NRR E-mail Capture - RAI for Browns Ferry Units 1, 2, and 3 Adoption of TSTF-501 (MF5417, MF5418, MF5419)
ML15245A598
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 09/02/2015
From: Farideh Saba
Plant Licensing Branch II
To: Gerald Williams
Tennessee Valley Authority
References
TAC MF5417, TAC MF5418, TAC MF5419
Download: ML15245A598 (4)


Text

1 NRR-PMDAPEm Resource From:

Saba, Farideh Sent:

Wednesday, September 02, 2015 1:47 PM To:

Williams, Gordon Robert (grwilliams1@tva.gov)

Cc:

Schrull, Edward Dustin (edschrull@tva.gov); Hon, Andrew; Tilton, Caroline

Subject:

RAI for Browns Ferry Units 1, 2, and 3 Adoption of TSTF-501 (MF5417, MF5418, MF5419)

Attachments:

MF5417-9 BFN 1-3 RAI TSTF-501.docx Importance:

High

Gordon, By [[letter::CNL-14-059, License Amendment Request for the Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-501 Revision 1, Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control (BFN TS-493)|letter dated December 11, 2014]] (Agencywide Documents Access and Management System (ADAMS) Accession No. ML14349A694), Tennessee Valley Authority (TVA) (the licensee) submitted a license amendment request (LAR) regarding Browns Ferry Nuclear Plant (BFN), Units 1, 2 and 3 Facility Operating Licenses. The proposed changes would revise TS 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air, consistent with Technical Specifications Task Force Traveler (TSTF) 501, Revision 1, Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control. The U.S. Nuclear Regulatory Commission (NRC) staff is reviewing the submittal and has determined that additional information below is needed to complete its review.

Attached please find the NRC staffs RAI on the subject LAR. As we agreed, please provide TVA response to the NRC staff request for additional information (RAI) by October 2, 2015.

Thank you, Farideh Farideh E. Saba, P.E.

Senior Project Manager NRC/ADRO/NRR/DORL 301-415-1447 Mail Stop O-8G9A Farideh.Saba@NRC.GOV

Hearing Identifier:

NRR_PMDA Email Number:

2358 Mail Envelope Properties (e0f12a5bbcf741118a2776f59e4f09a4)

Subject:

RAI for Browns Ferry Units 1, 2, and 3 Adoption of TSTF-501 (MF5417, MF5418, MF5419)

Sent Date:

9/2/2015 1:47:25 PM Received Date:

9/2/2015 1:47:25 PM From:

Saba, Farideh Created By:

Farideh.Saba@nrc.gov Recipients:

"Schrull, Edward Dustin (edschrull@tva.gov)" <edschrull@tva.gov>

Tracking Status: None "Hon, Andrew" <Andrew.Hon@nrc.gov>

Tracking Status: None "Tilton, Caroline" <Caroline.Tilton@nrc.gov>

Tracking Status: None "Williams, Gordon Robert (grwilliams1@tva.gov)" <grwilliams1@tva.gov>

Tracking Status: None Post Office:

HQPWMSMRS03.nrc.gov Files Size Date & Time MESSAGE 1107 9/2/2015 1:47:25 PM MF5417-9 BFN 1-3 RAI TSTF-501.docx 35551 Options Priority:

High Return Notification:

No Reply Requested:

Yes Sensitivity:

Normal Expiration Date:

Recipients Received:

ENCLOSURE REQUEST FOR ADDITIONAL INFORMATION (RAI)

LICENSE AMENDMENT REQUEST TO ADOPT TSTF-501 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNITS 1, 2 AND 3 DOCKET NOS. 50-259, 50-260, AND 50-296 (TAC NOS. MF5417, MF5418, MF5419)

By [[letter::CNL-14-059, License Amendment Request for the Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-501 Revision 1, Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control (BFN TS-493)|letter dated December 11, 2014]] (Agencywide Documents Access and Management System (ADAMS) Accession No. ML14349A694), Tennessee Valley Authority (TVA) (the licensee) submitted a license amendment request (LAR) regarding Browns Ferry Nuclear Plant (BFN),

Units 1, 2 and 3 Facility Operating Licenses. The proposed changes would revise TS 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air, consistent with Technical Specifications Task Force Traveler (TSTF) 501, Revision 1, Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control. The U.S. Nuclear Regulatory Commission (NRC) staff is reviewing the submittal and has determined that additional information below is needed to complete its review.

Basis for the Request of the licensees submittal, page 3 of 9 states:

A change toTS 5.5.9 "Diesel Fuel Oil Testing Program" is proposed to adopt thetesting of new fuel oil consistent with NUREG-1433, Revision 4. This change adds arequirement to test new fuel oil to a set of standards and limits and is a morerestrictive change to support the adoption of TSTF-501, Revision 1. The periodicityof testing the 7-day storage tank fuel oil particulate concentration has been retainedfrom the BFN Current Licensing Basis as every 92 days, consistent with ASTMD-2276, Method A-2 or A-3.

In addition, the licensees proposed TS change to TS 5.5.9 states the following:

c.

Total particulate concentration of the fuel oil in the 7-day storage tank is 10 mg/l when tested every 92 days.

Technical Specification (TS) 5.5.10, Diesel Fuel Oil Testing Program, of NUREG-1433, Revision 4, Standard Technical Specifications (STS) BWR/4 Plants establishes the following acceptance criteria for the total particulate concentration of the fuel oil:

c.

Total particulate concentration of the fuel oil is 10 mg/l when tested every 31 days.

In addition, the licensees proposed TS Bases change to SR 3.8.3.3 proposes the following:

Particulate concentrations should be determined in accordance with ASTM D6217-11 (Ref. 7). This method involves a gravimetric determination of total particulate concentration in the fuel oil and has a limit of 10 mg/l.

The equivalent NUREG-1433, Revision 4, Standard Technical Specifications (STS)

BWR/4 Plants Bases to SR 3.8.3.3 states the following:

Particulate concentrations should be determined in accordance withASTM D5452-[ ] (Ref. 6). This method involves a gravimetric determination of total particulate concentration in the fuel oil and has a limit of 10 mg/l.

RAI-1

Provide the documentation that establishes the current licensing basis for the periodicity of testing the 7-day storage tank fuel oil particulate concentration as every 92 daysversus 31 days as suggested in STS.

RAI-2

Provide a justification for deviation for determining particulate concentrations of the fuel oil in accordance with ASTM D6217-11 versus ASTM D5452-[ ] as suggested in STS.