UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Mr. Joseph W. Shea Vice President, Nuclear Licensing Tennessee Valley Authority 1101 Market Street, LP 3R-C Chattanooga, TN 37402-2801 August 24, 2015
SUBJECT:
WATTS BAR NUCLEAR PLANT, UNIT 1 - INDIVIDUAL NOTICE OF CONSIDERATION OF ISSUANCE OF AMENDMENT TO FACILITY OPERATING LICENSE AND OPPORTUNITY FOR HEARING (TAC NO. MF2549)
Dear Mr. Shea:
The U.S. Nuclear Regulatory Commission has forwarded the enclosed "Notice of Consideration of Issuance of Amendment to Facility Operating License and Opportunity for a Hearing," to the Office of the Federal Register for publication.
This notice relates to your application dated August 1, 2013, in which you request to modify the technical specification 3.8.1, "AC [Alternating Current] Sources - Operating," Surveillance Requirement (SR) 3.8.1.8 and the licensing basis as described in the Updated Final Safety Analysis Report (UFSAR). The Tennessee Valley Authority submitted supplements to the August 1, 2013, application by letters dated April 21, 2014, January 29, 2015, and June 12, 2015. The January 29, 2015, supplement revised the proposed changes to the UFSAR and expanded the scope of the proposed license amendment by adding a modification to SR 3.8.1.1 and proposing a new SR 3.8.1.22. The supplement changed the scope of the application as originally noticed in the Federal Register (FR) on October 29, 2013 (78 FR 64547). The expansion in the amendment description did not change the staff's original no significant hazards consideration determination.
J.Shea If you have any questions, please contact me at 301-415-1349 or Jeanne.Dion@nrc.gov.
Docket No. 50-390
Enclosure:
Notice of Consideration cc w/enclosure: Distribution via Listserv Sincerely, anne A. Dion, Project Manager atts Bar Special Projects Branch Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
ENCLOSURE FEDERAL REGISTER NOTICE
NUCLEAR REGULATORY COMMISSION
[Docket Nos. 50-390; NRC-2013-0233]
Watts Bar Nuclear Plant, Unit No. 1
[7590-01-P]
Application and Amendment to Facility Operating License Involving Proposed No Significant Hazards Consideration Determination AGENCY: Nuclear Regulatory Commission.
ACTION: License amendment request; opportunity to comment, request a hearing and petition for leave to intervene.
SUMMARY
- The U.S. Nuclear Regulatory Commission (NRC) is considering issuance of an amendment to Facility Operating License No. NFP-90, issued to the Tennessee Valley Authority (the licensee), for operation of Watts Bar Nuclear Plant (WBN), Unit 1. The amendment request submitted on August 1, 2013, proposed revisions to Technical Specification (TS) 3.8.1, Surveillance Requirement (SR) 3.8.1.8, and the licensing basis as described in the Updated Final Safety Analysis Report (UFSAR). The NRC staff had previously made a proposed determination that the amendment involved no significant hazards consideration. By letters dated April 21, 2014, January 29, 2015, and June 12, 2015, the licensee provided additional information that expanded the scope of the amendment request to include proposed changes to the UFSAR, a new modification to SR 3.8.1.1, and proposed a new SR 3.8.1.22. The purpose of this document is to update the description of the amendment request and to make a proposed determination that the expanded scope of the amendment request involves no significant hazards consideration.
DATES: Comments must be filed by [INSERT DATE 30 DAYS FROM DATE OF PUBLICATION IN THE FEDERAL REGISTER]. A request for a hearing must be filed by
[INSERT DATE 60 DAYS FROM DATE OF PUBLICATION IN THE FEDERAL REGISTER].
ADDRESSES: You may submit comments by any of the following methods (unless this document describes a different method for submitting comments on a specific subject):
Federal Rulemaking Web Site: Go to http://www.regulations.gov and search for Docket ID NRC-2013-0233. Address questions about NRC dockets to Carol Gallagher; telephone: 301-415-3463; e-mail: Carol.Gallagher@nrc.gov. For technical questions, contact the individual listed in the FOR FURTHER INFORMATION CONTACT section of this document.
Mail comments to: Cindy Bladey, Office of Administration, Mail Stop: OWFN H08, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001.
