Letter Sequence RAI |
|---|
|
|
MONTHYEARML13266A0642013-09-24024 September 2013 Supplemental Information Needed for Acceptance of Application to Adopt National Fire Protection Association NFPA 805, Performance-Based Standard for Fire Protection for LWR Generating Plants (2001 Edition) Project stage: Acceptance Review ML13281A4952013-10-30030 October 2013 Acceptance of Application Following Supplement, Adopt National Fire Protection Association NFPA 805, Performance-Based Standard for Fire Protection for LWR Generating Plants (2001 Edition) Project stage: Acceptance Review ML14162A4582014-06-12012 June 2014 Pacific Gas and Electric Company Diablo Canyon Power Plant Units 1 and 2, Regulatory Audit in Support of the License Amendment Request to Implement Risk-Informed, Performance-Based, Fire Protection Program as Allowed by Title 10 of the Code Project stage: Other ML14206A0082014-07-31031 July 2014 Request for Additional Information, Request to Adopt National Fire Protection Association NFPA 805, Performance-Based Standard for Fire Protection for LWR Generating Plants (2001 Edition) Project stage: RAI RC-14-0144, Third Six-Month Status Report in Response to March 12, 2012 Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (EA-12-04)2014-08-28028 August 2014 Third Six-Month Status Report in Response to March 12, 2012 Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (EA-12-04) Project stage: Other ML14268A4362014-09-23023 September 2014 NRR E-mail Capture - Request for Additional Information (RAI) - License Amendment Request (LAR) 13-03 to Adopt NFPA 805 Project stage: RAI DCL-14-098, Diablo Canyon, Units 1 and 2 - Ninety-Day Response to NRC Request for Additional Information- National Fire Protection Association Standard 8052014-10-29029 October 2014 Diablo Canyon, Units 1 and 2 - Ninety-Day Response to NRC Request for Additional Information- National Fire Protection Association Standard 805 Project stage: Request ML14302A8052014-10-29029 October 2014 Ninety-Day Response to NRC Request for Additional Information- National Fire Protection Association Standard 805 Project stage: Response to RAI ML14330A6392014-11-26026 November 2014 One-Hundred-Twenty-Day Response to NRC Request for Additional Information - National Fire Protection Association Standard 805, Part 2 of 2 Project stage: Response to RAI DCL-14-123, Radiation Release Response to NRC Request for Additional Information- National Fire Protection Association Standard 8052014-12-31031 December 2014 Radiation Release Response to NRC Request for Additional Information- National Fire Protection Association Standard 805 Project stage: Response to RAI ML15035A1622015-02-0404 February 2015 NRR E-mail Capture - Diablo Canyon, Units 1 and 2 - Requests for Additional Information (Rais) for Fire Protection (NFPA-805) License Amendment Request (LAR) Project stage: RAI ML15104A6992015-04-0202 April 2015 NRR E-mail Capture - FW: Generic Audit Plan - See Attachment Project stage: Other ML15098A0142015-04-0707 April 2015 NRR E-mail Capture - Diablo Canyon, Units 1 and 2 - National Fire Protection Association Standard 805 Radiation Release Additional Requests for Additional Information Project stage: RAI ML15092A0792015-04-16016 April 2015 July 14-17, 2014 - Summary of Diablo Canyon, Units 1 and 2, Audit to Adopt National Fire Protection Association NFPA 805, Performance-Based Standard for Fire Protection for LWR Generating Plants (2001 Edition) Project stage: Other DCL-15-061, Second Radiation Release Response to NRC Request for Additional Information - National Fire Protection Association Standard 8052015-05-0707 May 2015 Second Radiation Release Response to NRC Request for Additional Information - National Fire Protection Association Standard 805 Project stage: Response to RAI ML15300A0062015-10-15015 October 2015 Submittal of Response to NRC Request for Additional Information - National Fire Protection Association Standard 805 Project stage: Response to RAI ML15316A0092015-10-15015 October 2015 Response to NRC Request for Additional Information - National Fire Protection Association Standard 805, Enclosure, Attachment 3 Project stage: Response to RAI DCL-15-119, Response to NRC Request for Additional Information - National Fire Protection Association Standard 805, Enclosure, Attachment 12015-10-15015 October 2015 Response to NRC Request for Additional Information - National Fire Protection Association Standard 805, Enclosure, Attachment 1 Project stage: Response to RAI 2014-08-28
[Table View] |
Text
1 NRR-PMDAPEm Resource From:
Lingam, Siva Sent:
Tuesday, April 07, 2015 3:08 PM To:
mjrm@pge.com Cc:
Markley, Michael; Shoop, Undine; Pedersen, Roger; Miller, Barry
Subject:
Diablo Canyon, Units 1 and 2 - National Fire Protection Association Standard 805 Radiation Release Additional Requests for Additional Information (TAC Nos. MF2333 and MF2334)
By letter dated December 31, 2014 (Agencywide Documents Access and Management System Accession No. ML14365A377), Pacific Gas and Electric Company (the licensee) responded to the Nuclear Regulatory Commissions (NRCs) request for additional information (RAI) related to the review of the radioactive release portion of the subject license amendment request (LAR). The NRC staff noted that the response indicated that the licensee has chosen an alternative approach to ensure that 10 CFR 20 [Title 10 of the Code of Federal Regulations (10 CFR), Part 20] limits are met... The licensee further described that to support this alternative approach, two calculations are being developed to supersede existing calculations referenced in the LAR, but these calculations were not yet completed and/or approved. As a result, the NRC staff has the following official additional RAIs that need your responses by May 8, 2015:
Radiation Release RAI 09 Will each zone/area/building of interest have its own administrative activity limit, based on a zone specific calculation?
Radiation Release RAI 10 The response states that the Administrative Limit will ensure that "releases do not exceed 10 CFR Part 20 limits." Is this statement referring to the dose limit for a member of the public? If so, is the calculated dose to a real individual or a maximum exposed individual consistent with the Offsite Dose Calculation Manual? Is the Administrative Limit set bases on meeting the concentration limits in Appendix B to 10 CFR Part 20?
Radiation Release RAI 11 Describe the methodology used for each calculation to establish the maximum curie Administrative Limit, including all of the input assumptions and parameters used in these calculations.
Radiation Release RAI 12 What fraction of the contaminated oil stored in the Fire Zone is assumed to be consumed in the fire? If less than 1.0 provide basis for the assumption. What fraction of the activity in the contaminated oil is assumed to be released as an airborne effluent? - as a liquid effluent?
Radiation Release RAI 13 Are operator actions credited in the calculations for reducing the amount of effluent released? If so, specify the operator actions and describe the assumed impact on the resulting dose.
Siva P. Lingam U.S. Nuclear Regulatory Commission Project Manager (NRR/DORL/LPL4-1)
Cooper Nuclear Station Diablo Canyon Nuclear Power Plant Location: O8-D5; Mail Stop: O8-B3 Telephone: 301-415-1564; Fax: 301-415-1222 E-mail address: siva.lingam@nrc.gov
Hearing Identifier:
NRR_PMDA Email Number:
1977 Mail Envelope Properties (Siva.Lingam@nrc.gov20150407150800)
Subject:
Diablo Canyon, Units 1 and 2 - National Fire Protection Association Standard 805 Radiation Release Additional Requests for Additional Information (TAC Nos. MF2333 and MF2334)
Sent Date:
4/7/2015 3:08:27 PM Received Date:
4/7/2015 3:08:00 PM From:
Lingam, Siva Created By:
Siva.Lingam@nrc.gov Recipients:
"Markley, Michael" <Michael.Markley@nrc.gov>
Tracking Status: None "Shoop, Undine" <Undine.Shoop@nrc.gov>
Tracking Status: None "Pedersen, Roger" <Roger.Pedersen@nrc.gov>
Tracking Status: None "Miller, Barry" <Barry.Miller@nrc.gov>
Tracking Status: None "mjrm@pge.com" <mjrm@pge.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 2640 4/7/2015 3:08:00 PM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received: