I 2/2 SI SIGNAL TRAIN A TRIP --1--- 112 I ~ 2/2 2/2 TRIP TRIP 52/ll: *

  • 52/BT 17-18 UNIT 28B

<BUS TID 52/17 UNIT 25B <480V) 52/17 SS UNIT 18 (4160V) 52/FP UNIT 26D 52/IH!B UNIT 27 A 52/IHlD UNIT 27B 52/MCC-G2 UNIT 26C SEE D\\JGS. 10905-80, 91 & 100 ( °" CJ f- '-"' CJ (/) "" °" O::::'. w:=: w (/') z: ~~w n..._wDLJ

c :c
0

_J o...wzo "" w °" w<r:WI-Q,::'.j--0::::'.:Z -zUO L,,_,.__. (/) LJ I I I TRIPPED SEE D\\JG. 10905-63 52/17 SOLID STATE OVERCURRENT TRIP (74-1/17) IX <ON GENERATOR B ONLY) 480V S\\JGR 52/EGIB3 <MANUAU /~NOTE 2) SEE D\\./G. TRIPPED 10905-29 SEE D\\./G, 10905-6 7 I -l/EGIB2 <AUTO) 2/2 1/2 4/4 -1/EGIB2 <MANUAL) CLOSE i CLOSE 4~~)EJi~¥R foE9E05~Yo~ UNIT 25C CLOSED CLOSED 2/2 480V BUS 17 <TRAIN A ENERGIZED 27 /18) 27 /17 I 2/2 CLOSE 52/S\\./PlB DR 52/S\\JPlD <PB4) START PUSHBUTTON MCB I SEE D\\JG. ( 115 l 33013-710B \\:_;/ 43/EGIB-~ <REMDTD R3 RESET 3/3 <PB6) 1/EGIB ST ART START PUSHBUTTON MCB LOCAL l/EGIB <PULLOUT>

  • x I

43/EGIB- <LDCAU 2/2 112 2/2 2/2 TRIP 52/16SS UNIT 17 (4160V) 480V BUS 14 UNIT !BA UNDERVDL T AGE l_ 2/2 1/2 SI SIGNAL TRAIN A TRIP TRIP TRIP 52/16 UNIT llB (480Vl 52/BT 16-14 UNIT 12C <BUS TID 480V 52/BT 16-15 UNIT 12B mus TID M 212 I y <NOTE 3) / TRIPPED SEE D\\./G. 10905-66 TRIPPED SEE D\\./G. 10905-62 SEE D\\./G. 10905-61 2/BLB 40 SEC. START DIESEL GEN, B ST ART <Rl OR R2) CIRCUIT DIESEL GEN, B ALTERNATOR OUTPUT 480V I y > t=lO SEC. MAX. TO SAFEGUARDS SEQUENCE <SHT. 8) SEE D\\./G. 10905-27B l/EG1Bl I (AUTO> t l/EG1Bl - <MANUAU CLOSE 2/2 1/2 414 480V 52/EG!Bl UNIT llC CLOSED 52/16 SOLID STATE OVERCURRENT TRIP <74-1/16) x CLOSE SEE D\\JG. 10905-102 480V BUS 16 <TRAIN A ENERGIZED 27 /14) 27 /16 I { 112 2/2 TRIP 480V 52/CCPIB UNIT 16B SEE D\\./G, 10905-72B Q_

J Q_

z: - _J CJ Cl (_) f-

z:

w

z:

CJ Q_ CJ u I \\ 112 TRIP 480V 52/*

  • 52/CHP!B UNIT !SB 52/CHPlC UNIT !SC 52/PHBG UNIT 16A 52/SFPP2 UNIT 17A SEE D\\JGS.

10905-71, 90 & 108 { (U Q_ °" w

0 f-CL

<[ (/) w a... f--- 0.. :c :=i 1--1 CJ CL ~Ct::: ts _J 0.... k:l w L:J 1--1 Q_ :::J

z: Ct::: ~

w.... I L'.J (/) ~ 1-Q:'.: (/) (._) Z: <CW<CW I Ct::: IXl 0.... u Q_ V') I I I \\ TRIP 480V 52/ll: *

  • 52/S!PlB UNIT 12A 52/SIPlCl UNIT 13A 52/CF!B UNIT 13C 52/CF!C UNIT 14A 52/MAFP!B UNIT 14C 52/RHRPIB UNIT 15A SEE D\\JGS, 10905-73B, 74, 77, 78B, 94 & 95 A

{ I I l l { 2/2 R-lD RELAY TRIP MCC D UNIT 4B NON-SAFE GUARDS LOAD SEE D\\JG 10905-118 A °" '-"' w zC-

z:

""w _JLJ ~

0 _J

""CJ . °" Xf-

0 z:

<[CJ u °" CJOo'. f-CJ Uf- <I: CJ w"" °" I THIS D\\./G SUPERSEDES \\J D\\JG 882D612 NOTES: L SHO\\./N FOR TRAIN B <DIESEL GENERATOR B). TRAIN A <DIESEL GENERA TOR A) IS SIMILAR. <

REFERENCE:

33013-652 480V ONE -LINE DIAGRAM,) 2 BUS 17 4160V/480V STATION SERVICE TRANSFORMER BKRS.

3.

BUS 16 4160V I 480V ST A TIDN SERVICE TRANSFORMER BKRS. CLASS 1 E AS BUILT I DATE RELEASED FOR ENGINEER As BUILT PER ocR RMs c~J11 -:r.11*'"' ~ 2001 -0051 REV'D R3 RESET SYMBOL 3/6/01 l~h! '3/~(;!/ '3/C/{Ot 1--R_EV-'-___ R_E_VI_SE_D_F_OR __


J DRAWN CHECKED RESP REVIEWER FACIUTY GINNA BY BY ENGR 1-s_cA_L_E ----c-cN_O""'N'""'"E-,-----1 ROCHESTER GAS & ELECTRIC CORP.

CAD FILENAME 3G135305 ROCHESTER, NEW YORK ELECTRICAL LOGIC DIAGRAM EMERGENCY GENERATOR "B" STARTING JOB NUMBER DRAWING NUMBER SHEET REV 5282 33013-1353 s£ ~C_C_D_4_ ICNTRL COPY#

i~"'=**~,,,_7--**"w>""--'*'""""""""""""'"'"*-*"*~"'=""--"""">"=---~,..-"'*'"'""""~-**-""""'"""==="=l'-.*'-~...,..,,_,=w.--"'-~-"..,_"".:="""'"'~=,,,...... "'.""'"*~'-'"'*~-=-=,-=-,,.~"'-~-,,,=""'"=-=""=~~"'"'..,,_._~~-=-=~*~-=*=~'~-~.,~~~~==ii,,,,,,,,,,,,,,,,,,,,,,.==w~~==='""'~----~--~-~~~~=---~=-=---,--~-~*==<.1~-, ... -=.. =-=,~*==-'-=,,_---"-""-"'*==~*==""~=,,, ..,,=~-m=-.-'"-~*===-=,-~-~-,~~-=~----~-~--"""""~~~-~---*~~~*--~ .. ~ .. -....~--=---~~=-*-,*~*! I 2/4 LOW TAVG (SHl 14) T 1 (Fc\\ ~~ 1/2 SEE DWG. 33013-661 2 LOOP A 2 _r G26 --& SEE DWG. 10905-396 2/2 MS1 (TR. A) MS2 (TR. B) SEE DWGS. 33013-660 & 662 STEAM LINE 2/3 SEE DWG. 10905-396 llil-.,/R 021 SEE DWG. 10905-378 3 ~ __[ T HI 1/2 PRESSURIZER LOOP B SEE DWGS. 33013-661 & 662 3 1/2 G31

  • -&SEE DWG.

11/1905-397 SEE DWGS. 3311113-660 & 662 2 SEE DWG. 10905-396 2/3 SEE DWGS. 33013-660 & 662 --~ MANUAL SI BLOCK 1-. 2/3 (MOMENTARY) NOTE 2 r RESETS S!-B1 SI-82 1/2 +---cv --~LJ~ l~ Sl-B1 (TR. A) SI-82 (TR. 8)


~-*-----------

2~ ~l D22 <t't-& SEE DWG. L ___ 10905-379 ~~~--~,...,..,._,,.,, SEE DWGS. 33013-660 & 662 ~---~ 2 3 l T ~ C27 SEE DWG. ........... ~~~ 10905-371 2/3 2/2 D19 -.& SEE DWG. 11/1905-378 J I *----0 SI-A 1 (TR. A) SI-A2 (TR. B) 1/4 ---{ii) R L R L SHT. 07 SI-M1 (TR. A) Sl-M2 (TR B) MANUAL RESET SI (AUTO + MAN) PB/PSI 2/2 SHT. 07


SI-10X--~~--*--------8 (TR A)

SHl 07


*~-------*---

1/2 SI-20X ,---* -------~--------------**------- --**---*-*-----~---*~-~--J (TR. B) I ------------------------------------*-------.--------*-----------------~. ~----------*-----~-~~--------~. ------*-*-----~-----*-------......

  • ~-----------**- ------*------~-------

~- --=-- ----------0 SHl 07 r-**-------~. ----*~-- I ~----------------*---*--------*--*---- -----~-----*---.. --.. -=----~~~~-------- -------=~~ ------------------0 SHT. 0 7 T '~--~o-W*~~~*= .. ~* _,.-~~'*'*~---='-'"'-' ,_,_,~,~*~*=-~--~------ -*.e'-c--- EMERG. DIESEL (SHT. 8) ~ 1~ ~~ ~-&G~~E DWG. ~~G~~E DWG. c & -OTHER ACTUATIOI~ '1 10905-394 I 11/1905-39;) i r SIGNALS (SH. 9) ~ I I r S1EAJ LINE J [-STEA~~ LIN.El c* FfEDWA~ER-ISOLATION ISOLATION ISOLATION LOOP A -** LOOfl!_____ J~HT_._ 9_)_~ REACTOR TRIP LOGIC (SHT. 2) OTHER ACTUATION 1---~-------------------*---*----**---*---**-*------~---~---------. -----~.

  • SIGNALS 1**----**--**-----*-*------.-------~-----~--. -

(SHT. 9) l" r-* ~-------*~* - _J__ -- [ __ i<. __ J ~***

        • ------~ c: __ 1= _____ L::__ - ---~*

AUXILIARY SAFETY SERVICE WATER RESIDUAL HEAT FEEDV(~~~R 0UMPS INJECTION --- FAN COOLING-- P~~A~-START REMOVAL PUMPS SAFE GAU RDS SEQUENCE FINISHED (SHl 8) THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLJCABILITY. THIS DWG SUPERSEDES W DWG 882D612 NOTES:

1. PC-479A IS FED FROM A SEPARATE INVERTER (MQ-483)

SUPPLY WHICH JS CONNECTED TO 1A BATIERY.

2. MANUAL SI BLOCK IS A 3-POSITION SELECTOR SWITCH.

IT IS MAINTAINED IN THE BLOCK POSITION AND IT SPRING RETURNS TO NORMAL FROM THE UNBLOCK POSITION. THERE IS, ONE SWITCH FOR EACH TRAIN

  • - INCLUDES LEAD/LAG COMPENSATION FOR PREVIOUS REVISIONS SEE MICROFILM p:.;--:-12~ q 3* *..

==~~~--- ~=""""=~,,..,-,_,,<>=c_.._ AS BUI.LT EWR 41151'.> 1'111.t!> DATE RELEASED FOR E'NGINEER 6 ~. ~. 11 AS BUILT PER DPM 8D S\\ l\\B f¢.B EWR 47738 '-1-S- ~3 ~-9 AS SHOWN 3/22/93 '1-8~ REV REVISED FOR

==!DRAWN CHECKED RESP ENGR FAC!UTY GIN NA BY BY ENGR MANAG SCALE NONE ROCHESl ER GAS & ELECTRIC COR I I I I I ' I ! " I I I I I l i ! i ' ! I I !1 ! I I I ! i I I I I f; ' '

PC 945A 3 947A 2 PC '949A SEE DWG. --r-~- 10905-0371 2/3 HI 2 PC 946A 3 PC 948A ~I C~51 I -~-/ ~3 CONTAINMENT SEE DWGS. 33013-0660, 0661 & 0662 NOTE 1 4 PC 95111A I HI-HI C25 1 PC 945B C25 3 PC 947B 2 PC 949B JT 2/3 C25 HI-HI A28 A 6 NOTE 1 3 4 PC PC 948B 950B ~ A. C25 C25 SEE DWG. 1091115-0363 2/2 CONTAINMENT HI-HI PRESSURE SIGNAL 2/3 5 A C25 HI-HI A28 A 6 SEE DWG. 33013-0662 MANUAL SAFETY INJECTION PB/MSil PB/MSI2 1/2 CONTROL BOARD SEE DWG. 33013-0663 MANUAL STEAM LINE ISOLATION LOOP A PB/MMSl MSl (MS2) MANUAL STEAM LINE ISOLATION LOOP B PB/MMS2 MS3 (MS4) SEE DWG. 33013-111664 MANUAL MANUAL SPRAY CONTAINMENT ISOLATION PB/MS1 PB/MCl PB/MS2 PB/MC2 2/2 i n--*---------- 1 I AIR PARTICLE ~ 11 CONTAINMENT RADIOACTIVITY DETECTORS K850 Rl 1 I SEE DWG. 33013-111664 RADIO GAS MONITOR RC K850 12 R12 _f E16 SEE DWG. E16 10905-0038 1/2 TRAIN A SI TOXIC GAS A MANUAL r CL NH3' ISOLATION TRAIN A TRAIN A PB/ X6850J8J CR1A I 1/6 CONTROL ROOM RADIATION MONITOR TRAIN A TRAIN B 8 R46 I SEE DWG. 10905-0546, 1 D28 ~------- --------------------------------------------- A SHT. 1116 SHT. 06 R B SHT. 06 SEE DWG. 10905-038111 SHT. 06 81----------------- ------~ SHT. 06 8(;\\ SHT. 06 GI--------------* SEE DWG. 33013-0662 Sl-17X Sl-16X SHT. 06 0----------------- rni=~~~l 52/14-UNIT 18B 52/16-UNIT 11 B NOTES:

1. PC-950A AND PC-950B ARE FED FROM A SEPARATE INVERTER SUPPLY WHICH IS CONNECTED TO 1 A SUPPLY.
2. THIS DRAWING CONTAINS A PORTION OF 33013-1353 SHT. 6, REV. 2.

~---NORMAL SUPPLY 480V BKR TRIP -r-~~ SEE DWGS. 10905-0664 2/2 THRU 0675 MCB CLOSE SERVICE NON-SAFEGUARDS ISOLATION VALVES 42/* *

  • SHMV-lAl (SHMV-1A2)

ABIV-1 Bl ABIV-182) ABIV-1A1 ABIV-1A2} ACIV-1A1 ACIV-1A2 TBIV-1A1 TBIV-1 A2 TBIV-181 TBIV-182) MANUAL RESET (MOMENTARY PB) 2/2 I /\\ A27 ~SEEDWG. 10905-0362 CONTAINMENT SPRAY THE CONTENT OF 33013-1353 SHT. 7, REV. 0 HAS BEEN REDRAWN TO 33013-1353 SHT. 8, REV. 2. THIS DWG SUPERSEDES '!{ DWG 882D612 2/2 MANUAL RESET (MOMENTARY PB) I 2/2 A26 r----& SEE DWG. SEE DWG. 33013-0664 _J 10905-0362 ~C-0-NTAINME~-l ISOLATIO~ MANUAL RESET (MOMENTARY PB) 2/2 2/2 CONTAINMENT VENTILATION ISOLATION A25 A SEE DWG. 10905-0362 1/4 PURGE 1/ HS-88 SEE DWG. 10905-0542 CONTROL ROOM PURGE AKD01, AKD04 - OPEN El 1 SEE DWG. 10905-0384 RESET A TRAIN CREATS START AND CONTROL ROOM ISOLATION AKD02, AKD03, AKD21, AKD22, AKD23, AKD24 - CLOSE CREATS FAN AKF10A STARTS THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. TRAIN B SI TOXIC GAS CONTROL ROOM RADIATION MONITOR ~~A MANUAL r CL NH3 1 ISOLATION TRAIN B TRAIN B TRAIN B TRAIN A ~ X685~ X6853J R46 R45 1/6 SEE DWG. 10905-0546,2 El 1 SEE DWG. 10905-0384 RESET 8 TRAIN CREATS START AND CONTROL ROOM ISOLATION AKD02, AKD03, AKD21, AKD22, AKD23, AKD24 - CLOSE CREATS FAN AKFl 0B STARTS AS BUILT DATE RELEASED FOR ENGINEER f\\ REVISED PER PCR LD 2003-0037, REV. 1 1---REV~ ___ R_EVI_S_E_D _FO_R __ _, DRAWN CHECKED RESP REVIEWER FACIUTY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD flLENAME 3G135307 ONTARIO, NY ELECTRICAL LOGIC DIAGRAM SAFEGUARDS ACTUATION SIGNALS JOB NUMBER DRAWING NUMBER SHEET 33013-1353 7 CCD 4 CNTRL COPY# REV

I

r:

u; . CJ en (/) c "' rn

0

(/) rn CJ rn (/) CJ Ci) ro ro N CJ

0) -

N c... 0 co z 0. w wo (S) :0 ,_. :0 w"" I z ,_. G"> Wz CJ1 0 w (]) (S) I CD hi (/)

D

'1 rri, G)C) CG)

I)_
on CJ

(/)CJ (/) ::D rr1 G) o:o c:o rr1 3: z n rr1 15 Ci) z: z: rn z:

D zm rn r

"' m n o~

o n 7'< n 0 :0
o 0 ()
0 I lJ ffl z 0

1-i z (j) 2/871A \\.. I,.) 3 SEC. SEE DWG. 1090S-620 CLOSE MCC C POS. llC MOV 871A SI SIGNAL TRAIN A (SHT. 6l I Sl-10X SAFEGUARDS TRAIN A 480V BUS 14 UNDERVOLTRGE 27 /14 270/14 I l._ ~ 1/2 2/2 278/14 270-8/14 I l._I 112 ) y 52/SIPJC2 OPEN 278/16 270-8/16 I l._(112) T SAFEGUARDS TRAIN B 480V BUS 16 UNDERYOLTAGE 27 /16 270/16 I l._ ~ 1/2 212 x --""". x ~ 52/SIP1C2 .. I ALM SWITCH x 313 2!2v ~ SIS SEE DWG. ~----~J--~~t-1 PIA *. 1090S-73A \\. I.) 2/1C2X 30.SEC. SAFETY INJECTION PUMPS SAFETY INJECT ION PUMP lC RESIDUAL HEAT REMOVAL PUMPS SERVICE WATER PUMPS CONTAINMENT A IR RECIRCULATION FANS CONTAINMENT AIR RECIRCULATION FANS MOTOR OPERATED AUX FEEDWATER PUMPS z: 0 - _, [TJ (/).. 480V SWGR 52/SIPlA UNIT 20A 313 CLOSE x .-x..__ _ ___. 2/SIP1C2 \\.I.) S SEC. SEE DWG. 1090S-7S CLOSE 480V SWGR S2/SIP1C2 UNIT 19A 2/RHRPlA \\._ l,.1 10 SEC. SEE. DWG. 1090S-78A CLOSE 480V SWGR S2/RHRP1A UNIT 22A lS SEC. \\ J 2/SWP!A 52/SWP CLOSE SIGNAL TRAIN A (SHT. SJ I 112) SSS-TWO POSITION SWITCH TO SELECT EITHER PUMP lA 212 CLOSE 480V SWGR 52/SWPlA UNIT 29C 2/CFlA \\. L/20 SEC. SEE DWG. 1090S-94 CLOSE 480V SWGR S2/CFJA UNIT 23C 2/CF!D \\..I,.) 25 SEC. SEE DWG. 1090S-9S CLOSE 480V SWGR S2/CF10 UNIT 20C 2/MAFPJA \\.. L/ 30 SEC. TO AUX. FEED PUMP 52/MAFPJA (SHT. 91 2/SFJ \\..L/1-2 MIN SAFEGUARDS SEQUENCE FINISHED (SHT. 6J OR PUMP IC SEE DWG. 10905-81 SEE DWG. 10905~?6 SEE DWG. 33013-662 112 2/2 CLOSE 480V SWGR 52/SWP!C UNIT 29D 2/8718 \\.. l./ 3 SEC. ~12 SEE DWG. SIS 1090S-738 P IB SEE DWG. 10905-621 CLOSE CLOSE 480V SWGR 52/SIP!B MCC D POS. llC MDV 8718 UNIT 12A 2/2 2/SIPlCl \\ J? SEC SEE OWG.~t CLOSE 1090S~74 480V SWGR S2/SIP1Cl UNIT !3A 2/RHRPlB \\ ..I 12 SEC SEE DWG. 1090S-78B CLOSE .480V SWGR S2/RHRP1B UNIT !SA S2/SWP CLOSE SIGNAL TRAIN B (SHT. Sl 2/SWP!B \\.. I_/ 17 SEC ~ 1/2) 2/2 CLOSE 480V SWGR 52/SWP!B UNIT 27C l SSS-TWO POSIT ION SWITCH TO SELECT EITHER PUMP 18 I 112 OR PUMP ID SEE DWG. 1090S-82 2/2 CLOSE 480V SWGR 52/SWPID UNIT 270 2/CFJB \\.. l./ 22 SEC. SEE DWG. 1090S-9S CLOSE .480V SWGR 52/CFJB UNIT 13C 2/CFJC \\..I,.) 27 SEC. SEE DWG. 1090s~94 CLOSE 480V SWGR S2/CFJC UNIT 14A 2/MRFPIB \\.. l./ 32 SEC. TO AUX. FEED PUMP S2/MAFPIB (SHT. 9l 2/SF2 \\ 1 1-2 MIN SAFEGUARDS SEQUENCE FINISHED (SHT. 6) I SEE DWG. 10905-77 SEE OWG. 33013-662 SI SIGNAL TRAIN B (SHT. 61 I Sl-20X I I