For additional direction on obtaining information and submitting comments, see "Obtaining Information and Submitting Comments" in the SUPPLEMENTARY INFORMATION section of this document.
FOR FURTHER INFORMATION CONTACT: Jeanne A. Dion, Office of Nuclear Reactor Regulation, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001; telephone:
301-415-1349; e-mail: Jeanne.Dion@nrc.gov SUPPLEMENTARY INFORMATION:
I.
Obtaining Information and Submitting Comments A. Obtaining Information Please refer to Docket ID NRC-2013-0233 when contacting the NRC about the availability of information for this action. You may obtain publicly-available information related to this action by any of the following methods:
Federal rulemaking Web Site: Go to http://www.regulations.gov and search for Docket ID NRC-2013-0233.
NRC's Agencywide Documents Access and Management System (ADAMS):
You may obtain publicly-available documents online in the ADAMS Public Documents collection at http://www.nrc.gov/reading-rm/adams.html. To begin the search, select "ADAMS Public Documents" and then select "Begin Web-based ADAMS Search." For problems with ADAMS, please contact the NRC's Public Document Room (PDR) reference staff at 1-800-397-4209, 301-415-4737, or by e-mail to pdr.resource@nrc.gov. The application for amendment, dated August 1, 2013, as supplemented by letters dated April 21, 2014, January 29, 2015, and June 12, 2015, are available in ADAMS under ADAMS Accession Nos. ML13220A103, ML14112A341, ML15041A732, and ML15195A600, respectively.
NRC's PDR: You may examine and purchase copies of public documents at the NRC's PDR, Room 01-F21, One White Flint North, 11555 Rockville Pike, Rockville, Maryland 20852.
B. Submitting Comments.
Please include Docket ID NRC-2013-0233 in your comment submission.
The NRC cautions you not to include identifying or contact information that you do not want to be publicly disclosed in your comment submission. The NRC will post all comment submissions at http://www.regulations.gov as well as enter the comment submissions into ADAMS. The NRC does not routinely edit comment submissions to remove identifying or contact information.
If you are requesting or aggregating comments from other persons for submission to the NRC, then you should inform those persons not to include identifying or contact information that they do not want to be publicly disclosed in their comment submission. Your request should state that the NRG does not routinely edit comment submissions to remove such information before making the comment submissions available to the public or entering the comment into ADAMS.
II.
Introduction.
The NRG is considering issuance of an amendment to Facility Operating License No.
NFP-90, issued to the Tennessee Valley Authority for operation of WBN, Unit 1, located in Spring City, Tennessee.
The proposed license amendment was submitted by letter dated August 1, 2013, and proposed revisions to TS 3.8.1 "Alternating Current Sources - Operating," related SRs, and the licensing basis as described in the UFSAR for the available maintenance feeder for the Common Station Service Transformers (CSSTs) A and B. The proposed license amendment credited upgrades made to CSST A and B to provide two new sources of preferred Class 1 E power supply feeds in addition to the two normal Class 1 E power supply feeds. The NRG staff had previously made a proposed determination that the proposed amendment involved no significant hazards consideration (78 FR 64547; October 29, 2013). The proposed license amendment was supplemented by letters dated April 21, 2014, January 29, 2015, and June 12, 2015, and proposed additional changes to the UFSAR, a new modification to SR 3.8.1.1, and proposed a new SR 3.8.1.22.
The purpose of this document is to update the description of the amendment request and to make a proposed determination that the expanded scope of the amendment request involves no significant hazards consideration. Before issuance of the proposed license amendment, the NRG will have made findings required by the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations.
The NRG has made a proposed determination that the amendment request involves no significant hazards consideration. Under the NRC's regulations in § 50.92 of Title 1 O of the Code of Federal Regulations (10 CFR), this means that operation of the facility in accordance with the proposed amendment would not (1) involve a significant increase in the probability or consequences of an accident previously evaluated; or (2) create the possibility of a new or different kind of accident from any accident previously evaluated; or (3) involve a significant reduction in a margin of safety. As required by 10 CFR 50.91 (a), the licensee has provided its analysis of the issue of no significant hazards consideration, which is presented below:
- 1.
Does the proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?
Response: No.
The proposed changes described in this TS amendment request, do not alter the safety functions of the WBN Offsite Power system. Design calculations document that CSSTs A and B have adequate capacity to supply all connected loads including one train of shutdown boards in all allowable alignments and meet the separation requirements for offsite power sources. The consequences of an accident are not changed when using CSST A or B to power the shutdown boards because these CSSTs are rated to carry all required loads for any design basis accidents. The failure of a GSST is not considered to be an initiator of a plant accident and therefore the probability or consequences of accidents or events previously evaluated, as described in the UFSAR, is not changed.
Therefore, this proposed amendment does not involve a significant increase in the probability or consequences of an accident previously evaluated.
- 2.
Does the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated?
Response: No.
As stated above, malfunctions of the CSSTs are not considered to be an initiator for plant accidents and the modifications to the offsite power system do not create a new or different kind of accident. The purpose of the offsite power system is to provide a source of power to the safety related equipment required to mitigate a design basis accident. CSSTs A and B have been physically upgraded and proven by design calculation to meet all required GDC [General Design Criterion] 17 requirements for separation and voltage stability. Using CSSTs A and Bas alternate sources of shutdown power does not negatively affect the offsite power systems ability to meet its design function.
Therefore, the proposed amendment does not create the possibility of a new or different kind of accident from any accident previously evaluated.
- 3.
Does the proposed change involve a significant reduction in the margin of safety?
Response: No.
CSSTs A and B have adequate design margin to meet all possible loading scenarios as long as both CSSTs A and B are operational prior to one being used as a source of offsite power. This requirement is added to the control room drawings, plant design criteria and the UFSAR in order to ensure acceptable margin is always available prior to CSSTs A or B being used as a source of offsite power.
Therefore, the proposed changes do not involve a significant reduction in a margin of safety.
The NRC staff has reviewed the licensee's analysis and, based on this review, it appears that the three standards of 10 CFR 50.92(c) are satisfied. Therefore, the NRC staff proposes to determine that the amendment request involves no significant hazards consideration.
The NRC is seeking public comments on this proposed determination that the license amendment request involves no significant hazards consideration. Any comments received within 30 days after the date of publication of this notice will be considered in making any final determination.
Normally, the Commission will not issue the amendment until the expiration of 60 days after the date of publication of this notice. The Commission may issue the license amendment before expiration of the 60-day period provided that its final determination is that the amendment involves no significant hazards consideration. In addition, the Commission may issue the amendment prior to the expiration of the 30-day comment period should circumstances change during the 30-day comment period such that failure to act in a timely way would result, for example, in derating or shutdown of the facility. Should the Commission take action prior to the expiration of either the comment period or the notice period, it will publish in the Federal Register a notice of issuance. Should the Commission make a final No Significant Hazards Consideration Determination, any hearing will take place after issuance. The Commission expects that the need to take this action will occur very infrequently.
Ill.
Opportunity to Request a Hearing and Petition for Leave to Intervene Within 60 days after the date of publication of this notice, any person(s) whose interest may be affected by this action may file a request for a hearing and a petition to intervene with respect to issuance of the amendment to the subject facility operating license. Requests for a hearing and a petition for leave to intervene shall be filed in accordance with the Commission's "Agency Rules of Practice and Procedure" in 10 CFR Part 2. Interested person(s) should consult a current copy of 1 O CFR 2.309, which is available at the NRC's PDR, located at 01 F21, 11555 Rockville Pike (first floor), Rockville, Maryland 20852. The NRC's regulations are accessible electronically from the NRC Library on the NRC Web site at http://www.nrc.gov/reading-rm/doc-collections/cfrl. If a request for a hearing or petition for leave to intervene is filed within 60 days, the Commission or a presiding officer designated by the Commission or by the Chief Administrative Judge of the Atomic Safety and Licensing Board Panel, will rule on the request and/or petition; and the Secretary or the Chief Administrative Judge of the Atomic Safety and Licensing Board will issue a notice of a hearing or an appropriate order.
As required by 10 CFR 2.309, a petition for leave to intervene shall set forth with particularity the interest of the petitioner in the proceeding, and how that interest may be affected by the results of the proceeding. The petition should specifically explain the reasons why intervention should be permitted with particular reference to the following general requirements: (1) the name, address and telephone number of the requester or petitioner; (2) the nature of the requester's/petitioner's right under the Act to be made a party to the proceeding; (3) the nature and extent of the requester's/petitioner's property, financial, or other interest in the proceeding; and (4) the possible effect of any decision or order which may be entered in the proceeding on the requester's/petitioner's interest. The petition must also set forth the specific contentions which the requester/petitioner seeks to have litigated at the proceeding.
