ML15113A093

From kanterella
Jump to navigation Jump to search
Amends 128,128 & 125 to Licenses DPR-38,DPR-47 & DPR-55, Respectively,Revising Tech Specs to Establish Degraded Mode for Emergency Condenser Cooling Sys
ML15113A093
Person / Time
Site: Oconee  
Issue date: 04/30/1984
From: Stolz J
Office of Nuclear Reactor Regulation
To:
Duke Power Co
Shared Package
ML15113A094 List:
References
DPR-38-A-128, DPR-47-A-128, DPR-55-A-125 NUDOCS 8405160179
Download: ML15113A093 (8)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 DUKE POWER COMPANY DOCKET NO.

50-269 OCONEE NUCLEAR STATION, UNIT NO. 1 AMENDMVENT TO FACILITY OPERATING LICENSE Amendment No. 128 License No. DPR-38

1. The Nuclear Regulatory Commission (the Commission) has found that:

A. The application for amendment by Duke Power Company (the licensee) dated February 13, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2. Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.B of Facility Operating License No. DPR-38 is hereby amended to read as follows:

3.B Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 128are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

8405160179 840430 PDR ADOCK 05000269 P

PDR

-2

3. This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION do n F. Stolz, Chief perating Reactors Branch #4 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: April 30, 1984

p REG0 UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 DUKE POWER COMPANY DOCKET NO. 50-270 OCONEE NUCLEAR STATION, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 128 License No. DPR-47

1. The Nuclear Regulatory Commission (the Commission) has found that:

A. The application for amendment by Duke Power Company (the licensee) dated February 13, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2. Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.B of Facility Operating License No. DPR-47 is hereby amended to read as follows:

3.B Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 128are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

-2

3. This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

/Jo n F. Stolz, Chief 0 rating Reactors anch #4 ivision of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance:

April 30, 1984

o ptREG, 41 UNITED-STATES NUCLEAR REGULATORY COMMISSION Z

~WASHINGTON, D. C. 20555 DUKE POWER COMPANY DOCKET NO. 50-287 OCONEE NUCLEAR STATION, UNIT NO. 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 125 License No. DPR-55

1.

The Nuclear Regulatory Commission (the Commission) has found that:

A. The application for amendment by Duke Power Company (the licensee) dated February 13, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2. Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.B of Facility Operating License No. DPR-55 is hereby amended to read as follows:

3.B Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 125are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

-2

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

,o h F. Stolz, Chief (0 rating Reactors nch #4 1vision of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: April 30, 1984

ATTACHMENTS TO LICENSE AMENDMENTS AMENDMENT NO.128 TO DPR-38 AMENDMENT NO. 128 TO DPR-47 AMENDMENT NO. 125 TO DPR-55 DOCKETS NOS. 50-269, 50-270 AND 50-287 Replace the following page of the Appendix "A" Technical Specifications with the attached page. The revised page is identified by amendment number and contains a vertical line indicating the area of change.

Remove Page Insert Page 3.4-2 3.4-2

3.4.3 The 16 main steam safety relief valves shall be operable.

3.4.4 A minimum of 72,000 gallons of water per operating unit shall be available in the upper surge tank, condensate storage tank, and hot well.. A minimumof 5 ft. (=30,000 Gal.) shall be available in the upper surge tank.

3.4.5 Emergency Condenser Cooling Water (ECCW) System

a.

The RCS shall not be heated above 250'F unless the ECCW System is operable.

b.

If the ECCW System becomes inoperable during operation above 250'F, and the system is not restored to operable status in seven days, then the unit shall be brought to hot shutdown within an additional 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and below 250 0F in another 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

3.4.6 The controls of the emergency feedwater system shall be independent of the Integrated Control System.

Amendments Nos. 128, 128

, & 125

3. -