SAFETY EVALUATION REPORT BY THE OFFICE OF NUCLEAR REACTOR REGULATION EQUIPMENT QUALIFICATION BRANCH FOR DUKE POWER COMPANY OCONEE UNIT 1 DOCKET NO. 50-269 8106190013

(2) some of the items found deficient have been or are being replaced or

.relocated, thus improving the facility's capability to function following a LOCA or HELB (3) the harsh environmental conditions for which this equipment must be qualified result from low-probability events; events which might reasonably be anticipated during this very limited period would lead to less demanding service conditions for this equipment.

APPENDIX A Equipment Requiring Immediate Corrective Action (Category 4.1)

LEGEND:

Designation for Deficiency R -

Radiation T - Temperature QT - Qualification time RT -

Required time P -

Pressure H - Humidity CS -

Chemical spray A - Material aging evaluation, replacement schedule, ongoing equipment surveillance S -

Submergence M - Margin I -

HELB evaluation outside containment not completed QM - Qualification method

. RPN - Equipment relocation or replacement, adequate schedule not provided EXN - Exempted equipment justification inadequate SEN - Separate effects qualification justification inadequate QI - Qualification information being developed RPS - Equipment relocation or replacement schedule provided Equipment Description Manufacturer Item No.

Deficiency Valve Motor Rotork 1VMTROO09 QT,T,P,H,CS, R,A*

  • In a phone conversation, the licensee has stated that this valve has already been replaced.

A-1

APPENDIX 8 Equipment Requiring Additional Information and/or Corrective Action (Category 4.2)

LEGEND:

Designation for Deficiency R -

Radiation T - Temperature QT - Qualification time RT -

Required time P -

Pressure H - Humidity CS - Chemical spray A - Material aging evaluation, replacement schedule, ongoing equipment surveillance S -

Submergence M -

Margin I - HELB evaluation outside containment not completed QM - Qualification method

. RPN -

Equipment relocation or replacement, adequate schedule not provided EXN -

Exempted equipment justification inadequate SEN -

Separate effects qualification justification inadequate QI -

Qualification information being developed RPS -

Equipment relocation or replacement schedule provided Equipment Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLE0172 CS,A Cable Okonite ICBLE0173 CS,A Cable Okonite ICBLE0175 CS,A Cable Okonite ICBLE0177 CS,A Cable Okonite 1CBLE0094 CS,A Cable Okonite 1CBLE0092 CS,A Cable Okonite 1CBLE0139 CS,A B-1

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLE0144 CS,A Cable Okonite 1CBLE0146 CS,A Cable Okonite 1CBLE0148 CS,A Cable Okonite 1CBLE0160 CS,A Cable Okonite 1CBLE0165 CS,A Cable Okonite 1CBLE0166 CS,A Cable Okonite 1CBLE0167 CS,A Cable Okonite 1CBLE0168 CS,A Cable Okonite 1CBLE0170 CS,A Cable Okonite 1CBLE0180 CS,A Cable Okonite 1CBLE0181 CS,A Cable Okonite 1CBLE0185 CS,A Cable Okonite 1CBLE0187 CS,A Cable Okonite 1CBLE0188 CS,A Valve Motor Limitorque 1VMTR0025 CS,A Valve Motor Limitorque 1VMTR0026 CS,A Valve Motor Limitorque 1VMTR0027 CS,A Valve Motor Limitorque 1VMTR0028 CS,A Valve Motor Limitorque 1VMTR0021 CS,A Valve Motor Limitorque 1VMTROO15 CS,A Valve Motor Limitorque 1VMTROO12 CS,A Valve Motor Limitorque 1VMTROO07 CS,A

. Valve Motor Limitorque 1VMTROO08 CS,A Valve Motor Limitorque 1VMTROO01 CSA B-2

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Valve Motor Limitorque 1VMTROO02 CS,A Valve Motor Limitorque 1VMTR0022 CS,A Valve Motor Limitorque 1VMTR0023 CS,A Valve Motor Rotork 1VMTROO04 CS,A Valve Motor Rotork 1VMTROO05 CS,A Fan Motor Reliance 1FMTROO01 CS,A Fan Motor Reliance 1FMTROO03 CS,A Fan Motor Reliance 1FMTROO05 CS,A Terminal Block States 1TBOX0010 R,H,A,QI Terminal Block States 1TBOX0011 R,H,A,QI Terminal Block States 1TBOX0012 R,H,A,QI Terminal Block States 1TBOX0007 R,H,A,QI Terminal Block States 1TBOX0013 R,H,A,QI Terminal Block States 1TBOX0014 R,H,A,QI Terminal Block States 1TBOX0008 R,T,P,H,A,QI Terminal Block States 1TB0X0009 R,T,P,H,A,QI Terminal Block States ITBOX0015 R,H,A,QI Terminal Block States 1TBOX0001 R,H,A,QI Terminal Block States 1TBOX0002 R,H,A,QI Terminal Block States 1TBOX0003 R,H,A,QI Terminal Block States 1TBOX0004 R,H,A,QI Terminal Block States 1TBOX0006 R,H,A,QI Cable Brand Rex 1CBLE0025 R,T,P,H,A,QI Cable Brand Rex 1CBLE0063 R,T,P,H,AQI B-3

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Brand Rex 1CBLE0073 R,T,P,H,A,QI Cable Brand Rex 1CBLEO468 R,T,QT,P,HA,QI Cable Brand Rex 1CBLEO469 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO470 R,T,QT,P,H,A,QI Cable Brand Rex.

1CBLEO471 RT,QT,P,H,A,QI Cable Brand Rex 1CBLEO462 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO465 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO403 R,TQT,P,H,A,QI Cable Brand Rex 1CBLEO405 R,T,QT,PH,A,QI Cable Brand Rex 1CBLE0453 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO455 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO425 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO427 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO429 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLEO431 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLE0023 RT,QT,PH,A,QI Cable Brand Rex 1CBLE0061 R,T,QT,P,H,A,QI Cable Brand Rex 1CBLE0071 R,TQT,P,H,AQI Cable Brand Rex 1CBLE0105 R,T,QT,P,4,A,QI Cable Brand Rex 1CBLEO478 R,QT,H,A,QI Cable Brand Rex 1CBLEO479 R,QT,H,A,QI Cable Brand Rex 1CBLEO480 R,QT,H,A,QI Cable Brand Rex 1CBLEO481 R,QT,H,A,QI B-4

APPENDIX B (Continued)

Equi pment Description Manufacturer Item No.

Deficiency Cable Boston 1CBLEO434 QT,A,QI Insulated Wire Cable Boston 1CBLEO436 QT,A,QI Insulated Wire Cable Boston 1CBLEO438 QT,A,QI Insulated Wire Cable Boston 1CBLEO440 QT,A,QI Insulated Wire Cable Boston 1CBLEO442 QT,A,QI Insulated Wire Cable Boston 1CBLEO444 QT,A,QI Insulated Wire Cable Boston 1CBLEO446 QT,A,QI Insulated Wire Cable Boston 1CBLEO448 QT,A,QI Insulated Wire Cable Boston 1CBLEO450 QT,A,QI Insulated Wire Cable Boston 1CBLEO456 QT,A,QI Insulated Wire Cable Boston 1CBLE0022 QT,A,QI Insulated Wire Cable Boston 1CBLE0060 QT,A,QI Insulated Wire Cable Boston 1CBLE0070 QT,A,QI Insulated Wire Cable Boston 1CBLE0104 QT,A,QI Insulated Wire Cable Boston 1CBLEO402 QT,A,QI Insulated Wire Cable Boston 1CBLEO404 QT,A,QI Insulated Wire B-5

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Boston 1CBLEO452 QT,A,QI Insulated Wire Cable Boston 1CBLEO454 QT,A,QI Insulated Wire Cable Boston 1CBLEO406 QT,A,QI Insulated Wire Cable Boston 1CBLEO408 QT,A,QI Insulated Wire Cable Boston 1CBLEO410 QT,A,QI Insulated Wire Cable Boston 1CBLEO412 QT,A,QI Insulated Wire Cable Boston 1CBLEO414 QT,A,QI Insulated Wire Cable Boston 1CBLEO416 QTA,QI Insulated Wire Cable Boston 1CBLEO418 QT,A,QI Insulated Wire Cable Boston 1CBLEO420 QT,A,QI Insulated Wire Cable Boston 1CBLEO422 QT,A,QI Insulated Wire Cable Boston 1CBLEO424 QT,A,QI Insulated Wire Cable Boston 1CBLEO426 QT,A,QI Insulated Wire Cable Boston 1CBLEO428 QT,A,QI Insulated Wire Cable Boston 1CBLEO430 QT,A,QI Insulated Wire Cable Boston 1CBLEO432 QT,A,QI Insulated Wire B-6

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Okonite.

1CBLE0190 CS,A,S Cable Okonite 1CBLE0135 CS,A,S Cable Okonite 1CBLE0136 CS,A,S Valve Motor Limitorque 1VMTROO17 CS,A,S Valve Motor Limitorque 1VMTROO10 CS,AS Valve Motor Limitorque 1VMTR0011 CS,A,S Valve Motor Limitorque 1VMTR0055 R,QT,H,A Valve Motor Limitorque 1VMTROO61 R,T,QT,PH,A Valve Motor Limitorque 1VMTR0062 R,T,QT,P,H,A Valve Motor Limitorque 1VMTR0063 R,T,QT,P,H,A Valve Motor Limitorque 1VMTR0051 R,QT,H,A O

Valve Motor Rotork 1VMTR0065 R,T,QT,P,H'CS,A Valve Motor Limitorque 1VMTROO66 R,T,QT,P,H,CS,A Level Transmitter Rosemount 1LTRM0014 R,QT,CS,A,S Level Transmitter Rosemount 1LTRM0015 R,QT,CS,A,S Level Transmitter Rosemount 1LTRM0016 R,QT,CS,A,S Level Transmitter Rosemount 1LTRM0017 R,QT,CS,A,S Pressure Transmitter Rosemount 1PTRM0016 R,QT,CS,A Pressure Transmitter Rosemount 1PTRM0004 CS,A,M Pressure Transmitter Rosemount 1PTRM0005 CS,A,M Pressure Transmitter Rosemount 1PTRM0006 CS,A,M Pressure Transmitter Rosemount 1PTRM0007 CS,A,M Pressure Switch Mercoid 1PRSWO001 A,M Pressure Switch Mercoid 1PRSWO002 A,M B-7

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Pressure Switch Mercoid 1PRSWO003 A,M Pressure Switch Mercoid 1PRSWO004 A,M Pressure Switch Mercoid 1PRSWO005 A,M Pressure Switch Mercoid 1PRSWO006 A,M Pressure Switch Mercoid 1PRSWO007 A,M Pressure Switch Mercoid 1PRSWO008 A,M Pressure Switch Mercoid 1PRSWO009 A,M Pressure Switch Mercoid 1PRSWO010 A,M Pressure Switch Meletron 1PRSWO011 R,QT,H,A Pressure Switch Meletron 1PRSWO012 R,QT,H,A Pressure Transmitter Motorola 1PTRM0001 CS,A,M Pressure Transmitter Motorola 1PTRM0002 CS,A,M Pressure Transmitter Motorola 1PTRM0003 CS,A,M Fan Motor Lou-Allis 1FMTROO02 A,M Fan Motor Lou-Allis 1FMTROO04 A,M Solenoid Valve ASCO 1SLND0015 R,QT,H,A,RPN Solenoid Valve ASCO 1SLND0019 R,QT,H,A,RPN Solenoid Valve ASCO 1SLND0008 R,T,QT,P,H,A,RPN Solenoid Valve ASCO 1SLND0009 R,T,QT,P,H,A,RPN Solenoid Valve ASCO 1SLNDOO20 R,QT,H,A,RPN Solenoid Valve ASCO 1SLND0001 R,QT,H,A,RPN Solenoid Valve ASCO 1SLND0002 R,QT,H,A,RPN Solenoid Valve ASCO 1SLND0004 R,QT,H,A,RPN Solenoid Valve ASCO

.1SLND0005 R,QT,H,A,RPN B-8

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Solenoid Valve ASCO 1SLND0006 R,QT,H,A,RPN Solenoid Valve WEBCO 1SLND0017 R,QT,H,A,RPN Solenoid Valve WEBCO 1SLND0018 R,QT,H,A,RPN Solenoid Valve Super Spl.

1SLND0016 R,QT,H,A,RPN Solenoid Valve Pilot 1SLNDO007 R,QT,H,A,RPN Transzorb Gen. Semi.

1TBOX0110 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0111 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0112 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0107 RQT,H,A,RPS Transzorb Gen. Semi.

1TBOX0113 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0114 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0108 R,T,QT,P,H,A,RPS Transzorb Gen. Semi.

1TBOX0109 R,T,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0115 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0101 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0102 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0103 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0104 R,QT,H,A,RPS Transzorb Gen. Semi.

1TBOX0106 R,QT,H,A,RPS Pressure Transmitter Motorola 1PTRM0008 R,T,QT,P,H,A,RPN Pressure Transmitter Motorola 1PTRM0009 R,T,QT,P,H,A,RPN Pressure Transmitter Motorola 1PTRM0010 R,T,QT,P,H,A,RPN Pressure Transmitter Motorola 1PTRM0011 R,T,QT,P,H,A,RPN Pressure Transmitter Motorola 1PTRM0012 R,T,QT,P,H,CS,A,RPN B-9

APPENDIX B (Continued)

Equipment Description Manufacturer Item No.

Deficiency Pressure Transmitter Motorola 1PTRM0013 R,T,QT,P,H,CS,A,RPN Pressure Transmitter Motorola 1PTRM0014 R,T,QT,P,H,CS,A,RPN Pressure Transmitter Motorola 1PTRM0015 R,T,QT,P,H,CS,A,RPN Valve Motor Limitorque 1VMTROO13 R,A Valve Motor Limitorque 1VMTROO30 R,A Valve Motor Limitorque 1VMTROO03 R,A Valve Motor Limitorque 1VMTROO06 R,A Valve Motor Limitorque 1VMTROO18 R,A Valve Motor Limitorque 1VMTR0032 R,A, Cable Okonite 1CBLEO314 R,CS,A,RPN Cable Okonite 1CBLEO316 R,CS,A,RPN Cable Okonite 1CBLEO320 R,CS,A,RPN Cable Okonite 1CBLEO322 R,CS,A,RPN Cable Okonite 1CBLE0184 R,CS,A,RPN Heat Shrink Tubing Raychem Type WCSF-N RT,QT,CS,A Various Locations Cable Sealant 3M Scotch.Cast 9 RT,QT,CS,A,M Various Locations Transmitter 0-Ring

?

Various RT,QT,T,P,H,CS, Seals Locations R,A Lubricating Grease for Chevron Type SRI-2 RT,QT,R,A,M Limitorque MOVs Various Locations B-10

APPENDIX C Equipment Considered Acceptable or Conditionally Acceptable (Category 4.3)

LEGEND:

Designation for Deficiency R -

Radiation T - Temperature QT -

Qualification time RT -

Required time P -

Pressure H -

Humidity CS -

Chemical spray A - Material aging evaluation, replacement schedule, ongoing equipment surveillance S -

Submergence M -

Margin I -

HELB evaluation outside containment not completed QM - Qualification method RPN -

Equipment relocation or replacement, adequate schedule not provided EXN -

Exempted equipment justification inadequate SEN - Separate effects qualification justification inadequate QI -

Qualification information being developed RPS -

Equipment relocation or replacement schedule provided Equipment Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLE0171 A

Cable Okonite 1CBLE0174 A

Cable Okonite 1CBLE0176 A

Cable Okonite 1CBLEO262 A

Cable Okonite 1CBLEO266 A

Cable Okonite 1CBLEO267 A

Cable Okonite 1CBLEO271 A

Cable Okonite 1CBLEO272 A

Cable Okonite 1CBLEO276 A

C-1

EquipmentAPPENDIX C (Continued)

Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLE0093 A

Cable Okonite 1CBLEO257 A

Cable Okonite 1CBLEO260 A

Cable Okonite 1CBLE0091 A

Cable Okonite 1CBLE0189 A

Cable Okonite 1CBLEO242 A

Cable Okonite 1CBLEO243 A

Cable Okonite 1CBLEO247 A

Cable Okonite 1CBLEO250 A

Cable Okonite 1CBLEO472 A

Cable Okonite 1CBLEO473 A

. Cable Okonite 1CBLEO474 A

Cable Okonite 1CBLEO475 A

Cable Okonite 1CBLEO476 A

Cable Okonite 1CBLEO477 A

Cable Okonite 1CBLEO329 A

Cable Okonite ICBLEO330 A

Cable Okonite 1CBLE0001 A

Cable Okonite 1CBLE0002 A

Cable Okonite 1CBLE0020 A

Cable Okonite 1CBLE0021 A

Cable Okonite 1CBLE0095 A

Cable Okonite 1CBLE0096 A

Cable Okonite 1CBLE0097 A

C-2

APPENDIX C (Continued)

Equi pment Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLE0098 A

Cable Okonite 1CBLE0099 A

Cable Okonite 1CBLE0112 A

Cable Okonite 1CBLE0113 A

Cable Okonite 1CBLE0114 A

Cable Okonite 1CBLE0134 A

Cable Okonite 1CBLE0137 A

Cable Okonite 1CBLE0138 A

Cable Okonite 1CBLE0149 A

Cable Okonite 1CBLE0154 A

Cabl.e Okonite 1CBLE0141 A

Cable Okonite 1CBLE0142 A

Cable Okonite 1CBLE0143 A

Cable Okonite 1CBLE0145 A

Cable Okonite 1CBLE0147 A

Cable Okonite 1CBLEO210 A

Cable Okonite 1CBLEO227 A

Cable Okonite 1CBLEO306 A

Cable Okonite 1CBLEO309 A

Cable Okonite 1CBLEO310 A

Cable Okonite 1CBLEO312 A

Cable Okonite 1CBLEO313 A

Cable Okonite 1CBLEO315 A

Cable Okonite 1CBLEO319 A

C-3

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLEO321 A

Cable Okonite 1CBLEO376 A

Cable Okonite 1CBLEO381 A

Cable Okonite 1CBLEO386 A

Cable Okonite 1CBLEO482 A

Cable Okonite 1CBLEO483 A

Cable Okonite 1CBLE0484 A

Cable Okonite 1CBLEO485 A

Cable Okonite 1CBLEO486 A

Cable Okonite 1CBLEO487 A

Cable Okonite 1CBLEO488 A

Cable Okonite 1CBLEO489 A

Cable Okonite 1CBLEO490 A

Cable Okonite 1CBLEO491 A

Cable Okonite ICBLEO492 A

Cable Okonite 1CBLEO493 A

Cable Okonite 1CBLEO494 A

Cable Okonite 1CBLEO333 A

Cable Okonite 1CBLEO335 A

Cable Okonite 1CBLEO338 A

Cable Okonite 1CBLEO339 A

Cable Okonite 1CBLEO342 A

Cable Okonite 1CBLE0344 A

Cable Okonite 1CBLEO346 A

C-4

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLE0500 A

Cable Okonite 1CBLE0501 A

Cable Okonite 1CBLE0502 A

Cable Okonite 1CBLEO252 A

Cable Okonite 1CBLEO255 A

Cable Okonite 1CBLE0497 A

Cable Okonite 1CBLE0498 A

