ML14183A579

From kanterella
Jump to navigation Jump to search

Refers to Ltr,Dtd 940620,requesting NRC Approval of Use Equivalent Margins Analysis Performed for Rv Limiting Beltline Matls for Plant.Nrc Has Determined Request in Compliance w/10CFR50,app G & Request Approved.Se Encl
ML14183A579
Person / Time
Site: Robinson Duke Energy icon.png
Issue date: 09/19/1994
From: Mozafari B
Office of Nuclear Reactor Regulation
To: Hinnant C
Carolina Power & Light Co
Shared Package
ML14183A580 List:
References
TAC-M89701 NUDOCS 9409220087
Download: ML14183A579 (4)


Text

qlv,p REG&,,

N UNITED STATES 0

NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 September 19, 1994 Mr. C. S. Hinnant, Vice President Carolina Power & Light Company H. B. Robinson Steam Electric Plant, Unit No. 2 Post Office Box 790 Hartsville, South Carolina 29551-0790

SUBJECT:

SAFETY EVALUATION OF LOW UPPER SHELF ENERGY EQUIVALENT MARGINS.

ANALYSIS FOR THE H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO. 2 (TAC NO. M89701)

Dear Mr. Hinnant:

By letter dated June 20, 1994, Carolina Power & Light Company (CP&L or the licensee) requested NRC review and approval of an upper shelf energy (USE) equivalent margins analysis (EMA) performed for reactor vessel limiting beltline materials of the H. B. Robinson Steam Electric Plant, Unit No. 2 (HBR2). The required data and EMA were submitted by letters dated July 6, 1992; August 19, October 27, November 29, and December 21, 1993; and June 13, 1994. The licensee has confirmed the applicability of the Westinghouse Owners' Group (WOG) Report, WCAP-13587, Revision 1, to HBR2. Revision 1 of WCAP 13587 provided a bounding EMA for WOG plants and has been previously reviewed and approved by the staff.

The NRC staff has reviewed the above-referenced submittals and has determined that the licensee used methodology, modeling procedures, and acceptance criteria that fall within the scope of Draft Regulatory Guide DG-1023, Appendix K of the American Society of Mechanical Engineers Code (ASME Code),

Section XI, and ASME Code Case N-512. The NRC staff has completed a review of the information available on the limiting beltline materials for USE and the EMA. On the basis of the NRC review, it has been determined that the margins of safety against fracture for the HBR2 beltline materials are equivalent to those required by Appendix G of the ASME Code and, therefore, compliance with 9409220087 940919 PDR ADOCK 05000261 P

PDR

September 19, 1994 C. Hinnant

- 2 10 CFR Part 50, Appendix G, has been demonstrated until the end of license.

Our Safety Evaluation is enclosed.

Sincerely, Original Signed by:

Brenda Mozafari, Project Manager Project Directorate II-1 Division of Reactor Projects -

I/II Office of Nuclear Reactor Regulation Docket No.:

50-261

Enclosure:

Safety Evaluation cc w/enclosure:

See next page DISTRIBUTION:

Docket File PUBLIC PD II-1 R/F S. Varga, NRR G. Lainas, NRR J. Strosnider, NRR E. Hackett, NRR D. Matthews, NRR P. Anderson, NRR B. Mozafari, NRR OGC ACRS (10)

E. Merschoff, Region II DOCUMENT NAME:

G:\\ROBINSON\\ROB89701.LTR To receive a copy of this document, Indicate in the box: "C" = Copy K out attachment/enclosure "E" = Copy with attachment/enclosure "N" = No copy OFFICE LA:PD21:DRPE E PM:PDII-1:DRPE')

E D:PDI NAME PDAnderson I BMozafari:Jrm DMattheW DATE 09/1

/94 09/4 /94 09/IC1/94 OFFICIAL RECORD COPY

C. Hinnant

-2 10 CFR Part 50, Appendix G, has been demonstrated until the end of license.

Our Safety Evaluation is enclosed.

Sincerely, Brenda Mozafari, Project Manager Project Directorate II-1 Division of Reactor Projects -

I/II Office of Nuclear Reactor Regulation Docket No.: 50-261

Enclosure:

Safety Evaluation cc w/enclosure: See next page

Mr. C. S. Hinnant H. B. Robinson Steam Electric Carolina Power & Light Company Plant, Unit No. 2 cc:

Mr. H. Ray Starling Mr. Dayne H. Brown, Director Manager - Legal Department Department of Environmental, Carolina Power & Light Company Health and Natural Resources Post Office Box 1551 Division of Radiation Protection Raleigh, North Carolina 27602 Post Office Box 27687 Raleigh, North Carolina 27611-7687 Karen E. Long Assistant Attorney General Mr. Robert P. Gruber State of North Carolina Executive Director Post Office Box 629 Public Staff - NCUC Raleigh, North Carolina 27602 Post Office Box 29520 Raleigh, North Carolina 27626-0520 U.S. Nuclear Regulatory Commission Resident Inspector's Office Mr. Max Batavia, Chief H. B. Robinson Steam Electric Plant Bureau of Radiological Health Route 5, Box 413 South Carolina Department of Health Hartsville, South Carolina 29551 and Environmental Control 2600 Bull Street Regional Administrator, Region II Columbia, South Carolina 29201 U.S. Nuclear Regulatory Commission 101 Marietta St., N.W., Ste. 2900 Mr. H. W. Habermeyer, Jr.

Atlanta, Georgia 30323 Vice President Nuclear Services Department Mr. Marc P. Pearson Carolina Power & Light Company Plant Manager Post Office Box 1551 Carolina Power & Light Company Raleigh, North Carolina 27602 H. B. Robinson Steam Electric Plant Post Office Box 790 Hartsville Memorial Library Hartsville, South Carolina 29551 147 West College Avenue Hartsville, South Carolina 29550 Public Service Commission State of South Carolina Post Office Drawer 11649 Columbia, South Carolina 29211 Mr. R. M. Krich Manager -

Regulatory Affairs Carolina Power & Light Company H. B. Robinson Steam Electric Plant, Unit No. 2 Post Office Box 790 Hartsville, South Carolina 29551-0790