Each contention must consist of a specific statement of the issue of law or fact to be raised or controverted. In addition, the requester/petitioner shall provide a brief explanation of the bases for the contention and a concise statement of the alleged facts or expert opinion which support the contention and on which the requester/petitioner intends to rely in proving the contention at the hearing. The requester/petitioner must also provide references to those specific sources and documents of which the requester/petitioner is aware and on which the requester/petitioner intends to rely to establish those facts or expert opinion. The petition must include sufficient information to show that a genuine dispute exists with the applicant on a material issue of law or fact. Contentions shall be limited to matters within the scope of the amendment under consideration. The contention must be one which, if proven, would entitle the requestor/petitioner to relief. A requestor/petitioner who fails to satisfy these requirements with respect to at least one contention will not be permitted to participate as a party.
Those permitted to intervene become parties to the proceeding, subject to any limitations in the order granting leave to intervene, and have the opportunity to participate fully in the conduct of the hearing.
If a hearing is requested, the Commission will make a final determination on the issue of no significant hazards consideration. The final determination will serve to decide when the hearing is held. If the final determination is that the amendment request involves no significant hazards consideration, the Commission may issue the amendment and make it immediately effective, notwithstanding the request for a hearing. Any hearing held would take place after issuance of the amendment. If the final determination is that the amendment request involves a significant hazards consideration, then any hearing held would take place before the issuance of any amendment unless the Commission finds an imminent danger to the health or safety of the public, in which case it will issue an appropriate order or rule under 10 CFR Part 2.
IV.
Electronic Submissions (E-Filing).
All documents filed in NRC adjudicatory proceedings, including a request for hearing, a petition for leave to intervene, any motion or other document filed in the proceeding prior to the submission of a request for hearing or petition to intervene, and documents filed by interested governmental entities participating under 10 CFR 2.31 S(c), must be filed in accordance with the NRC E-Filing rule (72 FR 49139, August 28, 2007). The E-Filing process requires participants to submit and serve all adjudicatory documents over the internet, or in some cases to mail copies on electronic storage media. Participants may not submit paper copies of their filings unless they seek an exemption in accordance with the procedures described below.
To comply with the procedural requirements of E-Filing, at least ten (10) days prior to the filing deadline, the participant should contact the Office of the Secretary by e-mail at hearing.docket@nrc.gov, or by telephone at 301-415-1677, to request (1) a digital identification (ID) certificate, which allows the participant (or its counsel or representative) to digitally sign documents and access the E-Submittal server for any proceeding in which it is participating; and (2) advise the Secretary that the participant will be submitting a request or petition for hearing (even in instances in which the participant, or its counsel or representative, already holds an NRC-issued digital ID certificate). Based upon this information, the Secretary will establish an electronic docket for the hearing in this proceeding if the Secretary has not already established an electronic docket.
Information about applying for a digital ID certificate is available on the NRC's public Web site at http:l/www.nrc.gov/site-helple-submittalslgetting-started.html. System requirements for accessing the E-Submittal server are detailed in the NRC's "Guidance for Electronic Submission," which is available on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals.html. Participants may attempt to use other software not listed on the Web site, but should note that the NRC's E-Filing system does not support unlisted software, and the NRC Meta System Help Desk will not be able to offer assistance in using unlisted software.
If a participant is electronically submitting a document to the NRC in accordance with the E-Filing rule, the participant must file the document using the NRC's online, Web-based submission form. In order to serve documents through the Electronic Information Exchange System, users will be required to install a Web browser plug-in from the NRC's Web site.
Further information on the Web-based submission form, including the installation of the Web browser plug-in, is available on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals.html.
Once a participant has obtained a digital ID certificate and a docket has been created, the participant can then submit a request for hearing or petition for leave to intervene.
Submissions should be in Portable Document Format (PDF) in accordance with NRC guidance available on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals.html. A filing is considered complete at the time the documents are submitted through the NRC's E-Filing system. To be timely, an electronic filing must be submitted to the E-Filing system no later than 11 :59 p.m. Eastern Time on the due date. Upon receipt of a transmission, the E-Filing system time-stamps the document and sends the submitter an e-mail notice confirming receipt of the document. The E-Filing system also distributes an e-mail notice that provides access to the document to the NRC's Office of the General Counsel and any others who have advised the Office of the Secretary that they wish to participate in the proceeding, so that the filer need not serve the documents on those participants separately. Therefore, applicants and other participants (or their counsel or representative) must apply for and receive a digital ID certificate before a hearing request/petition to intervene is filed so that they can obtain access to the document via the E-Filing system.
A person filing electronically using the NRC's adjudicatory E-Filing system may seek assistance by contacting the NRC Meta System Help Desk through the "Contact Us" link located on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals.html, by e-mail to MSHD.Resource@nrc.gov, or by a toll-free call to 1-866-672-7640. The NRC Meta System Help Desk is available between 8 a.m. and 8 p.m., Eastern Time, Monday through Friday, excluding government holidays.
Participants who believe that they have a good cause for not submitting documents electronically must file an exemption request, in accordance with 10 CFR 2.302(g), with their initial paper filing requesting authorization to continue to submit documents in paper format.
Such filings must be submitted by: (1) first class mail addressed to the Office of the Secretary of the Commission, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, Attention: Rulemaking and Adjudications Staff; or (2) courier, express mail, or expedited delivery service to the Office of the Secretary, Sixteenth Floor, One White Flint North, 11555 Rockville Pike, Rockville, Maryland, 20852, Attention: Rulemaking and Adjudications Staff.
Participants filing a document in this manner are responsible for serving the document on all other participants. Filing is considered complete by first-class mail as of the time of deposit in the mail, or by courier, express mail, or expedited delivery service upon depositing the document with the provider of the service. A presiding officer, having granted an exemption request from using E-Filing, may require a participant or party to use E-Filing if the presiding officer subsequently determines that the reason for granting the exemption from use of E-Filing no longer exists.
Documents submitted in adjudicatory proceedings will appear in NRC's electronic hearing docket which is available to the public athttp://ehd1.nrc.gov/ehd/, unless excluded pursuant to an order of the Commission, or the presiding officer. Participants are requested not to include personal privacy information, such as social security numbers, home addresses, or home phone numbers in their filings, unless an NRC regulation or other law requires submission of such information. However, in some instances, a request to intervene will require including information on local residence in order to demonstrate a proximity assertion of interest in the proceeding. With respect to copyrighted works, except for limited excerpts that serve the purpose of the adjudicatory filings and would constitute a Fair Use application, participants are requested not to include copyrighted materials in their submission.
Petitions for leave to intervene must be filed no later than 60 days from the date of publication of this notice. Requests for hearing, petitions for leave to intervene, and motions for leave to file new or amended contentions that are filed after the 60-day deadline will not be entertained absent a determination by the presiding officer that the filing demonstrates good cause by satisfying the three factors in 10 CFR 2.309(c)(1 )(i)-(iii).
For further details with respect to this amendment request, see the application for amendment dated August 1, 2013, as supplemented by letters dated April 21, 2014, January 29, 2015, and June 12, 2015, which are available for public inspection at the NRC's PDR, located at One White Flint North, Room 01-F21, 11555 Rockville Pike (first floor), Rockville, Maryland 20852. Publicly-available documents created or received at the NRC are accessible electronically through ADAMS in the NRC Library at http://www.nrc.gov/reading-rm/adams.html.
If you do not have access to ADAMS or if there are problems in accessing the documents located in ADAMS, contact the PDR's Reference staff at 1-800-397-4209, 301-415-4737, or by e-mail to pdr.resource@nrc.gov.
Attorney for licensee: General Counsel, Tennessee Valley Authority, 400 West Summit Hill Drive, 6A West Tower, Knoxville, Tennessee 37902 NRC Branch Chief: Jessie F. Quichocho Dated at Rockville, Maryland, this 241h day of August 2015.
For the Nuclear Regulatory Commission.
o.P~
J nne A. Dion Project Manager, Watts Bar Special Projects Branch, Division of Operating Reactor Licensing, Office of Nuclear Reactor Regulation.