Cable Okonite 1CBLEO499 A

Cable Okonite 1CBLE0159 A

Cable Okonite 1CBLE0161 A

Cable Okonite 1CBLE0162 A

Cable Okonite 1CBLE0163 A

Cable Okonite 1CBLE0164 A

Cable Okonite 1CBLE0169 A

Cable Okonite 1CBLEO324 A

Cable Okonite 1CBLEO326 A

Cable Okonite 1CBLEO327 A

Cable Okonite 1CBLEO391 A

Cable Okonite IC8LEO396

.A Cable Okonite 1CBLEO495 A

Cable Okonite 1CBLE0496 A

Cable Okonite 1CBLE0178 A

Cable Okonite 1C8LE0179 A

Cable Okonite 1CBLE0182 A

C-5

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Okonite 1CBLE0183 A

Cable Okonite 1CBLE0186 A

Cable Okonite 1CBLEO277 A

Cable Okonite 1CBLEO280 A

Cable Okonite 1CBLEO282 A

Cable Okonite 1CBLEO285 A

Cable Okonite 1CBLEO287 A

Cable Okonite 1CBLEO289 A

Cable Okonite 1CBLEO292 A

Cable Okonite 1CBLEO294 A

Cable Okonite 1CBLEO297 A

Cable Okonite 1CBLEO299 A

Cable Okonite 1CBLEO300 A

Cable Okonite 1CBLEO301 A

Cable Okonite 1CBLEO304 A

Cable Okonite 1CBLEO349 A

Cable Okonite 1CBLEO351 A

Cable Okonite 1CBLEO353 A

Cable Okonite 1CBLEO355 A

Cable Anaconda 1CBLEO236 A

Cable Anaconda 1CBLEO238 A

Cable Anaconda 1CBLEO458 A

Cable Anaconda 1CBLEO459 A

Cable Anaconda 1CBLEO460 A

C-6

APPENDIX C (Continued)

Equi p ment Description Manufacturer Item No.

Deficiency Cable Anaconda 1CBLEO461 A

Electrical Penetration Viking 1PENT0004 A

Electrical Penetration Viking 1PENT0005 A

Electrical Penetration Viking 1PENT0011 A

Electrical Penetration Viking 1PENT0019 A

Electrical Penetration Viking 1PENT0013 A

Electrical Penetration Viking 1PENT0020 A

Electrical Penetration Viking 1PENT0021 A

Electrical Penetration Viking 1PENT0022 A

Electrical Penetration Viking 1PENT0023 A

Electrical Penetration Viking 1PENT0026 A

Electrical Penetration Viking 1PENT0031 A

Electrical Penetration Viking 1PENTO006 A

Electrical Penetration Viking 1PENT0010 A

Electrical Penetration Viking 1PENT0012 A

Electrical Penetration Viking 1PENT0015 A

Electrical Penetration Viking 1PENT0034 A

Electrical Penetration Viking 1PENT0037 A

Electrical Penetration Viking 1PENT0040 A

Electrical Penetration Viking 1PENT0003 A

Electrical Penetration Viking 1PENT0009 A

Electrical Penetration Viking 1PENT0014 A

Electrical Penetration Viking 1PENT0017 A

Electrical Penetration Viking 1PENT0018 A

C-7

APPENDIX C (Continued)

Equi pme nt Description Manufacturer Item No.

Deficiency Electrical Penetration Viking 1PENT0029 A

Electrical Penetration Viking 1PENT0030 A

Electrical Penetration Viking 1PENT0032 A

Electrical Penetration Viking 1PENT0033 A

Electrical Penetration Viking 1PENTOO38 A

Electrical Penetration Viking 1PENT0039 A

Electrical Penetration Viking 1PENT0041 A

Electrical Penetration Viking 1PENT0042 A

Electrical Penetration Viking 1PENT0043 A

Electrical Penetration Viking 1PENT0001 A

Electrical Penetration Viking 1PENT0002 A

Electrical Penetration Viking 1PENT0007 A

Valve Motor Limitorque 1VMTR0035 A

Valve Motor Limitorque IVMTROO36 A

Valve Motor Limitorque 1VMTRO014 A

Valve Motor Limitorque 1VMTR0031 A

Valve Motor Limitorque 1VMTR0043 A

Valve Motor Limitorque 1VMTR0044 A

Valve Motor Limitorque 1VMTROO52 A

Valve Motor Limitorque 1VMTR0053 A

Valve Motor Limitorque 1VMTR0054 A

Valve Motor Limitorque 1VMTR0056 A

. Valve Motor Limitorque 1VMTR0057 A

Valve Motor Limitorque 1VMTR0058 A

C-8

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Valve Motor

'Limitorque 1VMTR0059 A

Valve Motor Limitorque 1VMTROO60 A

Valve Motor Limitorque 1VMTROO19 A

Valve Motor Limitorque 1VMTROO20 A

Valve Motor Limitorque 1VMTRCO33 A

Valve Motor Limitorque 1VMTROO34 A

Valve Motor Limitorque 1VMTROO39 A

Valve Motor Limitorque 1VMTROO40 A

Valve Motor Limitorque 1VMTROO41 A

Valve Motor Limitorque 1VMTR0064 A

Valve Motor Limitorque 1VMTR0024 A

Valve Motor Limitorque 1VMTR0037 A

Valve Motor Limitorque IVMTROO50 A

Valve Motor Limitorque 1VMTR0029 A

Valve Motor Limitorque 1VMTR0038 A

Pump Motor Westinghouse 1PMTROO01 A

Pump Motor Westinghouse 1PMTROO08 A

Pump Motor Westinghouse 1PMTROO05 A

Pump Motor Westinghouse 1PMTROO02 A

Pump Motor Westinghouse 1PMTROO06 A

Pump Motor Westinghouse 1PMTROO09 A

Pump Motor Westinghouse 1PMTROO03 A

Pump Motor Westinghouse 1PMTROO10 A

Cable Raychem 1CBLE0150 A

C-9

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Raychem 1CBLE0151 A

Cable Raychem 1CBLE0152 A

Cable Raychem 1CBLE0153 A

Cable Raychem 1CBLE0155 A

Cable Raychem 1CBLE0156 A

Cable Raychem 1CBLE0157 A

Cable Raychem 1CBLE0158 A

Cable Boston 1CBLE0024 A

Insulated Wire Cable Boston 1CBLE0062 A

Insulated Wire Cable Boston 1CBLE0072 A

Insulated Wire Cable Boston 1CBLEO407 A

Insulated Wire Cable Boston 1CBLEO409 A

Insulated Wire Cable Boston 1CBLEO411 A

Insulated Wire Cable Boston 1CBLEO413 A

Insulated Wire Cable Boston 1CBLEO415 A

Insulated Wire Cable Boston 1CBLEO417 A

Insulated Wire Cable Boston 1CBLEO419 A

Insulated Wire Cable Boston 1CBLEO421 A

Insulated Wire C-10

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Boston 1CBLEO423 A

Insulated Wire Cable Boston 1CBLEO433 A

Insulated Wire Cable Boston 1CBLEO435 A

Insulated Wire Cable Boston ICBLEO437 A

Insulated Wire Cable Boston 1CBLEO439 A

Insulated Wire Cable Boston 1CBLEO441 A

Insulated Wire Cable Boston 1CBLE0443 A

Insulated Wire Cable Boston 1CBLEO445 A

Insulated Wire Cable Boston 1CBLEO447 A

Insulated Wire Cable Boston 1CBLEO449 A

Insulated Wire Cable Boston 1CBLEO451 A

Insulated Wire Cable Boston 1CBLEO457 A

Insulated Wire Level Transmitter Bailey 1LTRM0011 A

Level Transmitter Bailey 1LTRM0012 A

Level Transmitter Bailey 1LTRM0013 A

Cable Raychem 1CBLEO263 A, Note 1 O

Cable Raychem 1CBLEO264 A

Cable Raychem 1CBLEO265 A

C-11

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Raychem 1CBLEO268 A

Cable Raychem 1CBLE0269 A

Cable Raychem 1CBLEO270 A

Cable Raychem 1CBLEO273 A

Cable Raychem 1CBLEO274 A

Cable Raychem 1CBLEO275 A

Cable Raychem 1CBLEO258 A

Cable Raychem 1CBLEO259 A

Cable Raychem 1CBLEO261 A, Note 1 Cable Raychem 1CBLEO244 A, Note 1 Cable Raychem 1CBLEO245 A, Note 1 Cable Raychem 1CBLEO246 A, Note 1 Cable Raychem 1CBLEO248 A, Note 1 Cable Raychem 1CBLEO249 A, Note 1 Cable Raychem 1CBLE0251 A, Note 1 Cable Raychem 1CBLEO253 A, Note 1 Cable Raychem 1CBLE0254 A, Note 1 Cable Raychem 1CBLEO256 A, Note 1 Cable Raychem 1CBLEO278 A, Note 1 Cable Raychem 1CBLEO279 A, Note 1 Cable Raychem 1CBLEO281 A, Note 1 Cable Raychem' 1CBLEO283 A, Note 1 Cable Raychem 1CBLEO284 A, Note 1 Cable Raychem 1CBLEO286 A, Note 1 C-12

APPENDIX C (Continued)

Equipment Description Manufacturer Item No.

Deficiency Cable Raychem 1CBLEO290 A, Note 1 Cable Raychem 1CBLEO291 A, Note 1 Cable Raychem 1CBLEO293 A, Note 1 Cable Raychem 1CBLEO295 A, Note 1 Cable Raychem 1CBLEO296 A, Note 1 Cable Raychem 1CBLEO298 A, Note 1 Cable Raychem 1CBLEO302 A, Note 1 Cable Raychem 1CBLEO303 A, Note 1 Cable Raychem 1CBLEO305 A, Note 1 Cable Raychem 1CBLEO360 A, Note 1 Cable Raychem 1CBLEO369 A, Note 1 Cable Raychem 1CBLE0375 A, Note 1 Cable Okonite 1CBLE0140 A, Note 1 Electrical Penetration Viking 1PENT0008 A, Note 1 Note 1:

The licensee has stated, in a phone conversation on-January 7, 1981, that these components are qualified for one year; therefore, qualifica tion time has not been listed as a deficiency. A later revision to the submittal will reflect this change.

C-13

APPENDIX D Safety-Related Systems List' Function System Emergency Reactor Shutdown Chemical Addition and Sampling Reactor Coolant Engineered Safeguards Reactor Protection Containment Isolation Chemical Addition and Sampling Reactor Building Ventilation Feedwater Component Cooling Low Pressure Service Water Main Steam High Pressure Injection Low Pressure Injection Reactor Building Spray Reactor Building Cooling Liquid Waste Disposal Reactor Core Cooling High Pressure Injection Low Pressure Injection Accumulators (Part of Reactor Coolant)

'The NRC staff recognized that there are differences in nomenclature of systems because of plant vintage and engineering design; consequently, some systems performing identical or similar functions may have different names. In those instances, it was necessary to verify the function of the system(s) with the responsible IE regional reviewer and/or the licensee.

D-1

APPENDIX D (continued)

Function System Containment Heat Removal Reactor Building Spray Reactor Building Cooling Reactor Building Ventilation Containment Sump Recirculation (Part of Liquid Waste Disposal)

Core Residual Heat Removal Coolant Storage Quench Tank Residual Heat Removal (Part of Low Pressure Injection)

Auxiliary Feedwater (Part of Feedwater)

Pressurizer Spray(1 )

Power Operated Relief Valves( 1 )

Main Steam Steam Dump (Part of Main Steam)

Component Cooling Low Pressure Service Water Prevention of Significant Iodine Removal.

Release of Radioactive (Part of Reactor Building Spray)

Material to Environment Containment Radiation Monitoring(1)

Containment Combustible Gas Control Containment Radiation Sampling(1)

Containment Air Purification/Cleanup (Part of Reactor Building Ventilation)

-D-2

APPENDIX D (Continued)

Function System Supporting Systems Emergency Power(2)

Safety Equipment Area Ventilation(2)

Control Room Habitability(2)

Notes:

(1) Covered as part of TMI-2 Lessons Learned; does not appear in systems lists.

(2) Electrical components in system not exposed to harsh environment.

D-3