Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 April 2, 1993 Docket No. 50-261 Mr. R. A. Watson Senior Vice President Nuclear Generation Carolina Power & Light Company Post Office Box 1551 Raleigh, North Carolina 27602

SUBJECT:

INSTRUMENTATION TO FOLLOW THE COURSE OF AN ACCIDENT (REGULATORY GUIDE 1.97) - H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO. 2 (TAC NO. M51127)

Section 6.2 of Generic Letter 82-33 requested licensees to provide a report on their implementation of Regulatory Guide 1.97, Revision 2 (RG 1.97), including methods for complying with the Nuclear Regulatory Commission's (NRC) regulations and the supporting technical justification for any proposed alternatives or deviations. Carolina Power & Light Company (CP&L or the licensee) provided a final response to the Generic Letter on March 27, 1987.

In a letter dated April 29, 1987, the NRC acknowledged your commitment to upgrade current Category 3 instrumentation to Category 2 instrumentation during refueling outage 11.

Based on your commitment we considered the action related to RG 1.97 to be complete.

A large number of exception requests were received from PWR licensees asking that the environmental qualification requirement for accumulator level and pressure monitoring instrumentation be relaxed from Category 2 to Category 3, which would allow commercial grade instruments to be used.

Prior to 1987, these requests were denied by the staff. Since then, these exceptions have been considered as an open item until a generic resolution can be found.

The staff has now reviewed the bases for these exceptions and has concluded that no operator action is based on this post-accident instrumentation and that it does not perform a safety function. Since this instrumentation does not perform any post-accident safety function, its qualification requirements can be reduced to Category 3. A copy of the Safety Evaluation is enclosed.

As indicated in your letter of March 27, 1987, you have already installed Category 2 instrumentation to monitor accumulator level and pressure. You are no longer bound by this commitment, and may, at your discretion, replace this instrumentation with Category 3 instrumentation. Please notify me of the actions you plan to take and the schedule for implementation.

934060278 930402 PDR ADOCK 05000261 FLEC C PY)

PIRI

)

April 2, 1993

-2 If you have any questions regarding this issue, please do not hesitate to contact me at (301) 504-2020.

The reporting and/or recordkeeping requirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is not required under P. L.96-511.

Sincerely, ORIGINAL SIGNED BY:

Brenda L. Mozafari, Project Manager Project Directorate II-1 Division of Reactor Projects -

I/II Office of Nuclear Reactor Regulation

Enclosure:

Safety Evaluation cc w/

Enclosure:

See next page DISTRIBUTION:

Docket File NRC/Local PDRs PD II-1 Reading S. A. Varga G. C. Lainas J. A. Mitchell B. L. Mozafari P. D. Anderson A. Hansen B. Marcus J. Wermiel OGC ACRS (10)

E. W. Merschoff, R-II cc:

Plant Service list OFC LA:DQ 1:DRPE 21 NAME PDAn rson Mozafari:tmw A

_____"he DATE 04/,/93 04/

/93 04/01/93 Document Name:

ROB51127.LTR

Mr. R. A. Watson H. B. Robinson Steam Electric Carolina Power & Light Company Plant, Unit No. 2 cc:

Mr. H. Ray Starling Mr. Dayne H. Brown, Director Manager -

Legal Department Department of Environmental, Carolina Power & Light Company Health and Natural Resources Post Office Box 1551 Division of Radiation Protection Raleigh, North Carolina 27602 Post Office Box 27687 Raleigh, North Carolina 27611-7687 Mr. H. A. Cole Special Deputy Attorney General Mr. Robert P. Gruber State of North Carolina Executive Director Post Office Box 629 Public Staff -

NCUC Raleigh, North Carolina 27602 Post Office Box 29520 Raleigh, North Carolina 27626-0520 U.S. Nuclear Regulatory Commission Resident Inspector's Office Mr. C. R. Dietz H. B. Robinson Steam Electric Plant Vice President Route 5, Box 413 Robinson Nuclear Department Hartsville, South Carolina 29550 H. B. Robinson Steam Electric.Plant Post Office Box 790 Regional Administrator, Region II Hartsville, South Carolina 29550 U.S. Nuclear Regulatory Commission 101 Marietta St., N.W., Ste. 2900 Mr. Heyward G. Shealy, Chief Atlanta, Georgia 30323 Bureau of Radiological Health South Carolina Department of Health Mr. Ray H. Chambers, Jr.

and Environmental Control General Manager 2600 Bull Street H. B. Robinson Steam Electric Plant Columbia, South Carolina 29201 Post Office Box 790 Hartsville, South Carolina 29550 Mr. R. B. Starkey Public Service Commission Vice President State of South Carolina Nuclear Services Department Post Office Drawer 11649 Carolina Power & Light Company Columbia, South Carolina 29211 Post Office Box 1551 Raleigh, North Carolina 27602