I STM. GEN. A 2/3 HIGH LEVEL (SHT. 13) FCV-466 (MAIN) 1/2 F-10X (F-20X) CLOSE FEEDWATER ISOLATION SI SIGNAL (SHT. 6) STM. GEN. B 2/3 HIGH LEVEL (SHT. 13) SEE DWGS. 33013-665 10905-274 10905-733 THRU 736 I 1/2 TRIP 52/FPlA (NOTE 1) 4160V SWGR UNIT 7 TRIP 52/FP1B (NOTE 1) 4160V SWGR UNIT 25 SEE DWG. 10905-30 F-30X (F-40X) F1 CLOSE CLOSE F3 (F4) CLOSE (F2) FCV-480 (BY-PASS) FCV-476 (MAIN) MAIN & BY-PASS FEEDWATER CONTROL VALVES (NOTE 3) FCV-481 (BY-PASS) TRIP CLOSE FEEDWATER ISOLATION VALVES /\\ 3994, 3995 ill SEE DWG. 10905-0833 52b/FP1A FEEDWATER PUMP BREAKERS OPEN 52b/FP1B .-------1-. 2/2 SEE DWG. 10905-317 I 2/2 SEE DWG. 10905-76 AUTO 1/MAFP1A t 0iJ 480V BUS 14 REMOTE 43/MAFP1A - -S-I-SI-G-NA_L ____ ~ ~-ENERGIZED SI-11X 27/ 14 TRAIN A -x~ REMOTE (SHT. 6) 43/MAFP1A SAFEGUARDS SEQUENCE TRAIN A 3/3 (SHT. 8) 5/5 START 1/MAFP1A MANUAL START PB LOCAL 43/MAFP1A -~. 2/2 I OPEN ASSOCIATED PUMP DISCH. VALVE AFDV-1A (V4007) MCC A SEE DWG. 10905-659 CLOSE ALL BLOWDOWN ISOLATION VALVES OF STEAM GENERATORS V5737, V5738 SEE DWG. 10905-739 SHT. 1 & 2 START 52/MAFP1A 480V SWGR. 2/2 STEAM GENERATOR A 2/3 LO-LO LEVEL (SHT. 13) AUXILIARY FEEDWATER PUMPS STEAM GENERATOR B 2/3 LO-LO LEVEL (SHT. 13) LOSS OF 4KV VOLTAGE 1/2 2/2 SEE DWGS. BUS 11A 10905-15 & 317 (NOTE 2) BUS 118 (NOTE 2) SEE DWG. 10905-16 4160V SWGR. 27X1/11A UNIT 11 27X2/11A 4160V SWGR. UNIT 21 27X1/11B 27X2/11B SEE DWG. 10905-77 I T 1 I AM SAC 62/11A \\_L) 3-15 SEC. 67/11B \\_L} 3-15 SEC. 2/2 480V BUS 16 (2_;iJ AUTO 1/MAFP1B MANUAL OPEN __ ----------~ V-3505A OPENS MANUAL OPEN __ V-3504A CLOSE ENERGIZED-~ ~-----SI-SIG-N-AL-27 /16 SI-21X V-3504A & V-3505A REMOTE ~x TRAIN B 43/MAFPl B (SHT. 6) SAFEGUARDS - SEQUENCE TRAIN B REMOTE 43/MAFP1B START 5/5 1/MAFP1B (SHT. 8) 3/3 MANUAL START PB 2/2 START 52/MAFP18 480V SWGR. CLOSE ALL SLOWDOWN ISOLATION VALVES OF STEAM GENERATORS V5737, V5738 SEE DWG. 10905-739 SHT. 1 & 2 OPEN ASSOCIATED PUMP DISCH. VALVE AFDV-1B (V4008) MCC B SEE DWG. 10905-600 LOCAL j~*43/MAFP1 B _,.I---'~ 2/2 I THIS DWG SUPERSEDES W. DWG 882D612 10 ON TDAFW AUTO START ONLY ALL BLOWDOWN ISOLATION START TURBINE DRIVEN AFW PUMP THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. VALVES OF STEAM GENERATORS V5737, V5738 SEE DWG's, 10905-0739 & 10905-0740 8/ i 4-1 <>B DATE NOTES:

1.

FWP BREAKER TRIP CAUSES CLOSURE OF ASSOCIATED PUMP DISCHARGE MOV. V3977 FDV-1 A MCC A (V3976 FDV-18) MCC B SEE DWGS 10905-654 & 655

2. 2 CONTACTS PER BUS.
3. 2 SOLENOID VENT VALVES PER FCV.

DE-ENERGIZE TO VENT.

4.

THIS DRAWING CONTAINS THE INFORMATION THAT WAS PREVIOUSLY FOUND ON 33013-1353 SHT. 8, REV. 1. AS BUILT RELEASED FOR ENGINEER REVISED PER AJV3 /41-L-e.nj

f,4,/

OCR 2008-0148 PCR 2004-0057, REV.1 8/7/0JJ ~Ji{rf(, '}t1/c$ ?/r4fccg r----REV ____ R_EVIS_ED_FO_R __ DRAWN CHECKED RESP REV!EwEF FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G135309 ONTARIO, NY LOGIC DIAGRAM FEEDWATER ISOLATION ELECTRICAL & AUXILIARY FEEDWATER PUMP JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 9~ CCD 4 I ICNTRL COPY #

RACK 1 () R~K l r ' N('\\ _J I 31£/ TR IP BYPASS x l/N 318 -e-...t (NIS RACKl SEE DWG. 10905-383 313 RT 13 RT 14 RACK 3 l/N 33A LOGIC TRAIN A l/N 338 LOGIC TRAIN B SOURCE RANGE REACTOR TRIP LOGIC SEE DRAWING 33013-2i:J95 SHTS. 5, 6, 15, 36, 37 & 46 RACK 2 MANUAL BLOCK

  • MOMENTARY l/N 33 P-6 (CONTROL BOAROJ (SHT. lll DE-ENERGIZE SOURCE x

RANGE H-Y (BOTH A & B LOGIC TRAINS REQ'OJ e-___,... RACK 2 ENERGIZE SOURCE RANGE H.Y (EITHER LOGIC TRAIN) p ~ 112) .--"fiR D26 HIGH NEUTRON FLUX REACTOR TRIP (SHT. 2) SEE DWG

  • 10905-380 RACK 2 r il"'NC\\_J 1 32.!ll B

X RACK 2 -...i TRIP BYPASS 3/3 RT 13 RT 14 RACK 3 l/N 32B (NIS RACKl SEE DWG. 10905-383 RACK 1 TRIP BYPASS x l/N 35A ----t i-~ (NIS RACK) L ~E7 SEE DilG. l t 10905-383 TO IR ROD STOP (SHT. 11)

  • l/N 38R LOGIC TRAIN A l/N 38B LOGIC TRAIN B 313 INTERMEDIATE RANGE REACTOR TRIP LOGIC SEE DRAWING 33013-2095 SHTS. 6, 13, 37 & 44

.------RACK 2 RA.::.-2 I J NC' 1 36F j MANUAL BLOCK

  • MOMENTARY l/N 38 (CONTROL BOAROJ

~.---P-10 I 212 x (SHT. JD OTHER LOGIC TRAIN I t 2/2 RACK 2 -~* ( ) rx-~ _*.,..._ RACK 2 .---1 TRIP BYPASS l/N 36R 8 RT 13 RT 14 RACK 3 p TO IR ROD STOP (SHT. Ill ~ 112 _,R Dl8 HIGH NEUTRON FLUX REACTOR TRIP (SHT. 2l SEE DWG. 10905-378 E7 L ~ l 3/3 TO IR ROD STOP RT 13 ($HT* II) RT 14 RACK 3 (NIS RACK) SEE DWG. 10905~333 T POWER RANGE REACTOR TRIP LOGIC SEE DRAWING 33013-2095 SHTS. 4, 6, 35 & 37 Gr T Gr

  • l RACK 4 MANUAL BLOCK
  • MOMENTARY l/N 47 (CONTROL BOAROJ 112 )

...; ~- P-10 (SHT. 11) 2/2 OTHER LOGIC TRAIN I + ) 2/2 2/4 RACK 4 (114) x E27 e I ASEE DWG. ""110905-385 2/2 m SEE DWG. Dl010905-376 HIGH RANGE REACTOR TRIP LOW RANGE TRIP RT13 RT14 RACK 3 ~ 112 HI NEUTRON FLUX REACTOR TRIP (SHT. 2) NIS RACKI NIS RACK 2 NIS RACK 3 'NCI. {NC, JNC\\ s \\!_IR / s \\!_2R t s \\.!_3R I . ~19 i;_J9 !il9 T 1--_._,.~A. ~ \\.!) lJ;l.l, 2 2 2 SEE DWG. 10905-385 2/4 NIS RACK 4 ,!"'NC\\ r 44.V _J El9 A \\.!} ~ 2 RT! RT2 RACK I ~ D2 SEE DWG. 10905-374 HIGH RANGE TRIP

  • l/N 47A LOGIC TRAIN A l/N 478 LOGIC TRAIN B SEE DWG. 33013-2095 SHTS, 17 & 48 THIS DRAWING INCLUDES PORTIONS f\\

OF CLASS lE ELECTRICAL SYSTEMS. LJ REFER TO NOTES AND SPEC IF ICAT IONS 11----:---r-----------+----+--+---..+--_. TO DETERMINE SPECIFIC QA f\\ PROGRAM APPLICABILITY. LJ CHANGE PENDING /\\ AS BUil T - REDRAWN PER M§.--MJw ~ D !ZLC. -!'\\\\-\\"\\ ffi EWR 4777R EWR-~----- ~~=+-------,,--,--!---+-'--'-'-f--'-..:.:.-t-'-_:_:_m INITIAL 0 ORIGINAL DATE 117191 l-!0-91 /-/d*1 f 1-1<.A\\ ( BR JCL GG GWD 12/16/82 12/16/82 12/16/82 12/17 /82 DRAWN RESP. ENG. BY CHKD ENG. MANG'R NO. REVISION CAD FILENAME 38135310 CONSTRUCTION LIMITED CONSTRUCTION: AS NOTED PRELIMINARY NOT FOR CONSTRUCTION BIDDING PURPOSES RS BUILT DATE RELEASED FOR ENGR. ._F_AC_l_L l_T_Y _G_IN_N_A ____ __, ROCHESTER GAS & ELECTRIC CORP. SCALE NONE ROCHESTER, NEW YORK THIS DWG SUPERSEDES II_ DWG 882D612 LOGIC DIAGRAM NUCLEAR INSTRUMENTATION TRIP SIGNALS (~ ~, r--J=o=-B-:-N=o-. ---,,------=D-=-RA=-w""'1N"""G~No=-.---~S-HE_E_T~R-E-V.~ 33013-1353 10 11\\ CCD 4

