SE Authorizing Use of ASME Code Case N-416-1
ML16141A896
Person / Time
Site: Oconee, Mcguire, McGuire  
Issue date: 03/27/1995
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML16141A897 List:
References
NUDOCS 9503310220
Download: ML16141A896 (5)


Text

  • NkREGU 0

UNITED STATES

.0 NUCLEAR REGULATORY COMMISSION W

WASHINGTON, D.C. 20555-0001 SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION ON ASME CODE CASE N-416-1 FOR DUKE POWER COMPANY MCGUIRE NUCLEAR STATION, UNITS 1 AND 2 OCONEE NUCLEAR STATION, UNITS 1. 2. AND 3 DOCKETS NOS. 50-369, 50-370, 50-269, 50-270 AND 50-287

1.

INTRODUCTION The Technical Specifications for McGuire Nuclear Station, Units 1 and 2, and for Oconee Nuclear Station, Units 1,.2 and 3 state that the inservice inspection and testing of the American Society of Mechanical Engineers (ASME)

Code Class 1, 2, and 3 components shall be performed in accordance with Section XI of the ASME Boiler and Pressure Vessel Code and applicable Addenda as required by Title 10 of the Code of Federal Regulations (10 CFR) 50.55a(g),

except where specific written relief has been granted by the Commission pursuant to 10 CFR 50.55a(g)(6)(i). Section 50.55a(a)(3) states that alternatives to the requirements of paragraph (g) may be used, when authorized by the NRC, if (i) the proposed alternatives would provide an acceptable level of quality and safety or (ii) compliance with the specified requirements would result in hardship or unusual difficulties without a compensating increase in the level of quality and safety.

Pursuant to 10 CFR 50.55a(g)(4), ASME Code Class 1, 2, and 3 components (including supports) shall meet the requirements, except the design and access provisions and the preservice examination requirements, set forth in the ASME Code,Section XI, "Rules for Inservice Inspection of Nuclear Power Plant Components," to the extent practical within the limitations of design, geometry, and materials of construction of the components. The regulations require that inservice examination of components and system pressure tests conducted during the first 10-year interval and subsequent intervals comply with the requirements in the latest edition and addenda of Section XI of the ASME Code incorporated by reference in 10 CFR 50.55a(b) on the date 12 months prior to the start of the 120-month interval, subject to the limitations and modifications listed therein. The applicable edition of Section XI of the ASME Code for the McGuire Nuclear Station, second 10-year inservice inspection (ISI) interval, is the 1986 Edition for Unit 1 and the 1989 Edition for Unit 2. For the Oconee units, the applicable edition for the third 10-year inspection interval is the 1989 Edition with no Addenda. The components (including supports) may meet the requirements set forth in subsequent editions and addenda of the ASME Code incorporated by reference in 10 CFR 50.55a(b) subject to the limitations and modifications listed therein and subject to Commission approval.

950331O220 9'50321 PDR. ADOCK 05000269 p

PDR.

-2 By letter dated February 22, 1995, Duke Power Company (licensee) requested approval for the implementation of the alternative rules of ASME Section XI Code Case N-416-1 dated February 15, 1994, entitled "Alternative Pressure Test Requirement for Welded Repairs or Installation of Replacement Items by Welding Class 1, 2, and 3,Section XI, Division 1", pursuant to 10 CFR 50.55a(a)(3) to be applied to the Inservice Inspection (ISI) program for the McGuire Nuclear Station, Units 1 and 2, and for the Oconee Nuclear Station, Units 1, 2, and 3.

The staff has reviewed and evaluated the licensee's request and supporting information to use Code Case N-416-1 as a proposed alternative to the Code requirements for the McGuire Nuclear Station, Units 1 and 2, and for the Oconee Nuclear Station, Units 1, 2, and 3.

2.0 EVALUATION

CODE CASE N-416-1 ALTERNATIVE PRESSURE TEST REQUIREMENT FOR WELDED REPAIRS OR INSTALLATION OF REPLACEMENT ITEMS BY WELDING CLASS 1, 2. and 3 -

SECTION XI, DIVISION 1 Component Identification ASME Class 1, 2, and 3 Piping Systems ASME Code Section XI RequirementsSection XI requires that a system hydrostatic test be performed after repairs or replacement by welding on the pressure retaining boundary.

Licensee's Basis for Request The licensee's request states as follows:

In the past, at each of our Nuclear Stations, we have found it necessary to defer hydrostatic tests or ask relief from ASME Section XI hydrostatic tests following repair or replacement activities. This was due to various reasons of impracticality such as hardship on the plant due to extended system down time, difficulty in locating and installing hydrostatic pumps and gages necessary to pressurize the system, or special efforts such as dismantling valves or use of freeze plugs in order to isolate the test boundary. Many times, these problems are discovered during the test or prior to performing the test. As a consequence, these situations have necessitated prompt communications with the NRC to avoid exceeding the limiting condition for operation or delaying startup.

A hydrostatic test has never detected any leaks or flaws resulting from welded repairs or welded replacements at the Duke nuclear stations.

Thus it is felt the elimination of this hydrostatic testing will not compromise the safety of our operating units.

-3 Use of hydrostatic test deferrals, which are presently allowed in the current Code Case N-416 for Class 2 components, is not satisfactory because relief from the burden of conducting the test is not achieved.

Also, Code Case N-416 does not apply to Class 1 and 3 components. Code Case N-416-1 allows a system leakage test to be performed in lieu of a hydrostatic pressure test when Section XI code repairs are made, provided that NDE is performed in accordance with the methods and acceptance criteria of the applicable Subsection of the 1992 Edition of Section III and that prior to or immediately upon return to service, a visual examination (VT-2) shall be performed in conjunction with a system leakage test, using the 1992 Edition of Section XI, in accordance with paragraph IWA-5000, at nominal operating pressure and temperature.

Code Case N-416-1 applies to Class 1, 2 and 3 components and provides flexibility which should considerably reduce the number of relief requests associated with post welded repair/replacement hydrostatic testing while, as determined by the ASME Code, maintaining an acceptable level of safety and quality.

Proposed Alternative Examination The licensee proposes to apply Code Case N-416-1 as alternative rules for welded repairs or installation of replacement items by welding in Class 1, 2, and 3 piping.

Evaluation/Conclusions In lieu of hydrostatic pressure testing for welded repairs or installation of replacement items by welding, Code Case N-416-1 requires a visual examination (VT-2) be performed in conjunction with a system leakage test using the 1992 Edition of Section XI, in accordance with paragraph IWA-5000, at nominal operating pressure and temperature. This Code case also specifies that NDE of the welds be performed in accordance with the applicable subsection of the 1992 Edition of Section III.

The 1989 Edition of Sections XI and III are the-latest editions referenced in 10 CFR 50.55a. The staff has compared the system pressure test requirements of the 1992 Edition of Section XI to the requirements of IWA-5000 of the 1989 Edition of Section XI. In summary, the 1992 Edition imposes a more uniform set of system pressure test requirements for Code Class 1, 2, and 3 systems.

The terminology associated with the system pressure test requirements for all three Code classes has been clarified and streamlined. The.test frequency and test pressure conditions associated with these tests have not been changed.

The hold times for these tests have either remained unchanged or increased.

The corrective actions with respect to removal of bolts from leaking bolted connections have been relaxed in the 1992 Edition, but use of this change has been accepted by the staff in previous safety evaluations. The post-welded repair NDE requirements of the 1992 Edition of Section III remain the same as the requirements of the 1989 Edition of Section III.

Therefore, the staff finds this aspect of Code Case N-416-1 to be acceptable.

-4 Hardships are generally encountered with the performance of hydrostatic testing performed in accordance with the Code. For example, since hydrostatic test pressure would be higher than nominal operating pressure, hydrostatic pressure testing frequently requires significant effort to set up and perform.

The need to use special equipment, such as temporary attachment of test pumps and gages, and the need for individual valve lineups, can cause the testing to be on critical path.

Piping components'are designed for a number of loadings that would be postulated to occur under the various modes of plant operation. Hydrostatic testing only subjects the piping components to a small increase in pressure over the design pressure and, therefore, does not present a significant challenge to pressure boundary integrity. Accordingly, hydrostatic pressure testing is primarily regarded as a means to enhance leakage detection during the examination of components under pressure, rather than solely as a measure to determine the structural integrity of the components.

The industry indicates that experience has demonstrated that leaks are not being discovered as a result of hydrostatic test pressures propagating a preexisting flaw through wall.

They indicate that, when leaks are found, in.

most cases they are found when the system is at normal operating pressure.

This is largely due to the fact that hydrostatic pressure testing is required only upon installation and then once every 10-year inspection interval, while system leakage tests at nominal operating pressures are conducted a minimum of once each refueling outage for Class 1 systems and each 40-month inspection period for Class 2 and 3 systems. In addition, leaks may be identified by plant operators during system walkdowns which may be conducted as often as once a shift.

Following the performance of welding, the Code requires volumetric examination of repairs or replacements in Code Class 1 and 2, but only requires a surface examination of the final weld pass in Code Class 3 piping components. There are no ongoing NDE requirements for Code Class 3 components except for visual examination for leaks in conjunction with the 10-year hydrostatic tests and the periodic pressure tests.

Considering the NDE performed on Code Class 1 and 2 systems, and considering that the hydrostatic pressure tests rarely result in pressure boundary leaks that would not occur during system leakage tests, the staff believes that increased assurance of the integrity of Class 1 and 2 welds is not commensurate with the burden of performing hydrostatic testing. However, considering the nature of NDE requirements for Code Class 3 components, the staff does not believe that eliminating the hydrostatic pressure testing and only performing system pressure testing is an acceptable alternative to hydrostatic testing unless additional surface examinations are performed on the root pass layer of butt and socket welds on the pressure retaining boundary of Class 3 components when the surface examination method is used in accordance with Section III.

-5 The staff concludes that compliance with the Code hydrostatic testing requirements for welded repairs or replacements of Code Class 1, 2, and 3 components would result in hardships without a compensating increase in the level of quality and safety. Accordingly, the licensee's proposed alternative to use Code Case N-416-1 is authorized for McGuire Nuclear Station, Units 1 and 2, and for Oconee Nuclear Station, Units 1, 2, and 3 pursuant to 10 CFR 50.55a(a)(3)(ii) provided additional surface examinations are performed on the root pass layer of butt and socket welds on the pressure retaining boundary of Class 3 components when the surface examination method is used in accordance with Section III.

Use of Code Case N-416-1, with provision as noted above, is authorized until such time as the Code Case is published in a future revision of Regulatory Guide 1.147. At that time, if the licensee intends to continue to implement this Code case, the licensee is to follow all provisions in Code Case N-416-1, with limitations issued in Regulatory Guide 1.147, if any.

Principal Contributor: C. Battige Date:

March 27, 1995