10 CFR 50.55a Qaps Palo Verde Nuclear Generating Station P.O. Box 52034 Phoenix, AZ 85072 Mail Station 7636 Tel: (623) 393-5764 102-06983-TNW/CJS January 6, 2015 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001
Dear Sirs:
Subject:
Palo Verde Nuclear Generating Station (PVNGS)
Unit 1, Docket No. STN 50-528 Third 10-Year Interval, Second Period:
Owner's Activity Report Number U1R18 Pursuant to 10 CFR 50.55a and in accordance with the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Case N-532-4, Arizona Public Service Company (APS) hereby submits the Owner's Activity Report (Form OAR-i) for Unit 1 refueling outage 18 (UIR18). The outage ended on November 11, 2014.
No commitments are being made to the NRC by this letter. Should you need further information regarding this submittal, please contact me, at (623)393-5764.
Sincerely,
/t/ I. W ý4cql, ý -
Thomas N. Weber Department Leader, Regulatory Affairs TNW/CJS/hsc
Enclosure:
Unit 1 Eighteenth Refueling Outage Owner's Activity Report, Report UIR18 cc:
M. L. Dapas B. K. Singal M. M. Watford C. A. Peabody NRC Region IV Regional Administrator NRC NRR Project Manager for PVNGS NRC NRR Project Manager NRC Senior Resident Inspector for PVNGS A member of the STARS (Strategic Teaming and Resource Sharing) Alliance Callaway 0 Comanche Peak
- Diablo Canyon 0 Palo Verde
- Wolf Creek A-ciN-7
ENCLOSURE Unit 1 Eighteenth Refueling Outage Owner's Activity Report Report U1R18
FORM OAR-1 OWNER'S ACTIVITY REPORT Report Number: 1R18 Plant: Palo Verde Nuclear Generating Station, 5801 S. Wintersburg Road, Tonopah, Arizona 85354-7529 Unit No.: 1 Commercial service date:
Jan 28, 1986 Refueling Outage No.: 18 (if applicable)
Current inspection interval IWB, IWC, IWD, IWF = 3rd, IWE, IWL = 2nd (11t, 2 ',, 3',. 4h. other)
Current inspection period IWB,IWC, IWD, IWF, IWE = 2nd IWL = 1st (1-t, 2rm, 3rd
)
Edition and Addenda of Section Xl applicable to the inspection plans 2001 ed, 2003 ad, IWL 2007 ed 2008 ad Date and revision.of inspection plans ISI = 8/28/13 R3, Press Test = 3/19/14 R4, IWE = 4/2/09 RO, IWL = 11/8/12 R1 Edition and Addenda of Section Xl applicable to repair/replacement activities, if different than the inspection plans 2001 ed 2003 ad Code Cases used: N-532-4 (if applicable)
CERTIFICATE OF CONFORMANCE I certify that (a) the statements made in this report are correct; (b) the examinations and tests meet the Inspection Plan as required by the ASME Code, Section Xl; and (c) the repair/replacement activities and evaluations supporting the completion of U1R18 conform to the requirements of Section XI:
(refueling outage number)
Signed Lehman, William T(Z60076)
Digitally signed by Lehman, William T(Z60076)
DN: cn=Lehman, William T(Z60076)
Date: 2014.12.24 08:13:32 -07'00' Date:
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Arizona and employed by HSB GS of Hartford, Connecticut have inspected the items described in this Owner's Activity Report, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair/replacement activities and evaluation described in this report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- Hogstrom, Robert (YH2450)
(Inspect Date:
Digitally signed by Hogstrom, Robert (YH2450)
DN: cn=Hogstrom, Robert (YH2450)
Date: 2014.12.24 10:40.32 -07'00' or's Signature)
Commissions N.B. 9685 "A,N,I,C", Az 264 National Board, State, Province, and Endorsements PV-E0796 Ver. 1
Palo Verde Nuclear Generating Station Owners Activity Report - Unit 1 Refueling Outage 18 Table 1 Items with flaws or relevant conditions that required evaluation for continued service Examination Item Description Evaluation Category Number of Work Description NONE NONE NONE NONE 2
Palo Verde Nuclear Generating Station Owners Activity Report - Unit 1 Refueling Outage _18 Table 2 Abstract of repair/replacement activities required for continued service Item Description Date Repair/Replacement Code Class Description of Work Completed Plan Number 3
1MDGBE04 LO cooler base metal repair 5/16/2013 4019406 3
1MDGBE01B base metal repairs to intercooler 5/16/2013 4056012 3
1MDGBF05 tack welds to silencer 5/15/2013 4177411 2
1SI135H003 replace snubber failed testing 9/11/2014 4442538 3
1MDGBE01A base metal repairs to intercooler 9/19/2014 4413270 3
1MDGBE01B base metal repairs to intercooler 9/19/2014 4413270 3
1PSPBL104 replace piping due to corrosion 9/19/2014 4414257 3
1PSPBL106 replace piping due to corrosion 9/19/2014 4414257 3
1MDGBE04 LO cooler base metal repair 9/19/2014 4426325 3
1MDGBE01B base metal repair to intercooler 9/19/2014 4544780 3
1MDGAE01A base metal pipe repairs 10/5/2014 3915888 3
1MDGAE01A base metal repairs to intercooler 10/5/2014 3915888 3
1PSPAL080 replace piping due to corrosion 10/5/2014 4358934 3
1PSPAL098 replace piping due to corrosion 10/5/2014 4358935 3
1MDGAE05 JW cooler base metal repair 10/5/2014 4417797 3
1MDGAE04 LO cooler base metal repair 10/5/2014 4417798 3
1MDGAE01A base metal repair to intercooler 10/5/2014 4544778 2
1S1072H018 replace snubber failed testing 10/29/2014 4573116 2
1PSGEL008 replace piping due to corrosion 11/8/2014 3309334 3