RACK 1 RACK 2 _f ff----@ SEE DRAWING 33013-2095 SHTS. 12 & 43 SEE DRAWING 33013-2095 SHTS. 1©, 11, 41 & 42 RACK 1 ff----@I NUCLEAR POWER RACK 2 2/4 >Z% RACK 3 POWER RANGE NIS BISTABLES RACK 3 2/4 RACK 4 P-1© (SHT. 1©) RACK 4 NUCLEAR POWER RACK 4 RACK 1 HIGH COND PRESS _f LOSS OF CIRC. WATER PUMPS RACK 3 RACK 4 52 52 AX BX l_ T 2/2 l_ F2l SEE DWG. -&. 1©905-389 2 F21 SEE DWG. -&. 10905-389 2 RACK 1 pg (SHTS. 2 & 3) C0 RACK RACK RACK RACK 1 2 NC 41N I T p 1-----1 3 4 NC NC 43N 44N I I 2/4 > Y% RACK 1 P8 (SHT. 14) CD SEE DWG. 33013-2095 SHTS. 9 & 40 RACK 1 INTERMEDIATE RANGE RACK 1 RACK 2 POWER RANGE RACK 3 RACK 4 P-6 PERMISSNE 2 3 4 SEE DRAWING 33013-2095 SHTS. 7 & 38 INTERMEDIATE RANGE ROD WITHDRAWAL STOP /\\ SEE DRAWING NOTE 1 ~ RACK 1 ff----@ MANUAL RESET MOMENTARY 1/N 39A-- 1/N 39B 2/2 NOTE: _f RACK 2 1/2 2/2 33013-2095 SHTS. 13 & 44 _f RACK 1 RACK 2 FROM IR BLOCK LOGIC --JIY-----, (SHT. 10) FROM 1/N 36A ~-IR BYPASS (SHT. 10) FROM 1/N 35A IR BYPASS (SHT. 10) SEE DWG. 33013-1606 SHT. 4 3/3 3/3 1/2 RS1 ---1A E13 HIGH NEUTRON FLUX (SHT. 15) & NOTE 1 SEE DWG. 10905-384 PERMIT MANUAL BLOCK OF SOURCE RANGE TRIP (SHT. 10) ._-(p INTERMEDIATE RANGE PERMISSNE 6 (SHT. 10) RACK 1 2/2 RACK 2 _f 1/NC41L MANUAL BYPASS NC 42L 2/2 POWER RANGE RACK 3 _f 1/NC42L MANUAL BYPASS 1/4 NC 43L 2/2 RACK 4 _f 1/NC43L MANUAL BYPASS NC 44L 2/2 E21


IA SEE DWG.

OVERPOWER ROD STOP (BLOCK MANUAL ROD WITH-DRAWAL) (SHT. 15) & NOTE 1 10905-385 _f 1/NC44L MANUAL BYPASS -TS 1+TS M.R. NC1/41K NC _f 41K M.R. B -TS 1+TS NC1/42K _f M.R. B -TS 1+TS NC1/43K _f B M.R. -TS 1+TS NC1/44K _f B 2/2 A E7 1 SEE DWG. 10905-383 2/2 A E7 1 SEE DWG. 10905-383 2/2 A E7 1 SEE DWG. 1©905-383 2/2 A E7 1 SEE DWG. 10905-383 B TRAIN ONLY ---<D (33013-2095 SH.45) NIS ROD DROP SIGNAL (1/4) B TRAIN ONLY (SH. 15) /\\ NOTE 1 ~ SEE DWG. 33013-2095 SHTS. 14 & 45 1/4 E28 <11------IA SEE DWG. BOTH A & B TRAIN ---<D 10905-385 <D---A TRAIN ONLY ROD BOTTOM SIGNAL---- (33013-2095 SH.14) (ANY ROD) FROM MRPI SYSTEM (33013-1601) C14 SEE DWG. 10905-370 A TURBINE POWER MISC. RELAY RACK M1 1/2 ROD DROP SIGNAL (SH. 15) NOTE 1 (FIRST STAGE TURBINE PRESSURE) RACK 2 T p PC I 485A SEE DWG. 33013-2095 SHTS. 8 & 39 2/2 > X% RACK 4 P7 (SHTS. 2, 12 & 14) 8 THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPUCABILITY. THIS DWG SUPERSEDES @ DWG 882D612 NOTE: & SAME WINDOW AS ALARM 1 ON SHT. 10 NOTES: CD---A TRAIN ONLY (33013-2095 SH.14) NIS ROD DROP SIGNAL (1/4) A TRAIN ONLY /\\ (SH. 15) ~ NOTE 1

1. AUTOMATIC ROD WITHDRAWAL DISABLED PER ECP-2009-0015.

SEE MICROFILM FOR PREVIOS REVISIONS AS BUILT DATE RELEASED FOR REV.PER ECP-2009-0015 33013-1353, 11 -002 (000) ENGINEER ,__REV~~-_R_EVI_S_E_D _FO_R __ -< DRAWN CHECKED RESP REV!EWE FACIUTY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G 135311 ONTARIO, NY NUCLEAR INSTRUMENT PERMISSIVES AND BLOCKS LOGIC DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 11 & CCD 4 CNTRL COPY#

T SEE DRAWING 33013-2095 SHTS. 19 & 50 PRESSURIZER LOW PRESSURE A I RACK 1 RACK 2 RACK 3 RACK 4 PC l PC l PC l PC l 29 30 431 49 F27 F27 F27 F27 T I\\ T I\\ A A L..B::J. L..B::J. 1 1 1 1 SEE DWG. 10905-390 T P7 (RACK 4) 2/ 4 (SHT. 11) 2/2 RT1 RT2 ~ D20 REACTOR TRIP (SHT. 2) G SEE DWG. 10905-378 PRESSURIZER HIGH PRESSURE RACK 1 RACK 2 RACK 3 _r F26 A 2 SEE DWG. 10905-390 PC _r PC _r 30 31 F26 F26 T 2/3 RT1 RT2 A 2 ~ 6----a-fR T D12 SEE DWG. 10905-376 REACTOR TRIP (SHT 2) G A 2 PRESSURIZER HIGH WATER LEVEL RACK 1 RACK 2 RACK 3 _r F28 T A SEE DWG. 10905-390 LC 27 T 2/3 RT1 RT2 _r F28 A


tlR LC _r 28 F28 T

A 3 D4 SEE DWG. 10905-374 REACTOR TRIP (SHT. 2) e \\ SEE DRAWING 33013-2095 SHTS. 16 & 47 SEE DRAWING 33013-2095 SHTS. 18 & 49 LOW PRESSURIZER PRESSURE & LOW PRESSURIZER LEVEL TRIP LOGIC (SEE SHT. 6) THIS DWG SUPERSEDES @ DWG 8820612 THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. 12./n ~* I AS BUILT t-'-+'-'~--+--+------------j-* DATE RELEASED FOR 6 ~~=::~~A~S:-::cBU~l~LT:--:::P~ER=-----t-:::-D~P~M-:-t-i:;t;7T;\\J*~-t-j-G-P~l%\\c--~-~ OCR 97-0332 & PCR g 7-01.c=2. ______ +-12/_16_/9_7+/l_,_*1 /-+1f-'-'f/1t-+1_)l_n:__r._,t-J;,-*f7_.f_)--I t--R_EV~ ____ R_EVI_S_ED __ FO_R __ __, DRAWN CHECKED RESP REVIEWEF FACILITY GINNA BY BY ENGR SCALE NONE ROCHESTER GAS & ELECTRIC CORP. t-C-AO-Fl-LE-NA_M_E--3-G1_3_5_3-12 __ ROCHESTER, NEW YORK ~------------~-------------- ELECTRICAL LOGIC DIAGRAM PRESSURIZER TRIP SIGNALS JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 12 ~ CCD 4 I I CNTRL COPY #

STEAM LINE PRESSSURE REACTOR TRIP <INCLUDES LEAD/LAG COMPENSATION) <SEE SHT. 6) RACK 1 fLc\\ ~ l_ G28 T\\--...._-IA 3 LOOP A RACK 3 fLc\\ STEAM GEN. LO-LO \\JATER LEVEL SEE D\\JGS. 33013-2095 SHTS. 23, 24, 54 8. 55 AND 33013-1606 SHT. 9 RACK 4 RACK 1 (lc\\ (lc\\ LOOP B RACK 2 (lc\\ ~l_ ~l_ ~~ l_ ~~ l_ G28 G28 G30 G30 T A 3 2/3 T,___..,.___,A 3 I T,__....,___,A 4 RT3 RT4 RACK 4 REACTOR TRIP <SHT. 2l 0 T A 4 2/3 --tR RACK M2 LLSGBA LLSGAA RACK Ml \\ RACK 4 fLc\\ ~~ l_ G30 T A D-6 4 SEE D\\JG. 10905-317 RACK M2 LLSGBB LLSGAB RACK Ml y TO AUX. F D\\JT R PUMPS CSHT 9) SEE D\\JG. 33013-661 I RACK 1 (lc\\ ~!Y' T LOOP A STEAM GENERATOR HIGH LEVEL A RACK 3 (lc\\ ~~ G4 G4 A T A T 9 9 2/3 G12 R RACK 4 (lc\\ ~31 SEE D\\JG. 10905-393 CLOSE MAIN & BYPASS F.\\J. CONTROL VALVES CSHT. 9) { RACK 4 (lc\\ ~!Y G4 A T 9 SEE D\\JG. 10905-392 J LOOP B STEAM GENERATOR HIGH LEVEL A RACK 1 (lc\\ \\t'.~ G6 G6 A T A T 10 10 2/3 Gl4 R RACK 2 (lc\\ ~~ SEE D\\JG. 10905-394 CLOSE MAIN 8. BYPASS F.'v/. CONTROL VALVES CSHT. 9) G6 A 10 SEE D\\JG. 10905-392 THIS D'v/G SUPERSEDES _'v/ D'v/G 882D612 THIS DRA\\JING INCLUDES PORTIONS OF CLASS lE ELECTRICAL SYSTEMS. REFER TD NOTES AND SPECIFICA TIDNS TD DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. AS BUILT DAlt I RELEASED FOR ENGINEER f\\ AS BUILT PER PCR /__Jj, 97-061 AS NOTED RMS Qt! 10ll3 Jf!/' a/J1/9s 7/.?/.fJ' ~-i-'t>I 9lsn* REV R_EVI-cS_ED_FO_R __ -i DRAWN CHECKED RESP REV!EWEF GINNA BY BY ENGR FACILITY SCALE NONE ROCHESTER GAS & ELECTRIC CORP. 1-C-AD-"-FI-LE-NA_M_E --,-3G.,.-1-c3.,,-5.,-31-=3,-----i ROCHESTER, NEW YORK ELECTRICAL LOGIC DIAGRAM STEAM GENERATOR TRIP SIGNALS JOB NUMBER DRAW[NG NUMBER SHEET REV 4777A 33013-1353 13 fu CCD 4 I ICNTRL COPY#

SEE DWG. 33013-2095 SHTS. 29 & 60 RACK 1 MT1 -1 RACK 1 RACK 2 MT2 -1 RACK 2 MT2 -2 OVERTEMPERATURE ~ T SEE DWG. 33013-2095 SHTS. 21 & 52 LOOP A RACK 2 TC j" 406C LOOP B OVERPOWER ~ T SEE DWG. 33013-2095 SHT. 20 LOOP A LOOP B RACK1 RACK2 RACK3 TC ~ 405 TC ~ 407 RACK4 TC j" 40S C26 C26 C26 C26 A F23 T )---ili--IA F23 T l---illl--IA. F23 T )---ili--IA F23 F32 T )---ili--IA T,.........,,_,,A F32 T,__.,,_,,A F32 T }--@1--iA* 2 F32 T }---lll--IA 2 RACK 1 TC 4050 2/2 9 9 9 9 --.-'--....,__ MANUAL SEE DWG. 10905-371 2/2 2/2 TRIP (MAIN CNTRL BO).___,~ P.B. RT9 RT10 RACK 2 1/2 P.B. RT9 RT1 0 RACK 2 SEE DWG. 10905-374 TO REACTOR TRIP CKT (SHT. 2) OVERTEMPERATURE ~ T LOOP A LOOP B RACK RACK 3 RACK 4 1/TC405D MANUAL BYPASS 2/2 1/TC406D MANUAL BYPASS 2/4 2/2 1/TC407D MANUAL BYPASS F31


IA BLOCK AUTOMATIC AND MAUNAL ROD WITHDRAWAL (SHT. 15)

TC 40SD 2/2 1 1 2/4 RT5 RT6 RACK 1 1 SEE DWG. 10905-374 REACTOR TRIP (SHT. 2) 1 2 SEE DWG. 10905-3S9 2 2/4 RT5 RT6 RACK 1 D 11 R SEE DWG. 10905-376 REACTOR TRIP (SHT. 2) 0 SEE DWG. 33013-1606 SHT. 6 OVERPOWER HIGH ~ T RACK 1 1/TC40SD MANUAL BYPASS SEE DWG. 10905-390 START TURBINE LOAD REFERENCE REDUCTION (TURBINE RUNBACK) (SHT. 15) 2/2 LOOP A LOOP B RACK 3 RACK 4 1/TC405B MANUAL BYPASS 2/2 1/TC406B MANUAL BYPASS 2/4 2/2 1/TC407B MANUAL BYPASS F30


IA BLOCK MANUAL ROD WITHDRAWAL (SHT. 15) ffi NOTE 1 TC 40SB 2/2 1/TC40SB MANUAL BYPASS SEE DWG.

10905-390 SEE DWG. 33013-2095 SHTS. 27 & 5S SEE DWG. 33013-2095 SHTS. 29 & 60 REACTOR COOLANT LOOP A RACK 1 RACK 2 B27 T;-..---1.A 3 B27 T~--1A 3 2/3 RC1 FLOW RACK 3 827 T A 3 SEE DWG. 10905-367 RC2 RACK 3 2/2 RACK 3 LOOP A RCP BKR OPEN 2/2 829 A RACK 4 52S RCP1B LOOP B RCP BKR OPEN T SEE DWG. 10905-367 1/2 RACK 4 P7 (SHT. 11) -~ RACK 4 P7 (SHT. 11) RACK 1 PS (SHT. 11) 2/2 07 Rk-----$ SEE DWG. 10905-375 RT9 RT10 RACK 2 LOW TAVG SEE DWG. 33013-661 LOOP A RACK1 RACK2 LOOP B RACK3 TC 403 RACK4 TC 404 F7 F7 FS FS T,__.,__..,.A T,___.,,___,,A T )---ili--IA T,__.___,A 7 7 s s 2/2 017 2/2


l'R\\----*

SEE DWG. 10905-377 1/2 RT9 RT10 RACK 2 1/2 RT7 RTS RACK 2 BOTH PUMPS TO EITHER PUMP TO REACTOR TRIP CIRCUIT REACTOR TRIP CIRCUIT (SHT. 2) (SHT. 2) G G SEE DWG. 10905-3SS 2/4 LOW TAVG INTERLOCK (SHT. 6) SEE DWG. 33013-2095 SHTS. 2S & 59 REACTOR COOLANT LOOP B FLOW RACK 2 RACK 3 B2S 4 4 4 SEE DWG. 10905-367 2/3 RT7 RTS RACK 2 015 2/2 RC3 RC4 RACK 4 .----'---$---- PS RACK 1 -r-~~ RT7 (SHT. 11) 2/2 RTS RACK 2 023 SEE DWG. 10905-377 SEE DWG. 10905-379 1/2 NOTES:

1. AUTOMATIC ROD WITHDRAWAL DISABLED PER ECP-2009-0015.
  • ALARM ON ELECTR. TRIP ONLY TRAIN A TRAIN B RACK 1 IS RR-1 RACK 2 IS RW-1 RACK 3 IS RB-1 RACK 4 IS RY-1 RACK 5 IS RLTR-1 RACK 1 IS RR-2 RACK 2 IS RW-2 RACK 3 IS RB-2 RACK 4 IS RY-2 RACK 5 IS RLTR-2 DATE THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS.

REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. AS BUILT RELEASED FOR ENGINEER REV. PER ECP-2009-0015 33013-1353,14 -003, (000) AJV3./JP Vi 5/17/11 ;;-h*)<< 5 20 /. sin/<< l--REV_.__ __ REVI_SE_D_F_OR __


1 DRAWN CHECKED RESP REVIEWE FACIUTY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G 135314 ONTARIO, NY LOGIC DIAGRAM REACTOR COOLANT SYS TRIP SIGNALS JOB NUMBER DRAWING NUMBER SHEET REV THIS DWG SUPERSEDES W DWG 882D612 4777 33013-1353 14 &

CCD 4 CNTRL COPY#

HIGH FLUX (1/4 POWER RANGE) (SHT. 11) ROD STOP SIGNALS HIGH FLUX (1/2 INTERMEDIATE RANGE) -------e--~ 1 (SHT. 11) '--------~(r1/~f---------------~ 1.-------f\\o HIGH OVERTEMPERATURE t;, T (2/4)------~_:._____:___J (SHT. 14) HIGH OVERPOWER fl. T (2/4) ______ __J (SHT. 14) I '--~~~~~~~~I---~ '-----~~~~~~--iO { TC I fr 01 --L_J e---tA 1 F15 1x~* 2/2 ROD DROP SIGNAL FROM TURB A TAVG. DEVIATION TC I fr 02 --L_J e---tA 1 F15 1x~* 2/2 TC I fr 03 --L_J 7_,.~1 F15 1x~* 2/2 TC I fr 04 --L_J __,,JA\\1 F15 1x~* (NOTE 1) 2/2 RELAY-NIS OR MRPI (SH.11) ----------------------~ TRAIN A ONLY (33013-2095 SH.14) NIS ROD DROP SIGNAL ( 1j4) { (SH.11) TRAIN B ONLY (33013-2095 SH.45)


'-----------'--------~

TC-401 L ROD SPEED CONTROL ANALOG RACK FOXBORO CD-12 SH.2, BD-15 SEE DWG. 33013-1606 SHT. 6 SEE DWG. 10905-389 BLOCK AUTO WITHDRAWAL BLOCK AUTO INSERTION NOTE 2 \\ y BLOCK MANUAL WITHDRAWAL ROD CONTROL LOGIC CABINET TURBINE LOAD REFERENCE REDUCTION A I OVERTEMPERATURE HIGH fl. T (2/ 4) OVERPOWER HIGH fl. T (2/ 4) (SHT. 14) (SHT. 14) ~2 TIME DELAY RELAY LOGIC (CYCUC) ON OFF STD 30 SEC. I" "I __\\ 1-- 1.5 SEC. SEE DWG. 33013-1606 SH.6 REDUCE LOAD REFERENCE AT 211JllJ%/MIN (CONTACT CLOSURE) TURBINE GENERATOR HORIZONTAL (X) & VERTICAL (Y) HIGH VIBRATION FOR BEARINGS NO. 1X,1Y.... 9X,9Y ( T K1 Ill 1/18 2/2 TO HIGH VIBRATION TURBINE TRIP (SH. 3) NOTE: A J19 MCB BLOCK/ARM SWITCH FOR HIGH VIBR. TURBINE TRIP 1 /HVTT ARMED

1. MANUAL BYPASS (M.B.) IS PROVIDED FOR EACH TAVG. DEVIATION CHANNEL.
2. AUTO ROD WITHDRAWAL FUNCTION DISABLED AT ROD CONTROL LOGIC CABINET PER ECP-2009-0015.

THIS DRAWING INCLUDES PORTIONS OF CLASS 1 E ELECTRICAL SYSTEMS. REFER TO NOTES AND SPECIFICATIONS TO DETERMINE SPECIFIC QA PROGRAM APPLICABILITY. THIS DWG SUPERSEDES @ DWG 8820612 AS BUILT DATE RELEASED FOR ENGINEER j\\ REV. PER ECP-2009-ii\\JV3 ~ If?& {)//Ir... ~ ~~J51ii°ii50~13-1353, 15-5/11;11 5lt'l/11 s/rt/11,-/,./,, f--REV_L.._ ____ R.::...EVI.::...S.::...ED_Fc.:Oc.:_R ----1 DRAWN CHECKED RESP REVIEWEF FACILITY GINNA BY BY ENGR SCALE NONE R.E. GINNA STATION CAD FILENAME 3G135315 ONTARIO, NY ROD STOPS & TURBINE RUNBACKS LOGIC DIAGRAM JOB NUMBER DRAWING NUMBER SHEET REV 33013-1353 15 ~ ~C~C~D------'4_ IC NT R L C 0 PY #}}