1 NRR-PMDAPEm Resource From:

EDWARDS, MICHAEL L [medwards@oppd.com]

Sent:

Monday, December 15, 2014 11:31 AM To:

Lyon, Fred Cc:

HANSHER, BILL R

Subject:

RE: Clarification request from technical staff on FCS Supplement to License Amendment Request; One-Time Extension of Technical Specification Surveillance Requirements (MF5143)

Attachments:

Pages from 470850.pdf Fred, The attached page shows that is was signed off by the ST Coordinator on June 27, 2013.

Michael Edwards Nuclear Licensing Engineer Regulatory Assurance Department Omaha Public Power District 9610 Power Lane, Blair NE 68008 402-533-6929 medwards@oppd.com From: Lyon, Fred [1]

Sent: Monday, December 15, 2014 10:19 AM To: EDWARDS, MICHAEL L Cc: HANSHER, BILL R

Subject:

FW: Clarification request from technical staff on FCS Supplement to License Amendment Request; One-Time Extension of Technical Specification Surveillance Requirements (MF5143)

Mike, what is the date OP-ST-ESF-0002 was last completed? Thanks, Fred From: EDWARDS, MICHAEL L [2]

Sent: Friday, December 12, 2014 11:57 AM To: George, Andrea Cc: NGUYEN, TRUNG T; MCMANIS, JOE L; HANSHER, BILL R; WALKER, MEGAN A

Subject:

RE: Clarification request from technical staff on FCS Supplement to License Amendment Request; One-Time Extension of Technical Specification Surveillance Requirements (MF5143)

Hello Annie, Here are the answers to your questions:

Technical Specification 3.7(1)c.i (diesel auto start) is covered in OP-ST-ESF-0002 Diesel Generator Number 1 and Number 2 Auto Operation.

Technical Specification 3.7(1)c.iii (verification of emergency loads) is covered in SE-ST-DG-0001 Verification of Diesel Generator Loads, which was completed in October 2013. It is within its test interval and does not expire before the April 2015 refueling outage.

2 Michael Edwards Nuclear Licensing Engineer Regulatory Assurance Department Omaha Public Power District 9610 Power Lane, Blair NE 68008 402-533-6929 medwards@oppd.com From: George, Andrea [3]

Sent: Friday, December 12, 2014 6:20 AM To: EDWARDS, MICHAEL L

Subject:

Clarification request from technical staff on FCS Supplement to License Amendment Request; One-Time Extension of Technical Specification Surveillance Requirements (MF5143)

Mike, Im the backup PM for Fred. Please see a clarification question below.

Since the footnote is added to SR 3.7(1)c, are SR3.7(1) c.i (diesel auto-start) and SR 3.7(1)c.iii (verification of emergency loads) covered in OP-ST-ESF-0002?

If not, what surveillances tests (STs) meet SR3.7(1) c.i and SR 3.7(1)c.iii? Are those STs within tests intervals?

Thanks, Andrea George Project Manager Division of Operating Reactor Licensing U.S. Nuclear Regulatory Commission 301-415-1081 This e-mail contains Omaha Public Power District's confidential and proprietary information and is for use only by the intended recipient. Unless explicitly stated otherwise, this e-mail is not a contract offer, amendment, or acceptance. If you are not the intended recipient you are notified that disclosing, copying, distributing or taking any action in reliance on the contents of this information is strictly prohibited.

Hearing Identifier:

NRR_PMDA Email Number:

1760 Mail Envelope Properties (D9B37C2F1C3EA14784A17E929D6E4771ACD9B89D)

Subject:

RE: Clarification request from technical staff on FCS Supplement to License Amendment Request; One-Time Extension of Technical Specification Surveillance Requirements (MF5143)

Sent Date:

12/15/2014 11:30:31 AM Received Date:

12/15/2014 11:31:03 AM From:

EDWARDS, MICHAEL L Created By:

medwards@oppd.com Recipients:

"HANSHER, BILL R" <bhansher@oppd.com>

Tracking Status: None "Lyon, Fred" <Fred.Lyon@nrc.gov>

Tracking Status: None Post Office:

SECEX733.oppd.oppd-ds.com Files Size Date & Time MESSAGE 3145 12/15/2014 11:31:03 AM Pages from 470850.pdf 60121 Options Priority:

Standard Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received: