%DISTRIBUTION

'pocket Fil.e NRC PDR SEP 3 0 1981 Local PDR NSIC TERA D. Eisenhut Docket No. 50-261 ORB 1 File

3. Heltemes OCT 7 1981 S. Varga u es Qu Mr. J. A. Jones C. Parrish w

Senior Vice President W. Ross Carolina Power and Light Company OELD 336 Fayetteville Street G. Vissing Raleigh, North Carolina 27602 ACRS (10)

Dear Mr. Jones:

By letter dated January 7, 1980, signed by Darrell G. Eisenhut, we requested that you review your Quality Assurance Program for Robinson Unit 2 to assure that diesel generators& (DG) fuel oil is included. Your letter of May 14, 1980 did not respond directly to our request. As the result of subsequent discus sions between the staff and CP&L representatives our current understanding of your position on this.matter is as follows:

1. Diesel generators fuel oil is not included in the Quality Assurance Program for Robinson Unit 2.

2., You do not completely subscribe to the Regulatory Position in Regulatory Guide 1.137 (Revision 1) dated October 1979.

The staff's position remains as stated in Mr. Eisenhut's letter, i.e., consumable items shall be classified as safety related -nd subject to applicable provisions of Appendix B to 10 CFR Part 50 when the quality of the item is necessry for functiona) performance of safety related components. If you do not intend to includeq the DG fuel oil Within your Quality Assurance Program, w consider that ygf current Technical Specifications regarding DG fuel oil shoul be revised to include the following requirements:

1. At least once per 92 days a sample of diesel fuel from each Emergency Diesel Generator Fuel Oil Storage Tanks be obtained in ac ordance with ASTM D270-65 and be within the acceptable limits specified in Table 1 of ASTM D975-74 when checked for viscosity, water, and sediment.
2. Immedi-ately prior to transfer of the diesel fuel oil tb an Emergency Diesel Generatpr Fuel Oil Storage Tank, a sample of fuel being transferred by obtained in accordance with ASTM D270-65 and be within the acceptable limits specified in Table 1 of ASTM D975-74 when checked for viscosity, water, and sediment.

OFFICE SURNAME.................................

110150047 910930 PDR ADOCK 05000261 Np PBR)

OFFICIAL RECORD COPY USGPO: 1981-335-960

Mr. J.

SEP 3 0198 You are requested to comply with our position in our January 7, 1980 letter or, in the alternative, propose a Technical Specification change to reflect the requirements stated above. You are requested to reply within 45 days of receipt of this letter.

Sincerely, 1igista Signed BO!

Steven A. Varga, Chief Operating Reactors Branch No. 1 Division of Licensing cc:

See next page

~

ORB 1ORB 4

OFFICE SURNAME.

.W.

....S......

DAT. E NRC FORM 318 (10-80) NRCM 0240 OFFICIAL RECORDCOPY USGPO: 1981-335-960

Mr. J. A. Jones Carolina Power and Light Company cc: G. F. Trowbridge, Esquire Shaw, Pittman, Potts and Trowbridge 1800 M Street, N.W.

Washington, D. C. 20036 Hartsville Memorial Library Home and Fifth Avenues Hartsville, South Carolina 29550 U. S. Nuclear Regulatory Commission Resident Inspector's Office H. B. Robinson Steam Electric Plant Route 5, Box 266-1A Hartsville, South Carolina 29550 Michael C. Farrar, Chairman Atomic Safety and Licensing Appeal Board Panel U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Richard S. Salzman Atomic Safety and Licensing Appeal Board Panel U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Dr. W. Reed Johnson Atomic Safety and Licensing Appeal Board Panel U. S. Nuclear Regulatory Commission Washington, D. C. 20555