MONTHYEARL-16-034, Distribution Notice for License Amendment Request to Adopt NFPA Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants (2001 Edition)2016-02-0202 February 2016 Distribution Notice for License Amendment Request to Adopt NFPA Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants (2001 Edition) Project stage: Request ML14177A5782016-02-22022 February 2016 November 13, 2013, Summary of Meeting with Firstenergy Nuclear Operating Company to Discuss Delay in Submittal of Fire Risk Reduction Amendment Request Project stage: Meeting ML16047A1452016-02-22022 February 2016 Supplemental Information Needed for Acceptance of License Amendment Request to Adopt National Fire Protection Associated Standard 805 Project stage: Acceptance Review L-16-079, Supplemental Information for License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 8052016-03-0707 March 2016 Supplemental Information for License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 805 Project stage: Supplement ML16074A1232016-03-15015 March 2016 Acceptance of License Amendment Request to Adopt National Fire Protection Associated Standard 805 Project stage: Acceptance Review ML16075A1112016-03-23023 March 2016 Online Reference Portal for License Amendment Request to Adopt National Fire Protection Associated Standard 805 Project stage: Other ML16126A2362016-05-0505 May 2016 NRR E-mail Capture - Davis-Besse NFPA 805 Portal Project stage: Other ML16130A7182016-05-0909 May 2016 NRR E-mail Capture - Davis-Besse NFPA 805 Portal Project stage: Other L-16-170, Online Reference Portal for Review of National Fire Protection Association (NFPA) Standard 805 License Amendment Request2016-05-31031 May 2016 Online Reference Portal for Review of National Fire Protection Association (NFPA) Standard 805 License Amendment Request Project stage: Request ML16172A0312016-06-20020 June 2016 NRR E-mail Capture - Davis-Besse NFPA 805 Portal Project stage: Other ML16190A0752016-07-0808 July 2016 NRR E-mail Capture - Davis-Besse NFPA 805 Portal Project stage: Other ML16201A0172016-07-20020 July 2016 Regulatory Audit in Support of the License Amendment Request to Implement Risk-Informed, Performance-Based, Fire Protection Program as Allowed by Title 10 CFR, Paragraph 50.48(c) Project stage: Other L-16-232, Correction of Fire Probabilistic Risk Analysis (PRA) Results2016-07-28028 July 2016 Correction of Fire Probabilistic Risk Analysis (PRA) Results Project stage: Other ML16256A0662016-10-18018 October 2016 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Associated Standard 805 Project stage: RAI L-16-345, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Cnfpa) Standard 8052016-12-16016 December 2016 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Cnfpa) Standard 805 Project stage: Response to RAI L-16-371, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 8052017-01-17017 January 2017 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 805 Project stage: Response to RAI ML17100A1732017-04-19019 April 2017 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Associated Standard 805 Project stage: RAI L-17-189, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 8052017-06-16016 June 2017 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 805 Project stage: Response to RAI ML17257A1402017-09-14014 September 2017 NRR E-mail Capture - Davis-Besse Nuclear Power Station, Unit No. 1 - Request for Additional Information Regarding License Amendment Request to Adopt NFPA 805 Project stage: RAI ML17258A1462017-09-20020 September 2017 Summary of September 12, 2017, Meeting with Firstenergy Nuclear Operating Company Regarding Its Licensing Amendment Request to Adopt National Fire Protection Association Standard 805 at Davis-Besse Nuclear Power Station, Unit No. 1 Project stage: Meeting L-17-253, Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 8052017-10-0909 October 2017 Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 805 Project stage: Supplement ML17355A3722017-12-21021 December 2017 NRR E-mail Capture - Davis-Besse Nuclear Power Station, Unit No. 1 - Request for Additional Information Regarding License Amendment Request to Adopt NFPA 805 Project stage: RAI L-18-085, Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 8052018-04-0202 April 2018 Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 805 Project stage: Supplement ML18201A4122018-07-19019 July 2018 NRR E-mail Capture - Davis-Besse - Request for Additional Information Regarding License Amendment Request to Adopt NFPA 805 Project stage: RAI L-18-249, Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 8052018-11-20020 November 2018 Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association (NFPA) Standard 805 Project stage: Supplement ML19106A2512019-04-16016 April 2019 NRR E-mail Capture - Davis-Besse - Proposed License Condition and Draft Safety Evaluation for the License Amendment Request to Adopt NFPA 805 Project stage: Draft Approval ML19100A3062019-06-21021 June 2019 Issuance of Amendment No. 298 to Adopt National Fire Protection Association Standard 805 Project stage: Approval 2016-07-28
[Table View] |
Text
1 NRR-PMDAPEm Resource From:
Purnell, Blake Sent:
Thursday, May 05, 2016 10:49 AM To:
kgarey-irons@curtisswright.com Cc:
Lashley, Phil H.; Fields, Leslie; Robinson, Jay
Subject:
Davis-Besse NFPA 805 Portal (CAC No. MF7190)
- Kelly, Please add report number C-FP-013.10-034 to the Davis-Besse NFPA 805 portal. It describes the CFAST main control room abandonment calculations. Let me know when the document has been added to the portal and which folder it was placed in.
This document will be used to support the audit described in the NRCs letter to FENOC dated March 23, 2016 (ADAMS Accession No. ML16075A111).
- Thanks, Blake Purnell, Project Manager Plant Licensing Branch III-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission ph: 301-415-1380
Hearing Identifier:
NRR_PMDA Email Number:
2822 Mail Envelope Properties (Blake.Purnell@nrc.gov20160505104900)
Subject:
Davis-Besse NFPA 805 Portal (CAC No. MF7190)
Sent Date:
5/5/2016 10:49:21 AM Received Date:
5/5/2016 10:49:00 AM From:
Purnell, Blake Created By:
Blake.Purnell@nrc.gov Recipients:
"Lashley, Phil H." <phlashley@firstenergycorp.com>
Tracking Status: None "Fields, Leslie" <Leslie.Fields@nrc.gov>
Tracking Status: None "Robinson, Jay" <Jay.Robinson@nrc.gov>
Tracking Status: None "kgarey-irons@curtisswright.com" <kgarey-irons@curtisswright.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 613 5/5/2016 10:49:00 AM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received:
1 NRR-PMDAPEm Resource From:
Purnell, Blake Sent:
Thursday, May 05, 2016 10:49 AM To:
kgarey-irons@curtisswright.com Cc:
Lashley, Phil H.; Fields, Leslie; Robinson, Jay
Subject:
Davis-Besse NFPA 805 Portal (CAC No. MF7190)
- Kelly, Please add report number C-FP-013.10-034 to the Davis-Besse NFPA 805 portal. It describes the CFAST main control room abandonment calculations. Let me know when the document has been added to the portal and which folder it was placed in.
This document will be used to support the audit described in the NRCs letter to FENOC dated March 23, 2016 (ADAMS Accession No. ML16075A111).
- Thanks, Blake Purnell, Project Manager Plant Licensing Branch III-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission ph: 301-415-1380
Hearing Identifier:
NRR_PMDA Email Number:
2822 Mail Envelope Properties (Blake.Purnell@nrc.gov20160505104900)
Subject:
Davis-Besse NFPA 805 Portal (CAC No. MF7190)
Sent Date:
5/5/2016 10:49:21 AM Received Date:
5/5/2016 10:49:00 AM From:
Purnell, Blake Created By:
Blake.Purnell@nrc.gov Recipients:
"Lashley, Phil H." <phlashley@firstenergycorp.com>
Tracking Status: None "Fields, Leslie" <Leslie.Fields@nrc.gov>
Tracking Status: None "Robinson, Jay" <Jay.Robinson@nrc.gov>
Tracking Status: None "kgarey-irons@curtisswright.com" <kgarey-irons@curtisswright.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 613 5/5/2016 10:49:00 AM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received: